64
Overview of the software Sepam software CD Parameter setting Main points to remember A B C D ? Situate SFT disconnected SFT2841 disconnected Prepare setting files Experts: L.GIGLI Pedagogy: C.CAYLA Duration: mn

SFT2841 disconnected

Embed Size (px)

DESCRIPTION

SFT2841 disconnected. Prepare setting files. Experts: L.GIGLI Pedagogy: C.CAYLA. Duration: mn. SFT 2841 expert UMI. The UMI on the front panel of Sepam may be completed by an expert UMI comprising the SFT2841 PC software tool, which may be used for all Sepam functions parameter setting, - PowerPoint PPT Presentation

Citation preview

Page 1: SFT2841 disconnected

Overview of the software

Sepam software CD

Parameter setting

Main points to remember

A

B

C

D

? Situate SFT disconnected

SFT2841 disconnected

Prepare setting files

Experts: L.GIGLIPedagogy: C.CAYLA

Duration: mn

Page 2: SFT2841 disconnected

SFT 2841 expert UMI

The UMI on the front panel of Sepam may be completed by an expert UMI comprising the SFT2841 PC software tool, which may be used for all Sepam functions

– parameter setting, – local operation – and customization.

The expert UMI comes as a kit, the SFT 2841 kit, which includes:– Sepam software CD– CCA 783 cord

Cable usb telemecanique

Page 3: SFT2841 disconnected

Overview of the software

Sepam software CD

Parameter setting

Main points to remember

A

B

C

D

? Situate SFT disconnected

Sepam software CD

Sepam software CD

Page 4: SFT2841 disconnected

After the CD is inserted, Autorundisplays this screen.

You may choose: SFT2841 installation SFT2826 installation Presentation of the Sepam offer

– Sepam range

– application solutions

– documentation

– product implementation

– different specifications per application

– order form

Autorun● Sepam software CD

● Overview of the software

● Parameter setting

Page 5: SFT2841 disconnected

Code entry

SFT2841 may be installed in

demonstration version or full version

Demonstration version– no serial number requested– connected mode disabled– file saving disabled

Full version– enter the serial number on the label

stuck on the back of the CD box– format: XXXXXXX-XX

● Sepam software CD

● Généralités

● Parameter setting

Page 6: SFT2841 disconnected

Content

The Readme files give the required configuration for installation of the software

The Demo directory contains the files used by the Sepams in Series 80 demo case

SFT2841 v9

Readme.txt

Lisezmoi.txt

Install

Demo

SFT2826v0202

Readme.txt

Lisezmoi.txt

Install

Disks

Sepam_presentation

Readme.txt

Lisezmoi.txt

Sepam v4.0_FR

Sepam v4.0_E

● Sepam software CD

● Généralités

● Parameter setting

Page 7: SFT2841 disconnected

Overview of the software

Sepam software CD

Parameter setting

Main points to remember

A

B

C

D

? Situate SFT disconnected

Overview of the software

OVERVIEW OF THE SOFTWARE

Page 8: SFT2841 disconnected

Starting the application

Click on the icon

Select the working language

Choose the operating mode:

– connected– point to point via the front

panel– via the network

– disconnected (according to Sepam)– create a new file– or edit an existing file

● Sepam software CD

● Overview of the software

● Parameter setting

Same access for SFT connected

Page 9: SFT2841 disconnected

Screen organization

Title bar: displays the Sepam file identification name

Menu bar (contextual): provides access to all of the software functions

Toolbar (contextual): Direct access to principal functions

Work zone: contextual tab boxes available to the user

Status bar: gives information on the active window

● Sepam software CD

● Overview of the software

● Parameter setting

Page 10: SFT2841 disconnected

Toolbar

Guided navigation– for logical sequencing of screens

● Sepam software CD

● Overview of the software

● Parameter setting

Sepam parameter setting

Protection setting

Logipam setting

Equation editor

– automation– inputs / outputs

Matrix

Function setting– disturbance recording– mimic diagram

– setup– environment

Page 11: SFT2841 disconnected

Guided navigation

Series 20 Series 40 Series 80

Hardware setup 1 1 1

General characteristics 3 2 2

CT-VT sensors 3 2 3

CT-VT circuit supervision 3 4

Particular characteristics 5

Control logic 2 4 6

Logic input/output assignment 2 4 7

Protection functions 4 5 8

Logipam 9

Logic equations 6 10

Matrix 5 7 11

Disturbance recording 3 8 12

Mimic-based UMI 13

Linking of screens

● Sepam software CD

● Overview of the software

● Parameter setting

Page 12: SFT2841 disconnected

Software help

Opening of the Sepam operating manual

The file opens up directly on the page that corresponds to the SFT2841 screen

Series 80

● Sepam software CD

● Overview of the software

● Parameter setting

Series 20 & 40

Page 13: SFT2841 disconnected

Saving the file

Saving by default in the Sepam directory

Entry of the file name

File extension– series 20, rpg– series 40 and 80, type

of Sepam (e.g. M41)

● Sepam software CD

● Overview of the software

● Parameter setting

Page 14: SFT2841 disconnected

Editing a report

Enter the report identification information

Print

● Sepam software CD

● Overview of the software

● Parameter setting

Page 15: SFT2841 disconnected

Editing a report

Text file

All the parameters are listed

Sepam xxxx (21/03/2006)

PropertiesCustomer: TrainingProject: Series 20, 40 & 80Switchboard: FileCubicle: Series 20Print date: 24/04/06

Sepam hardware configurationType of application: Substation (S20)Sepam Type: Sepam xxxxSepam model: UD model (with fixed advanced UMI)MES (Input / output module): MES114 (10I + 4O module)MSA141 (1 analog output module): AbsentDSM303 (Remote advanced UMI module): AbsentInterface de communication: AbsentSynchronization mode: Network

Set up outputs Used Shunt coil Undervoltage coil Pulse mode O1 Yes X O2 Yes X O3 Yes X O4 Yes X O11 Yes X O12 No - - - O13 No - - - O14 No - - -

Series 20 & 40

● Sepam software CD

● Overview of the software

● Parameter setting

Page 16: SFT2841 disconnected

Editing a report

Word file

Cover page Contents

Series 80

Structure presentation of parameters

● Sepam software CD

● Overview of the software

● Parameter setting

Page 17: SFT2841 disconnected
Page 18: SFT2841 disconnected

Customizing the label

Enter the required label for each indicator

● Sepam software CD

● Overview of the software

● Parameter setting

Page 19: SFT2841 disconnected

Printing labels

Print

● Sepam software CD

● Overview of the software

● Parameter setting

Page 20: SFT2841 disconnected

Advanced settings

Access to additional settings which are not compulsory but may be used on function operation

Series 40 & 80

● Sepam software CD

● Overview of the software

● Parameter setting

Page 21: SFT2841 disconnected

Overview of the software

Sepam software CD

Parameter setting

Main points to remember

A

B

C

D

? Situate SFT disconnected

PARAMETER SETTING

Parameter setting

Page 22: SFT2841 disconnected

1. Define Sepam hardware setup

2. Define Sepam hardware environment

3. Define automation functions used

4. Assign inputs / outputs

5. Set protection functions

6. Create mimic diagrams (series 80)

7. Create logic equations (series 40 & 80)

8. Set up Logipam (series 80)

9. Validate control matrix

10. Define disturbance recording function

Full parameter setting

Some operations may be done before others,

which is why we propose the following sequence:

● Sepam software CD

● Overview of the software

● Parameter setting

Page 23: SFT2841 disconnected

1. Define Sepam setup

Sepam name– 20 characters max.

Sepam model– with or without fixed

advanced UMI

Optional modules– optional inputs / outputs– temperature acquisition – analog output– communication

Series 20

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

● Sepam software CD

● Overview of the software

● Parameter setting

Page 24: SFT2841 disconnected

1. Define Sepam setup

Sepam name Sepam model Optional modules

Series 40

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 25: SFT2841 disconnected

1. Define Sepam setup

Sepam name Sepam model Optional modules

Series 80

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 26: SFT2841 disconnected

2. Define Sepam environment

Frequency Active group of settings Remote setting enabling Sepam working

language Sensors

Series 20

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 27: SFT2841 disconnected

2. Define Sepam environment

Frequency Active group of settings Remote setting enabling Sepam working

language Sensors

Type of cubicle External counters

Series 40

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 28: SFT2841 disconnected

2. Type of cubicle

Incomer Power supplied to the busbars is

positive.

Feeder Power exported by the busbars is

positive.

Direction of flow

Direction of flow

Series 40 & 80

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 29: SFT2841 disconnected

2. Define Sepam environment

Frequency Active group of settings Remote setting enabling Sepam working

language Type of cubicle External counters

Phase rotation direction Supply voltage

monitoring

and …

Series 80

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 30: SFT2841 disconnected

2. Define Sepam environment

Sensors

Series 80

as well as …

● Sepam software CD

● Overview of the software

● Parameter setting

2.

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 31: SFT2841 disconnected

2. Define Sepam environment

Specific load characteristics

– transformer: SFT2841 calculates In and Ib according to rated voltage and power

– machines

– capacitor

Series 80

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 32: SFT2841 disconnected

3. Define automation functions used

CB control Protection units excluded

from CB control Logic discrimination

Series 20

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 33: SFT2841 disconnected

3. Define automation functions used

CB control Logic discrimination

Series 40

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 34: SFT2841 disconnected

3. Define automation functions used

Switchgear control Logic discrimination

And, according toapplications Restart Load shedding De-excitation Genset shutdown Automatic transfer Capacitor step control

Series 80

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 35: SFT2841 disconnected

3. Define automation functions used

CT circuit supervision VT circuit supervision

Series 40

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 36: SFT2841 disconnected

3. Define automation functions used

CT circuit supervision VT circuit supervision

Series 80

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 37: SFT2841 disconnected

4. Assign inputs / outputs

Inputs Outputs

Series 20

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 38: SFT2841 disconnected

4. Assign inputs / outputs

Inputs Outputs

Standard assignment oflogic inputs

– according to the type of application

– described in the "Control and monitoring function" chapter of the documentation

Series 40

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 39: SFT2841 disconnected

4. Assign inputs / outputs

Inputs Outputs

Assignment of other uses oflogic inputs

– all "not used" inputs are assigned to "other use"

– if inputs are used in Logipam, they are assigned automatically

Series 80

The inputs/outputs used by Logipam are displayed in yellow

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 40: SFT2841 disconnected

5. Set protection functions

Choice of protection functions

Activation Setting Control matrix

Series 20

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 41: SFT2841 disconnected

5. Set protection functions

Choice of protection functions

Activation Setting Control matrix

Define whether the unit– is latched– affects CB control

Series 40

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 42: SFT2841 disconnected

5. Set protection functions

This screen displays– protection functions in

service– which sensors are used

by the protection functions

Series 80

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 43: SFT2841 disconnected

5. Set protection functions

Choice of protection functions

Activation Setting Control matrix Define whether the unit

– is latched– affects CB control

Series 80

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 44: SFT2841 disconnected

5. Timer hold

Definitions:– Timer hold: time added to reset time to:

– delay the return to the initial situation – and activate a memory for the detection of recurrent faults.

– Reset time (of a protection function): time of return to the initial situation of a protection function after the disappearance of the fault (<50ms)

Applications:– definite time: detection of recurrent faults on networks earthed by a

Petersen coil (for directional earth fault protection)– IDMT: used to have a reset time similar that of a disc-type

electromechanical relay for improved discrimination when the relay is situated upstream.

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 45: SFT2841 disconnected

5. Timer hold

Influence on tripping time

100% of trippingdelay

Time

I > Is

timer hold = 0

IDMT timer hold

definite-time timer hold

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 46: SFT2841 disconnected

5. H2 restraint

Stability upon transformer energizing

This function should only be activated with Σ 3I earth fault protection upstream from a transformer

Transformer energizing generates number 2 harmonics . This function restrains the protection if the harmonic is above the set 17% threshold.

H2 > seuil

I1

I2

I3

TC + CSH30

CSH120 ou 200

Tore + ACE990

Σ Signal "pick up"

SortietemporiséeIo > Iso t 0

Schéma de principe protection 50N/51N

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 47: SFT2841 disconnected

5. CT saturation caused by transformer energizing

I1

I2

I3

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 48: SFT2841 disconnected

5. Io = I1+I2+I3● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 49: SFT2841 disconnected

6. Create mimic diagrams

Will be explained in the "Mimic-based UMI" chapter

Series 80

● Sepam software CD

● Overview of the software

● Parameter setting

5.

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 50: SFT2841 disconnected

7. Create logic equations

Will be explained in the "Equation editor" chapter

Series 40 & 80

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 51: SFT2841 disconnected

8. Set up Logipam

Selection of the program– the files are placed in the

following directory:

C:\ProgramFiles\Schneider\SFT2841\Logipam

Activate Logipam

Series 80

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 52: SFT2841 disconnected

8. Set up Logipam

Set up internal bits

Series 80

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 53: SFT2841 disconnected

8. Set up Logipam

Set time delays

Series 80

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 54: SFT2841 disconnected

9. Validate control matrix

Column 1: input resources

– protection function delayed outputs

– logic inputs– miscellaneous

information

Row 1: output resources– logic outputs– indicators– activation of

disturbance recording

Series 20

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

grey: not modifiable

black: unavailable

red: off

white: on

Page 55: SFT2841 disconnected

9. Validate control matrix

The principle and the rules are the same as for those for series 20

Since there are more data items, the matrix is split into several screens

Series 40 & 80

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

grey: not modifiable

black: unavailable

red: off

white: on

Page 56: SFT2841 disconnected

9. Customize messages

Double-click on the message to be customized

Create the message Double-click on the new

message Enter the message

Series 40 & 80

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 57: SFT2841 disconnected

9. Assign messages

Double-click on the message to be customized

Select the new message by clicking on the number

Assign the message

Series 40 & 80

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 58: SFT2841 disconnected

10. Define disturbance recording function This function supplies a file:

– created by a trigger – composed of the recording of analog signals and logic

states (COMTRADE format)

Recording begins before the trigger and continues after the event (according to parameter setting)

stored recording

trigger

time

number of pretrig periods

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 59: SFT2841 disconnected

10. Define disturbance recording function

Non-modifiable characteristics

– max. of 2 stored recordings

– 86 periods– 4 current or voltage

channels– 10 logic inputs– output O1– pick-up

Setting of pretrig

Series 20

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 60: SFT2841 disconnected

10. Define disturbance recording function

Non-modifiable characteristics

– all analog channels– 10 logic inputs– outputs O1 to O4– pick-up– 1 equation editor

variable

Setting according to memory allocated

– number of recordings – duration of each

recording

Setting of pretrig

Series 40

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 61: SFT2841 disconnected

10. Define disturbance recording function

Non-modifiable characteristics

– all analog channels

Setting according to memory allocated

– number of recordings – duration of each

recording– sampling frequency

Setting of pretrig Selection of recorded

logic states

Series 80

● Sepam software CD

● Overview of the software

● Parameter setting

1. Sepam hardware setup2. Sepam hardware environment3. Automation functions used4. Inputs / outputs5. Protection functions6. Mimic diagram (series 80)7. Logic equations (series 40 & 80)8. Logipam (series 80)9. Control matrix10. Disturbance recording

Page 62: SFT2841 disconnected

Overview of the software

Sepam software CD

Parameter setting

Main points to remember

A

B

C

D

? Situate SFT disconnected

MAIN POINTS TO REMEMBER

Main points to remember

faire "ce qu'il faut retenir"

Page 63: SFT2841 disconnected

A compléter

Page 64: SFT2841 disconnected

Astuces de paramétrage

Faire attention que le type de fichier corresponde au type de Sepam

Ne pas oublier de mettre les protections en service

Ne pas perdre le code de déverrouillage du SFT2841 qui se trouve sur la boite du CD d’installation.

Penser à valider les sorties qui doivent être utilisées dans la matrice de commande.

Le changement du type arrivée / départ modifie le signe de la puissance.

La passage par la navigation guidée permet de ne pas oublier de configurer des écrans.

Le SFT2841 vérifie la cohérence des valeurs rentrées en fonction des plages de réglage et du ratio des TC / TP