10
Vacuum Interrupters for Medium Voltage

Sym Katalog

Embed Size (px)

DESCRIPTION

vacuum chamber for Circuit Breaker

Citation preview

  • 03571_Vacuum Interrupters 22.10.1999 12:49 Uhr Seite 2

    Probedruck

    C M Y CM MY CY CMY K

    Vacuum Interrupters for Medium Voltage

  • 03571_Vacuum Interrupters 22.10.1999 12:49 Uhr Seite 3

    Probedruck

    C M Y CM MY CY CMY K

    Today, vacuum as an arcextinguishing medium pro-vides the most cost-effectivesolution for medium-voltagecircuit-breakers.

    Siemens vacuum interruptersconvince in respect of relia-bility, long service life and fullyenvironmentally friendly mate-rials used for and during pro-duction process.Decades of experience, con-tinuos research and develop-ment as well as latest pro-duction technology andupdated quality conceptsmakes Siemens superior invacuum technology.

    The high reliability of ourvacuum interrupters arebased on all commondesigns:

    The arc chamber that actsas a vapour shield: During the switching process, ametal vapour arc occurs between the contacts andis extinguished at current zero. The small amount ofmetal vapour that is not redistributed over the contact pieces condenseson the arc chamber wall. The arc chamber protects the inside of the ceramic housing against the effectof the metal vapour, whichwould reduce the insulation.

    Reliable, Maintenance-Free and Environmentally Friendly

    One contact is fixed tothe ceramic housing. The other is a moving contact connected to the housing via bellows.

    The metal bellows forms the vacuum-tight connection between the moving contact and the interrupter housing, thus allowing the moving contact to perform its stroke. The stroke is a function of the rated voltageof the vacuum interrupter.

    The insulators are made ofmetallized aluminum oxideceramics.

    All connections, whether metal-to-metal or metal-to-ceramics, are brazed in vacuum ovens and there-fore provide a vacuum sealfor life.

    Long service life means

    up to 30,000 interruptions with rated current;

    high short-circuit breaking operations(average of 50 times);

    mechanical operations ofup to 2 million(e.g. contactor interrupters).

    The vacuum interrupters aremanufactured in an environ-mentally friendly productionprocess, using only materialsfor the interrupters which caneasily be disposed afterusage.

    Selected materials, minimalwear and contact erosionensure that the vacuum inter-rupter is maintenance-freefor its entire life and makesfor maximum availability.

    Va c u u m I n t e r r u p t e r s

    2

  • 03571_Vacuum Interrupters 22.10.1999 12:49 Uhr Seite 4

    Probedruck

    C M Y CM MY CY CMY K

    Switching Duties

    Loads with highswitching rate

    The use of vacuum interrup-ters is an especially economicproposition in cases whereloads have to be switchedfrequently (e.g. motors, arcfurnaces, reactive powercompensating coils and capac-itors). This is because theyare capable of switching ratednormal current up to 30,000times.

    Capacitive currents

    Unloaded cables, overheadlines and capacitor banks areswitched off without voltagesurges because Siemens va-cuum interrupters are capableof interrupting capacitive cir-cuits without restrike. Evenwhere the contact gap issmall, dielectric recovery isremarkable. In numeroustests, currents of up to 1000 Aat 36 kV were reliably inter-rupted without restrike. Thecapacitive currents switchedin test laboratories are limitedby the capacitors installed,and operating experience hasshown that even greater ca-pacitive currents can be relia-bly switched. Even parallelingof capacitors poses no prob-lems.

    Short-circuit currents

    Siemens vacuum circuit-breakers switch short-circuitcurrents of up to 80 kA. Thearcing times are less than15 ms, even at the highestcurrents. These short arcingtimes and the minimal arcvoltage keep energy conver-sion in the break to a mini-mum. Consequently, thebreakers are suitable not onlyfor the usual O-0.3s-CO auto-reclosure cycle, but also formultiple auto-reclosures.An O-0.3s-CO-15s-CO-15s-CO-15s-CO duty cycle wascarried out successfully(up to 31.5 kA).

    Small inductive currents

    Magnetizing currents ofunloaded transformers areinterrupted without unduevoltage surges building up,because the chopping currentof Siemens vacuum interrup-ters is below 5 A. In numer-ous tests it was shown that

    the overvoltagefactor k was lessthan 3.1 at 12 kVand less than2.2 at 24 kV.

    NXACT

    vacuum

    circuit-breaker

    module

    Horizontal

    installation of

    vacuum

    interupters

    High power

    vacuum

    circuit-breaker

    Traction

    vacuum

    circuit-breaker

    Va c u u m I n t e r r u p t e r s

    3

  • 03571_Vacuum Interrupters 22.10.1999 12:49 Uhr Seite 5

    Probedruck

    C M Y CM MY CY CMY K

    Compact and Economical Concept for the Low Range of Rating

    Va c u u m I n t e r r u p t e r s

    Single ceramic housing

    interrupters with copper

    flanges were developed

    with the creation of a

    compact circuit-breaker

    and switchgear assembly

    design as well as con-

    tactors and load breakers

    uppermost in mind.

    4

  • 03571_Vacuum Interrupters 22.10.1999 12:49 Uhr Seite 6

    Probedruck

    C M Y CM MY CY CMY K

    Versatile Standard Concept for all Voltage Levels

    Va c u u m I n t e r r u p t e r s

    With their two-element ceramic

    housing and internal

    copper arc chamber, the

    interrupters are a convincing

    concept for both industry

    and power supply utilities.

    5

  • 03571_Vacuum Interrupters 22.10.1999 12:49 Uhr Seite 7

    Probedruck

    C M Y CM MY CY CMY K

    The High-End Solutionfor up to 40.5 kV or High Short-Circuit Ratings

    Va c u u m I n t e r r u p t e r s

    The interrupters with a

    two-element ceramic housing

    and external copper arc

    chamber were specially

    developed for requirements

    on the 36-kV level and

    for short-circuit ratings

    50 kA e.g. generator

    circuit-breakers, as well

    as for traction systems

    with 16 2/3 Hz.

    6

  • 03571_Vacuum Interrupters 22.10.1999 12:49 Uhr Seite 8

    Probedruck

    C M Y CM MY CY CMY K

    Arc Quenching

    Va c u u m I n t e r r u p t e r s

    When an arc is quenched, itare the contacts (the primecomponents of a vacuum in-terrupter) that must meet thehighest demands in terms of:

    High short-circuit breakingcapacity;

    High dielectric strength;

    Minimal chopping current;

    Minimal contact erosion;

    Minimal contact resistance.

    The requirements have allbeen met to optimum effect,in both technical and econo-mic terms, as a result of basicresearch in our laboratories,development of suitable ma-terials (including the contactgeometry) and state-of-the-art manufacturing technology.

    High dielectric strength

    On opening of the contact,the current to be interruptedproduces a metal vapour arcdischarge and continues flow-ing through the plasma untilthe next current zero. The arcis extinguished in the vicinityof the current zero, and themetal vapour loses its con-ductivity within a few micro-seconds.

    The dielectric strength of thebreak is thus reestablishedvery quickly. The steady-statepressure in a vacuum interup-ter is less than 10-9 bar. Con-tact clearances of between6 and 20 mm suffice thereforeto produce a high dielectricstrength.

    Minimal chopping current

    Below a certain minimum cur-rent, the metal vapour arc isinterrupted prior to the naturalcurrent zero. In inductive cir-cuits this chopping currentmust therefore be as low aspossible in order to preventthe build-up of impermissiblyhigh voltage surges.The magnitude of the chop-ping current depends largelyon the contact material used.Optimized chromium copperkeeps the chopping currentbelow 5 A.

    High breaking current

    Two contact geometry vari-ants are used in Siemensvacuum interrupters.

    Radial magnetic field contact:With this contact, the arc re-mains diffuse up to currentsof 10 kA (instantaneous val-ue). Higher currents flowthrough a constricted arc.

    Local overheating of the con-tacts must be avoided. Anadditional radial magnetic fieldproduces a force which drivesthe arc around the contactarcing rings. In this way, thecontact erosion occurring inthe arc root is distributed overthe full arcing ring area.

    With axial magnetic field con-tacts, short-circuit currents ofup to 80 kA can be reliablyhandled.

    The axial magnetic field al-lows a diffuse arc even wherethe current intensity is high.The disc-shaped contact sur-faces are uniformly stressedover their full area.Both the radial and axialmagnetic fields are producedby special current paths pro-vided in the contacts underthe surface.

    Minimal contact erosion

    The metal vapour plasma ofthe vacuum arc is highly con-ductive. The arc voltage (only20 V to 200 V) and the energyconversion in the break arelikewise minimal. The highconductivity, in conjunctionwith the minimal energy con-version and short arcing timesare the reasons for the mini-mal contact erosion and thelong electrical service life ofthe vacuum interrupters.

    Minimal contact resistance

    In a vacuum, the contact sur-faces are free of impuritiesand pollution layers. Highlyconductive materials areused. This ensures minimalcontact resistance. Betweenthe two outer terminations ofan interrupter the figure isbetween 8 and 15 . Heatlosses are correspondinglylow.

    Current distributionof a diffuse arc

    Axial magnetic field contact

    Contact piececonstructionB: Contact carrierC: Contact disc CrCu

    Current pathand directionof a constricted arc

    Radial magnetic field contact

    ContactconstructionA: Arcing ring:Contact material CrCuB: Contact carrier

    Diffuse high current discharge(i=60 kA)(Axial magnetic field contact)

    Arc formations with radial andaxial magnetic field contacts

    Diffuse arc prior to current zero(i=10 kA)(Axial magnetic field contact)

    Constricted arc(i=40 kA)(Radial magnetic field contact)

    Diffuse arc prior to current zero(i=2 kA)(Radial magnetic field contact)

    7

    B

    C

    B

    C

    A

    B

    A

    B

  • 03571_Vacuum Interrupters 22.10.1999 16:19 Uhr Seite 5

    Probedruck

    C M Y CM MY CY CMY K

    Va c u u m I n t e r r u p t e r s

    Supply Program

    Ratedvoltage

    kV

    7.2

    Rated light-ning impulsewithstandvoltagekV

    Rated powerfrequencywithstandvoltagekV

    Ratedshort-circuitbreakingcapacitykA

    Ratedshort-circuitmakingcapacitykA

    Rated current and interrupter type

    630 A 1250 A 1600 A 2000 A

    60 20 12.5 31.5 VS 7000116 40 VS 1202020 50 VS 1202525 63 VS 1203131.5 8040 10050 125

    80 200

    V

    12 75 28 32.8 VS 1201213.116 40 VS 1202020 50 VS 1202525 63 VS 1203131.5 80 V40 10050 125

    80 20015 95 36 20 50

    V25 6331.5 8040 10050 12563 160

    17.5 95 38 20 50V25 63

    31.5 8040 10063 160

    24 125 50 VS 24016

    V

    36** 170** 70 16 4020 50

    V25 63VS 30029 / VS31.5 80

    V40 100

    V

    VS25016*/ VS 25005

    800 A

    VS 25005

    63 160

    63 160

    80 200

    16 4020 5025 6331.5 8040 100

    80 200

    Ratedvoltage

    kV7.27.21224

    RatedlightningimpulsewithstandvoltagekV60607595

    RatedpowerfrequencywithstandvoltagekV 20 20 30 50

    Ratedcurrent

    A400400400800

    Max.breakingcurrent

    kA3.23.23.23.6

    Max.makingcurrent

    kA4444.5

    Number ofoperatingcycles atratedcurrent

    1.0 106

    0.25 106

    0.5 106

    0.5 106

    Interruptertype

    VS 7202VS 7203VS 12003VS 24001

    Dimension

    diameterin mm

    lengthin mm

    75606868

    134115160190

    8

    Vacuum circuit-breaker interrupters (50 to 60 Hz)

    Vacuum contactor interrupters (50 to 60 Hz)

  • 03571_Vacuum Interrupters 22.10.1999 16:19 Uhr Seite 6

    Probedruck

    C M Y CM MY CY CMY K

    * With the use of aninsulating covering

    ** Higher values on request

    Va c u u m I n t e r r u p t e r s

    Design A Design B Design C

    l

    d

    l

    d

    l

    d

    2500 A 3150 A 4000 A

    VS 15100VS 15050

    VS 17080

    VS 17005

    VS 17005VS 15100VS 15050

    VS 10047

    VS 17005VS 15100

    VS 10047

    VS 17005

    VS 10047

    VS 25007

    VS 36025/ VSG 36031*

    VS 30040

    VS 30040

    VS 15050

    VS 15100

    VS 10047

    VS 17080

    VS 17080

    VS 17080

    Type Design Diameterd (mm)

    LengthI (mm)

    VSG 36031

    9

    VS 70001

    VS 12012

    VS 12020

    VS 12025

    VS 12031

    VS 24016

    VS 17005

    VS 15100

    VS 25016

    VS 25005

    VS 25007

    VS 36025

    VS 15050

    VS 10047

    VS 17080

    VS 30029

    VS 30040

    A

    A

    A

    A

    A

    B

    B

    B

    B

    B

    B

    B

    C

    C

    C

    C

    C

    C

    68

    68

    68

    76

    85

    96

    100

    125

    100

    110

    116

    116

    135

    138

    125

    156

    123

    138

    124

    124

    144

    187

    219

    284

    219

    255

    219

    284

    315

    326

    368

    379

    315

    379

    494

    494

    Interrupters to ANSI Standard

    Interrupters to Chinese Standard

    Load break switch

    Recloser

    Transformer tap changer

    Traction systems (16 2/3 Hz)

    Installation under gas and oil pressure

    Special applications

    Dimensions (in mm) Illustrations of principle

  • 03571_Vacuum Interrupters 22.10.1999 16:46 Uhr Seite 1

    Probedruck

    C M Y CM MY CY CMY K

    Quality assurance

    This starts at the very drawingboard, since this is where de-signs and jointing methods

    are selected, with aview to eliminatingsources of faults inmanufacture. The var-rious manufacturingprocess stages aredevised in close

    cooperation between produc-tion and development depart-ments, with safety and easeof handling in mind as well asthe technical requirements.

    Material testing

    This is of particular signifcance,due to the special materialsused. The technical data ofthe materials agreed with oursuppliers are subject to verytight tolerance ranges, adher-ence to which is checked onevery consignment delivered.Extensive qualitative andquantitative gas analyses en-sure that only fully satisfactorymaterials are processed.

    Quality Assured by Sophisticated Testing

    Vacuum tightness

    A special internal pressuremeasuring process has beendeveloped to test for leakageeven after the interrupter hasbeen sealed. In a stationarymeasuring facility, anelectrical and a magneticfield are superimposedin such a way thatfree electrons ionizeany residual gasmolecules andproduce ameasuring currentthat varies as a functionof the pressure. All interrup-ters are stored in argon andthen tested by means of thisprocess; they are released forshipment only if a leakagerate of up to 10 -17 bar x l/s isnot exceeded. This amountsto a storage time of 20 yearswithout any loss in quality.Time compression methodscan be used to verify such astatement.

    To this end, circuit-breakerinterrupters were stored for5000 hrs at 300 C. It wassubsequently verified thatno inadmissible rise inpressure had occurred.

    Powerto the

    Siemens Aktiengesellschaft Subject to change without prior notice Order No. E50001-U229-A117-X-7600Printed in GermanyDispo-Stelle 3040061D6089 Ra/EK 101374 PA 10991.

    Siemens AGPower Transmission andDistribution GroupMedium Voltage DivisionP.O. Box 32 20D-91050 Erlangen

    www.ev.siemens.de