3
Sheet 1 of 1 B01-0200.xls - Front sheet 02 Originator / Contractor Code Short Requisition No / PO Identifier Sheet Rev FC EL0016-A01 02 Alternative Document No: (if applicable): Rev Orig. Chk'd App'd 02 GR DH NCR 01 GR DH NCR Code 1 2 3 4 5 6 Date UPDATED SUBMISSION Accepted (Reviewed and Agreed) Comments to Incorporated and Resubmitted Rejected, Do Not start work (Comments to be incorporated and resubmitted) Description of Code Date Description INITIAL SUBMISSION Signature of Purchaser's Responsible Engineer SUPPLIER DOCUMENT FRONT SHEET Supplier Name: ABB Ltd For Information 20-Nov-13 18-Feb-14 Project ID CLB Equipment Tag No(s): Supplier Document No: Document Title: Z-89902 N/A GENERAL ARRANGEMENT - GM TEMPORARY SUBSTATION Supplier Document Revision No. Purchaser Document Number Sequence no. 0200 SDDR code B01 Purchaser Review of Supplier Document Cancelled / Superseded As-Built

SUPPLIER DOCUMENT FRONT SHEET - .NET Framework

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Page 1: SUPPLIER DOCUMENT FRONT SHEET - .NET Framework

Sheet 1 of 1 B01-0200.xls - Front sheet

02

Originator / Contractor Code

Short Requisition No / PO Identifier Sheet Rev

FC EL0016-A01 02

Alternative Document No: (if applicable):

Rev Orig. Chk'd App'd

02 GR DH NCR

01 GR DH NCR

Code

1

2

3

4

5

6

Date

UPDATED SUBMISSION

Accepted (Reviewed and Agreed)

Comments to Incorporated and Resubmitted

Rejected, Do Not start work (Comments to be incorporated and resubmitted)

Description of Code

DateDescription

INITIAL SUBMISSION

Signature of Purchaser'sResponsible Engineer

SUPPLIER DOCUMENT FRONT SHEET

Supplier Name: ABB Ltd

For Information

20-Nov-13

18-Feb-14

Project ID

CLB

Equipment Tag No(s):

Supplier Document No:

Document Title:

Z-89902

N/A

GENERAL ARRANGEMENT - GM TEMPORARY SUBSTATION

Supplier Document Revision No.

Purchaser Document Number

Sequence no.

0200

SDDR code

B01

Purchaser Review of Supplier Document

Cancelled / Superseded

As-Built

Page 2: SUPPLIER DOCUMENT FRONT SHEET - .NET Framework

8000

10061001600

100

100

1450 LOUVERS 5047

100

953

3000

240015004100

650

100

1580

610

610

100

100

810

1180

810

369 821 410

535 565157.5 435

65

550 550 435

65

535

65

535

65

535 342.5 600 65

6525

0

430

210

430

210

210

430

1600

2300 1500 STRUCTURAL OPENING 2300

6100

2800

100

100

100

100

100

1501200

800

150

750

750

350

100

150500300

HV S

IDE

LV S

IDE

HV S

IDE

LV S

IDE

670 W

HEEL

CRS

670 WHEEL CRS

410821369

360 115090

500

375

CABLE APERTURE THROUGH BASE FRAME& FLOOR PLATE. C/W MARINE GRADEALUMINIUM GLAND PLATE TO U/SIDE.

(ACCESS FOR INCOMING HV & EARTH CABLES)

7 OFF CABLE APERTURES THROUGH BASE FRAME& FLOOR PLATE. C/W MARINE GRADE ALUMINIUMGLAND PLATES TO U/SIDE.(ACCESS FOR SWITCHBOARD CABLES)

CABLE APERTURE THROUGH BASE FRAME& FLOOR PLATE. C/W MARINE GRADE ALUMINIUMGLAND PLATES TO U/SIDE.(ACCESS FOR CABLES / SERVICES)

INTERNAL PLAN VIEW AT CEILING LEVEL

INTERNAL PLAN VIEW (INCLUDING ALL FLOOR APERTURES)

REFERENCE TABLE OF EQUIPMENT FOR GM TEMPORARY SUBSTATION MODULE (TAG No. Z-89902)

REF EQUIPMENT TAG DESCRIPTION QTY. WIDTH. (mm) DEPTH (mm) HEIGHT (mm) WEIGHT (kg) HEAT LOSS (kW) SUPPLIER COMMENTS

01 ETR-89902 1000 kVA TRANSFORMER 1 1580 849 1918 2249 11 ABB

02 ESW-89902 690V SWITCHBOARD 1 5050 750 2300 2850 2.858 ABB03 ECP-89902 SWITCHBOARD REMOTE CONTROL 1 400 250 600 - - ABB

04 EDB-89902 690/230V, 100 kVA LV DIST. BOARD + TRANSFORMER 1 1200 800 2200 800 - ABB

05 EIN-89902 TRIP & CLOSE UPS 1 750 455 1252 180 - ABB06 HCN-89902 HVAC EXTERNAL CONDENSER UNIT 1 970 450 845 83 - GAT07 HAH-89902 HVAC INTERNAL AIR HANDLING UNIT 1 950 950 333 81 - GAT08 HCP-89902 HVAC CONTROL PANEL 1 - - - - - GAT09 DRP-89902 FIRE PANEL 1 - - - - - CFS10 DSA-89902-01 SMOKE DETECTOR 2 - - - - - CFS11 DSA-89902-02 SMOKE DETECTOR 2 - - - - - CFS12 DHR-89902-01 RoR HEAT DETECTORS (WEATHERPROOF) 2 - - - - - CFS13 DHR-89902-02 RoR HEAT DETECTORS (WEATHERPROOF) 2 - - - - - CFS14 MAC-89902 FIRE MANUAL CALL POINT 1 - - - - - CFS15 DAL-89902-01 FIRE SOUNDER BEACON IP65 (RED) - INTERNAL 1 - - - - - CFS16 DAL-89902-02 FIRE SOUNDER BEACON IP65 (RED) - EXTERNAL 1 - - - - - CFS17 SFC-89902 CO2 FIRE EXTINGUISHER & ID SIGN 1 - - - - - CFS18 EME-89902 STAIRS & LANDINGS 1 - - - 860 - BRADGATE19 ES3-89902-01 DOMESTIC ELECTRICAL TWIN SOCKET 230V 60 Hz 16A 2 - - - - - BRADGATE 3 PIN (RCD PROT.)

20 ES3-89902-02 DOMESTIC ELECTRICAL TWIN SOCKET 230V 60 Hz 16A 2 - - - - - BRADGATE 3 PIN (RCD PROT.)

21 EFL-89902-01 FLOURESCENT LUMINAIRE C/W EMERGENCY BACK-UP 4 - - - - - BRADGATE

22 EFL-89902-02 FLOURESCENT LUMINAIRE C/W EMERGENCY BACK-UP 4 - - - - - BRADGATE

23 EFL-89902-03 FLOURESCENT LUMINAIRE C/W EMERGENCY BACK-UP 4 - - - - - BRADGATE

24 EFL-89902-04 FLOURESCENT LUMINAIRE C/W EMERGENCY BACK-UP 4 - - - - - BRADGATE

25 EIS-89902 ELECTRICAL LIGHT SWITCH ISOLATOR 1 - - - - - BRADGATE

26

27 EFL-89902-05 LIT EMERGENCY EXIT SIGN 1 - - - - - BRADGATE

28 HAC-89902-03 15 kVA 3 PHASE AUTOTRANSFORMER 1 350 242 353 25 - BRADGATE HVAC SUPPLY

29 EWL-89902 COMMON FAULT WARNING LIGHT 1 - - - - - BRADGATE

30 SEK-89902 ELECTRICAL INTERVENTION KIT (LIFE SAVING KIT) 1 840 754 270 20 - ABB

31 EEL-89902 KEY BOX/SAFE 1 190 50 250 - - BRADGATE

32 RSL-89902 PORTABLE EMERGENCY HAND LAMP 1 - - - - - BRADGATE

NOTES:

ALL EXTERNAL HINGES AND REMOVABLE PANELS ARE FIXED WITH M8 STAINLESS STEEL TORX SECURITYSCREWS.

ALL REMOVABLE PANELS ARE FIXED WITH M10 STAINLESS STEEL TORX SECURITY SCREWS.

ALL DOORS AND REMOVABLE PANELS ARE 'EARTH BONDED'.

ALL ELECTRICAL ITEMS AS SPECIFICATION.

NON-DESTRUCTIVE TESTING (NDT):

ALL LIFTING LUG WELDS AND LIFT PATH WELDS ARE TO BE MAGNETIC PARTICLE TESTED TO BRADGATE WORKSPROCEDURE 010.INSPECTION / TEST RESULTS ARE TO BE RECORDED.

MATERIAL SPECIFICATION:

STRUCTURAL:ALL RHS AND SHS SECTIONS TO BS EN 10210 S355J2HALL PLATE MATERIAL OVER 5mm THK. TO BS EN 10025 S355J2ALL PLATE MATERIAL 5mm AND UNDER TO BS EN 10025 S275JRALL ALUMINIUM GLAND PLATES 6mm MARINE GRADE, 5083 - H111

CERTIFICATES FOR ALL STRUCTURAL MATERIALS WILL BE ISSUED IN PROJECT DOCUMENTATION.

ROOF:OUTER SKIN 14swg (2.0mm) ZINTEC SHEET.INNER SKIN 16swg (1.6mm) ZINTEC SHEET.TREATMENT 100mm RWA45 MINERAL WOOL.

WALL:OUTER SKIN 14swg (2.0mm) STEEL CORRUGATED SHEET.INNER SKIN 18swg (1.2mm) ZINTEC SHEET.TREATMENT 100mm RWA45 MINERAL WOOL.

FLOOR:STRUCTURE 300x100x46 UKPFC PERIMETER BEAMS.STRUCTURE 260x90x35 UKPFC CROSS BEAMS.STRUCTURE 125x65x15 UKPFC CROSS BEAMS.TRIMMERS 10swg FOLDED CHANNEL.FLOOR PLATE 5mm PLAIN STEEL PLATE.GLAND PLATES 6mm THK. MARINE GRADE ALUMINIUM PLATE.TREATMENT 100mm RWA45 MINERAL WOOL.

EARTH BAR 50x6 THK.FLAT NON INSULATED COPPER

DOOR FURNITURE DETAILS:

ACTIVE LEAF DOOR FURNITURE:EXTERNAL STAINLESS STEEL DOOR HANDLE EXIDOR (0210081005) LEVER OPERATED C/W EURO-PROFILECYLINDER & THREE KEYS.INTERNAL EXIDOR (0210180324) 3 POINT LATCHING EMERGENCY PANIC BAR & DOOR GEAR.INTERNAL & EXTERNAL PULL HANDLES (HENDERSON 436)DOOR STAY, BRADGATE STANDARD BCL-DS-01

INACTIVE LEAF DOOR FURNITURE:TOP & BOTTOM SPRING LOADED SHOOT BOLTS.

HINGES:FURGOCAR 304 STAINLESS STEEL MAINTENANCE FREE .

WEATHER LOUVERS (TRANSFORMER ROOM):

EXTERNAL WEATHER LOUVERS COMBINED WITH INTERNAL MESH GIVE AN IP33 PROTECTION RATING.

EARTH BAR:

INTERNAL HIGH LEVEL PERIMETER EARTH BAR, 50x6 thk. UN-INSULATED PLAIN COPPER MOUNTED ON TOP HATFOLDED SECTIONS. WITH DROPPERS & THROUGH WALL EXTERNAL CONNECTION POINTS. NOTE THAT ONLY THEHORIZONTAL CABLE CONNECTION EARTH BAR LENGTH WILL BE MOUNTED ON INSULATION BOBBINS. BOLTEDDISCONNECT LINK AT LOW LEVEL.

STAIR & LANDING:

STAIRS & LANDINGS ARE TO THE BRADGATE STANDARD STEEL CONSTRUCTION DESIGN CONFORMING TO THESTANDARDS OUTLINED IN EEMUA PUBLICATION 105 SEVENTH EDITION ' FACTORY STAIRWAYS, LADDERS ANDHANDRAILS'. LANDING GRATING IS SERRATED & STAIR TREAD NOSING IS NON-SLIP. ALL STAIRS & LANDINGSCOMPONETS ARE SUPPLIED WITH EARTH BONDING TAPPING POINTS. ALL STAIRS & LANDINGS COMPONENTS AREFINISHED 'HOT DIP GALVANISED' IN ACCORDANCE WITH BS EN ISO 1461:2009NOTE, THAT STAIRS & LANDINGS ARE DESIGNED FOR PERSONNEL ACCESS USE ONLY!I.E. NO EQUIPMENT IS TO BE PLACED ON THE LANDINGS.

UNDERSTRUCTURE:

THE UNDERSTRUCTURE IS DESIGNED AS A BOLT TOGETHER SET OF FRAMES.THERE ARE A TOTAL OF SIX FRAMES, TWO ALONG EACH SIDE & ONE EITHER END.THE MODULE WILL BE CONNECTED TO THE UNDERSTRUCTURE USING BRADGATE DESIGNED CLAMPS.THE UNDERSTRUCTURE WILL BE SUPPLIED WITH ADDITIONAL BRADGATE DESIGNED CLAMPS ALLOW THE WHOLESTRUCTURE & MODULE TO BE SECURELY FASTENED DOWN WHEN INSTALLED AT SITE.THE CLAMPS WILL BE FASTENED DOWN AT SITE BY USING MECHANICAL FIXINGS INTO THE CIVILS FOUNDATION /CONCORSE AREA. NOTE IT IS THE RESPONSIBILITY OF OTHERS TO SELECT & SUPPLY THE CORRECT MECHANICALFIXINGS FOR THE CLAMPING DOWN.THERE IS PROVISION PROVIDED TO FIT EARTH BONDING BETWEEN THE MODULE & THE UNDERSTRUCTURE FRAME& PROVISION TO EARTH BOND BETWEEN EACH OF THE UNDERSTRUCTURE FRAMES.THE UNDERSTRUCTURE WIL BE 'HOT DIP GALVANISED' IN ACCORDANCE WITH BS EN ISO 1461:2009

MODULE PAINT SPECIFICATION:

PAINT SYSTEM BRADGATE STD SPEC 005 (OFF SHORE).EXTERNAL DFT 220 MICRONS.INTERNAL DFT 150 MICRONS.

OUTSIDE BS 4800 10-A-05 GOOSEWING GREYINSIDE BRADGATE STANDARD WHITE.FLOOR BRADGATE STANDARD BLACK.UNDERSIDE BRADGATE STANDARD BLACK UNDERSEAL.

TRANSPORT & STORAGE:

ALL BUILDING DOORS WILL BE SECURED WITH A SCREWED RETAINING PLATE.ALL EXTERNAL LOUVERS WILL BE TEMPORARILY BOARDED WITH PLYWOOD SHEET C/W PLASTIC MEMBRANE.DURING TRANSPORTATION.TEMPORARY PLYWOOD BOARDING OF THE HVAC EXTERNAL CONDENSER.DURING LENGTHY SEA TRANSIT & ANY STORAGE, IT IS RECOMENDED THAT TEMPORARY BACK GROUND HEATINGIS USED TO ALLEVIATE THE ONSET OF A DAMP ATMOSPHERE.THE UNDERSTRUCTURE SUPPORT FRAMES, STAIRS & LANDINGS WILL BE SHIPPED IN STANDARD ISO CONTAINERS.

APPROXIMATE WEIGHTS AS SUPPLIED BY BRADGATE CONTAINERS LTD:

EMPTY MODULE ------------------------------------------------------------------- = 10500 kgINSTALLED EQUIPMENT SUB TOTAL ---------------------------------------- = 6288 kgBRADGATE ELECTRICAL EQUIPMENT (ESTIMATED.) ---------------- = 812 kg

TOTAL CALCULATED WEIGHT = 17600 kg

PLEASE NOTE THAT THE EQUIPMENT INDIVIDUAL WEIGHTS SHOWN HAVE BEEN TAKEN FROMINFORMATION/DRAWINGS SUPPLIED TO BRADGATE CONTAINERS LTD. CUSTOMER TO ADVISE IF ANY OF THEEQUIPMENT WEIGHTS ARE INCORRECT PRIOR TO MANUFACTURE OF THE MODULE.

LIFTING & RIGGING OF MODULE:

4 OFF TOP LIFTING LUG POINTS ARE PROVIDED, NOTING THAT THESE LIFTING LUGS ARE ONLY TO BE USED FORLIFTING A FULLY FITTED OUT MODULE ONLY! THE UNDERSTRUCTURE OR STAIRS & LANDINGS MUST BE LIFTEDSEPERATLY. SEE LIFTING & RIGGING DRAWING 13239-1-5 FOR DETAILS.

0308 09 04

05

02

01

05

01

07

06

06

12

10

21 22

23 24

17

14

25

STAINLESS STEEL TRANSITFRAME FOR POWER CABLES(S.S. TYPE - TO STOP EDDY CURRENTS)

11

13

500

300

500mm WIDE LADDER RACK CARRYINGPOWER SERVICE CABLES INCLUDING ANUPPER CABLE TRAY CARRYING SIGNAL CABLES

300mm WIDE LADDERRACK CARRYINGPOWER SERVICE CABLES

RUBBER MAT IN FRONT OF SWITCHBOARDS

28

02

14

25

17

2715

0308 09

16

STEEL TRANSIT FRAMEFOR SIGNAL CABLES

M12 PERIMETER EARTH BAR THRO'WALL EXTERNAL CONNECTION

M12 PERIMETER EARTH BAR THRO'WALL EXTERNAL CONNECTION

30

30

28

04

1100

800

150

31

31

1000

MAT

29

455

31

THIS DRAWING IS THE SOLE PROPERTY OF 'BRADGATE CONTAINERS LTD' AND MAY NOTBE COPIED OR USED FOR ANY PURPOSE OTHER THAN THAT FOR WHICH IT IS SUPPLIEDWITHOUT THE EXPRESS WRITTEN PERMISSION OF 'BRADGATE CONTAINERS LTD' (©2013)

BRADGATE CONTAINERS LTD. LEICESTER ROAD,

SHEPSHED, LEICS.

LE12 9EG

ISSUE SHEET SIZE

A0

BQ/

THIRD ANGLE PROJECTION

IF IN DOUBT ASK - DO NOT SCALE GENERAL FABRICATING TOLERANCES

ALL DIMENSIONS UP TO & INCLUDING 300 ±1 IN MILLIMETRES 301 UP TO 1500 ±2UNLESS STATED ABOVE 1500 ±3

DESCRIPTION

ORIGINAL ISSUE

ABB Ltd.

30/7/13G.N. Rogers17433

1:20

N/A NCR

DH 31/7/13

31/7/13

Equipment Layout of Generation Substation Module(690V) for BP Clair Ridge Temporary Substations

13239-1-1 D 1

SUPPLIER DRAWING DECAL

ProjectID

Alternative Document No.

1- Accepted (Reviewed andAgreed)

2- Comments to be Incorporatedand Resubmitted

Signature Date

3- Rejected, Do Not Start Work(Comments to beIncorporated andresubmitted)

4- For Information

Review Status

Short RequisitionNo/PO Identifier

Sequence Sheet. Rev

5- Cancelled/Superseded

6- As Built

Purchaser Document Number

Originator/ContractorCode

SDDRCode

CLB- AA- AANNNN-ANN ANN- NNNN- (NN) NN

DRAWING TO BE READ IN CONJUNCTION WITH SHEET 2

B ALLUPDATED INLINE WITH COMMENTS

BY AMEC ON 8/8/13.THE FOLLOWING NOTE SUBSECTIONS

ALSO UPDATED; MATL. SPEC.DOOR FURNITURE DETAILS.

STAIR & LANDINGUNDERSTRUCTURE.

06.09.13

C ALLUPDATED INLINE WITH COMMENTS

BY AMEC REC'D ON 11/9/13. 19.11.13

D 4C4F

LIGHTING & SMALL POWER DIST. BOARD(WAS ITEM 26) REMOVED & TABLEUPDATED INLINE WITH CUSTOMER

COMMENTS DATED 22/1/14

03.02.14

gbnatil
Rectangle
Page 3: SUPPLIER DOCUMENT FRONT SHEET - .NET Framework

PLAN VIEW ON MODULE ROOF

Y

8000

SIDE ELEVATION

END VIEW

END VIEW

4 OFF LIFTING LUGS

7850 LIFT LUG CRS.75 75

M16 SAFETY HARNESS BOSSES(TYPICAL 8 POSITIONS)

TRANSFORMER ROOM VENTILATIONWEATHER LOUVERS WITH MESHPANEL TO INSIDE (SEE NOTES).

8000

SIDE ELEVATION

7850 LIFT LUG CRS. 7575

UNDERSTRUCTURE BOLT TOGETHER FRAMESSEE NOTES & DRAWING 13239-1-6 SHEET 1

RETANGULAR BASE EYE PLATESFULLY WELDED TO SIDE & END RAILSFOR LASHING DURING TRANSPORTATION(7 POSITIONS EACH SIDE & 4 POSITIONS EACH END)

2255

CLE

ARAN

CE H

T.

2555

3400

845

1094.5405.5

FULLY LINED REMOVABLE HEADER PANEL TO ALLOW EQUIPMENTACCESS FITTED WITH 2 OFF M12 EYEBOLTS TO BS4278. FULLYSEALED USING NEOPRENE BETWEEN PANEL & MODULE WALL

HVAC SERVICES PASSTHROUGH TRANSIT

3040 OVER LIFT LUGS

30001400 APPROX.

4400 APPROX.

3040 OVER LIFT LUGS

REMOVABLE BOTTOM THREASOLDTO ALLOW TRANSFORMER INSTALLATIONOR REMOVAL I.E. GIVING CLEAR ACCESS

TO AT FLOOR LEVEL

2795

STR

UCTU

RAL O

PENI

NG

BOLT-ON UN-LINNED CORRUGATED REMOVABLE END PANEL.C/W A PAIR OF M20 EYEBOLTS TO BS 4278 POSITIONED AT THE TOP CORNERS.APERTURE SIZE SHOWS STRUCTURAL OPENING. NOTING THAT THIS IS THE ONLY ACCESSIN TO THE TRANSFORMER ROOM.

2600 STRUCTURAL OPENING

5 FLO

OR P

LT.

3000

1800

100 2800 100

200

5 FLO

OR P

LT.

2102160 REF.

1675

125

HVAC AHU CONDENSATEDRAIN PASSES OUT THRO'

THE FLOOR

LADDER RACK CARRYINGPOWER SERVICE CABLES

430 APER.

06

06

06

07

18

18

18

CABLE TRAY CARRYINGSIGNAL CABLES

04

19

20

25

14

27

1500 2400

02

VERTICAL EARTH BAR MOUNTEDON ISOLATORS FOR CONNECTING

OF FIELD EARTH CABLES RISINGUP THROUGH FLOOR APERTURE

EARTH BAR BOLTED DISCONNECT LINK

EARTH BAR RISER MOUNTEDTO INNER WALL ON STEEL

BRACKETS (NON-ISOLATED)

PERIMETER EARTH BAR MOUNTEDTO INNER WALL ON STEEL

BRACKETS (NON-ISOLATED)

EARTH BAR RISER MOUNTEDTO INNER WALL ON STEEL

BRACKETS (NON-ISOLATED)

EARTH BAR RISER MOUNTEDTO INNER WALL ON STEELBRACKETS (NON-ISOLATED)

06

EARTH BOSS TAPPED M12(EXTERNAL BUILDING EARTH CONNECTION)

EARTH BOSS TAPPED M12(EXTERNAL BUILDING EARTH CONNECTION)

EARTH BOSSES TAPPED M12 WELDEDTO MODULE & REMOVABLE PANEL.

CONNECTED WITH COVERED EARTH BRAID

4000 4000

UNDE

RSTR

UCTU

REFR

AME

SPLIT

M12 PERIMETER EARTHBAR EXTERNAL CONNECTION

SECTION A-A

1500

U/S

TRUC

T.36

63 M

ODUL

E HT

.

5163

OVE

RALL

HT.

3000

A

A

TRANSFORMER ROOM VENTILATIONWEATHER LOUVERS WITH MESHPANEL TO INSIDE (SEE NOTES).

1629

920.5

LADDER RACK CARRYINGPOWER CABLES

375500 APER.1925100 100

5 FLO

OR P

LT.

1829

.5

17

3000

01

SIGNAL CABLE TRANSIT FRAME

POWER CABLE TRANSIT FRAME

CABLE APERTURE C/W MARINEGRADE ALUM. GLAND PLATE

030908

B

B

EARTH BOSS TAPPED M12(LANDING TO BUILDING EARTH CONNECTION)

EARTH BOSS TAPPED M12(EXTERNAL BUILDING EARTH CONNECTION)

03

17

30

1728

31

18

!Warning

No Equipment is tobe placed or wheeledonto the landing area

WARNING SIGN SHOWN, FITTEDTO INSIDE OF DOOR

THIS DRAWING IS THE SOLE PROPERTY OF 'BRADGATE CONTAINERS LTD' AND MAY NOTBE COPIED OR USED FOR ANY PURPOSE OTHER THAN THAT FOR WHICH IT IS SUPPLIEDWITHOUT THE EXPRESS WRITTEN PERMISSION OF 'BRADGATE CONTAINERS LTD' (©2013)

BRADGATE CONTAINERS LTD. LEICESTER ROAD,

SHEPSHED, LEICS.

LE12 9EG

ISSUE SHEET SIZE

A0

BQ/

THIRD ANGLE PROJECTION

IF IN DOUBT ASK - DO NOT SCALE GENERAL FABRICATING TOLERANCES

ALL DIMENSIONS UP TO & INCLUDING 300 ±1 IN MILLIMETRES 301 UP TO 1500 ±2UNLESS STATED ABOVE 1500 ±3

DESCRIPTION

ORIGINAL ISSUE

ABB Ltd.

30/7/13G.N. Rogers17433

1:30

N/A NCR

DH 31/7/13

31/7/13

G.A. of Generation Substation Module (690V)for BP Clair Ridge Temporary Substations

13239-1-1 D 2

SUPPLIER DRAWING DECAL

ProjectID

Alternative Document No.

1- Accepted (Reviewed andAgreed)

2- Comments to be Incorporatedand Resubmitted

Signature Date

3- Rejected, Do Not Start Work(Comments to beIncorporated andresubmitted)

4- For Information

Review Status

Short RequisitionNo/PO Identifier

Sequence Sheet. Rev

5- Cancelled/Superseded

6- As Built

Purchaser Document Number

Originator/ContractorCode

SDDRCode

CLB- AA- AANNNN-ANN ANN- NNNN- (NN) NN

DRAWING TO BE READ IN CONJUNCTION WITH SHEET 1

B ALLUPDATED INLINE WITH COMMENTS

BY AMEC ON 8/8/13.UPDATED TO SHOW LOUVERS WHICHGIVE THE CORRECT VENTILATION TOTHE TRANSFORMER (POST CALCS.)

06.09.13

C 6E'LANDING AREA' WARNING SIGN ADDED

TO INSIDE OF DOOR 19.11.13

D 5E LIGHTING & SMALL POWER DIST. BOARD

(WAS ITEM 26) REMOVED INLINEWITH CUSTOMER COMMENTS

DATED 22/1/14

03.02.14

gbnatil
Rectangle