8
CIBSE National Conference 1997 THE DESIGN OF ASSISTED NATURALLY VENTILATED THEATRES Richard Quincey MEng, Neil Knowles MSc, Eur Ing Randoll Thomas Ph.D, FCIBSE MASHRAE Max Fordham and Partners, London NW 1 7PE As experience with assisted naturally ventilated buildings ( 1) has increased designers hove extended the approach to larger and more demanding building types. This paper looks at two very different theatre projects where assisted natural ventilation systems have been designed, examines the design tools used, illustrates the solutions and shows how the built form was influenced. INTRODUCTION Theatres ore characterised by intermittent heavy occupancy and high stage lighting loads. Theatre ouditoria ore generally quite high and of large volume, do not usually hove windows and require strict blackout conditions. Air conditioned solutions for theatres hove relatively high running and maintenance costs. Where oppropr iole, on assisted nolurolly ventilated solution con offer dramatic savings; however it should be recognised that although the capitol and maintenance costs of the mechanical plant for such an approach are lower, the building costs con be higher. Naturally ventilated solutions require a high degree of coordination and integration between the design team members at on early stage. The need for the services engineer to analyse many preliminary solutions quickly, but with an acceptable level of confidence, has tended to present a difficulty for designers. With this in mind, this paper discusses the approach taken on two projects. THE PROJECTS The projects considered are Bedoles Theatre, set in rural Hampshire, and the Contact Theatre in central Manchester. In both projects the design brief was agreed early on with the client. The brief included the goal of restricting summertime temperatures in occupied areas to a maximum of C above the external ambient level. EDAS (21 funded scheme design studies for both projects were carried out lo investigate the expected peak internal summertime temperatures, given differing patterns of use and control regimes. 83

THE DESIGN OF ASSISTED NATURALLY VENTILATED THEATRES · 2015-04-06 · THE DESIGN OF ASSISTED NATURALLY VENTILATED THEATRES Richard Quincey MEng, ... • A temperature sensor within

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: THE DESIGN OF ASSISTED NATURALLY VENTILATED THEATRES · 2015-04-06 · THE DESIGN OF ASSISTED NATURALLY VENTILATED THEATRES Richard Quincey MEng, ... • A temperature sensor within

CIBSE National Conference 1997

THE DESIGN OF ASSISTED NATURALLY VENTILATED THEATRES

Richard Quincey MEng, Neil Knowles MSc, Eur Ing Randoll Thomas Ph.D, FCIBSE MASHRAE

Max Fordham and Partners, London NW 1 7PE

As experience with assisted naturally ventilated buildings ( 1) has increased

designers hove extended the approach to larger and more demanding build ing

types. This paper looks at two very different theatre projects where assisted natural

ventilation systems have been designed, examines the design tools used, illustrates

the solutions and shows how the built form was influenced.

INTRODUCTION

Theatres ore characterised by intermittent heavy occupancy and high stage lighting loads. Theatre ouditoria

ore generally quite high and of large volume, do not usually hove windows and require strict blackout

conditions.

A ir conditioned solutions for theatres hove relatively high running and maintenance costs. Where

oppropriole, on assisted nolurolly ventilated solution con offer dramatic savings; however it should be

recognised that although the capitol and maintenance costs of the mechanical plant for such an approach are

lower, the build ing costs con be higher.

Naturally ventilated solutions require a high degree of coordination and integration between the design team

members at on early stage. The need for the services engineer to analyse many preliminary solutions quickly,

but with an acceptable level of confidence, has tended to present a difficulty for designers. With this in mind,

this paper discusses the approach taken on two projects.

THE PROJECTS

The projects considered are Bedoles Theatre, set in rural Hampshire, and the Contact Theatre in central

Manchester. In both projects the design brief was agreed early on with the client . The brief included the goal

of restricting summertime temperatures in occupied areas to a maximum of 3° C above the external ambient

level.

EDAS (21 funded scheme design studies for both projects were carried out lo investigate the expected peak

internal summertime temperatures, given differing patterns of use and control regimes.

83

Page 2: THE DESIGN OF ASSISTED NATURALLY VENTILATED THEATRES · 2015-04-06 · THE DESIGN OF ASSISTED NATURALLY VENTILATED THEATRES Richard Quincey MEng, ... • A temperature sensor within

CIBSE National Conference 1997

The projects pose similar environmental problems, but they differ considerably in their requirement for noise

separation to and from outside. The resultant design for each building clearly reAects the solutions selected to

these problems.

The building form is affected in two principal ways; the high fresh air requirement means large openings and

the summertime temperature goal is only achievable by the use of a night - time cooling regime coupled with

significant exposed thermal mass. Each project addresses these issues in a different way.

In both projects a balance was sought between the size of openings, their effect on the construction and the

running costs of using fan assistance.

BEDALES THEATRE

Bedoles School new theatre, in rural Hampshire, seats on audience of 270. The build ing hos o traditional

peg jointed oak frame with o sandwich wall construction of lapped wooden boards and insulation . This

wooden construction sits on a concrete undercroft.

Ventilation is primarily by stack effect in the tall space; however a slow speed punkah fan in the slack

operates in conditions of high temperature to increase ventilation or al night for cooling the structure. The fan

also operates in reverse in the w intertime to reduce stratification .

The auditorium is heated using steel finned tubes, located in the undercroft, which heat the incoming air. The

coils are fed by a LTHW injection circuit.

Lighting in the theatre is generally at high level and was assumed to contribute about 30 kW of heat gain to

the occupied areas. The main features of the build ing are illustrated in Figure 1.

c:.C:.. ---:.:, Opening$ on four $ides f---·-{.,.._ ________ 1.5% each

Air out ___ • ..__ ----+• A'ir out Punkoh fan 1 pha$e

+--"'"-------- 0.8 kw motor

9.5m

15.5m

Figure 1 . Short section through building .

Supply air

3.75%

17m x 17m

Air palhwoy free area$ ore expressed 0$ o percentage of Roor area

84

2.5% 3.6m sq. lower

Page 3: THE DESIGN OF ASSISTED NATURALLY VENTILATED THEATRES · 2015-04-06 · THE DESIGN OF ASSISTED NATURALLY VENTILATED THEATRES Richard Quincey MEng, ... • A temperature sensor within

~­~

CIBSE National Conference 1997

Preliminary calculations on the building involved the use of the CIBSE standard admittance procedure 131. A

more detailed analysis using computational fluid dynamics (CFD) was carried out al a later stage to obtain a

better picture of the temperature gradient in the spacE? (Figure 21 and lo indicate to what extent temperature

stratification occurred .

:!

~

~

;:

~

"' ., .....

"' "' ... M

\ \ \ , -

~ ~ ~ ~ l(t ~ T emperolure - degC

Booed upon an external temperoture of 25 degC

Figure 2 . Temperature gradient as determined by CFD study.

0

E

0 .,g .. > 0

..l:J 0

_;: . !i!' " J:

In order to control the space temperature the building requires significant thermal mass and a night time

cooling regime. A large proportion of the thermal moss provided is located in a divided concrete undercroft

which acts as the fresh air intake. Fresh air is drawn through this undercroft from two opposing sides of the

building and then rises in the back of the seats .

The ventilation is controlled by a BMS . Important control features include:

• The exhaust damper opening range is restricted in windy and rainy conditions to provide better control of

the air change rate and lo prevent ra in ingress;

• The ventilation exhaust dampers open fully and the fan operates in a fire alarm condition, to aid smoke

extraction;

• Each side of the extract tower is individually controlled lo allow windward openings lo be closed to

prevent downdraughts in the lower;

• A temperature sensor w ithin the undercrofl concrete slab is used in conjunction w ith the space temperature

sensors to op timise night-lime cooling;

• Velocity sensors mounted under the seals limil the a ir velocity to ovoid discomfort;

• The a ir change ra te is controlled on the monitored carbon dioxide level and the measured space

temperature;

85

Page 4: THE DESIGN OF ASSISTED NATURALLY VENTILATED THEATRES · 2015-04-06 · THE DESIGN OF ASSISTED NATURALLY VENTILATED THEATRES Richard Quincey MEng, ... • A temperature sensor within

CIBSE National Conference 1997

CONT ACT THEATRE

The Contact Theatre is an existing masonry building located on the Manchester University campus, close lo o

busy road. Its redevelopment includes refitting the main auditorium to seat 380 people and improving the

lighting and acoustic arrangements . The exposed brickwork walls remain unchanged, but the woodwool roof

construction is being revised and improved by the addition of o new external roof covering and insulation

layer.

Ventilation is primarily by stack effect in the ta ll space. There ore slow speed oxiol fans, one in each stack,

which are designed to operate in conditions of high temperature to increase ventilation or at night for cooling

the slrudure. A single air intake is located at ground level in a courtyard away from road traffic. The extract

lowers for the auditorium are built on lop of the existing roof. Both conta in acoustic splitters selected for a low

pressure drop (Figure 3 J.

20.Sm

Sm

14.Sm

Supply air labyrinrh

Ajr out via 5 slacks

Supply air j ~-~ Exposed walls J '

1

- .• ••· •• .. 1._ I . • . • • _L.Ji! n

Air in 3.2% and allenua10r 60% free area

25mx 16m

'! I I

r-~L ___ =-1.-=:= ! .. -·· ·-1

Air pathway free areas are expressed as a percenlage of floor area

Figure 3. long section through auditorium.

H pot with four arms total ou~et area 3.4%

Attenuators 45% free area Stocks 1 % each Axial fans 3 bloded 3 phase 0.13 kw motor Stage lighring

An investigation was carried out to determine the heat load expected from the stage lighting . It is clear from

measured readings taken from a similar theatre (4) that stage lighting loads con vary dramatically between

different shows (about 2: l max/min) and throughout the show (about 5 : 1 max/min) . An analysis of the heat

generated by o typical stage luminoire was considered (Figure 4o) and the average electrical consumption

from the measured theatre lighting rig used to decide the heat load arrangement in the space (Figure 4b).

86

OMN i»CJai

Page 5: THE DESIGN OF ASSISTED NATURALLY VENTILATED THEATRES · 2015-04-06 · THE DESIGN OF ASSISTED NATURALLY VENTILATED THEATRES Richard Quincey MEng, ... • A temperature sensor within

CIBSE National Conference 1997

LJ LJ LJ lJ

83 103

Absorbed in luminaire

Absorbed in lomp glo ...

21 3

Total energy convected off luminoire 43%

43

Absorbed in luminaire

Total energy radiated as heat and light out of luminoire 57%

Figure 4a . Energy oulput from stage luminaire Figure 4b . Heat load arrangement.

24 kW 40% El

The CFD analysis on Bedales Theatre showed a high level of stratification. Preliminary calculations on the

Contact Theatre involved the use of a variant of the CIBSE admittance procedure (5) to estimate this

stratification. The method adopted d ivided the theatre into horizontal layers and applied the procedure to

~ch layer in turn (Figure 5) .

Air out

lulululul ~mAY ~ I Heat ga iru kw

SumAY Heat gains kw -4

A - Area Y - Admittance

Predicted temperarures

T CIBSE AS calculation

Predicted temperal\Jres

T CIBSE AB cotculafon

Fresh air in CIBSE design day dote

(Hourly)

Figure 5. Diagram of layered admittance procedure .

~ T j layer 2 - upper layer

l T

Loyer 1 - occupied layer

l

This method was used to quickly examine a wide range of alternative schemes and to determine on optimum

solution that takes into account !he major conslrainls affecting lhe buih form. A design a ir change role limit of l 0 per hour was chosen as a higher rote does not appear to significantly lower temperatures in the occupied

areas (Figure 6) and would risk unacceptable air velocities below the seating .

87

Page 6: THE DESIGN OF ASSISTED NATURALLY VENTILATED THEATRES · 2015-04-06 · THE DESIGN OF ASSISTED NATURALLY VENTILATED THEATRES Richard Quincey MEng, ... • A temperature sensor within

'

I~ j ·~

Q)

·~ ~ :>

~ Q)

0. E Q) I-

CIBSE National Conference 1997

25----~~--~-~~~----~-~

20

15

Note A - - -10

5

2

Note A : Layered admittance results comparable to CFO results:

Odcupied layer

4 8 lb

Air changes

32

2.S --------------------.

15 Q)

·~ ~ :> Ci 10 Qi 0. E Q)

...... 5

Ratio of admittance to design condition

Thermal moss ( admittance )

Figure 6 . The effect of ventilation· and admittance on temperature rise in the space.

A CFO analysis was then carried out by Design Flow Solutions on the final design arrangement: to check the

layered admittance results, lo provide a better picture of the temperature gradient (Figure 7) and to look at the

airflow patterns in the space . The CFO results indicated that the layered admittance procedure provides a

useful design tool.

Sum AY Night cooled

Fresh cir in CIBSE design doy doto

IPeok)

kr out

5

4

A-Area Y - Admittance

Figure 7 . Summary diagram of CFO results with stage lighting on .

88

Predicted temperatures based on peak external temperature;

I overage of zone )

I - - 2.5 degC 2 - + 0.7 degC J - + 3.5 degC 4 - + 6.3 degC 5 - + 9.1 degC

Sum AY Night cooled Hect gains kw

Page 7: THE DESIGN OF ASSISTED NATURALLY VENTILATED THEATRES · 2015-04-06 · THE DESIGN OF ASSISTED NATURALLY VENTILATED THEATRES Richard Quincey MEng, ... • A temperature sensor within

CIBSE National Conference 1997

The CFO analysis predicted that adding the stage lighting heat load into the simulation increased stratification

and stack effect with a subsequent higher ventilation rate . In this situation the CFO analysis predicted that

temperatures in the occupied areas increased only marginally.

The amount of thermal mass in the intake plenum is particularly important as it is expected to provide about 2 degC of precooling to the incoming air, when a night cooling regime is used.

During the development of the design there was concern that the wind conditions on the site, which has a

number of large adjacent buildings, might adversely affect airflow at the intakes and out of the extracts . A

wind tunnel test carried out by The Welsh Schaal of Architecture confirmed that adverse wind gradients,

between the intake and extract openings, would occur in certain wind conditions, mainly as a result of the

single sided intake arrangement. The stack height was raised to improve the situation. The stack termination

design was considered to be particularly important and it was decided that an H - pot arrangement (6) would

provide good operation in all wind conditions and good rain protection.

The controls used in this project are very similar to those at the Bedales Theatre, however:

• The BMS is able to speed control the fans to minimise power use and noise;

• The range of both the air intake and extract dampers is restricted in windy conditions;

• The IAQ (Indoor air quality) sensor specified is complemented by a staff operated manual occupancy

control as on override and as a fail safe feature.

SUMMARY OF AUDITORIUM DATA

A comparison of the dimensions, occupancy and surface area in both projects is summarised in the table

below; the lower half of the table expresses the data on a per person basis. Note the different distribution

between the projects of admittance between the undercroft and auditorium.

Floor area m2 including balcony & stage.

Room volume m3

Occupancy

Stack height m

Max air change per hr

Supply undercroft surface area m2

Auditorium surface area exc fittings m2

Supply undercroft admittance W /K

Auditorium admittance W /K

Floor area / person m2

Room volume / person m 3

dm3 /s /person max.

Undercroft surface area per person m2

/ p

Auditorium surface area per person m2

/ p

Undercroft admittance per person W /K/ p

Auditorium admittance per person W /K/ p

89

Bedoles Theatre

435 2421 270 15.5 15

805 1220 3081 3072

l.6 9 37 3.0 4.5 l l.4 11.4

Contact Theatre

390 4100 380 20.5 10

250 1642 1500 6199

10.8 30 0.7 4.3 4.0 16.3

Page 8: THE DESIGN OF ASSISTED NATURALLY VENTILATED THEATRES · 2015-04-06 · THE DESIGN OF ASSISTED NATURALLY VENTILATED THEATRES Richard Quincey MEng, ... • A temperature sensor within

CIBSE National Conference 1997

CONCLUSIONS

Assisted natural ventilation offers a practicable solution lo the satisfactory vent ilation of theatres. The predicted

temperatures for these projects indicate that acceptable temperatures can be achieved in theatres using

assisted natural vent ilation and o night lime cooling regime.

These projects illustrate a number of interesting points:

• Lorge low resistance air paths in and oul of the building ore requ ired;

• Opening sizes for air intakes and exhausts of about 5 % each (free area) of floor area offer a reasonable

starting poinl during early design;

• Acoustic constraints will dramatically affect the air intake and exhaust free areas . In the Contact Theatre

the acoustic splitters and limitations sel by the existing build ing reduc•~ the free area available and increase

the resistance lo airflow. When high ventilation rotes ore required far. assistance is used;

• The CFD analyses (Figures 2 & 71 predict o high level stratified layer of hot air. All occuponls should be

located below th is layer and in the case of the Contact Theatre this precluded the use of a balcony;

• The Contact Theatre CFD analysis predicted that the stage lighting heal load increased stratification and

stack venti la tion with only a small increase in temperature in the occupied areas;

• The layered admillance calculalions (Figure 6 ) clearly show a diminishing return as venlilation or

admitlance is increased . For the Contact Theatre it indicales that on air change rote greater than 10 per

hour does nol result in significonl ly lower peak internal temperatures;

• Air Intake and exhaust openings need lo be designed for local wind conditions .

ACKNOWLEDGEMENTS

The authors would like lo acknowledge the conlribution of their colleagues at Mox Fordham and Partners; the

funding provided by EDAS and the input of the other members of the design teams;

Client

Architect

Structural

Engineer

Ouanlily

Surveyor

Specialists

REFERENCES

Bedales School

Bedales School

Feilden Clegg Design

Ian Duncan

Bedales School

Prof. Tom Lawson, Bristol

University; Oak Design Group.

Contact Theatre

Contact Theatre Co.

Short Ford Associates

Modus Consult ing

Dearle and Henderson

Prof. P J Jones of Design Flow Solutions

and the Welsh School of Architecture.

1. Thomas R (ed) 1996. Environmental Design, Spans London UK.

2 . EDAS ( Energy Design Advice Scheme) .

3 . CIBSE section AB - Summer1ime lemperalures in buildings . 5th ed. l 9B6.

4 . Based upon dole collected by Stage Electrics at !he Northcoll Theatre, Exeter, Dec 1996.

5. CIBSE section AB - Summertime temperatures in buildings . 5th ed. l 9B6.

6 . BRE Information paper IP 6/95 · Flow resistance and wind performance of some common ventilation

terminals, PA Welsh.

90