Symmetra MW UPS

800 kW400 V

InstallationGuide

Page 2: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety
Page 3: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Contents

Safety ......................................................................1

IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Symbols used in this guide . . . . . . . . . . . . . . . . . . . . . . . . . 1

Installation safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

System Overview......................................................3

UPS Sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Serial number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Inverter Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Control Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Input/Output Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Configuration 1 (Inverter Section placed to the left) . . . . . . . . 4

Configuration 2 (Inverter Section placed to the right) . . . . . . . 5

External Bypass Static Switch. . . . . . . . . . . . . . . . . . . . . . . . . . . 6Serial number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Electrical Installation ................................................7

Typical UPS Wiring Principle . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Power wiring overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

External disconnection switches . . . . . . . . . . . . . . . . . . . . . 8

Input/Output wiring precautions . . . . . . . . . . . . . . . . . . . . . 8

Top Cable Entry. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Preparing for top cable entry (Default) . . . . . . . . . . . . . . . . . 9

Battery cable connections (top cable entry) . . . . . . . . . . . . . 10

PE and AC cable connections (top cable entry) . . . . . . . . . . . 12

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i

Page 4: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Bottom Cable Entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Preparing for bottom cable entry . . . . . . . . . . . . . . . . . . . . 13

Battery cable connection (bottom cable entry) . . . . . . . . . . . 15

PE and AC cable connections (bottom cable entry) . . . . . . . . 17

External Bypass Static Switch Wiring . . . . . . . . . . . . . . . . . . . . 18Top cable entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Bottom cable entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Communication cable overview . . . . . . . . . . . . . . . . . . . . . . . . 21

Relay Board (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Location of optional Relay Board . . . . . . . . . . . . . . . . . . . . 22

Communication cables with optional Relay Board . . . . . . . . 23

Relay Board functions . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Specifications ........................................................ 27

Low-Impedance/High-Impedance Earthing . . . . . . . . . . . . . . . . 27

Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28AC Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

DC Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

AC Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

AC Input External Bypass SSW . . . . . . . . . . . . . . . . . . . . . 29

Heat dissipation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Torque specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Required Breaker Settings (400 V Systems) . . . . . . . . . . . . . . . 31Input and upstream breakers — minimum settings . . . . . . . . 31

Output and downstream breakers -— minimum settings . . . . 31

Appendix .............................................................. 33

System and Protective Earthing . . . . . . . . . . . . . . . . . . . . . . . . 33

TN Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Reference to IEC 60364-4-41 413.1.3 . . . . . . . . . . . . . . . . . 34

Reference to IEC 60364-5-54 546.2.3 . . . . . . . . . . . . . . . . . 34

Additional requirements for generating sets (IEC 60364-5-55 551.4.2) . . . . . . . . . . . . . . . . . . . . . . . . . 35

Protective devices in TN systems . . . . . . . . . . . . . . . . . . . . 35

ii Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B

Page 5: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

TT Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Reference to IEC 60364-4-41 413.1.4 . . . . . . . . . . . . . . . . . 37

Protective devices in TT systems . . . . . . . . . . . . . . . . . . . . . 37

IT Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

Reference to IEC 60364-4-41 413.1.5 . . . . . . . . . . . . . . . . . 39

Protective devices in IT systems . . . . . . . . . . . . . . . . . . . . . 40

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B iii

Page 6: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety
Page 7: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Safety

IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS

This guide contains important instructions for 800K800H that should be followed when handling the UPS, External Bypass Static Switch, Battery Enclosures, and Batteries.

Symbols used in this guide

WARNING!Indicates an electrical hazard, which, if not avoided, could result in injury or death.

CAUTION!Indicates a hazard, which, if not avoided, could result in injury or death.

Note

Indicates important information.

Indicates that more information is available on this subject in a different section of this manual.

See also

Indicates that more information is available on the same subject in a different manual.

Main Protective Earthing Terminal symbol.

Ground symbol.

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 1

Page 8: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Safety: IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS

Installation safety

Press the optional EPO (Emergency Power Off) button to switch off all AC and DC power supply to connected equipment in the room and to cut off the load supply. The EPO is typically located on a wall in the room in which the UPS is installed. See “Communication cable overview” section for information on how to wire the UPS to the EPO.

WARNING!Before installation work is carried out, check and test that all AC and DC power source breakers are in open position.

WARNING!Only personnel trained in the construction and operation of the equipment, and the electrical and mechanical hazards involved, may install or remove system components.

WARNING!Do not use High Voltage Testing Equipment. This equipement will destroy the electronic circuits in the unit.

CAUTION!The system is equipped with an optional auto-start function, enabling the system to start without any warning when power is applied.

CAUTION!All wiring to be in accordance with applicable national and/or local electrical wiring rules.

This unit contains components that are sensitive to electrostatic discharge (ESD). Follow proper ESD procedures to avoid severe damage to electronic components.

EPO

2 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B

Page 9: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

System Overview

UPS Sections

Serial number

The serial number is stated on the type label behind the finishing panel above the display unit. Remove finishing panel to see serial number.

Inverter Section

The Inverter Section regulates the UPS output and operates from battery power in the event of utility input loss.

Control Section

The Control Section controls and monitors the UPS and the Mains Static Switch Module (incorporated in the Control Section).

Input/Output Section

The Input/Output Section provides electrical connection of input and output.

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 3

Page 10: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Configurations

The UPS system can be configured in two ways. The Inverter Section can be placed either to the left or to the right of the Control Section. The two configurations are shown below.

Configuration 1 (Inverter Section placed to the left)

ON OFF EMO

Weight: 610 kg

Weight: 480 kg

2032

mm

Width:1690 mm

Width:1012 mm

1067 mm

Width:1014 mm

Control Section Input/Output SectionInverter Section

Total weight of UPS sections:4220 kg

Total width of UPS sections:3716 mm

Weight: Without Power Modules: 2456 kgWith Power Modules: 3130 kg

4 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B

Page 11: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

System Overview: Configurations

Configuration 2 (Inverter Section placed to the right)

Weight: 610 kg

Weight: 480 kg

Width:1012 mm

Width:1014 mm

Control SectionInput/Output Section

Total width of UPS sections:3716 mm

Total weight of UPS sections:4220 kg

2032

mm

1067 mm

Weight: Without Power Modules: 2456 kgWith Power Modules: 3130 kg

Width:1690 mm

Inverter Section

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 5

Page 12: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

External Bypass Static Switch

The External Bypass Static Switch (External Bypass SSW) transfers the load (manually or automatically) from the UPS to an alternate source without interrupting the supply to the load.

Serial number

The serial number is stated on the type label behind the finishing panel above the display unit. Remove finishing panel to see serial number.

~~

Weight:1 MW: 460 kg

2032 mm

Width:1016 mm

1067mm

External Bypass Static Switch

6 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B

Page 13: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Electrical Installation

Typical UPS Wiring Principle

Power wiring overview

See also

See separate guide on parallel operation for wiring overview in parallel systems.

Mai

nten

ance

Byp

ass

Pan

el (

MB

P)

Sym

met

ra M

W

Ext

erna

l Byp

ass

Sta

tic S

witc

h

Bat

tery

Bre

aker

Box

1

Bat

tery

Bre

aker

Box

2

Bat

terie

s 1

Bat

terie

s 2

MA

INS

6

6

9 9

1. 2. 3. 4. 5. 6. 7.

8. 9. 10.

11.

12.

13.

14.

MA

INS

SO

UR

CE

3X

40

0/2

30

V T

N-S

(P

RO

VID

ED

BY

OT

HE

RS

).

Q1

-

Q6

WIT

H 2

NO

/2N

C A

UX

ILIA

RY

CO

NT

AC

TS

.

Q7

, Q

8 D

C R

AT

ED

TH

ER

MA

L M

AG

NE

TIC

TR

IP M

OL

DE

D C

AS

E C

IRC

UIT

BR

EA

KE

R.

WIT

H 2

4V

OL

T D

C U

ND

ER

VO

LT

AG

E R

EL

EA

SE

(U

VR

) A

ND

2N

O/2

NC

AU

XIL

IAR

Y C

ON

TA

CT

S.

AL

L A

C P

OW

ER

CA

BL

ING

IS

L1

,L2

,L3

,N,P

E.

UP

S I

NP

UT

AN

D O

UT

PU

T C

ON

DU

CT

OR

S M

US

T B

E I

N S

EP

AR

AT

E C

AB

LE

RU

NS

.

UP

S A

ND

ST

AT

IC B

YP

AS

S W

ITH

ST

AN

D R

AT

ING

, Ic

w =

20

0 K

A

SE

E T

HE

IN

ST

AL

LA

TIO

N G

UID

E F

OR

TH

E B

RE

AK

ER

SE

TT

ING

S O

F Q

1,

Q3

, Q

4 A

ND

Q5

.

DC

CA

BL

ING

SH

OU

LD

BE

SE

GR

EG

AT

ED

FR

OM

AC

CA

BL

ING

SE

E B

AT

TE

RY

IN

ST

AL

LA

TIO

N I

NF

OR

MA

TIO

N

PO

WE

R W

IRIN

G A

ND

CO

NT

RO

L W

IRIN

G M

US

T B

E S

EG

RE

GA

TE

D.

AC

CIR

CU

IT C

AB

LE

LE

NG

TH

S (

INP

UT

AN

D O

UT

PU

T)

SH

OU

LD

BE

EQ

UA

L O

N A

LL

MO

DU

LE

S

DC

CIR

CU

IT C

AB

LE

LE

NG

TH

S S

HO

UL

D B

E E

QU

AL

ON

AL

L M

OD

UL

ES

= C

AB

LIN

G P

RO

VID

ED

BY

OT

HE

RS

INS

TA

LL

AT

ION

MU

ST

CO

MP

LY

WIT

H N

AT

ION

AL

AN

D L

OC

AL

EL

EC

TR

ICA

L R

UL

ES

.

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 7

Page 14: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Electrical Installation: Typical UPS Wiring Principle

External disconnection switches

Input/Output wiring precautions

WARNING!The UPS has no internal manual disconnect devices to switch off external AC (Q1 and Q5) and DC (Q7 and Q8) input power. Ensure that disconnection devices are available as separate components for this installation.

Note

The installer must provide each external disconnection device for this UPS system with labels displaying the following text:“Isolate the Uninterruptible Power Supply (UPS) as instructed in the User Guide before working on circuit.”

WARNING!Only personnel trained in the construction and operation of the equipment, and the electrical and mechanical hazards involved, may install or remove system components.

WARNING!Before installation work is carried out, check and test that all AC and DC power source breakers are in open position.

WARNING!Supply the UPS from a 3 × 400/230 V, L1, L2, L3, N, PE source or a high-impedance grounded system.

CAUTION!All wiring to be in accordance with applicable national and/or local electrical wiring rules.

Note

Use only copper conductors.

8 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B

Page 15: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Top Cable Entry

Preparing for top cable entry (Default)

Cable entry in Top Cover of Input/Output Section.

Loosen the 8 bolts in both cable entry covers (4 bolts in each cover). Drill holes for the grommets in areas shown. Install the grommets and re-fit the covers.

NN

L2 IN

L1 IN

L3 IN

L1 OUT

L2 OUT

L3 OUT

AC IN AC OUT

BAT 1 BAT 2

92 93

9590

91 94

L3 OUT

L2 OUT

92 93

90

91 94

95

L1 OUT

L3 IN

L2 IN

L1 IN

58 mm

44.45 mm44.45 mm

IN/OUT power cable (top entry)

AC IN cable entry

AC OUT cable entry

DC cable entry

DC cable entry

Top viewM6 Bolt

Top view

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 9

Page 16: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Electrical Installation: Top Cable Entry

Install cable lugs on busbars. Use M12 bolts. Feed cables through the top grommets.

Connect L1, L2 and L3 to busbars where indicated.

Battery cable connections (top cable entry)

WARNING!Make sure that the battery breakers are open (OFF) prior to running the cables.

CAUTION!Refer to the battery manufacturer’s installation manual.

CAUTION!The minimum DC voltage rating of the battery supply over-current protective device is 500 V.

Note

Over-current protection for the battery circuit is required by national wiring rules.

10 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B

Page 17: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Electrical Installation: Top Cable Entry

Feed the battery cables through the grommets

Connect cables from battery system.

Connect cables from battery system.

BAT1+

BAT2-

L3 In

L2 In

L1 In

L2 Out

L3 Out

L1 Out

BAT1-

BAT1+

BAT2+

BAT2—

N N

BAT1- BAT2+

IN/OUT power cable (top entry)

Top view of Input/Output Section

Battery 1(DC1 +/-)

Battery 2(DC2 +/-)

Input/Output Section

AC IN cable entry

AC OUT cable entry

DC cable entry

DC cable entry

M6 Bolt

58 mm

44.45 mm44.45 mm

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 11

Page 18: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Electrical Installation: Top Cable Entry

PE and AC cable connections (top cable entry)

Feed the AC and PE cables through the top of Input/Output Section.

Connect cables.

NNProtective Earthing conductors (red) for Battery 1 & AC IN

Protective Earthing conductors (red) for Battery 2 & AC OUT

Battery 2

Battery 1

Earthing conductor connected to suitable earth electrode TN-systems

Output circuit grounding bar.

PE

58 mm

44.45 mm44.45 mm

Bonding Jumper (TN-systems) to Input Neutral Bar

12 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B

Page 19: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Bottom Cable Entry

Preparing for bottom cable entry

Cable entry in bottom cover of Input/Output Section

AC IN AC OUT

N N

AC IN AC OUT

BAT 1 BAT 2

BAT 1 BAT 2

M14

M14

90 95

9392

91 94

M14

M14

M10

M10

M10M10

M10

M10

M10

L1 OUT

L2 OUT

L3 OUT

L1 IN

L2 IN

L3 IN

L3 OUT

L2 OUT

95

93 L1 OUT

L3 OUT

L2 OUT

95

93 L1 OUT

L3 IN

L2 IN

L1 IN

90

92

L3 IN

L2 IN

L1 IN

90

92

AC IN cable entry

AC OUT cable entry

DC cable entry

DC cable entry

IN/OUT power cable (bottom entry).

Top view

Top view

Top view M6 Bolt

58 mm

44.45 mm44.45 mm

Front view

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 13

Page 20: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Electrical Installation: Bottom Cable Entry

Preparation for bottom cable entry

a. Loosen bolts of both cable entry covers and remove.

b. Drill holes for grommets for AC, DC, and Output circuit grounding electrode cable in areas shown.

c. Install grommets.

d. Remount covers.

Interchange of AC IN busbars for bottom entry

a. Remove nuts from M14 bolts at busbars 90 and 92.

b. Remove bolt, washer and fuse.

c. Remove bolts from M10 at busbars 90 and 92.

d. Remove busbars 90 and 92 at AC IN.

e. Move the two front isolators in the topmost busbar position two steps to the front.

f. Move the two front isolators in the lowest busbar position two steps to the rear.

g. Install busbar 90 in original position of busbar 92.

h. Install busbar 92 in original position of busbar 90.

i. Reattach M14 bolts at busbars 90 and 92.

j. Install cable lugs on busbars using M12 bolts.

Interchange of AC OUT busbars for bottom entry

a. Remove nuts from M14 bolts at busbars 93 and 95.

b. Remove bolt, washer and fuse.

c. Remove bolts from M10 at busbars 93 and 95.

d. Remove busbars 93 and 95 at AC OUT.

e. Move the two front isolators in the topmost busbar position two steps to the front.

f. Move the two front isolators in the lowest busbar position two steps to the rear.

g. Install busbar 93 in original position of busbar 95.

h. Install busbar 95 in original position of busbar 93.

i. Reattach M14 bolts at busbars 93 and 95.

j. Install cable lugs on busbars using M12 bolts.

Moving busbar for grounding

a. Move busbar for grounding from upper right corner to lower left corner as illustrated.

Note

No drilling or cutting should take place inside the UPS.

14 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B

Page 21: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Electrical Installation: Bottom Cable Entry

Battery cable connection (bottom cable entry)

WARNING!Make sure that the battery breakers are open (OFF) prior to running the cables.

CAUTION!Refer to the battery manufacturer’s installation manual.

CAUTION!The minimum DC voltage rating of the battery supply over-current protective device is 500 V.

Note

Over-current protection for the battery circuit is required by national wiring rules.

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 15

Page 22: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Electrical Installation: Bottom Cable Entry

Connect cables from battery system.

Connect cables from battery system.

BAT1+

BAT2-

BAT1- BAT2+

L3 In

L2 In

L1 In

L2 Out

L3 Out

L1 Out

BAT1-

BAT1+

BAT 2+

BAT2—

N N

58 mm

44.45 mm44.45 mm

IN/OUT power cable (bottom entry)

Bottom view of Input/Output Section

Battery 1(DC1 +/-)

Battery 2(DC2 +/-)

AC IN cable entry

AC OUT cable entry

DC cable entry

DC cable entry

M6 Bolt

16 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B

Page 23: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Electrical Installation: Bottom Cable Entry

PE and AC cable connections (bottom cable entry)

Feed the AC and PE cables through the bottom of Input/Output Section.

Connect cables.

NN

Protective Earthing Conductors for Battery 1 & AC IN

Protective Earthing Conductors for Battery 2 & AC OUT

Battery 2

Battery 1

Output circuit grounding bar

Earthing conductor connected to suitable earth electrode TN-systems

Output circuit grounding bar

58 mm

44.45 mm44.45 mm

PE

Bonding Jumber (TN-systems) to Input Neutral Bar

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 17

Page 24: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

External Bypass Static Switch Wiring

WARNING!Before installation work is carried out, check and test that all AC and DC power source breakers are in open position.

WARNING!Use only manual reset protection as input over-current protection.

WARNING!Over-current protection required by national wiring rules.

WARNING!The UPS has no internal manual disconnect devices to switch off external AC (Q1 and Q5) and DC (Q7 and Q8) input power. Ensure that disconnection devices are available as separate components for this installation.

CAUTION!The External Bypass Static Switch is not provided with built-in backfeed protection. Use suitable breakers with a minimum of 0.8 in/20 mm air gap and trip function. The breaker is controlled from the External Bypass SSW and will be tripped in case of backfeed.

Note

The installer must provide each external disconnection device for this UPS system with labels displaying the following text:“Isolate the Uninterruptible Power Supply (UPS) as instructed in the User Guide before working on circuit.”

Note

The installation of the External Bypass Static Switch must comply with local and national regulations.

Note

Run matched set of phase cables in the same cable run(s).Do not separate phases into different cable runs.

Note

Use only copper conductors.

Page 25: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Electrical Installation: External Bypass Static Switch Wiring

Top cable entry

Loosen the 8 screws to remove top covers. Drill holes for grommets. Re-fit the covers and install the grommets.

Feed the cables through the grommets. Connect cables at cable connection points.

Connect grounding electrode conductor to busbar locations.

58 mm

44.45 mm44.45 mm

X022

X021

X007

X010

X011

X008B

X008A

X012

X013

X014A

X014B

X017

X40

5

~~

Normal

UPS SummaryNormal

L1

IN

L2

IN

L3

IN

L1

OU

T

L2

OU

T

L3

OU

T

L1 IN

L1 OUT

L2 IN

L2 OUT

L3 IN

L3 OUT

PE

Top view of top cable entry

Port for communication cables

Top view of AC IN & OUT cable connections

Ext. Bypass SSW

Note

No drilling or cutting should take place over the top of the External Bypass SSW.

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 19

Page 26: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Electrical Installation: External Bypass Static Switch Wiring

Bottom cable entry

Loosen the 8 screws to remove bottom covers. Drill holes for the grommets. Re-fit the covers and install the grommets.

Feed the cables through the grommets. Connect cables at cable connection points.

Connect grounding electrode conductor to busbar locations.

~~

Normal

UPS SummaryNormal

L1

IN

L2

IN

L3

IN

L1

OUT

L2

OUT

L3

OUT

X022

X021

X007

X010

X011

X008B

X008A

X012

X013

X014A

X014B

X017

X40

5

L1 IN

L1 OUT

L2 IN

L2 OUT

L3 IN

L3 OUT

Top view of bottom cable entry

Communication cable Port

Top view of AC IN & OUT bottom cable connections

PE

58 mm

44.45 mm44.45 mm

Ext. Bypass SSW

Note

No drilling or cutting should take place inside the External Bypass SSW.

20 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B

Page 27: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Communication cable overviewC

onne

ctio

n pl

ane

0P09

57

X131

X130

ExternalEPO

placed onwall

X133A 21X185

UPS

EM

O (

Dis

play

)

X134A

X1281

1 2

2

X1291

2

Bac

kfee

d pr

otec

tion

EPO out

EPO out

Con

nect

ion

plan

e0P

0957

External Bypass Static Switch

X128

X12

6A

X12

7A

X129

X131

X130

1

2

1

2

EM

O (

Dis

play

)

X134A

MBP CAN I/O board1

Maintenance Bypass Panel

Maintenance Bypass Panel

0P4533

C2

43

C1

21

X17

8

61

23

45

X17

3M

BP

Bre

aker

s

X17

6

87

109

1211

X134A

X134B

Terminator0M-1878

56

Q2

34

12

Q1

X1771

2X177

1

2

X1771

2

X134A

X1281

2

X129

710

11

X17

3

MB

PB

reak

ers

X172Lamps

H6

109

H5

87

H4

65

H3

43 3 41 2

Q5

X176

11 1221

C2

43

C1

21

X17

8

X175

12

Norm.op

Relay output

X174

12

Earth fault sensor

5 6

Q6

Q6

X1771

2

Q5

912

Q4

8

Q3

65

43

21

Q1

21

X175

12

Norm.op

Relay output

X174

12

Earth fault sensor

X172Lamps

X128

12

X129

12

MBP CAN I/O board 20P4533

4321 121187 10965

X134B

Terminator0M-1878

Q2

+

-

External Lampsupply V r V oMax. 250V 5A

+ - + - + - + -

24VShunt trip forback feedprotection

+

-

-+

+

-

+-

+

-

+

-

-

+

+ - + - + -

24V

Shunt trip

X12

6B

X12

7B

X12

6B

X12

7B

X12

6A

X12

7A

1 42 3X170

1 42 3X170

X186

Q7

1 2 3 4

Q8

X182

X133A

12

X185

Battery CAN I/O boardID 0

0P4512

X18

01

42

3

X133B

Fus

e1

1 2

Fus

e2

3 4

Fus

e3

5 6

Fus

e4

7 8

1 2 3X183

H7

H8

4

+ - + -

31

Temp sensor+

+

42 -X18

1

Temp sensor

NTC

NTC-

31

Q8

Q7

UVR+

+

42

UVR

-

-

X18

4DC

DC

DC DC

AC

Note 1

Note 1

Note 3

Note 2

Note 3

Note 1: Contact APC Application Team for correct sizing.Note 2: H7, H8 = 5V LEDNote 3: Q2, Q4 and Q6 are optional. If Q2 is not present pins 3 and 4 must be shorted on both boards. If Q4 is not present pins 7 and 8 must be shorted on both boards. If Q6 is not present pins 11 and 12 must be shorted on both boards.

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 21

Page 28: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Relay Board (Optional)

Location of optional Relay Board

12

31

23

12

31

23

12

31

23

NC

3

12

31

23

22 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B

Page 29: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Electrical Installation: Relay Board (Optional)

Communication cables with optional Relay Board

Shunt trip 24V

External Lampsupply V or V

Max. 250V 5A

DC

DC

AC

AC

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 23

Page 30: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Electrical Installation: Relay Board (Optional)

Relay Board functions

The Relay Board informs the user of the operation mode, status, and alarm conditionsand has 8 ports on the input side and 16 output terminals.

Note

Use Normally Closed (NC) contacts for Fail safe Mode and Normally Open (NO) for Active on.

Relay ID Name Events that will trigger the alarm Mode Comment

K1 Common Alarm • Any of the functions below, except relays K8, K9, K10, K11;

• Inverter section fault;• Main PSU fault;• System locked in operation mode;• Internal memory fault;• Internal communication fault.

Fail safe Warning

K2 Battery voltage out of tolerance

• DC voltage is too high (shut down);• DC voltage is under warning level;• DC voltage is low (shut down).

Fail safe Warning

K3 Mains out of tolerance • Mains voltage RMS value is out of tolerance;

• Mains waveform not accepted (fast detector);

• Mains frequency is out of tolerance.

Fail safe Warning

K4 Bypass out of tolerance • Bypass voltage RMS value is out of tolerance;

• Bypass waveform not accepted (fast detector);

• Bypass frequency is out of tolerance.

Fail safe Warning

K5 Battery condition fault • Battery monitor has detected a weak battery;

• Battery monitor has detected a defective battery.

Fail safe Fault

K6 Battery disconnected • Battery breaker tripped/open. Fail safe Fault

K7 System overload • Output load exceeded 100%;• Delta Inverter current limiter is active;• Main Inverter current limiter is active.

Fail safe Fault

K8 Output out of tolerance • Output voltage RMS value is out of tolerance;

• Output waveform not accepted (fast detector);

• Output frequency is out of tolerance.

Fail safe Fault

K9 Normal operation • UPS is running in normal operation. Active on Opr. mode

K10 Battery operation • UPS is running in battery operation. Active on Opr. mode

24 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B

Page 31: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Electrical Installation: Relay Board (Optional)

K11 Bypass operation • UPS is running in normal operation/bypass operation according to AS400/Novell.

Active on Opr. mode

K12 Maintenance bypass ON • The maintenance bypass switch is active. Active on Opr. mode

K13 Stand-by operation • UPS is in stand-by operation. Active on Opr. mode

K14 Boost charge operation • UPS is boost charging the batteries. Active on Opr. mode

K15 Fan fault • Blocked or faulty fan. Fail safe Fault

K16 High equipment temperature or inverter fuse blown

• Static Switch temperature is high;• Main Inverter failure (high temperature

or blown fuse);• Delta Inverter temperature is high;• Magnetics temperature is high;• Isolation Transformer temperature is high

(optional);• Battery temperature is high.

Fail safe Warning

IN1 Generator active • System on generator System is running on generator.Battery charging is derated.

IN2 Battery room ventilation fault

• Battery room ventilation Ventilation fault in battery room.Battery charging is off.

IN3 - IN8

Reserved for future use

Relay ID Name Events that will trigger the alarm Mode Comment

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 25

Page 32: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety
Page 33: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Specifications

Low-Impedance/High-Impedance Earthing

The Symmetra® MW is easily integrated into either a solid grounded system, or a high-impedance grounded system.

In a solid grounded system, the neutral power source (mains, generator, or UPS) is solidly grounded. In the event of a down-stream ground fault, the fault current will have a path back to the source, and the over-current device feeding the faulted part of the installation will trip and isolate the fault.

In a high-impedance grounded system, the source is grounded with an impedance (grounding resistor). In the event of a down-stream fault, the fault current will be limited by the impedance of the grounding resistor. The value of a high-impedance system is its ability to maintain operation with a given system fault to ground, i.e. the over-current device will only trip at line-to-line faults or double ground faults. For a high-impedance system to provide enhanced power system reliability and availability, a ground-fault monitoring/alarm system is required.

Note

Grounding electrode conductor to be supplied by the customer.

For more information refer to “Appendix” in Installation Guide.

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 27

Page 34: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Electrical Specifications

AC Input

WARNING!Supply the UPS from a dedicated, 3 × 400/230 V, L1, L2, L3, N, PE source or a high-impedance grounded system.

CAUTION!Ensure clockwise phase rotation (L1, L2, L3) of input voltages.

CAUTION!AC and DC disconnect switches and over-current protection must be included in the installation.

Note

All wiring must comply with all applicable national and/or local electrical codes.

Note

Max. prospective RMS short-circuit current on input terminals: 200 kAMax. prospective RMS short-circuit current on DC terminals: 50 kA

AC Input

Input rating 800 kW/kVA

Power Factor 1

Input Voltage 380 V

Input Frequency 50 Hz

Nominal input current (note 1) 1132 A

Input Current Limitation (note 2) 1422 A

Input Voltage 400 V

Input Frequency 50 Hz

Nominal input current (note 1) 1203 A

Input Current Limitation (note 2) 1466 A

Input Voltage 415 V

Input Frequency 50 Hz

Nominal input current (note 1) 1159 A

Input Current Limitation (note 2) 1447 A

28 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B

Page 35: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Specifications: Electrical Specifications

DC Input

AC Output

AC Input External Bypass SSW

The External Bypass SSW is rated to a thermal overload of 25%.

Heat dissipation

24.74 kW / 84.4 kBTU/hr (note 6)

DC Input

Nominal Voltage (note 3) 2 x 384 V

INom Discharge (note 4) 1085 A

IMax Discharge (note 5) 1276 A

CAUTION!The minimum DC voltage rating of the battery supply over-current protective device is 500 V.

AC Output

Voltage 380 V

- Current Nom (note 8) 1094 A

- Max (note 7) 1311 A

Voltage 400 V

- Current Nom 1155 A

- Max (note 7) 1444 A

Voltage 415 V

- Current Nom 1113 A

- Max (note 7) 1391 A

AC Input External Bypass SSW

External Bypass SSW Max Input Current (100% load)

380 V 1094 A

400 V 1155 A

415 V 1113 A

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 29

Page 36: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Specifications: Electrical Specifications

Notes

1. Nominal (Nom): Input current based on rated load, nominal input voltage and fully charged batteries.

2. Current limitation is maximum allowed via electronic current limiting and is based on full battery recharge + nominal load and -10% input voltage.

3. Nominal battery voltage assumed to be 2.0 volts/cell (lead technology).

4. Nominal Battery Discharge current based on rated load, and nominal Battery voltage.

5. Maximum Battery Discharge current based on rated load at end of Discharge.

6. Heat dissipation calculated at rated load capacity.

7. This current is at 125% of rated load and is electronically current-limited to a maximum of 10 minutes. This value is only provided so the engineer can ensure that the selected AC output circuit overcurrent device’s time-current characteristic will support this condition.

8. At 380 V, nominal output is reduced from 200 kW to 180 kW in each section.

Torque specifications

Torque specifications

Bolt Size M8 13.5 Nm

Bolt Size M10 30 Nm

Bolt Size M12 50 Nm

Bolt Size M14 75 Nm

30 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B

Page 37: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Required Breaker Settings (400 V Systems)

The Symmetra® MW is a fault-tolerant system capable of handling and surviving overloads and internal/external faults. The overload performances and fault clearings are possible when the system meets specified minimum requirements for breaker settings. The settings are specified in the tables below, but some of them can also be found in the Electrical Specification section. The settings are all minimum settings and may not result in a drop-out.

Input and upstream breakers — minimum settings

Output and downstream breakers -— minimum settings

Note

Contact APC Application Team for Required Breaker Settings in 380 V and 415 V systems.

See also

See separate guide on parallel operation for information on required breaker settings in parallel systems.

Q1, Q5, and any upstream breaker

Duration [S] Current [A] Total load [%] Event/Operation

< 0.005 22 kA -- Internal fault clearing

600 1466* 127 Overload on-line

1203 100 On-line

1270 110 On-line+ Max. Battery charge

* Only applicable to Q1

Q2, Q4, Q6, and any downstream breaker

Duration [S] Current [A] Total load [%] Event/Operation

< 0.005 22 kA -- Internal fault clearing. Will end as upstream

60 2406* 200 Overload on-line

600 1504* 125 Overload on-line

1155 100 On-line

* Only applciable to Q2 and Q4

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 31

Page 38: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Specifications: Required Breaker Settings (400 V Systems)

22 kA is the maximum peak let-through current (including safety factor) available during clearing of an internal fault in a 200 kW section or a Power Module. During or after a controlled fault clearing, none of the breakers are allowed to trip on the instantaneous trip setting below the specified value. The maximum peak let through current is applicable to utility with prospective short-circuit currents up to 200 kA.

The following diagram shows a dual mains systems in which the upstream breakers are named Q. Correct settings of upstream breaker settings are mandatory. The systems can also be configured as single mains systems.

Note

The instantaneous trip setting must not be derated even though the UPS system is derated in system output power. The system size has no influence on the instantaneous trip setting.

Note

For derated or parallel systems, the APC Application Team provides the correct breaker settings and breaker frame sizes.

Note

For upstream breakers not mentioned in the table, the APC Application Team provides the correct breaker settings for on-line, overload, and trip currents.

Q1 Q2

Q3

Q6Q5

Q4

Q

Q

T1

T2

Dual Mains Single Installation

32 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B

Page 39: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Appendix

System and Protective Earthing

The purpose of this appendix is to describe the system- and protective earthing principles of the Symmetra® MW.

CAUTION!All wiring to be in accordance with applicable national and/or local electrical wiring rules.

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 33

Page 40: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

TN Systems

Characteristics

TN systems have one point connected directly to ground. All exposed conductive parts must be connected to that point by protective conductors.

Depending on the way the neutral and protective conductors are fed, there are three types of TN systems:

• TN-S system: a separate protective conductor is used in the system

• TN-C-S system: the neutral and protective conductors are combined to one single conductor in a part of the system

• TN-C system: the neutral and protective conductors are combined to one single conductor in the whole system

Reference to IEC 60364-4-41 413.1.3

All exposed conductive parts of the installation must be connected to the earthed point of the power system by protective conductors which must be earthed at or near to each relevant transformer or generator.

Exposed conductive parts that are accessible at the same time must be connected to the same earthing system, either individually, in groups or collectively.

Normally the earthed point of the power system is the neutral point. If a neutral point is not available or accessible, a phase conductor must be earthed. The phase conductor must not serve as a PEN conductor.

In fixed installations a single conductor may serve both as a protective conductor and a neutral conductor (PEN conductor).

Reference to IEC 60364-5-54 546.2.3

If from any point in the installation the neutral and protective functions are provided by separate conductors, it is inadmissible to connect these conductors to each other from that point. At the point of separation, separate terminals or bars must be provided for the protective and neutral conductors. The PEN conductor must be connected to the terminal or bar intended for the protective conductor.

If there are other effective earth connections, the protective conductors must be connected to such points when it is possible. It may be necessary to earth at additional points to ensure that the potentials of protective conductors remain as close as possible to that of earth in case of a fault.

34 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B

Page 41: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Appendix: TN Systems

Additional requirements for generating sets (IEC 60364-5-55 551.4.2)

To be used when the generating set provides a switched alternative to the public supply.

Protection by automatic disconnection of supply must not rely on the connection to the earthed points of the public supply system when the generator is operating as a switched alternative to a TN system. A suitable earth electrode must be provided.

Protective devices in TN systems

The following protective devices are recognized in TN systems:

• Overcurrent protective devices

• Residual current protective devices (not to be used in TN-C systems)

When a residual current protective device is used in a TN-C-S system, a PEN conductor must not be used on the load side. The connection of the protective conductor to the PEN conductor must be made on the source side of the residual current protective device (see below illustration):

L1 L1L1 L1

L1 L1PEN N

SOURCE SOURCE

PE

Res

idu

al C

urr

ent

Sen

se

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 35

Page 42: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Appendix: TN Systems

The characteristics of protective devices and the circuit impedances shall be such that, if a fault of negligible impedance occurs anywhere in the installation between a phase conductor and a protective conductor or exposed conductive part, automatic disconnection of the supply will occur within 5 seconds (valid for distribution circuits), the following condition fulfilling this requirement:

In the condition:

If a fault occurs close to the UPS (before the power distribution) while the UPS system is in Battery Operation and Bypass is unavailable, the available power is unable to activate the protective device. In that situation the Inverter will shut down in five seconds (IEC 60364-4-41 413.1.3.5 norm). If a residual current protective device is used, this device will disconnect the supply.

The four diagrams show the Symmetra MW installed in four different TN systems:

• Earthing arrangements and protective conductors - Symmetra® MW in “TN-S installation”

• Earthing arrangements and protective conductors - Symmetra® MW in “TN-S installation” (Legal in DK - special cases)

• Earthing arrangements and protective conductors - Symmetra® MW in “TN-C-S installation”

• Earthing arrangements and protective conductors - Symmetra® MW in “TN-C installation”

is the impedance of the fault loop comprising the source, the live conductor up to the point of the fault, and the protective conductor between the point of the fault and the source

is the current causing the automatic operation of the disconnecting protective device within a conventional time not exceeding five seconds

is the nominal AC RMS voltage to earth

Zs Ia× U0≤

Zs

Ia

U0

36 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B

Page 43: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

TT Systems

Characteristics

TT systems have one point connected directly to ground and all exposed conductive parts of the installation must be connected to an earth electrode. This earth electrode is independent of the power system earthed point.

Reference to IEC 60364-4-41 413.1.4

All exposed conductive parts that are protected collectively by the same protective device must be connected to a common earth electrode together with the protective conductors. In installations where several protective devices are utilized in series, the requirement applies separately to all exposed conductive parts protected by each device.

The neutral point or, if a neutral point does not exist, a phase conductor of each generator station or transformer station must be earthed.

Protective devices in TT systems

The following protective devices are recognized in TT systems:

• Overcurrent protective devices

• Residual current protective devices

Overcurrent protective devices are only applicable for protection against indirect contact in TT systems where a low RA value exists (see specification below).

The condition must be fulfilled.

In the condition:

For discrimination purposes, S-type residual current protective devices may be used in series with general type residual current protective devices. To provide discrimination with S-type residual current protective devices, an operating time not exceeding 1 second is permitted in distribution circuits.

is the sum of resistance of the earth electrode and the protective conductor for the exposed conductive parts

is the current causing the automatic operation of the protective device. When the protective device is a residual current protective device, Ia is the rated residual operating current I n

RA Ia× 50V≤

RA

Ia

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 37

Page 44: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Appendix: TT Systems

When the protective device is an overcurrent protective device, it must be either:

• a device with inverse time characteristics and Ia must be the current causing automatic operation within 5 seconds, or

• a device with an instantaneous tripping characteristic and Ia must be the minimum current causing instantaneous tripping

The following diagram shows a Symmetra® MW installed in a TT system:

• Earthing arrangements and protective conductors - Symmetra® MW in “TT installation”

38 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B

Page 45: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

IT Systems

Characteristics

In IT systems the installation is insulated from earth or connected to earth through a sufficiently high impedance. Exposed conductive parts are earthed individually, in groups, or collectively.

Reference to IEC 60364-4-41 413.1.5

In IT systems the installation must be insulated from earth or connected to earth through a sufficiently high impedance. This connection must be made either at the neutral point of the system or at an artificial neutral point. The latter may be connected directly to earth if the resulting zero-sequence impedance is sufficiently high. In installations where no neutral point exists, a phase conductor can be connected to earth through an impedance. In case of a single fault to an exposed conductive part or to earth, the fault current will be low and disconnection will not be imperative.

Exposed conductive parts must be earthed individually, in groups or collectively and the condition must be fulfilled.

In the condition:

In systems where an IT system is used for continuity of supply, an insulation monitoring device must be provided to indicate the occurrence of a first fault from a live part to the exposed conductive parts or to the earth. It is recommended to eliminate a first fault as soon as possible.

Depending on whether all exposed conductive parts are interconnected by a protective conductor (collectively earthed) or are earthed in groups or individually, after a first fault, the disconnection conditions of the supply for a second fault must be as follows:

a. In installations where the exposed conductive parts are earthed in groups or individually, the protection conditions for TT systems apply (see 413.1.4.1)

b. In installations where the exposed conductive parts interconnected by a protective conductor collectively earthed, the conditions for TN systems apply

In installations where the neutral is not distributed, the following conditions must be fulfilled:

is the resistance of the earth electrode for exposed conductive parts

is the fault current of the first fault of negligible impedance between a phase conductor and an exposed conductive part. The Id value takes the leakage currents and the total earthing impedance of the electrical installation into account

RA Id× 50V≤

RA

Id

Zs3 U0×2 Ia×

--------------------≡

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 39

Page 46: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Appendix: IT Systems

In installations where the neutral is distributed, the following conditions must be fulfilled:

In the condition:

Protective devices in IT systems

The following protective devices are recognized in IT systems:

• Insulation monitoring devices

• Overcurrent protective devices

• Residual current protective devices

The following diagram shows a Symmetra® MW installed in a IT system:

• Earthing arrangements and protective conductors - Symmetra® MW in “IT installation”

is the nominal AC RMS voltage between phase and neutral

is the impedance of the fault loop comprising the phase conductor and the protective conductor of the circuit

is the impedance of the fault loop comprising the neutral conductor and the protective conductor of the circuit

is the operating current of the protective device. The disconnecting time is 5 seconds (distribution circuits)

Z′sU0

2 Ia×-------------≤

U0

Zs

Z′s

Ia

40 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B

Page 47: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Residual Current Sense

Mai

ns -

inpu

tU

PS

- o

utpu

t

PE

N PE

PE P

E

Byp

ass

- in

pu

tB

ypas

s -

outp

ut

L1 L3L2

L1 L3L2 N

L1 L3L2

L1 L3L2

Pro

tect

ive

Ear

thin

g C

ondu

cto

r

Protective Earthing Conductor

Mai

n P

rote

ctiv

e E

arth

ing

Ter

min

al

Ext

ern

al S

SW

-Byp

ass

Sym

met

ra M

W

( P

DU

)S

ervi

ce E

ntr

ance

Mai

nin

vert

er

u

uu

M

Mai

n P

rote

ctiv

e E

arth

ing

Ter

min

al

N PE

PE

Q1

Q6

Q3

Q5

Ear

thin

g a

rran

gem

ents

an

d p

rote

ctiv

e co

nd

uct

ors

- S

ymm

etra

MW

in T

N-S

inst

alla

tio

n

E

Sui

tabl

e ea

rth

elec

trode

with

ref

eren

ce to

IEC

603

64-5

-55

§ 55

1.4.

2

Res

idua

l cur

rent

pro

tect

ive

devi

ceca

n be

use

d.

Residual Current Sense

Res

idua

l cur

rent

pro

tect

ive

devi

ce c

an n

ot b

eus

ed a

t thi

s po

int.

Ow

ing

to p

aral

lel r

etur

n pa

th fo

r the

faul

t cur

rent

With

ref

eren

ce to

:IE

C 6

0364

-4-4

1 §

413.

1.3.

1

Min

imum

cro

ss-s

ectio

nal a

reas

:IE

C 3

64-5

-54

§ 54

3.1.

1

+-

+-

Battery 1

Battery 2

Q7

Q8

Bat

tery

1B

atte

ry 2

PE

PEBat

tery

rack

Bat

tery

bre

aker

bo

x

Q4

Del

taIn

vert

er

i

i

i

Common-mode filter

Sw

itch

gea

r

See

: IE

C 6

0364

-4-4

1 §

413

.1.3

Page 48: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Residual Current Sense

Mai

ns -

inpu

tU

PS

- o

utpu

t

PE

N PE

PE P

E

Byp

ass

- in

pu

tB

ypas

s -

outp

ut

L1 L3L2

L1 L3L2 N

L1 L3L2

L1 L3L2

Pro

tect

ive

Ear

thin

g C

ondu

cto

r

Protective Earthing Conductor

Mai

n P

rote

ctiv

e E

arth

ing

Ter

min

al

Ext

ern

al S

SW

-Byp

ass

Sym

met

ra M

W

( P

DU

)S

ervi

ce E

ntr

ance

Mai

nin

vert

er

u

uu

M

Mai

n P

rote

ctiv

e E

arth

ing

Ter

min

al

N PE

PE

Q1

Q6

Q3

Q5

Ear

thin

g a

rran

gem

ents

an

d p

rote

ctiv

e co

nd

uct

ors

- S

ymm

etra

MW

in "

TN

-S in

stal

lati

on

"(

Leg

al in

DK

- s

pec

ial c

ases

)

E

Res

idua

l cur

rent

pro

tect

ive

devi

ce c

an b

e us

ed.

Residual Current Sense

Res

idua

l cur

rent

pro

tect

ive

devi

ce c

an n

ot b

eus

ed a

t thi

s po

int.

Ow

ing

to p

aral

lel r

etur

n pa

th fo

r the

faul

t cur

rent

With

ref

eren

ce to

:IE

C 6

0364

-4-4

1 §

413.

1.3.

1

Min

imum

cro

ss-s

ectio

nal a

reas

:IE

C 3

64-5

-54

§ 54

3.1.

1

+-

+-

Battery 1

Battery 2Q

7Q

8

Bat

tery

1B

atte

ry 2

PE

PEBat

tery

rack

Bat

tery

bre

aker

bo

x

Q4

Del

taIn

vert

er

i

i

i

Common-mode filter

Sw

itch

gea

r

Lega

l in

DK

( S

peci

al c

ases

)

With

ref

eren

ce to

:S

tærk

strø

msb

eken

dtgø

rels

en §

551

.6.3

Not

e(

§ 55

1.6.

3 is

mis

sing

in IE

C 6

0364

-5-5

5 )

See

: IE

C 6

0364

-4-4

1 §

413

.1.4

and

"S

tærk

strø

msb

eken

dtgø

rels

en"

§ 5

51.6

.3, N

ote

Page 49: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Residual Current Sense

Mai

ns -

inpu

tU

PS

- o

utpu

t

PE

N PE

PE P

E

Byp

ass

- in

pu

tB

ypas

s -

outp

ut

L1 L3L2

L1 L3L2 N

L1 L3L2

L1 L3L2

PE

Protective Earthing Conductor

Mai

n P

rote

ctiv

e E

arth

ing

Ter

min

al

Ext

ern

al S

SW

-Byp

ass

Sym

met

ra M

W

( P

DU

)S

ervi

ce E

ntr

ance

Mai

nin

vert

er

u

uu

M

Mai

n P

rote

ctiv

e E

arth

ing

Ter

min

al

PE

N

PE

Q1

Q6

Q3

Q5

Ear

thin

g a

rran

gem

ents

an

d p

rote

ctiv

e co

nd

uct

ors

- S

ymm

etra

MW

in "

TN

-C-S

inst

alla

tio

n"

E

Sui

tabl

e ea

rth

elec

trode

with

ref

eren

ce to

IEC

603

64-5

-55

§ 55

1.4.

2

Res

idua

l cur

rent

pro

tect

ive

devi

ce c

an b

e us

ed.

Residual Current Sense

Res

idua

l cur

rent

pro

tect

ive

devi

ce c

an n

ot b

e us

ed.

With

ref

eren

ce to

:IE

C 6

0364

-4-4

1 §

413.

1.3.

1

+-

+-

Battery 1

Battery 2

Q7

Q8

Bat

tery

1B

atte

ry 2

PE

PEBat

tery

rack

Bat

tery

bre

aker

bo

x

Q4

Del

taIn

vert

er

i

i

i

Common-mode filter

Sw

itch

gea

r

PE

N

See

: IE

C 6

0364

-4-4

1 §

413

.1.3

Page 50: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Mai

ns -

inpu

tU

PS

- o

utpu

t

PE

N PE

PE P

E

Byp

ass

- in

pu

tB

ypas

s -

outp

ut

L1 L3L2

L1 L3L2 N

L1 L3L2

L1 L3L2

Mai

n P

rote

ctiv

e E

arth

ing

Ter

min

al

Ext

ern

al S

SW

-Byp

ass

Sym

met

ra M

W

( P

DU

)S

ervi

ce E

ntr

ance

Mai

nin

vert

er

u

uu

M

Mai

n P

rote

ctiv

e E

arth

ing

Ter

min

al

PE

N

PE

Q1

Q6

Q3

Q5

Ear

thin

g a

rran

gem

ents

an

d p

rote

ctiv

e co

nd

uct

ors

- S

ymm

etra

MW

in T

N-C

inst

alla

tio

n

E

Sui

tabl

e ea

rth

elec

trode

with

ref

eren

ce to

IEC

603

64-5

-55

§ 55

1.4.

2

With

ref

eren

ce to

:IE

C 6

0364

-4-4

1 §

413.

1.3.

1

+-

+-

Battery 1

Battery 2Q

7Q

8

Bat

tery

1B

atte

ry 2

PE

PEBat

tery

rack

Bat

tery

bre

aker

bo

x

Q4

Del

taIn

vert

er

i

i

i

Common-mode filter

Sw

itch

gea

r

N

PE

N

PE

NP

EN

PE

N

The

"C

omm

on-M

ode

Filt

er"

has

no e

ffect

in th

issy

stem

con

figur

atio

n.

Thi

s sy

stem

con

figur

atio

n is

not

rec

omm

ende

d

See

: IE

C 6

0364

-4-4

1 §

413

.1.3

Page 51: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Residual Current Sense

Mai

ns -

inpu

tU

PS

- o

utpu

t

PE

N PE

PE P

E

Byp

ass

- in

pu

tB

ypas

s -

outp

ut

L1 L3L2

L1 L3L2 N

L1 L3L2

L1 L3L2

PE

Protective Earthing Conductor

Mai

n P

rote

ctiv

e E

arth

ing

Ter

min

al

Ext

ern

al S

SW

-Byp

ass

Sym

met

ra M

W

( P

DU

)S

ervi

ce E

ntr

ance

Mai

nin

vert

er

u

uu

M

Mai

n P

rote

ctiv

e E

arth

ing

Ter

min

al

N

PE

Q1

Q6

Q3

Q5

Ear

thin

g a

rran

gem

ents

an

d p

rote

ctiv

e co

nd

uct

ors

- S

ymm

etra

MW

in T

T in

stal

lati

on

E

Sui

tabl

e ea

rth

elec

trod

e:

RA x

I a

< 5

0V

With

ref

eren

ce to

IEC

603

64-4

-41

§ 4

13.1

.4.2

Res

idua

l cur

rent

pro

tect

ive

devi

ceca

n be

use

d.Residual Current Sense

+-

+-

Battery 1

Battery 2

Q7

Q8

Bat

tery

1B

atte

ry 2

PE

PEBat

tery

rack

Bat

tery

bre

aker

bo

x

Q4

Del

taIn

vert

er

i

i

i

Common-mode filter

Sw

itch

gea

r

See

: IE

C 6

0364

-4-4

1 §

413

.1.4

With

ref

eren

ce to

IEC

603

64-4

-41

§ 4

13.1

.4.1

Res

idua

l cur

rent

pro

tect

ive

devi

ce c

an n

ot b

eus

ed a

t thi

s po

int.

Ow

ing

to p

aral

lel r

etur

n pa

th fo

r the

faul

t cur

rent

Page 52: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

Residual Current Sense

Mai

ns -

inpu

tU

PS

- o

utpu

t

PE

N PE

PE P

E

Byp

ass

- in

pu

tB

ypas

s -

outp

ut

L1 L3L2

L1 L3L2 N

L1 L3L2

L1 L3L2

( A

ltern

ativ

e to

ear

th e

lect

rode

)

Earthing Conductor

Mai

n P

rote

ctiv

e E

arth

ing

Ter

min

al

Ext

ern

al S

SW

-Byp

ass

Sym

met

ra M

W

( P

DU

)S

ervi

ce E

ntr

ance

Mai

nin

vert

er

u

uu

M

Mai

n P

rote

ctiv

e E

arth

ing

Ter

min

al

N

PE

Q1

Q6

Q3

Q5

Ear

thin

g a

rran

gem

ents

an

d p

rote

ctiv

e co

nd

uct

ors

- S

ymm

etra

MW

in

"IT

- in

stal

lati

on

"

E

Res

idua

l cur

rent

pro

tect

ive

devi

ceca

n be

use

d.

+-

+-

Battery 1

Battery 2

Q7

Q8

Bat

tery

1B

atte

ry 2

PE

PEBat

tery

rack

Bat

tery

bre

aker

bo

x

Q4

Del

taIn

vert

er

i

i

i

Common-mode filter

Sw

itch

gea

r

See

: IE

C 6

0364

-4-4

1 §

413

.1.5

Pro

tect

ive

Ear

thin

g C

ondu

cto

r

Insu

latio

nM

onito

ring

Dev

ice

Req

uire

men

t !!

IEC

606

64-4

-41

§ 4

13.1

.5.4

Sui

tabl

e ea

rth

elec

trode

: R

A x

Id

< 5

0VW

ith r

efer

ence

to IE

C 6

0364

-4-4

1 §

413

.1.5

.3A

ltern

ativ

e:T

he e

xpos

ed-c

ondu

ctiv

e-pa

rts

can

be e

arth

ed in

divi

dual

ly o

r in

grou

ps.

Bu

t sp

ecia

l dem

ands

are

req

uire

d. S

ee IE

C 6

0364

-4-4

1 §

413

.1.5

.5 a

)

Z

ZG

roun

ding

impe

danc

e

Gro

undi

ngim

peda

nce

Page 53: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety
Page 54: Symmetra MW UPS - Schneider Electric · Symmetra MW UPS 800 kW 400 V Installation Guide. Contents Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B i Safety

*990-1510B*

APC Worldwide Customer Support

Customer support for this or any other APC product is available at no charge in any of the following ways:• Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer

support requests.– www.apc.com (Corporate Headquarters)

Connect to localized APC Web sites for specific countries, each of which provides customer support information.

– www.apc.com/support/Global support searching APC Knowledge Base and using e-support.

• Contact an APC Customer Support center by telephone or e-mail.– Regional centers:

– Local, country-specific centers: go to www.apc.com/support/contact for contact information.

Contact the APC representative or other distributor from whom you purchased your APC product for information on how to obtain local customer support.

Direct InfraStruXure Customer Support Line (1)(877)537-0607 (toll free)

APC headquarters U.S., Canada (1)(800)800-4272 (toll free)

Latin America (1)(401)789-5735 (USA)

Europe, Middle East, Africa (353)(91)702000 (Ireland)

Japan (0) 35434-2021

Australia, New Zealand, South Pacific area (61) (2) 9955 9366 (Australia)

Entire contents © 2005 American Power Conversion. All rights reserved. Reproduction in whole or in part without permission is prohibited. APC, the APC logo, and Symmetra are trademarks of American Power Conversion Corporation and may be registered in some