STAINES AP-PLANS PHDD C2-A0 HVAC MECH

  • View
    16

  • Download
    1

Embed Size (px)

Text of STAINES AP-PLANS PHDD C2-A0 HVAC MECH

  • 150mm AV / DATA CABLE TRAY.

    TRUNKINGS RISE TO SOFFIT

    DB L

    18CHANNEL

    6A DIMMABLE POWER UNIT

    TIGER MODE TP-06-18

    MODE REMOTE TIMER

    RT-00-10

    2" GAS TO KITCHEN

    SOLENOID VALVE CONTROLLED

    BY MERLIN CT1200S GAS SAFETY SYSTEM

    2" GAS SPLITS

    1) RISES IN

    CEILING TO PLANTROOM

    2)RISES TO GROUND CEILING TO KITCHEN

    300MM CABLE TRAYS

    15mm CWS

    15mm CWS TO DISHWASHER

    DHW DROP FROM ABOVE

    28mm FLOW

    DHW RISES TO ABOVE

    15mm RETURN

    2" GAS DROPS IN

    SERVICES COLUMN

    5" E

    V

    6L/S

    15mmCWS

    RISES TO ABOVE

    1050x360x1338

    22mm CWS RISES TO SOFFIT

    22mm DHW F&R RISE TO SOFFIT

    28MM CWS IN CEILING

    WCs & BAR

    28MM CWS IN CEILING VOID

    TO SERVE BOH

    15mm CWS TO ICE MACHINES

    WC FAN

    150mm /

    66L/[email protected]

    5" EV

    6L/S

    GROUND LEVEL

    22mm CWS,22mmDHW F&15mmR, 2"DRAIN

    POP UP

    No.1

    POP UP

    No.2

    POP UP

    No.3

    POP UP

    No.6

    POP UP

    No.5

    POP UP

    No.4

    Soil Manifold Gradient = 1deg(18mm/m)

    Air admittance valve before last connection

    AIR ADMITTANCE VALE

    IT DB

    14W SPN

    2" GAS SOLENOID

    DRAIN MAJOR

    400mmH

    DRAIN MAJOR

    400mmH

    RETURN AIR LOUVER

    1580

    BAR WASTE 50MM SS Europipe

    VCD

    FA SG13 -

    PREP AREA FRESH AIR

    SUPPLY100L/s

    VCD

    FA SG14 -

    PREP AREA FRESH AIR

    SUPPLY 100L/s

    2" DRAINMAJOR DISCHARGE PIPES

    403

    302

    690

    82mm BLUCHER

    50mm BLUCHER

    50mm BLUCHER

    FA SG15 -

    WASHUP AREA FRESH AIR

    SUPPLY250L/s

    EG14 -

    220L/s

    EG13 -

    220L/s

    FA SG16 -

    SUPPLY 250L/s

    POP UP

    No.1

    POP UP

    No.2

    POP UP

    No.3

    POP UP

    No.6

    POP UP

    No.5

    POP UP

    No.4

    CLEANERS'

    SINK

    E E

    E E

    E E

    E E

    E E

    2820 (S

    TA

    IN

    LE

    SS

    G

    AN

    TR

    Y)

    3235 (STAINLESS GANTRY)

    800

    4235 (STAINLESS GANTRY)

    400 400

    2920 (T

    IM

    BE

    R B

    ULK

    HE

    AD

    )

    7920 (STAINLESS GANTRY)

    8020 (TIMBER BULKHEAD)

    500

    400

    8020 (TIMBER BULKHEAD)

    450

    2820 (S

    TA

    IN

    LE

    SS

    G

    AN

    TR

    Y)

    2920 (T

    IM

    BE

    R B

    ULK

    HE

    AD

    )

    400

    500

    400

    500

    400

    500

    GAS

    METER

    TEAM

    ROOM

    300L DHW

    CALORIFIER

    2046mmH

    C13 TYPE FLUES

    5" EV

    6L/S

    5" EV

    6L/S

    MIT

    SUBI

    SHI (20.

    25kW

    )

    40mm DRAIN DROPS TO POP UP NO3 BELOW

    WC FAN

    100MM /

    12L/[email protected]

    C13 TYPE FLUES

    DHW DROP TO BELOW

    28mm FLOW

    DHW RISES FROM BELOW

    15mm RETURN

    15mmCWS

    RISES TO ABOVE

    MEZZANINE LEVEL

    3000.0000

    3850.0000

    3 X MITSUBISHI PUHZ-P250YHA3

    FAN COIL CONDENSERS

    MIT

    SUBI

    SHI (20.

    25kW

    )

    FR

    EE

    ZE

    R

    LP

    HC

    0

    68

    16

    A T

    PN

    CH

    IL

    LE

    R

    MP

    HC

    0

    26

    16

    A T

    PN

    CE

    LL

    AR

    MP

    HC

    0

    34

    20

    A T

    PN

    LPHW EXPANSION VESSEL

    LOWLOSS HEADER

    8-A

    C-0

    .1

    95

    m3

    /S

    14-AC-0.18m3/S

    5-AC-0.195m3/S 6-AC-0.195m3/S

    15

    -A

    C-0

    .1

    95

    m3

    /S

    17-AC-0.195m3/S18-AC-0.195m3/S 16-FA-0.144m3/S

    800x800mm KITCHEN EXTRACT DUCT

    DISCHARGE NOZZLE 0.55m2 / 15m/s.

    DUCT RUNS VERTICAL TO 1m ABOVE

    PARAPIT

    SUPPLY AIR CONNECTIONS

    DUCT RISES TO MEZZ LEVEL

    AND ENTERS PLANTROOM

    0.88m3/s0.88m3/s

    0.88m3/s 0.88m3/s

    0.76m3/s

    0.76m3/s 0.76m3/s

    VCD

    F/D

    F/D

    12-AC-0.18m3/S

    11-AC-0.18m3/S

    2-AC-0.195m3/S 3-AC-0.195m3/S

    20-AC-0.195m3/S21-AC-0.195m3/S22-FA-0.144m3/S19-FA-0.144m3/S

    1-FA-0.144m3/S 4-FA-0.144m3/S

    1.12m3/s

    1.12m3/s

    7-FA-0.144m3/S

    SUPPLY DUCTS RISES TO HL

    AND RUNS ALONG SOFFIT

    0.76m3/s

    0.76m3/s 0.76m3/s

    800Wx400H

    1000X400

    VCD

    VCD

    VCD

    1000Wx400H - 2416L/[email protected]/s

    KITCHEN SUPPLY

    SET UP

    OVER EXTRACT

    AIR

    TEM

    PERI

    NG

    CON

    DEN

    SER

    20KW

    . 154

    0X90

    0X32

    0AI

    R TE

    MPE

    RIN

    G CO

    NDE

    NSE

    R20

    KW. 1

    540X

    900X

    320

    AIR

    TEM

    PERI

    NG

    CON

    DEN

    SER

    20KW

    . 154

    0X90

    0X32

    0

    2" GAS SOLENOID

    SYSTEM PUMP

    MAGNA3 D40-100F

    GLYCOL

    UNIT

    13A SPN

    GLYCOL

    UNIT

    13A SPN

    GLYCOL

    UNIT

    13A SPN

    GLYCOL

    UNIT

    13A SPN

    22mm CWS FOR COKE

    VCD

    IT CONDENSERS

    23

    -R

    ET

    UR

    N A

    IR

    500

    1200Wx600H

    5.8m3/[email protected]/s

    1200Wx600H

    8m/s

    1200Wx600H

    8m/s

    TRANSITION

    1100 x 800H TO

    800 x 500H

    800x500H

    9504m3/hR 6m/s

    WASHUP/ICE MACHINE EXTRACT 0.64m3/S

    PREP AREA FRESH AIR

    SUPPLY150L/s

    654

    614

    700

    1004

    754

    548

    596

    793 377

    POP UP

    No.1

    RELIEF VALVE PIPEWORK RATED TO 110degC

    50mm BLUCHER

    50mm BLUCHER

    WASHUPSUPPLY 0.25m3/S

    FA SG11 -

    SUPPLY 24L/s

    2 PERSON BANQUETTE SEATS x 11 = 22 No. COVERS

    TOTAL RESTAURANT DINING COVERS = 248 No. COVERS

    6 & OVER 58 No. COVERS 23%

    4 & 5 144 No. COVERS 58%

    2 46 No. COVERS 19%

    WITH 'ZONE A' CLOSED = 226 No. COVERS

    WITH 'ZONE B' CLOSED = 228 No. COVERS

    WITH 'ZONES A & B' CLOSED = 206 No. COVERS

    PINK DOTTED LINE INDICATES WALL TO BE

    TAKEN FULL HEIGHT - 6500mm

    SEALS

    ELECTRICS

    ALL ELECTRICAL WORKS TO BE CARRIED OUT IN ACCORDANCE WITH

    PHDD DRAWINGS

    FIRE ALARM SYSTEM

    THE PROPOSED FIRE ALARM WILL BE INSTALLED TO BS 5839 : PART 1

    : 2002 TO L2 STANDARD. THIS WILL BE CONNECTED TO THE

    LANDLORD'S SYSTEM IN ACCORDANCE WITH THEIR INSTRUCTION.

    SMOKE DETECTION TO CEILING VOIDS TO BE INCLUDED

    EMERGENCY LIGHTING

    EMERGENCY LIGHTING SYSTEM TO BE PROVIDED IN ACCORDANCE

    WITH BS 5266 : PART 1 : 2005

    FIRE STOPPING

    FIRE STOPPING TO BE INSERTED INTO CEILING AS REQUIRED.

    ALL DUCTWORK PASSING THROUGH COMPARTMENT FLOORS AND

    WALLS TO BE PROTECTED BY FIRE COLLARS

    NOTICES

    NOTICES WITH THE WORDS 'PUSH BAR TO OPEN' TO BE DISPLAYED

    ON ALL DOORS FITTED WITH PANIC BOLTS

    ALL FIRE RESISTING SELF CLOSING DOORS TO BE PERMANENTLY

    MARKED ON EACH SIDE AT EYE LEVEL WITH A BLUE CIRCULAR

    NOTICE BEARING THE WORDS 'FIRE DOOR - KEEP SHUT' IN WHICH

    LETTERS ARE NOT TO BE LESS THAN 5mm IN HEIGHT

    PLANT

    ROOM

    TEAM

    ROOM

    OFFICE

    STORE

    800x800mm KITCHEN

    EXTRACT DUCT

    E E

    STORE

    FA

    -0

    .5

    76

    m3

    /S

    34-FA-0.266m3/S

    500 x 200 BELLMOUTH

    30-AC-0.22m3/S 25-AC-0.22m3/S

    29-AC-0.22m3/S 26-AC-0.22m3/S

    28-AC-0.22m3/S 27-AC-0.22m3/S

    MULTI-CONE DIFFUSERS C/W

    TWIN BLADE TYPE (R) DAMPER

    3No: 450 X 200 DOUBLE

    DEFLECTION SIDE WALL

    GRILLE.

    31-FA- 0.19m3s

    32-FA- 0.19m3s

    500

    30mm external Mezz

    flanges on MMF casing.

    30mm external Mezz

    flanges on MMF casing.

    Side Elevation of ESPs, UVO and MMF

    PUHZ-P250YHA3

    PUHZ-P250YHA3

    PUHZ-P250YHA3

    PEA-RP250GAQ

    PEA-RP250GAQ

    PEA-RP250GAQ

    300L

    EXPANSION

    VESSEL

    MIKROFILL

    SOLENOID VALVE

    FUSIBLE

    LINK

    DHW SCHEMATIC

    GAS

    CWS

    2"

    1

    1

    2

    "

    1

    1 2

    "

    1"

    1"

    1

    1 2

    "

    1

    1

    4

    "

    1

    1

    4

    "

    1"

    1"

    MULTI-CONE DIFFUSERS

    C/W TWIN BLADE TYPE (R)

    DAMPER

    3No: 450 X 200 DOUBLE

    DEFLECTION SIDE WALL

    GRILLE.

    500 x 200 BELLMOUTH

    HVAC

    TGI FRIDAYS STAINES

    C2

    1of1

    1:[email protected]/10/2015NJH

    Project

    PH Design & Deliver Ltd, Park Holland Building

    Sampson Street, Stoke on Trent, ST1 5EZ

    PHDD