tran ac units2305 00-001 HVAC Submittals_1

Embed Size (px)

Citation preview

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    1/294

    15-13089011No

     Arrive Architecture2344 Highway 121 Suite 100Bedford TX 76021

    TO:

    01/06/2016DATE:

    HVACRE:

    Clayton Arnal ATTN:

    Shop Drawings

    Letter 

    Prints

    Change Order 

    Plans

    Samples

    Specifications

    Other: Submittal

     Approval

    Your Use

     As Requested

    Review and Comment

     Attached

    Sent Via: Newforma

     Approved as Submitted

     Approved as Noted

    Returned After Loan

    Resubmit

    Submit

    Returned

    Returned for Corrections

    Due Date: 01/20/2016

    WE ARE SENDING: SUBMITTED FOR:

    SENT VIA:

     ACTION TAKEN:

    TRANSMITTAL

    Courtney Linsacum

    Signed:

    PROJECT: Mariposa Point of Gilbert

    Remarks:

    01/06/2016

    Date

    23 05 00-001

    Code

    HVAC

    Description

    Submitted t Architect

    Status

    CC:

    Item

    Submittal 23

    Package

    1

    Rev. Copies

    3333 E Camelback Road Suite 122Phoenix, AZ 85018

    602-840-7700Phone:

    Fax:

    15-13089PROJECT NO

    817-514-0584

    817-514-0694

    PHONE:

    FAX:

    Other:

    Page

    Courtney Linsacum

    DATE:__8/21/15____ BY:_Courtney Linsacum_ 

     ___X__REVIEWED ____REVIEWED AS NOTED _____REVISE & RESUBMIT

    SUMMIT DCK, LLC

    (602) 840-7700

    08/28/15Dennis Janes

    9/9/1509/15/1512/11/15

    Dave Geroux

    12/16/1501/06/16

    Evan Oates

    TELIOS COMMENTS:

    1. NO TYPE II GREASE DUCT MATERIALS WERE FOUND IN THIS

    SUBMITTAL. PROVIDE SUBMITTAL PRIOR TO PROCUREMENT.2. PTAC UNITS SHALL BE PROVIDED WITH HARDWIRE KIT ANDDISCONNECT SWITCH IN LIEU OF CORD AND PLUG AS APPEAR

    BE SUBMITTED. COORDINATE FINAL REQUIREMENTS WITHELECTRICAL CONTRACTOR PRIOR TO ROUGH IN.

    3. DISCONNECTING MEANS APPEARS TO BE EXCLUDED FROMPACKAGED ROOFTOP UNITS. PROVIDE INTEGRAL DISCONNEC

    COORDINATE REQUIREMENT OF DISCONNECTING MEANS WIT

    ELECTRICAL CONTRACTOR.4. MECHANICAL CONTRACTOR SHALL COORDINATE ANY

    ELECTRICAL CHANGES THAT MAY BE REQUIRED DUE TO ALTERNATE EQUIPMENT CONTAINED IN THIS SUBMITTAL WITH

    ELECTRICAL CONTRACTOR PRIOR TO PROCUREMENT OF

    MATERIALS.5. REFER TO FOLLOWING PAGES FOR ADDITIONAL COMMENT.

    01/24/16

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    2/294

     

     

     

    SUBMITTAL DATA

    Mariposa Point of Gilbert

    DCK Summit

    Telios

    15-1-1767

    23

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    3/294

      Mariposa Point of Gilbert

    230500 Common Work Results- NA

    230513 Common Motor Requirements- NA230529 Hangers and Supports

    230553 Identification of HVAC Piping & Equipment

    230593 Testing, Adjusting and Balancing

    230700 HVAC Insulation

    230713 Duct Insulation- Please see section 230700

    230719 HVAC Piping Insulation

    231123 Facility Natural Gas Piping- NA

    232300 Piping

    233113 Metal Ducts

    233300 Air Duct Accessories

    233416 Centrifugal HVAC Fans

    233713 Diffusers, Registers, and Grilles

    234100 Particulate Air Filtration

    236200 Package Compressor and Condenser Units

    238113 Package Terminal Air Conditioners

    238126 Split System AC- Please see section 236200

    238219 Fan Coil Units- Please see section 236200

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    4/294

     

     

    To Ind

    Mariposa Point of Gilbert

    230500

    Common Work Results- NA

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    5/294

     

     

    To Ind

    Mariposa Point of Gilbert

    230513

    Common Motor Requirements- NA

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    6/294

     

     

    To Ind

    Mariposa Point of Gilbert

    230529

    Hangers and Supports

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    7/294

    Project: ______________________________________________________________ Approval Stamp:

    Architect / Engineer: ___________________________________________________

    Date: _________________________ Phone: ________________________________

    Contractor: ___________________________________________________________

    Address: _____________________________________________________________

    ____________________________________________________________________

    Notes 1: _____________________________________________________________

    ____________________________________________________________________

    Notes 2: _____________________________________________________________

    ____________________________________________________________________

    MATERIAL

    Unistrut channels are accurately and carefully cold formed to size

    from low-carbon strip steel. All spot-welded combination members,

    except P1001T, are welded 3" (76 mm) maximum on center.

    STEEL: PLAIN

    12 Ga. (2.7 mm), 14 Ga.(1.9 mm) and 16 Ga. (1.5 mm)

     ASTM A1011 GR33

    STEEL: PRE-GALVANIZED

    12 Ga. (2.7 mm), 14 Ga. (1.9 mm) and 16 Ga. (1.5mm)

     ASTM A653 GR 33

    For other materials, see Special Metals or Fiberglass sections.

    FINISHES

     All channels are available in:

    • Perma Green II (GR)

    • Pre-galvanized (PG), conforming to ASTM A653 G90

    • Hot-dipped galvanized (HG), conforming to ASTM A123

    • Plain (PL)

    ® 15  ⁄  8" Channel

    41.3

    82.61

    22

    1 5  ⁄  8"

    3 1  ⁄  4"1

    P1001 Wt/100 Ft: 380 Lbs (566 kg/100 mAllowable Moment 14,390 In-Lbs (1,630 N•m

    12 Gauge Nominal Thickness .105" (2.7mm

    BEAM LOADING – P1001Max Defl. at

    Allowable Uniform Uniform Loading at Deflection

    Span Uniform Load Load Span/180 Span/240 Span/360

    In Lbs In Lbs Lbs Lbs

    24 3,130 * 0.03 3,130 * 3,130 * 3,130 *

    36 3,130 * 0.07 3,130 * 3,130 * 3,130 *

    48 2,400 0.13 2,400 2,400 2,400

    60 1,920 0.20 1,920 1,920 1,630

    72 1,600 0.28 1,600 1,600 1,130

    84 1,370 0.39 1,370 1,240 830

    96 1,200 0.50 1,200 950 640

    108 1,070 0.64 1,000 750 500

    120 960 0.79 810 610 410

    144 800 1.13 560 420 280

    168 690 1.54 410 310 210

    192 600 2.01 320 240 160

    216 530 2.55 250 190 130

    240 480 3.15 200 150 100

    COLUMN LOADING – P1001Maximum

    Unbraced Allowable Load Maximum Column Load Applied at C.G.

    Height at Slot Face K = 0.65 K = 0.80 K =1.0 K = 1.2

    In Lbs Lbs Lbs Lbs Lbs24 6,430 25,060 24,620 23,900 23,050

    36 6,230 24,000 23,050 21,570 19,890

    48 5,950 22,590 21,030 18,690 16,170

    60 5,620 20,890 18,690 15,540 12,400

    72 5,240 18,990 16,170 12,400 8,960

    84 4,830 16,970 13,640 9,470 6,580

    96 4,390 14,900 11,200 7,250 5,040

    108 3,930 12,860 8,960 5,730 3,980

    120 3,510 10,910 7,250 4,640 **

    Channel Finishes:PL, GR, HG, PG;Standard Lengths:10' & 20'

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    8/294PH-1.15

    PROJECT INFORMATION APPROVAL STAMP

    Project:   Approved

    Address:   Approved as noted

    Contractor:   Not approved

    Engineer: Remarks:

    Submittal Date:

    Notes 1:

    Notes 2:

    HANGER RODS

    Fig. 146 Continuous Threaded Rod

    Size Range: 1⁄4" through 1 1⁄2" Stocked in six, ten, and twelve foot

    lengths. Other even foot lengths can be furnished to order.

    Material: Carbon steel or Stainless Steel Gr 304

    Threads: National Coarse (USS), rod threaded complete length.Finish: Plain or Zinc Plated (Hot-Dip Galvanized optional)

    Maximum Temperature: 650° F.

    Ordering: Specify rod diameter and length, figure number,

    name and finish.

    Note: The acceptability of galvanized coatings at temperatures

    above 450°F is at the discretion of the end user.

    FIG. 146:LOADS (LBS) • WEIGHTS (LBS) • DIMENSIONS (IN)

    Rod SizeA

    Threadsper Inch

    Max Load Weightper Ft.650˚ F

    1 ⁄ 4 20 240 0.123 ⁄ 8 16 730 0.301 ⁄ 2 13 1,350 0.535 ⁄ 8 11 2,160 0.843 ⁄ 4 10 3,230 1.207 ⁄ 8 9 4,480 1.70

    1 8 5,900 2.30

    11 ⁄ 4 7 9,500 3.60

    11 ⁄ 2 6 13,800 5.10

    Note: Other rod sizes available upon request. Class 2 fit is available upon request.

    A

    Length

    Telios

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    9/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    10/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    11/294PH-11.11

    PROJECT INFORMATION APPROVAL STAMP

    Project:   Approved

    Address:   Approved as noted

    Contractor:   Not approved

    Engineer: Remarks:

    Submittal Date:

    Notes 1:

    Notes 2:

    CLEVIS HANGERS

    Fig. 67 Pipe or Conduit Hanger

    Size Range: 1⁄2" through 6"

    Material: Carbon steel

    Finish: Galvanized

    Service: Can be suspended by hanger rod or attached to wall. “T” slot in hangerpermits side bolt to be installed after installation and setting of pipe.

    Approvals: Complies with Federal Specification A-A-1192A (Type 5),

    ANSI/MSS SP-69 and MSS SP-58 (Type 5).

    Components: Strap and bolt with nut – assembled.

    Ordering: Specify pipe size, figure number and name.

    FIG. 67: LOADS (LBS) • WEIGHT (LBS) • DIMENSIONS (IN)

    PipeSize

    LoadRating

    WeightRod Size

    AB C D E F G

    HWidth

    1 ⁄ 2

    400

    0.21

    3 ⁄ 8

    25 ⁄ 8

    1 ⁄ 4

    13 ⁄ 4

    7 ⁄ 16

    11 ⁄ 2 115 ⁄ 16

    1

    3 ⁄ 4 0.22 27 ⁄ 8 17 ⁄ 8 111 ⁄ 16 21 ⁄ 8

    1 0.25 215 ⁄ 16 115 ⁄ 16 113 ⁄ 16 25 ⁄ 16

    11 ⁄ 4 0.27 31 ⁄ 4 2 21 ⁄ 16 25 ⁄ 8

    11 ⁄ 2 0.29 39 ⁄ 16 23 ⁄ 16 27 ⁄ 16 27 ⁄ 8

    2 0.31 311 ⁄ 16 21 ⁄ 8 29 ⁄ 16 31 ⁄ 16

    21 ⁄ 2500

    0.71 1 ⁄ 247 ⁄ 16

    3 ⁄ 8

    27 ⁄ 16

    9 ⁄ 16

    33 ⁄ 16 35 ⁄ 8

    11 / 4

    3 0.78 413 ⁄ 16 29 ⁄ 16 31 ⁄ 2 41 ⁄ 16

    4550

    1.39 5 ⁄ 861 ⁄ 8 33 ⁄ 16 45 ⁄ 8 53 ⁄ 16

    5 1.66 63

     ⁄ 4 31

     ⁄ 4 51

     ⁄ 16 53

     ⁄ 46 600 2.26 3 ⁄ 4 73 ⁄ 4 39 ⁄ 16 513 ⁄ 16 65 ⁄ 8

    F

    CL

    A

    G

    D

    C

    B

    CL

    H

    Alternate Installation

    Bolt/Screw to Vertical Support

    Telios

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    12/294

     

     

    To Ind

    Mariposa Point of Gilbert

    230553

    Identification of HVAC Piping & Equipment

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    13/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    14/294

    Use:

    Features:

    Identification & Safety Experts

    20 Thompson Rd. Branford, CT 06405-

    Phone: 800-243-

    Fax: 800-345-

    Email: SetonUSA@seton

    Date: / / Job:

    Contractor

    1763/0409

    www.seton.com Phone: 800-243-6624 Fax: 800-345-7819

    PRODUCT DATA SHEET

     VALVE TAGS

    BRASS VALVE TAGS

    Material:

    Size/Shape:

    Ink Fill Color Options:

    Maximum Temperature:Top Hole Size:

    Letter Height:

    Number Height:

    STAINLESS STEEL VALVE TAGS

    Material:

    Size/Shape:

    Ink Fill Color Options:

    Maximum Temperature:Top Hole Size:

    Letter Height:

    Number Height:

     ALUMINUM VALVE TAGS

    Material:

    Size/Shape:

    Ink Fill Color Options:

    Maximum Temperature:Top Hole Size:

    Letter Height:

    Number Height:

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    15/294

    Identification & Safety Experts

    20 Thompson Rd. Branford, CT 06405-

    Phone: 800-243-

    Fax: 800-345-

    Email: SetonUSA@seton

    Date: / / Job:

    Contractor

    1763/0409

    www.seton.com Phone: 800-243-6624 Fax: 800-345-7819

    PRODUCT DATA SHEET

    BEADED CHAIN

     ALUMINUM BEADED CHAIN

    Description: Flexible beaded chain is lightweight and

    corrosion resistant

    Melting Point: 1250°F

    Specifications: 4-1/2" lengths of flexible beaded chain

    Ball Diameter: 1/8"

    Avg. Tensile Strength: 16 lbs.

    STAINLESS STEEL BEADED CHAIN

    Description: Grade 304 of stainless steel is great for roughenvironments that need corrosion resistanceand strength.

    Melting Point: 2550°F

    Specifications: 4-1/2" lengths of flexible beaded chain

    Ball Diameter: 1/8"

    Avg. Tensile Strength: 45 lbs.

    NICKEL BEADED CHAIN

    Description: Nickel plate over solid steel material willnot rust or corrode.

    Melting Point: 1680°F

    Specifications: 4-1/2" lengths of flexible beaded chain

    Ball Diameter: 1/8"

    Avg. Tensile Strength: 30 lbs.

    BRASS BEADED CHAIN

    Description: Polished, durable Brass beaded chain willnot rust or corrode.

    Melting Point: 1680°F

    Specifications: 4-1/2" lengths of flexible beaded chain

    Ball Diameter: 1/8"

    Avg. Tensile Strength: 30 lbs.

    Use: Adjustable open and close links allow for varying the length of

    chain for each particular valve.

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    16/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    17/294

     

     

    To Ind

    Mariposa Point of Gilbert

    230593

    Testing, Adjusting and Balancing

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    18/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    19/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    20/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    21/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    22/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    23/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    24/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    25/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    26/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    27/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    28/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    29/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    30/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    31/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    32/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    33/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    34/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    35/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    36/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    37/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    38/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    39/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    40/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    41/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    42/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    43/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    44/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    45/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    46/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    47/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    48/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    49/294

     

     

    To Ind

    Mariposa Point of Gilbert

    230700

    HVAC Insulation

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    50/294

     

     

     Jeff Herron

    Vice President  Preferred Insulation Contractors, Inc.

    Cell (602) 763-1652

     [email protected] 

    P  referred 

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    51/294

    Subm ittal Sheet

     

    TYPE 75 

    TYPE 100

    11/2" (38mm) 11/2" (38mm)

    2" (51mm) 2" (51mm)

    21/5" (56mm)

    2

    2

    /5" (61mm) 

    TYPE 15021/2" (64 mm) 11/2" (38mm)

    3" (76 mm) 2" (51mm)

    31/2" (89 mm)

    4" (102 mm)

    SO FTR A ll-Service Fiber G lass D uct W rap is now

    reform ulated to reduce dust and itch.

    Description

    SOFTR All-Service F iber Glass D uct W rap is ablanket of glass fiber insulation factory-lam inated toFRK vapor retarder facing. A 2" (50m m ) stapling andtaping flange is provided on one edge. This product isdesigned to m eet existing perform ance standards suchas N FPA 90A and 90B and other m odel building andenergy codes.

    Uses

    SOFTR A ll-Service Fiber Glass Duct W rap is usedfor external insulation of com m ercial and residentialheating, air conditioning and d ual-tem perature ductsoperating at tem peratures from 40F (4C) to 250F(121C). This insulation, w hen applied inaccordance w ith installation instructions, w illprovide the “installed R-value”as published for theproduct and printed on the facing, assuring specifiedin-place therm al perform ance an d condensationcontrol.

    Features/ Benefits

    Assured Thermal Performance

    W hen installed in accordance w ith instructions sothat com pression is controlled, SO FTR A ll-Service Fiber G lass Duct W rap provides specifiedtherm al perform ance. See R-value table below .O perating costs are controlled due to reduction of

    heat loss or gain through duct walls.

    All-Service Fiber Glass Duct W rap

    Condensation Control

    SO FTR All-Service Fiber G lass D uct W rap helps

    control m oisture condensation on the ductw ork as well ason the outer vapor retarder jacket. This helps m aintaininsulation efficiency and reduces the likelihood of stained

    ceilings due to m oisture dam age.

    Enhanced Comfort Control

    SO FTR All-Service Fiber G lass D uct W rap helpsheating and cooling system s to deliver conditioned air tooccupied spaces at or near design tem peratures.By conserving heating and cooling energy, H VA C

    system s m ay operate under reduced load.

    Meets Model Energy and Mechanical Codes

    SO FTR All-Service Fiber G lass D uct W rap, w hencorrectly installed, com plies w ith m odel energy codes

    and standards including A SH RA E 90.1 and 90.2.A rchitects, contractors, code officials and ow ners areassured of com pliance and “no-problem ”inspection.A pplication of insulation is the responsibility of the

    engineer and contractor

    Flexible and Easy to Install

    SO FTR All-Service Fiber G lass D uct W rap is easily

    cut and fit to flat, curved or irregular duct surfaces fora neat, therm ally effective insulation blanket. Becauseit’s easier to install than rigid boards, installation costs

    are low ered.

    Facings

    The facing on O w ens Corning SO FTR A ll-ServiceFiber G lass Duct W rap is a F oil Reinforced K raft(FR K ) low perm eance vapor retarder m eeting therequirem ents of A ST M C 1136, Type II.

    Availability and Installed R-ValuesStandard roll w idth: 48" (1.2m )Installed R (RSI) values: W hen installed in accordance w ith recom m ended installation procedures, SO FTRAll-Service Fiber G lass D uct W rap w ill provide installed R (RSI) values as follow s:

    Nominal Out-of-Package Installed Installed

     Thickness, in. (mm) R (RSI) Value(1)   Thickness(2), in. (mm) R (RSI) Value(1)(2)

    TYPE 75 – 0.75 pcf (12 kg/ m3)

    11/2  (38) 5.1 (0.90) 1 1/8 (29) 4.2 (0.74)2 (51) 6.8 (1.20) 11/2 (38) 5.6 (0.99)21/5  (56) 7.4 (1.30) 1 5/8 (42) 6.0 (1.06)22/5  (61) 8.0 (1.41) 1 13/16 (46) 6.5 (1.14)21/2  (64) 8.3 (1.46) 1 7/8 (48) 6.9 (1.22)3 (76) 10.0 (1.76) 21/4 (57) 8.3 (1.46)

    31/2  (89) 11.0 (1.94) 2 5/8 (67) 9.7 (1.71)4 (102) 13.25 (2.33) 3 (76) 11.0 (1.94)

    TYPE 100 – 1.00 pcf (16 kg/ m3

    )11/2  (38) 5.6 (0.99) 1 1/8 (29) 4.5 (0.79)2 (51) 7.4 (1.30) 11/2 (38) 6.0 (1.06)

    TYPE 150 – 1.50 pcf (24 kg/ m3)

    11/2 (38) 6.0 (1.06) 1 1/8 (29) 4.8 (0.85)2 (51) 8.0 (1.41) 11/2 (38) 6.4 (1.13)

    (1)hr•ft2•F/Btu (m 2•C/W ) at 75F (24C) m ean tem perature. (2)A ssum es 25% com pression of insulation.

    Specification Compliance

    •A ST M C 1290, Flexible Fibrous G lass Blanket Insulation U sed to E xternally Insulate H VA C D ucts, Type III

    •A ST M C 1136, Flexible Low Perm eance Vapor Retarders for Therm al Insulation, Type II (facing only)

    •A ST M C 553,* M ineral Fiber Therm al Insulation: Type I –Fiberglas All-Service D uct W rap Type 75; Type II –SO FTR All-Service Fiber Glass D uct W rap Types 100 and 150. (O perating tem peratures to 250F (121C)and therm al values to 150F (66C) m ean.

    * Preferred specification is AST M C 1290.

    N O TE T O SP E CIFIER S –Fed eral Specification H H -I-558B (Am endm ent 3), Form B (covering the duct w rap), and FederalSpecification H H -B-100B (covering the facing), are obsolete. These are replaced by the above referenced A ST M specifications

    Thermal Conductivity

    Mean Temperature, F

    Apparent thermal conductivity curve determinedin accordance with ASTM Practice C 1045 withdata obtained by ASTM Test Method C 177.Values are nominal, subject to normal testingand manufacturing tolerances.

    0.45

    0.40

    0.35

    0.30

    0.25

    0.20

    k, Btu•in/hr•ft2•F

    TYPE 75TYPE 100

    TYPE 150

    25 50 75 100 125 150

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    52/294

    OWENS CORNING WORLD HEADQUARTERS

    O N E O W E N S C O R N IN G P A R KW A Y

    TO LEDO , O H IO , U SA 43659

    1-800-G ET-PIN K

    w w w .ow enscorning.com

    Pub. N o. 59241-A Printed in US A , O ctobe r 2003 Copyright © 200 3 O w ens C orning.

    Title Subhead is Futura Bold 9pt/ 12 Leading

    SO FTR All Service Fiber Glass D uct W rap

    Application Recommendations

    Before applying SO FTR A ll-Service Fiber G lassD uct W rap, ducts shall be clean, dry and tightly sealed

    at all joints and seam s. SO FTR A ll-Service Fiber

    G lass D uct W rap shall be cut to “stretch-out”dim en-

    sions and a 2" (50m m ) (approx.) piece of duct w rap

    rem oved from the facing at the end of the piece of

    duct w rap to form an overlapping staple and tape

    flap, as show n below .

    Install duct w rap tightly butted w ith facing outside.

    O verlap 2" (50m m ) form ed tape flap and facing at

    other end of piece of duct wrap. If du cts are

    rectangular or squ are, install so insulation is not

    excessively com pressed at duct corners. Seam s shall

    be stapled 6" (150 m m ) (approx.) on center with

    outward clinching staples. A djacent sections of duct

    w rap shall be tightly butted w ith the 2" (50m m )

    tape flap overlapping.

    W here a vapor retarder is required, seal all seam s

    and joints w ith pressure-sensitive tape m atching the

    facing (either plain foil or FR K backing stock) or

    Physical Property Data

    Property Test Method Value

    O perating tem perature A STM C 411 up to 250F (121C)

    Insulation jackettem perature lim it A STM C 1136 up to 150F (66C)

    W ater vapor perm eance A STM E 96 0.02 perm s

    W ater vapor sorption A STM C 1104

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    53/294

    HVAC Insulation

    Microlite® EQFormaldehyde-free ™  Fiber Glass Duct Wrap Insulation 

    Description

    Microlite® EQ Formaldehyde-free ™ duct wrap insulation is a brown,

    lightweight, highly resilient, blanket-type thermal insulation.

    The insulation blanket is manufactured from rotary-process fiberglass bonded with a resin made primarily from rapidly renewable

    plant-based materials.

    Available Forms

    Microlite EQ Formaldehyde-free ™ insulation is available in a variety

    of densities, thicknesses and roll lengths. It is supplied with an FSK

    (foil-scrim-kraft) vapor barrier facing to meet installed performance

    requirements, with a 2" (51 mm) stapling tab.

    Uses

    Microlite EQ insulation is recommended as thermal insulation for the

    exterior of HVAC systems or other spaces or surfaces where temperature

    control is required.

    Facing Information

    FSK Aluminum FoilReinforced with fiber glass scrim laminated to UL-rated kraft.

    Permeance: 0.02 perms*

    *Per ASTM E96, Procedure A for facing material prior to lamination. After

    lamination, permeance values may be higher.

    General Properties

    Temperature (max.) – ASTM C411 250°F (121°C)

    Water vapor sorption – ASTM C1104

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    54/294

    717 17th St.

    Denver, CO 80202

    800-654-3103

    www.JM.com

    North American Sales Offices,Insulation Systems

    Eastern RegionP.O. Box 158

    Defiance, OH 43512

    (800) 334-2399

    Fax: (419) 784-7866

     Western Region and CanadaP.O. Box 5108

    Denver, CO 80217

    (800) 368-4431

    Fax: (303) 978-4661

    The physical and chemical properties of the Microlite® EQ

    Formaldehyde-free ™ fiber glass duct wrap insulation listed hereinrepresent typical, average values obtained in accordance with

    accepted test methods and are subject to normal manufacturing

    variations. They are supplied as a technical service and are subject

     to change without notice. Numerical flame spread and smoke

    developed ratings are not intended to reflect hazards presented by

     these or any other materials under actual fire conditions. Check with

     the Regional Sales Office nearest you to ensure current information.

    All Johns Manville products are sold subject to Johns Manville’s

    standard Terms and Conditions, including Limited Warranty and

    Limitation of Remedy. For a copy of the Johns Manville standard

    Terms and Conditions, Limited Warranty and Limitation of Remedy,

    and information on other Johns Manville thermal insulation and

    systems, call (800) 654-3103.

    © 2015 Johns Manville. All Rights Reserved.

    Microlite® EQ

    Formaldehyde-free ™  Fiber Glass Duct Wrap Insulation 

    Application Recommendations

    The R-value will vary depending upon how much the insulation is

    compressed during installation. To obtain the published installed

    R-values, the insulation stretch-out should be determined using the

    following table:

    Duct Wrap Stretch-outs

      Installed

    Labeled Compressed

    Thick. (in) Thickness (in) Round Square Rectangular

    1 0.75 P+ 7.0" P+ 6.0" P+ 5.0"

    1½ 1.125 P+ 9.5" P+ 8.0" P+ 7.0"

    2 1.50 P+ 12.0" P+ 10.0" P+ 8.0"

    21 ⁄ 3  1.75 P+ 13.0" P+ 11.0" P+ 8.5"

    3 2.25 P+ 17.0" P+ 14.5" P+11.5"

    Stretch-outs include 2" (51 mm) for overlap. P = perimeter of duct to be insulated.

    Prepare overlap by removing approximately 2" (51 mm) of insulation

    from facing.

    Stretch-outDimension

    2" (51 mm)Overlap

    Before applying duct wrap, sheet metal duct shall be clean, dry and

     tightly sealed at all joints and seams.

    Wrap insulation around duct with facing to the outside so the 2" (51 mm)

    flap completely overlaps facing and insulation at the other end of stretch-

    out. Insulation shall be snugly butted.

    Secure seams with outward clinching staples placed approximately

    6" (152 mm) on center. If required, seal seam with pressure-sensitive

     tape designed for use with duct insulation. Insulation on the underside of

    ducts spanning 24" (610 mm) or greater shall be secured with mechanical

    fasteners and speed clips spaced approximately 18" (457 mm) on center.

    Fasteners should be cut off flush after the speed clips are installed, and

    when required, sealed with the same tape as specified above.

    Adjacent sections of duct wrap insulation shall be snugly butted with

     the circumferential 2" (51 mm) tape flap overlapping and secured as

    recommended for the longitudinal seam. When a vapor seal is required,

     two coats of vapor retarder mastic reinforced with one layer of 4"

    (102 mm) wide, open-weave glass fabric may be used in lieu of pressure-

    sensitive tape.

    Guide Specifications

    Insulation for Metal Ducts. All ducts shall be insulated on the outsidewith a Formaldehyde-free ™, flexible glass fiber blanket. Microlite EQ

    Formaldehyde-free ™ fiber glass duct wrap insulation should have a

    minimum installed R-value* of _______, and a Type_____ facing.

    Insulation shall be furnished with a factory-applied facing with a

    composite UL FHC rating of 25/50.

    *The minimum insulation installed R-value should be determined in accordance tothe duct operating and ambient conditions.

    Installed R-values

    LabeledThickness Installed “R”** Out-of-Package “R”

    Type in mm (hr•ft2•°F) /Btu m2•°C/W (hr•ft2•°F)/Btu m2•°C/W

    75 1½ 38 4.2 0.74 5.2 0.922 51 5.6 0.99 6.9 1.2221 ⁄ 3 58 6.5 1.15 8.0 1.413 76 8.3 1.46 10.3 1.81

    100 1½ 38 4.5 0.79 5.6 0.99

    2 51 6.0 1.06 7.4 1.30150 1½ 38 4.7 0.83 6.0 1.06

    2 51 6.3 1.11 8.0 1.41

    **Installed R-value calculated with a material thickness compressed to a

    maximum of 25% following recommended duct wrap stretch-outs.

    Thermal Conductivity (ASTM C518)

      k* k

      Compressed Thickness Labeled Thickness

    Type Btu•in/(hr•ft2•°F) W/m•°C Btu•in/(hr•ft2•°F) W/m•°C

      75 0.27 0.039 0.29 0.042100 0.25 0.036 0.27 0.039

    150 0.24 0.035 0.25 0.036

    Conductivity at 75°F (24°C) mean temperature.

    *Tested with material thickness compressed 25%.

    HVAC-448 5/15 (Replaces 11/14)

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    55/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    56/294

    • For cooling, heating or dual

    temperature service.

    • Friendly Feel® Duct Wrap—

    meets the most stringent

    IAQ tests—GREENGUARD

    Children & SchoolsSM

     andCalifornia’s Section 01350

    standard.

    • Both white and black PSK

    facings offer exceptional

    durability and performance

    for exposed applications.

    • KwikStretch Markings allow

    for easier, faster measure-

    ment of stretch-out lengths.

    Facts at a glance

    • Black PSK facing is a

    desirable solution for

    exposed ductwork because

    of its appearance and

    resiliency.

    • Fire-resistant facing

    • Conforms to flat or irregular surfaces

    • Excellent acoustical properties

    • ECOSE Technology is a revolutionary new more sustainable binder based on

    rapidly renewable bio-based materials rather than non-renewable petroleum-based

    chemicals such as phenol, formaldehyde, acrylics or artificial colors.

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    57/294

    Friendly Feel® Duct Wrap with ECOSE ® Technology 

    Description

    Knauf Friendly Feel® Duct Wrap with ECOSE

    Technology and KwikStretch® Markings is a thermal

    and acoustical insulation blanket made from

    highly resilient, inorganic glass fibers bonded by

    a thermosetting resin. It is available unfaced, with

    a foil-scrim-kraft (FSK) jacket and with a white or

    black metalized polypropylene-scrim-kraft (PSK)

     jacket. Vapor retarders provide a 2" (51 mm) staple

    flange on one edge, and the factory-applied facing

    assures uniform quality. KwikStretch Markings on

    the staple flange allow for easy and accurate job

    site measurements.

    ECOSE Technology

    ECOSE Technology is a revolutionary new binder

    chemistry that makes Knauf Insulation products

    even more sustainable than ever. It is based on

    rapidly renewable bio-based materials rather

    than non-renewable petroleum-based chemicals

    traditionally used in fiberglass insulation products.

    ECOSE Technology reduces binder embodied

    energy and does not contain phenol, formaldehyde,

    acrylics or artificial colors.

    Application

    Knauf Friendly Feel® Duct Wrap is used as external

    insulation on commercial or residential heating or

    air conditioning ducts. It is suitable for the exterior

    of rectangular or round sheet metal ducts and

    spaces or surfaces where temperature and conden-

    sation must be controlled.

    Features and Benefits

    • Low “k” factor significantly reduces heat gain or

    loss when applied with proper compression.

    • Flexible.

    • Lightweight.

    • KwikStretch Markings on the FSK and PSK

    staple flanges.

    • Excellent acoustical properties.

    • Tough and resilient.

    • Energy conservation, which lowers operating costs.

    • System efficiency increases; energy usage/costs

    decrease.

    • Conforms easily to flat or irregular surfaces.

    • Rolls allow for faster installation, lower labor costs.

    • Easier, faster measurement of stretch-out

    lengths.

    • Reduces sound transmission through the duct wall.

    • Assured condensation control when used with

    FSK or PSK facings, proper installation and

    sealed joints, seams and penetrations.

    • Resists damage in shipment and during and

    after installation.

    • Certified for indoor air quality as a low emitting

    product by The GREENGUARD Environmental

    Institute to both the GREENGUARD Certification

    ProgramSM  and the more stringent GREEN-

    GUARD Children and SchoolsSM standard.

    Specification Compliance

    In U.S.:

    • ASTM C 1139 - unfaced; Type I, Type II,

    Grade 1 - 0.75 lb/ft3

      Grade 2 - 1.0 lb/ft3

      Grade 3 - 1.5 lb/ft3

    • ASTM C 553; Type I, II, III• ASTM C 1136; Type II

    • ASTM C 1290

    • GREENGUARD Children & SchoolsSM

    Certification

    • California Title 24 (installed at 25%

    compression)

    • HH-I-558C; Form B, Type I, Class 7

    • NFPA 90A and 90B

    In Canada:

    • CAN/ULC S102-M88

    • CAN/CGSB-51.5M; Type II (FSK facing)

    • CAN/CGSB-51.11-92

    Technical Data

    Surface Burning Characteristics

    • UL/ULC Classified (FSK).

    • Unfaced or composite (insulation, facing and

    adhesive) does not exceed 25 Flame Spread,

    50 Smoke Developed when tested in accor-

    dance with ASTM E 84 (PSK only), CAN/ULC

    S102-M88, NFPA 255 and UL 723.

    Temperature Range (ASTM C 411)

    • Faced, can be used on ducts operating up to

    250°F (121°C).

    • Unfaced, up to 350°F (177°C).

    Water Vapor Permeance (ASTM E 96,

    Procedure A)

    • FSK and white PSK facings have maximum

    water vapor permeance of .02 perms.

    • Black PSK facing has a maximum water vapor

    permeance of .09 perms.

    Water Vapor Sorption (ASTM C 1104)

    • Less than 5% by weight when tested for

    96 hours at 120°F (49°C) and 95% relative

    humidity.

    Corrosiveness (ASTM C 665)

    • Does not accelerate corrosion on steel,

    copper or aluminum.Corrosion (ASTM C 1617)

    • The corrosion rate in mils/yr will not exceed that

    of the 1 ppm chloride solution.

    Mold Growth (ASTM C 1338)

    • No growth.

    Puncture Resistance

    (TAPPI Test T803) (Beach Units)

    • FSK and PSK: 25

    Application & Specification Guidelines

    Storage

    • Protect stored insulation from water damage,

    construction damage and other abuse.

    • If stored outside, proper protection from weather

    conditions should be provided.

    Preparation

    • Install Knauf Friendly Feel® Duct Wrap over

    clean, dry sheet metal ducts. All sheet metal

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    58/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    59/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    60/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    61/294

     

     

    To Ind

    Mariposa Point of Gilbert

    230713

    Duct Insulation- Please see section 230700

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    62/294

     

     

    To Ind

    Mariposa Point of Gilbert

    230719

    HVAC Piping Insulation

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    63/294

     

     

     Jeff Herron

    Vice President  Preferred Insulation Contractors, Inc.

    Cell (602) 763-1652

     [email protected] 

    P  referred 

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    64/294

     

     

     

     

     

     

      

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    65/294

     

     

     

     

     

     

       

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    66/294

     

     

    To Ind

    Mariposa Point of Gilbert

    231123

    Facility Natural Gas Piping- NA

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    67/294

     

     

    To Ind

    Mariposa Point of Gilbert

    232300

    Piping

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    68/294

    tubeCOPPER TUBE FOR CONSTRUCTION APPLICATIONS

    Technical Data: 7-04

    Corporate Headquarters

    PO Box 66800 • St. Louis, MO 63166-6800

    888-237-7611 | 618-337-6000 • f. 618-337-6958

    www.cerroflow.com

    Copper UNS No. C12200Types K, L, and MASTM B88

    Color marking is not applicable to tube furnished in annealed straight

    lengths or coils.

    Typical uses include:

    • Type M - above ground residential and light

    commercial uses. (Sizes range from 3/8" - 8"

    diameter)

    • Type L - residential and commercial uses.

    (Sizes range from 1/4" - 8" diameter)

    • Type K - underground residential, commercial

    and industrial uses. (Sizes range from

    1/4" - 8" diameter)• Type DWV - ASTM B306: used for drainage,

    waste and vents

    Cerro tube is the original copper tube for plumbing, air conditioning and

    refrigeration applications in residential, commercial and institutional

    installations. We provide a complete range of sizes and types, engineered

     to exact specifications to meet the highest standards of performance.

    Product

    Copper 

    Water Tube,

    Type K 

    (heavy wall) 

    Copper 

    Water Tube,

    Type L 

    (medium wall) 

    Copper 

    Water Tube,

    Type M

    (light wall) 

    Copper 

    Drainage 

    Tube,

    Type DWV 

    Temper

    Hard

    Soft

    Hard

    Soft

    Hard

    Hard

    Lengths

    10 ft. straight

    20 ft. straight

    20 ft. straight40 ft. coils

    60 ft. coils

    100 ft. coils

    10 ft. straight

    20 ft. straight

    20 ft. straight

    30 ft. coils

    40 ft. coils

    60 ft. coils

    100 ft. coils

    10 ft. straight

    20 ft. straight

    10 ft. straight

    20 ft. straight

    Uses

    Domestic water

    service and

    distribution, fire

    protection, solar,fuel/fuel oil, HVAC,

    snow melting,

    compressed air,

    natural gas,

    liquefied petroleum

    (LP) gas, vacuum

    Domestic water

    service and

    distribution, fire

    protection, solar,

    fuel/fuel oil, HVAC,

    snow melting,

    compressed air,

    natural gas,

    liquefied petroleum

    (LP) gas, vacuum

    General plumbing

    and heating purposes;

    drainage waste,

    vent and other light

    pressure uses.

    Drainage waste,

    vents, soil and other

    non-pressure

    applications

    Specifications

    ASTM B88

    ASTM B88

    ASTM B88

    ASTM B306

    Code

    Green

    Blue

    Red

    Yellow

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    69/294

    AHEAD OF THE F LOW®

    C o p p e r F i t t i n g

    CATALOG C-CF-0508

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    70/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    71/294

      A H E A D O F T H E F L O W® www.nibco.com

    NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455

    www.nibco.com6

    Revision 5/1/08

    703-2Fitting Adapter Ftg x F – Cast  APPROX. DIM. B  NOM. SIZE NET WT./LBS. INCHES

      1/2 x 1/4 0.11 17 /32

      3/4 x 1/2 0.12 19 /16

      1 x 3/4 0.38 131 /32

      1 x 1/2 0.15 17 /16

      2 1/2 1.65 215

     /16  3 2.47 31 /4

    703-5 Special

    Drop Adapter C x F – Cast  APPROX. DIM. A  NOM. SIZE NET WT./LBS. INCHES

      1/2 0.16 3 /4

      3/4 0.24 31 /32

    703-5BDrop Adapter C x F – Cast  APPROX. DIM. A  NOM. SIZE NET WT./LBS. INCHES

      1/2 0.15 3 /4

    ADAPTERS

    603Adapter C x F – Wrot  APPROX. DIM. A  NOM. SIZE NET WT./LBS. INCHES

      1/8 0.03 13 /32

      1/8 x 1/4 0.03 1 /2

      1/4 0.03 5 /8

      1/4 x 3/8 0.05 21 /32

      3/8 0.04

    11

     /16

      3/8 x 1/2 0.09 29 /32

      3/8 x 1/4 0.03 9 /16

      1/2 0.09 27 /32

      1/2 x 3/4 0.14 1

      1/2 x 3/8 0.04 17 /32

      1/2 x 1/4 0.05 1 /2

      5/8 x 3/4 0.12 29 /32

      5/8 x 1/2 0.11 3 /4

      3/4 0.15 29 /32

      3/4 x 1 0.21 11 /8

      3/4 x 1/2 0.10 5 /8

      1 0.24 31 /32

      1 x 1 1/4 0.28 17 /32  1 x 3/4 0.19 25 /32

      1 x 1/2 0.24 5 /8

      1 1/4 0.33 13 /32

      1 1/4 x 1 1/2 0.40 11 /4

      1 1/4 x 1 0.27 31 /32

      1 1/2 0.44 11 /8

      1 1/2 x 2 0.50 11 /32

      2 0.63 13 /32

      2 x 1 1/2 0.74 13 /16 

    2 1/2 1.13 –

      3 1.94 –

    703Adapter C x F – Cast  APPROX. DIM. A  NOM. SIZE NET WT./LBS. INCHES

      1/4 x 1/2 0.13 27 /32

      1/2 x 1 0.30 1

      3/4 x 1 1/4 0.55 11 /8

      3/4 x 3/8 0.17 3 /4

      1 x 1 1/2 0.6813

     /32

      1 1/4 x 1 0.27 31 /32

      1 1/4 x 3/4 0.29 3 /4

      1 1/2 x 2 0.78 11 /32

      1 1/2 x 1 0.37 25 /32

      1 1/2 x 1 1/4 0.47 11 /4

      2 x 1 1/4 0.76 27 /32

      2 1/2 1.62 13 /8

      3 2.34 11 /2

      4 4.05 19 /16

     

    603-2Fitting Adapter Ftg x F – Wrot  APPROX. DIM. B  NOM. SIZE NET WT./LBS. INCHES

      1/4 0.03 13 /32

      3/8 0.06 13 /16

      1/2 0.09 17 /16

      1/2 x 3/8 0.05 11 /4

      3/4 0.13 111 /16  1 0.27 21 /32

      1 1/4 0.31 21 /8

      1 1/2 0.43 25 /16

      2 0.61 217 /32

     Consult price sheet for Made to Order items andfor minimum order quantities.

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    72/294

      A H E A D O F T H E F L O W® www.nibco.com

    NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455

    www.nibco.com

    7

    Revision 5/1/08

    ADAPTERS continued 

    604Adapter C x M – Wrot  APPROX. DIM. B  NOM. SIZE NET WT./LBS. INCHES

      1/8 x 1/4 0.03 7 /16

      1/4 0.03 23 /32

      3/8 0.04 15 /32

      3/8 x 3/4 0.15 15 /16

      3/8 x 1/2 0.09 1  1/2 0.07 5 /8

      1/2 x 1 0.25 11 /2

      1/2 x 3/4 0.15 13 /16

      1/2 x 3/8 0.05 19 /32

      1/2 x 1/4 0.07 5 /8

      5/8 x 3/4 0.16 11 /8

      5/8 x 1/2 0.08 3 /4

      3/4 0.14 13 /16

      3/4 x 1 0.26 17 /16

      3/4 x 1/2 0.10 27 /32

      1 0.21 31 /32

      1 x 1 1/2 0.54 29 /32

      1 x 1 1/4 0.38 11 /2  1 x 3/4 0.18 29 /32

      1 x 1/2 0.18 31 /32

      1 1/4 0.35 15 /16

      1 1/4 x 1 1/2 0.51 119 /32

      1 1/4 x 1 0.27 15 /32

      1 1/2 0.44 31 /32

      1 1/2 x 2 0.81 11 /8

      1 1/2 x 1 1/4 0.38 13 /16

      1 1/2 x 1 0.37 13 /32

      2 0.81 13 /32

      2 x 1 1/2 0.64 11 /8

      2 1/2 1.48 121 /32

      3 1.69 –

     Consult price sheet for Made to Order items andfor minimum order quantities.

    704Adapter C x M – Cast  APPROX. DIM. B  NOM. SIZE NET WT./LBS. INCHES

      3/4 x 1 1/2 0.60 117 /32

      3/4 x 1 1/4 0.38 17 /32

      3/4 x 3/8 0.19 13 /16

      1 x 2 1.15 –

      1 x 1 1/2 0.6429

     /32

      1 1/4 x 2 0.88 19 /32

      1 1/4 x 3/4 0.30 31 /32

      1 1/2 x 2 0.77 11 /8

      2 x 2 1/2 1.57 115 /32

      2 x 1 1/2 0.71 11 /8

      2 x 1 1/4 1.08 –

      2 1/2 1.48 121 /32

      2 1/2 x 2 1.83 111 /16

      3 1.96 11 /2

      4 3.66 111 /16

      5 8.60 25 /8

      6 10.73 2

    704-FFlush Adapter C x M – Cast  APPROX. DIM. B  NOM. SIZE NET WT./LBS. INCHES

      1/2 0.03 9 /16

      3/4 0.03 19 /32

    704-HHose Adapter C x Hose – Cast  APPROX. DIM. A  NOM. SIZE NET WT./LBS. INCHES

      1/2 0.09 9 /32

    NOTE: Fits 1 /2," 5 /8" and 3 /4" Garden Hose.

    604-2Fitting Adapter Ftg x M – Wrot  APPROX. DIM. B  NOM. SIZE NET WT./LBS. INCHES

      1/8 0.02 11 /8

      3/8 0.04 11 /4

      1/2 0.09 115 /32

      1/2 x 3/4 0.16 113 /16

      1/2 x 3/8 0.04 111 /32

      3/4 0.17 115 /16

      1 0.25 21 /4

    704-2

    Fitting Adapter Ftg x M – Cast  APPROX. DIM. B  NOM. SIZE NET WT./LBS. INCHES

      3/4 x 1 0.27 131 /32

      3/4 x 1/2 0.12 123 /32

      1 x 3/4 0.24 115 /16

      1 1/4 0.43 227 /32

      1 1/2 0.54 213 /32

      2 0.89 23 /4

      2 1/2 1.55 33 /8

      3 2.21 323 /32

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    73/294

      A H E A D O F T H E F L O W® www.nibco.com

    NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455

    www.nibco.com8

    Revision 5/1/08

    750Bulkhead Fitting C x C – Cast  APPROX. DIM. A DIM. B  NOM. SIZE NET WT./LBS. INCHES INCHES

      1/2 0.48 11 /4 1

      3/4 0.77 19 /32 11 /4

      1 1.30 11 /2 15 /8

      1 1/2 2.87 11 /2 23 /8

      2 3.82 21 /32 25 /8

    750-3Bulkhead Fitting C x F – Cast  APPROX. DIM. A DIM. B  NOM. SIZE NET WT./LBS. INCHES INCHES

      1/2 0.48 115 /16 1

      3/4 0.79 21 /16 11 /4

      1 1.43 215 /32 15 /8

    750-4Bulkhead Fitting C x M – Cast  APPROX. DIM. A DIM. B  NOM. SIZE NET WT./LBS. INCHES INCHES

      1/2 0.40 131 /32 1

      3/4 0.79 25 /32 11 /4

    704-2-HHose Adapter Ftg x Hose – Cast  APPROX. DIM. B  NOM. SIZE NET WT./LBS. INCHES

      3/4 F x 3/4 H 0.16 15 /8

    NOTE: Fits 1 /2," 5 /8" and 3 /4" Garden Hose.

    619Air Chamber Ftg. – Wrot  APPROX. DIM. A DIM. L  NOM. SIZE NET WT./LBS. INCHES INCHES

      1/2 x 6 0.21 1 6

      1/2 x 12 0.41 1 12

      1/2 x 14 0.78 11 /8 14

      3/4 x 12 0.40 1 12

    620-LAir Chamber or Stub-OutFtg – Wrot

    As Air Chamber, just solder one joint. When usedas Stub-Out, simply pressure test system then cutoff stub-out (save piece for future use) and installvalve or fixture.

      APPROX. DIM. L  NOM. SIZE NET WT./LBS. INCHES

      1/2 x 6 0.14 6

      1/2 x 8 0.19 8

      1/2 x 10 0.24  10

      1/2 x 12 0.28 12

      3/4 x 12 0.46 12

     AIR CHAMBERS

     BULKHEADFITTINGS

     Consult price sheet for Made to Order items andfor minimum order quantities.

    618Flush Bushing Ftg x C – Wrot  APPROX. DIM. C  NOM. SIZE NET WT./LBS. INCHES

      1/4 x 1/8 0.01 1 /16

      3/8 x 1/4 0.01 1 /16

      1/2 x 3/8 0.02 3 /32

      1/2 x 1/4 0.04 1 /4

      5/8 x 1/2 0.03 1 /16

      3/4 x 5/8 0.22 3 /16

      3/4 x 1/2 0.08 3 /32

      3/4 x 3/8 0.11 7 /16

      1 x 3/4 0.12 1 /8

      1 x 1/2 0.22 15 /32

      1 1/4 x 1 0.17 3 /32

      1 1/2 x 1 1/4 0.22 5 /32

      2 x 1 1/2 0.66 1 /8

    618-3Flush Bushing Ftg x F – Wrot  APPROX. DIM. B  NOM. SIZE NET WT./LBS. INCHES

      1/2 x 1/8 0.03 9 /16

      1/2 x 1/4 0.03 9 /16

    718-3Flush Bushing Ftg x F – Cast  APPROX. DIM. B  NOM. SIZE NET WT./LBS. INCHES

      3/4 x 3/8 0.06 131 /32

      1 x 1/2 0.13 31 /32

      1 1/4 x 3/4 0.18 11 /32

      1 1/2 x 1 0.25 15 /32

     BUSHINGSADAPTERS continued 

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    74/294

      A H E A D O F T H E F L O W® www.nibco.com

    NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455

    www.nibco.com

    9

    Revision 5/1/08

     Consult price sheet for Made to Order items andfor minimum order quantities.

    CAPS

    617Tube Cap C – Wrot  APPROX. DIM. N  NOM. SIZE NET WT./LBS. INCHES

      1/8 0.01 1 /32

      1/4 0.01 3 /32

      3/8 0.01 3 /32

      1/2 0.02 3 /32

      5/8 0.03 1 /8

      3/4 0.04 1 /8

      1 0.07 5 /32

      1 1/4 0.10 3 /32

      1 1/2 0.16 1 /8

      2 0.27 5 /32

      2 1/2 0.50 7 /32

      3 0.78 7 /32

      4 1.66 1 /4

    717Tube Cap C – Cast  APPROX. DIM. N  NOM. SIZE NET WT./LBS. INCHES

      5 5.48 7 /16

      6 9.07 17 /32

    717-DDrain Cap – Cast  APPROX. DIM. A  NOM. SIZE NET WT./LBS. INCHES

      1/2 0.06 21 /32

     COUPLINGS

    600Reducing Coupling C x C – Wrot  APPROX. DIM. A  NOM. SIZE NET WT./LBS. INCHES

      1/8 x 3/16 O.D. 0.01 5 /32

      5/16 O.D. x 1/8 0.01 3 /16

      1/4 x 5/16 O.D. 0.01 3 /16

      1/4 x 1/8 0.01 3 /16

      3/8 x 1/4 0.02 3 /16

      3/8 x 5/16 O.D. 0.01 1 /4

      3/8 x 1/8 0.01 1 /4

      1/2 x 3/8 0.03 3 /16

      1/2 x 1/4 0.02 1 /4

      1/2 x 1/8 0.03 11 /32

      5/8 x 1/2 0.05 3 /16

      5/8 x 3/8 0.04 11 /32

      5/8 x 1/4 0.03 13 /32

      3/4 x 5/8 0.07 3 /16

      3/4 x 1/2 0.06 9 /32

      3/4 x 3/8 0.06 3 /8

      3/4 x 1/4 0.05 11 /32

      1 x 3/4 0.11 11 /32

      1 x 5/8 0.09 3 /8

      1 x 1/2 0.10 11 /32

      1 x 3/8 0.10 13 /32

      1 1/4 x 1 0.16 5 /16

      1 1/4 x 3/4 0.18 17 /32

      1 1/4 x 5/8 0.18 5 /8

      1 1/4 x 1/2 0.14 7 /16

      1 1/2 x 1 1/4 0.23 5 /16

      1 1/2 x 1 0.22 9 /16

      1 1/2 x 3/4 0.20 3 /8

      1 1/2 x 1/2 0.19 1 /2

      2 x 1 1/2 0.41 9 /16

      2 x 1 1/4 0.35 11 /16

      2 x 1 0.37 7 /16

      2 x 3/4 0.34

    17

     /32  2 x 1/2 0.35 23 /32

      2 1/2 x 2 0.59 9 /16

      2 1/2 x 1 1/2 0.65 11 /16

      2 1/2 x 1 1/4 0.65 13 /16

      2 1/2 x 1 0.73 29 /32

    Continues…

      APPROX. DIM. A  NOM. SIZE NET WT./LBS. INCHES

      3 x 2 1/2 0.98 1 /2

      3 x 2 1.06 15 /16

      3 x 1 1/2 0.92 11 /32

      3 1/2 x 3 1.52 1 /2

      4 x 3 1/2 2.12 19 /32

      4 x 3 1.92 27 /32

      4 x 2 1/2 1.77 1

      4 x 2 1.92 11 /4

      5 x 4 3.50 331 /32

      5 x 3 3.18 115 /32

      5 x 2 1/2 3.50 13 /16

      5 x 2 3.09 21 /32

      6 x 5 5.70 11 /8

      6 x 4 5.24 11 /2

      6 x 3 5.04 2

      6 x 2 1/2 5.13 21 /4

      6 x 2 4.89 21 /2

      8 x 6 13.06 119 /32

      8 x 4 12.22 219 /32

      8 x 3 11.79 33 /32

      8 x 2 1/2 12.64 33 /8

    600-RSCoupling with Rolled Tube StopC x C – Wrot  APPROX. DIM. A  NOM. SIZE NET WT./LBS. INCHES

      1/8 O.D. 0.01 1 /16

      3/16 O.D. 0.01 3 /32

      1/8 0.01 1 /16

      5/16 O.D. 0.01 3 /32

      1/4 0.01 1 /16

      3/8 0.01 3 /32

      1/2 0.03 3 /32

      5/8 0.04 3 /32

      3/4 0.06 3 /32

      7/8 0.09 3 /32

      1 0.11 3 /32

      1 1/4 0.16 1 /8

      1 1/2 0.23 1 /8

      2 0.41 1 /8

      2 1/2 0.65 1 /8

      3 0.93 1 /8

      3 1/2 1.45 5 /32

      4 1.93 7 /32

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    75/294

      A H E A D O F T H E F L O W® www.nibco.com

    NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455

    www.nibco.com10

    Revision 5/1/08

    601Coupling without StopC x C – Wrot  APPROX. DIM. B  NOM. SIZE NET WT./LBS. INCHES

      1/4 0.01 11 /16

      3/8 0.01 27 /32

      1/2 0.03 1

      5/8 0.04 111

     /32  3/4 0.06 119 /32

      1 0.11 129 /32

      1 1/4 0.16 21 /16

      1 1/2 0.23 25 /16

      2 0.41 213 /16

      2 1/2 0.64 215 /16

      3 0.86 35 /16

      3 1/2 1.40 313 /16

      4 1.84 45 /16

      5 3.50 55 /16

      6 5.60 63 /16

      8 13.68 83 /32

    701Reducing Coupling C x C – Cast  APPROX. DIM. A  NOM. SIZE NET WT./LBS. INCHES

      3 x 1 1/4 1.35 23 /32

      3 x 1 1.64 27 /32

    COUPLINGS continued 

     Consult price sheet for Made to Order items andfor minimum order quantities.

    600-DSCoupling with Dimpled Tube StopC x C – Wrot  APPROX. DIM. A  NOM. SIZE NET WT./LBS. INCHES

      3/16 O.D. 0.01 3 /32

      1/8 0.01 1 /16

      5/16 O.D. 0.01 3 /32

      1/4 0.011

     /16  3/8 0.01 3 /32

      1/2 0.03 3 /32

      5/8 0.04 3 /32

      3/4 0.06 3 /32

      7/8 0.09 3 /32

      1 0.11 3 /32

      1 1/4 0.16 1 /8

      1 1/2 0.23 1 /8

      2 0.41 1 /8

      2 1/2 0.65 1 /8

      3 0.93 1 /8

      3 1/2 1.45 5 /32

      4 1.93 7 /32

      5 3.53 7 /32

      6 5.63 7 /32

      8 14.12 15 /32

    701-DDrain Coupling C x C – Cast  APPROX. DIM. A  NOM. SIZE NET WT./LBS. INCHES

      1/2 0.08 1 /4

      3/4 0.14 1 /4

      1 0.22 1 /4

    702Eccentric Coupling C x C – Cast  APPROX. DIM. A  NOM. SIZE NET WT./LBS. INCHES

      3/4 x 1/2 0.10 17 /32

      1 x 3/4 0.18 1 /4

      1 1/4 x 1 0.25 1 /4

      1 1/4 x 3/4 0.24 9 /32

    724-5-A

    Hy-Set Hanger CouplingC – Cast  APPROX. DIM. C DIM. D  NOM. SIZE NET WT./LBS. INCHES INCHES

      1/2 0.05 15 /8  23 /32

      3/4 0.09 15 /8  27 /32

      1 0.13 15 /8  1

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    76/294

      A H E A D O F T H E F L O W® www.nibco.com

    NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455

    www.nibco.com

    11

    Revision 5/1/08

    736Cross-Over CouplingC x C – Cast  APPROX. DIM. A  NOM. SIZE NET WT./LBS. INCHES

      1/2 0.27 17 /16

      3/4 0.60 129 /32

    COUPLINGS continued 

    735Cross C x C x C x C – Cast  APPROX. DIM. A  NOM. SIZE NET WT./LBS. INCHES

      3/8 0.09 3 /8

      1/2 0.15 7 /16

      3/4 0.30 9 /16

      1 0.54 23 /32

      1 1/4 0.78 7 /8

      1 1/2 1.05 1

      2 2.00 11 /4

      2 1/2 2.96 11 /2

     CROSSES ELBOWS

    60645° Elbow C x C – Wrot  APPROX. DIM. C DIM. D  NOM. SIZE NET WT./LBS. INCHES INCHES

      1/8 0.01 1 /4  1 /4

      1/4 0.02 9 /32  9 /32

      3/8 0.03 3 /16  3 /16

      1/2 0.04 9 /32  9 /32

      5/8 0.09

    15

     /32

     

    15

     /32

      3/4 0.10 11 /32  11 /32

      7/8 0.20 11 /16  11 /16

      1 0.16 3 /8  3 /8

      1 1/4 0.25 17 /32  17 /32

      1 1/2 0.35 19 /32  19 /32

      2 0.65 25 /32  25 /32

      2 1/2 1.07 29 /32  29 /32

      3 1.58 11 /8  11 /8

      4 3.35 17 /16  17 /16

      5 11.05 19 /16  19 /16

      6 16.95 2 2

      8 23.00 29 /32  29 /32

    606-245° Fitting Elbow Ftg x C – Wrot  APPROX. DIM. B DIM. C  NOM. SIZE NET WT./LBS. INCHES INCHES

      1/4 0.029

     /16 1

     /4  1/2 0.04 3 /4  7 /32

      5/8 0.08 11 /8  13 /32

      3/4 0.10 11 /16  5 /16

      1 0.16 17 /32  15 /32

      1 1/4 0.25 119 /32  17 /32

      1 1/2 0.35 125 /32  19 /32

      2 0.65 23 /16  25 /32

      2 1/2 1.07 23 /16  29 /32

      3 1.55 219 /32  15 /32

     Consult price sheet for Made to Order items andfor minimum order quantities.

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    77/294

      A H E A D O F T H E F L O W® www.nibco.com

    NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455

    www.nibco.com12

    Revision 5/1/08

    ELBOWS continued 

     Consult price sheet for Made to Order items andfor minimum order quantities.

    706-245° Fitting Elbow Ftg x C – Cast  APPROX. DIM. B DIM. C  NOM. SIZE NET WT./LBS. INCHES INCHES

      4 4.31 311 /32  15 /16

    60790° Elbow – Close RoughC x C – Wrot  APPROX. DIM. C DIM. D  NOM. SIZE NET WT./LBS. INCHES INCHES

      1/8 0.01 13 /32  13 /32

      1/4 0.02 9 /32  9 /32

      3/8 0.03 1 /2  1 /2

      1/2 0.04 3 /8  3 /8

      1/2 x 3/8 0.04 9 /16  21 /32

      3/4 0.10 17 /32  17 /32

      3/4 x 5/8 0.12 29 /32  7 /8

      3/4 x 1/2 0.10 17 /32  3 /4

      1 0.21 23 /32  23 /32

      1 x 3/4 0.16 23 /32  5 /8

      1 1/4 0.31 11 /32  11 /32

      1 1/4 x 1 0.31 15 /8  115 /32

      1 1/2 0.46 17 /32  17 /32

      1 1/2 x 1 1/4 0.35 15 /32  13 /32

      2 0.84 11 /2  11 /2

      2 x 1 1/2 0.58 17 /16  11 /4

      2 1/2 1.41 127 /32  127 /32

      3 2.07 23 /32  23 /32

      3 1/2 2.94 23 /8  23 /8

      4 4.23 225 /32  225 /32

      5 7.74 27 /8  27 /8

      6 10.95 37 /16  37 /16

      8 29.50 423 /32  423 /32

    70790° Elbow – Close RoughC x C – Cast  APPROX. DIM. C DIM. D  NOM. SIZE NET WT./LBS. INCHES INCHES

      1 1/4 x 1 0.42 15 /8  115 /32

      1 1/4 x 3/4 0.34 9 /16  13 /16

      1 1/4 x 1/2 0.28 15 /32  27 /32

      1 1/2 x 1 0.5411

     /16  1  1 1/2 x 3/4 0.42 19 /32  31 /32

      1 1/2 x 1/2 0.40 5 /8  29 /32

      2 x 1 1/4 0.86 7 /8  11 /4

      2 x 1 0.78 3 /4  11 /4

      2 x 3/4 0.69 5 /8  11 /4

      2 1/2 x 2 2.16 13 /16  19 /32

      3 x 2 1/2 2.26 111 /16  11 /2

      3 x 2 2.68 13 /8  19 /16

      4 x 3 5.18 129 /32  215 /32

    607-I90° Elbow –Intermediate Radius C x C– Wrot  APPROX. DIM. C DIM. D  NOM. SIZE NET WT./LBS. INCHES INCHES

      1/2 0.06 19 /32 19 /32

      5/8 0.09 7 /8 7 /8

      3/4 0.14 13 /16 3 /16

      1 0.24 11 /16 11 /16

    607-LT90° Elbow – Long RadiusC x C – Wrot  APPROX. DIM. C DIM. D NOM. SIZE NET WT./LBS. INCHES INCHES

      3/16 O.D. 0.01 13 /32  13 /32

      1/8 0.01 13 /32  13 /32

      5/16 O.D. 0.02 9 /16  9 /16

      1/4 0.0217

     /32 17

     /32  1/4 x 1/8 0.01 19 /32  1 /2

      3/8 0.04 23 /32  23 /32

      1/2 0.08 7 /8  7 /8

      1/2 x 3/8 0.06 13 /16  13 /16

      1/2 x 1/4 0.03 25 /32  21 /32

      5/8 0.10 13 /32  13 /32

      5/8 x 1/2 0.09 11 /16  11 /16

      3/4 0.16 11 /8  11 /8

      3/4 x 5/8 0.13 11 /4  13 /32

      3/4 x 1/2 0.10 11 /8  11 /16

      7/8 0.28 119 /32  119 /32

      1 0.28 17 /16  17 /16

      1 x 3/4 0.20 11 /4  11 /8

      1 x 5/8 0.15 113 /32  13 /32

      1 1/4 0.42 17 /8  17 /8

      1 1/4 x 1 0.33 125 /32  11 /2

      1 1/2 0.66 21 /4  21 /4

      2 1.23 215 /16  215 /16

      2 1/2 1.96 311 /16  311 /16

      3 2.93 41 /32  41 /32

      4 5.95 51 /4  51 /4

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    78/294

      A H E A D O F T H E F L O W® www.nibco.com

    NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455

    www.nibco.com

    13

    Revision 5/1/08

     Consult price sheet for Made to Order items andfor minimum order quantities.

    607-290° Fitting Elbow – Close RoughFtg x C – Wrot  APPROX. DIM. B DIM. C  NOM. SIZE NET WT./LBS. INCHES INCHES

      1/4 0.02 3 /4  3 /8

      3/8 0.03 15 /16  1 /2

      1/2 0.04 31 /32  3 /8

      5/8 0.07 17

     /32 17

     /32  3/4 0.10 111 /32  17 /32

      1 0.20 13 /4  27 /32

      1 1/4 0.33 21 /8  11 /32

      1 1/2 0.46 213 /32  17 /32

      2 0.84 227 /32  11 /2

      2 1/2 1.39 315 /32  129 /32

      3 2.10 313 /16  23 /32

      4 4.00 43 /4  225 /32

    607-2-I90° Fitting Elbow –Intermediate RadiusFtg x C – Wrot  APPROX. DIM. B DIM. C  NOM. SIZE NET WT./LBS. INCHES INCHES

      1/2 0.06 15 /32  19 /32

      5/8 0.09 19

     /16 7

     /8  3/4 0.14 15 /8  13 /16

      1 0.24 21 /32  11 /16

    607-2-LT90° Fitting Elbow – Long RadiusFtg x C – Wrot  APPROX. DIM. B DIM. C  NOM. SIZE NET WT./LBS. INCHES INCHES

      1/8 0.01 13 /32  1 /2

      1/4 0.02 11 /8  3 /4

      3/8 0.05 11 /8  7 /8

      1/2 0.08 19

     /16  13

     /32  1/2 x 3/8 0.06 15 /16  13 /16

      1/2 x 1/4 0.03 11 /4  5 /8

      5/8 0.10 125 /32  13 /32

      3/4 0.16 115 /16  11 /8

      1 0.31 21 /2  121 /32

      1 1/4 0.43 229 /32  17 /8

      1 1/2 0.66 213 /32  21 /4

      1 1/2 x 1 1/4 0.50 33 /8  23 /32

      2 1.27 411 /32  231 /32

      2 1/2 2.16 57 /32  311 /16

      3 3.10 53 /4  41 /32

    607-2-290° Fitting Elbow – Close RoughFtg x Ftg – Wrot  APPROX. DIM. B  NOM. SIZE NET WT./LBS. INCHES

      1/2 0.04 11 /16

      3/4 0.12 115 /32

      1 0.20 123 /32

      1 1/4 0.33 21 /8

      1 1/2 0.46 213 /32

      2 0.82 227 /32

      3 2.12 37 /8

     ELBOWS continued 

    607-2-2-LT90° Fitting Elbow – Long RadiusFtg x Ftg – Wrot  APPROX. DIM. B  NOM. SIZE NET WT./LBS. INCHES

      1/4 0.02 27 /32

      3/8 0.04 11 /8

      1/2 0.08 119 /32

      5/8 0.10 111 /16

      3/4 0.16 115 /16

      1 0.31 21 /2

      1 1/4 0.43 229 /32

      1 1/2 0.65 37 /16

      2 1.25 411 /32

    707-2-490° Fitting ElbowFtg x M – Cast  APPROX. DIM. B DIM. E  NOM. SIZE NET WT./LBS. INCHES INCHES

      1/2 0.12 7 /8  25 /32

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    79/294

      A H E A D O F T H E F L O W® www.nibco.com

    NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455

    www.nibco.com14

    Revision 5/1/08

     ELBOWS continued 

     Consult price sheet for Made to Order items andfor minimum order quantities.

    707-390° Elbow C x F – Cast  APPROX. DIM. C DIM. E  NOM. SIZE NET WT./LBS. INCHES INCHES

      1/4 0.06 13 /32  9 /16

      3/8 0.09 7 /16  11 /16

      3/8 x 1/2 0.13 9 /16  13 /16

      1/2 0.12 7 /16  13 /16

      1/2 x 3/4 0.18

    11

     /16

     

    15

     /16

      1/2 x 3/8 0.09 1 /2  13 /16

      1/2 x 1/4 0.10 3 /8  23 /32

      3/4 0.18 21 /32  15 /16

      3/4 x 1 0.35 13 /16  11 /8

      3/4 x 1/2 0.20 9 /16  15 /16

      1 0.43 25 /32  11 /4

      1 x 3/4 0.35 11 /16  13 /16

      1 x 1/2 0.26 9 /16  11 /8

      1 1/4 0.67 1 11 /2

      1 1/4 x 3/4 0.47 9 /16  111 /16

      1 1/2 0.89 11 /8  15 /8

      2 1.46 13 /8  115 /16

    707-3-590° Drop Elbow C x F – Cast  NOM. APPROX. DIM. A DIM. C DIM. E  SIZE NET WT./LBS. INCHES INCHES INCHES

      3/8 0.12 11 /32  7 /16  11 /16

      3/8 x 1/2 0.18 11 /32  9 /16  13 /16

      1/2 0.15 13 /32  9 /16  7 /8

      1/2 x 3/8 0.17 3 /8  1 /2  13 /16

      3/4 0.28 17 /32  21 /32  15 /16

      3/4 x 1/2 0.24 17 /32  9 /16  15 /16

      1 0.49 5 /8  25 /32  11 /4

    707-3-5-A90° Hy-Set Elbow C x F – Cast  APPROX. DIM. C DIM. E  NOM. SIZE NET WT./LBS. INCHES INCHES

      1/2 0.21 9 /16  7 /8

    707-3-690° Union Elbow C x F – Cast  APPROX. DIM. A DIM. E  NOM. SIZE NET WT./LBS. INCHES INCHES

      1/2 0.31 11 /8  7 /8

      3/4 0.49 17 /16  1

      1 0.79 17 /8  11 /4

    707-490° Elbow C x M – Cast  APPROX. DIM. C DIM. E  NOM. SIZE NET WT./LBS. INCHES INCHES

      3/8 0.08 5 /16  7 /8  1/2 0.12 7 /16  15 /32

      1/2 x 3/4 0.18 9 /16  15 /32

      1/2 x 3/8 0.10 5 /16  15 /16

      3/4 0.21 9 /16  111 /32

      3/4 x 1 0.33 21 /32  113 /32

      3/4 x 1/2 0.18 7 /16  17 /32

      1 0.43 23 /32  15 /8

      1 1/4 0.58 7 /8  111 /16

      1 1/2 0.81 1 131 /32

      2 1.38 11 /4  29 /32

    707-4-690° Union Elbow C x M – Cast  APPROX. DIM. A DIM. E  NOM. SIZE NET WT./LBS. INCHES INCHES

      3/8 0.21 13 /32  13 /16

      1/2 0.30 11 /32  11 /2

      3/4 0.49 15 /16  113 /16

      1 0.72 123 /32  15 /8

      1 1/4 1.16 1

    3

     /4

      1

    27

     /32

    707-590° Drop Elbow C x C – Cast  APPROX. DIM. A DIM. C  NOM. SIZE NET WT./LBS. INCHES INCHES

      1/2 0.13 13 /32  7 /16

      3/4 0.24 17 /32  9 /16

    707-5-A90° Hy-Set Elbow C x C – Cast  NOM. APPROX. DIM. A DIM. C DIM. D  SIZE NET WT./LBS. INCHES INCHES INCHES

      1/2 0.13 31 /32  7 /16  15 /32

      3/4 0.21 15 /16  9 /16  9 /16

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    80/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    81/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    82/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    83/294

      A H E A D O F T H E F L O W® www.nibco.com

    NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455

    www.nibco.com18

    Revision 5/1/08

      APPROX. DIMENSIONS  NET WT. INCHES  NOM. SIZE LBS. C F G

      1 x 1/2 x 1 0.29 11 /16  1 21 /32

      1 x 1/2 x 3/4 0.27 9 /16  13 /16  3 /4

      1 x 1/2 x 1/2 0.22 15 /32  25 /32  23 /32

      1 1/4 0.43 13 /16  3 /16  13 /16

      1 1/4 x 1 1/4 x 2 1.13 130

     /32 130

     /32  13

     /32  1 1/4 x 1 1/4 x 1 1/2 0.60 13 /16  13 /16  29 /32

      1 1/4 x 1 1/4 x 1 0.45 25 /32  25 /32  29 /32

      1 1/4 x 1 1/4 x 3/4 0.37 21 /32  21 /32  3 /4

      1 1/4 x 1 1/4 x 1/2 0.30 1 /2  1 /2  25 /32

      1 1/4 x 1 1/4 x 3/8 0.34 23 /32  23 /32  29 /32

      1 1/4 x 1 x 1 1/4 0.43 13 /16  11 /32  13 /16

      1 1/4 x 1 x 1 0.47 25 /32  7 /8  29 /32

      1 1/4 x 1 x 3/4 0.35 21 /32  25 /32  7 /8

      1 1/4 x 1 x 1/2 0.30 1 /2  5 /8  29 /32

      1 1/4 x 3/4 x 1 1/4 0.42 13 /16  11 /8  13 /16

      1 1/4 x 3/4 x 1 0.45 25 /32  11 /32  29 /32

      1 1/4 x 3/4 x 3/4 0.37 21 /32  15 /16  7 /8

      1 1/4 x 3/4 x 1/2 0.30 1 /2  3 /4  29 /32

      1 1/4 x 1/2 x 1 1/4 0.41 13 /16  17 /32  13 /16

      1 1/2 0.61 31 /32  31 /32  29 /32

      1 1/2 x 1 1/2 x 2 1.11 125 /32 125 /32  13 /32

      1 1/2 x 1 1/2 x 1 1/4 0.62 29 /32  29 /32  11 /16

      1 1/2 x 1 1/2 x 1 0.55 11 /16  11 /16  7 /8

      1 1/2 x 1 1/2 x 3/4 0.45 11 /16  11 /16  11 /32

      1 1/2 x 1 1/2 x 1/2 0.40 1 /2  1 /2  11 /32

      1 1/2 x 1 1/4 x 1 1/2 0.62 11 /32  13 /16  29 /32

      1 1/2 x 1 1/4 x 1 1/4 0.62 31 /32  13 /32  31 /32

      1 1/2 x 1 1/4 x 1 0.51 25 /32  1 11 /32

      1 1/2 x 1 1/4 x 3/4 0.49 11 /16  13 /16  11 /32

      1 1/2 x 1 1/4 x 1/2 0.41 1 /2  25 /32  11 /32

      1 1/2 x 1 x 1 1/2 0.59 11 /32  111 /32  29 /32

      1 1/2 x 1 x 1 1/4 0.63 29 /32  11 /8  11 /16

      1 1/2 x 1 x 1 0.54 25 /32  11 /16  11 /32

      1 1/2 x 1 x 3/4 0.44 11 /16  31 /32  15 /16

      1 1/2 x 1 x 1/2 0.39 1 /2  25 /32  11 /32

    1 1/2 x 3/4 x 1 1/2 0.62 11 /32  17 /16  11 /16

      1 1/2 x 3/4 x 1 1/4 0.58 29 /32  111 /32  11 /16

      1 1/2 x 3/4 x 1 0.54 25 /32  11 /4  11 /32

      1 1/2 x 3/4 x 3/4 0.47 11 /16  13 /32  29 /32

      1 1/2 x 3/4 x 1/2 0.39 1 /2  29 /32  31 /32

      1 1/2 x 1/2 x 1 1/2 0.62 11 /32  113 /32  31 /32

    Continues…

      APPROX. DIMENSIONS  NET WT. INCHES  NOM. SIZE LBS. C F G

      2 1.30 19 /32  19 /32  11 /32

      2 x 2 x 2 1/2 2.34 2 2 121 /32

      2 x 2 x 1 1/2 1.17 11 /4  11 /4  123 /32

      2 x 2 x 1 1/4 1.12 9 /32  9 /32  17 /8

      2 x 2 x 1 0.90 27 /32  27 /32  11 /4

      2 x 2 x 3/4 0.88 19 /32  19 /32  11 /4

      2 x 2 x 1/2 1.17 1

    1

     /4

      1

    1

     /4

      2

    1

     /4

      2 x 1 1/2 x 2 1.16 19 /32  17 /8  111 /32

      2 x 1 1/2 x 1 1/2 1.15 11 /4  13 /4  123 /32

      2 x 1 1/2 x 1 1/4 1.15 7 /32  13 /4  111 /32

      2 x 1 1/2 x 3/4 0.83 21 /32  15 /16  17 /32

      2 x 1 1/2 x 1/2 1.12 11 /4  125 /32  21 /4

      2 x 1 1/4 x 2 1.58 19 /32  115 /32  19 /32

      2 x 1 1/4 x 1 1/2 1.16 11 /4  131 /32 123 /32

      2 x 1 1/4 x 1 1/4 1.19 15 /16  111 /32 111 /32

      2 x 1 1/4 x 1 0.90 27 /32  19 /32  111 /32

      2 x 1 1/4 x 3/4 0.85 21 /32  1 18 /27

      2 x 1 x 2 1.11 11 /8  125 /32  11 /4

      2 x 1 x 1 0.89 27 /32  19 /32  111 /32

      2 x 3/4 x 2 1.15 19

     /32  23

     /16  11

     /4  2 x 1/2 x 2 1.15 19 /32  23 /8  11 /4

      2 1/2 2.40 15 /8  15 /8  15 /8

      2 1/2 x 2 1/2 x 2 1.97 15 /16  15 /16  121 /32

      2 1/2 x 2 1/2 x 1 1/2 1.53 13 /32  13 /32  121 /32

      2 1/2 x 2 1/2 x 1 1/4 1.72 13 /32  13 /32  127 /32

      2 1/2 x 2 1/2 x 1 1.34 25 /32  25 /32  111 /16

      2 1/2 x 2 1/2 x 3/4 1.34 25 /32  25 /32  113 /16

      2 1/2 x 2 1/2 x 1/2 1.34 25 /32  25 /32  21 /8

      2 1/2 x 2 x 2 1/2 1.99 121 /32  23 /32  121 /32

      2 1/2 x 2 x 2 1.95 111 /32  15 /8  123 /32

      2 1/2 x 2 x 1 1/2 1.57 13 /32  213 /32 121 /32

      2 1/2 x 2 x 1 1/4 1.57 13 /32  119 /32 127 /32

      2 1/2 x 2 x 1 1.40 25 /32  19 /32  13 /4

      2 1/2 x 2 x 3/4 1.35 25 /32  19 /32  127 /32

      2 1/2 x 1 1/2 x 1 1/2 1.76 13 /32  113 /32  13 /8

      2 1/2 x 1 1/4 x 2 1/2 2.40 121 /32  27 /16  121 /32

      2 1/2 x 1 x 2 1/2 2.04 121 /32 223 /32 121 /32

      2 1/2 x 3/4 x 2 1/2 2.00 121 /32 211 /16 121 /32

    Continues…

      APPROX. DIMENSIONS  NET WT. INCHES  NOM. SIZE LBS. C F G

      3 3.15 17 /8  17 /8  21 /32

      3 x 3 x 2 1/2 3.55 129 /32 129 /32  23 /8

      3 x 3 x 2 3.19 115 /32 115 /32 131 /32

      3 x 3 x 1 1/2 3.08 115 /32 115 /32  29 /32

      3 x 3 x 1 1/4 3.10 115 /32 115 /32  27 /16

      3 x 3 x 1 2.12 27 /32  27 /32  131 /32

      3 x 3 x 3/4 2.39 27 /32  27 /32  23 /16

      3 x 3 x 1/2 1.82 27 /32  27 /32  23 /8

      3 x 2 1/2 x 3 3.08 17 /8  23 /8  131 /32

      3 x 2 1/2 x 2 1/2 3.12 129 /32 211 /32  25 /32

      3 x 2 1/2 x 2 2.28 115 /32 127 /32 131 /32

      3 x 2 x 3 3.62 129 /32 217 /32 115 /16

      3 x 2 x 2 1/2 3.56 129 /32  29 /16  25 /16

      3 x 2 x 2 3.22 115 /32 131 /32 131 /32

      3 x 1 1/2 x 3 3.13 129 /32 225 /32  23 /32

      3 x 1 1/4 x 3 3.63 129 /32 225 /32 115 /16

      3 x 1 x 3 3.20 131 /32 219 /32  23 /16

      3 x 3/4 x 3 3.55 131 /32 229 /32  23 /16

      3 1/2 5.20 217 /32 217 /32 217 /32

      4 8.12 213

     /32 213

     /32 217

     /32  4 x 4 x 3 6.70 21 /32  21 /32  221 /32

      4 x 4 x 2 1/2 6.65 21 /32  21 /32  35 /32

      4 x 4 x 2 5.82 115 /32 115 /32  27 /16

      4 x 4 x 1 1/2 3.94 111 /32 111 /32 217 /32

      4 x 4 x 1 1/4 4.04 111 /32 111 /32 229 /32

      4 x 4 x 1 3.72 1 1 29 /16

      4 x 4 x 3/4 3.70 1 1 211 /16

      4 x 3 x 4 7.05 225 /32  37 /32  217 /32

      4 x 3 x 3 5.03 21 /32  215 /32 215 /32

      4 x 3 x 2 1/2 5.04 21 /32  215 /32 229 /32

      4 x 3 x 2 5.87 115 /32 131 /32  27 /16

      4 x 2 1/2 x 4 7.19 225 /32 315 /32 227 /32

      4 x 2 x 4 7.08 225 /32 319 /32 227 /32

    Continued on next page.

    NOTE: Tee sizes are read Run x Run x Outlet.

    611Tee C x C x C – Wrot continued

    TEES continued 

     Consult price sheet for Made to Order items andfor minimum order quantities.

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    84/294

      A H E A D O F T H E F L O W® www.nibco.com

    NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455

    www.nibco.com

    19

    Revision 5/1/08

    611-HEHeat Exchanger TeeC x C x C – Wrot

     

    Tube slips entirely through fitting on small endof run. Sizes same as listed under 611 where teehas one or more reductions on one end of run.

    711Tee C x C x C – Cast  APPROX. DIMENSIONS  NET WT. INCHES  NOM. SIZE LBS. C F G

      1 1/4 x 1/2 x 1 0.48 3 /4  3 /4  7 /8

      1 1/4 x 1/2 x 1/2 0.50 9 /16  5 /8  1

      1 1/2 x 1/2 x 1 1/4 0.70 7 /8  31 /32  1

      2 x 2 x 3 3.11 121 /32 121 /32  15 /16

      2 x 1 x 1 1/2 1.23 1 11 /4  11 /4

      2 x 3/4 x 3/4 0.84 21 /32  7 /8  11 /4

      2 1/2 x 2 1/2 x 3 2.98 13 /4  13 /4  117 /32

      2 1/2 x 1 1/2 x 2 2.02 11 /4  115 /32  11 /2

      2 1/2 x 1 1/2 x 1 1/2 1.76 13 /32  113 /32  13 /8  2 1/2 x 1/2 x 2 1/2 2.46 11 /2  27 /32  11 /2

      3 x 3 x 4 6.96 211 /32 211 /32 123 /32

      3 x 2 1/2 x 1 1/2 2.53 1 13 /32  13 /4

      3 x 2 x 1 1/2 2.62 1 11 /4  13 /4

      4 x 4 x 6 16.47 37 /32  37 /32  29 /32

      4 x 2 x 2 4.64 11 /4  13 /4  21 /4

    711-ASupply and Return TeeC x C x C – Cast  APPROX. DIMENSIONS  NET WT. INCHES  NOM. SIZE LBS. C J

      1/2 0.17 13 /16  1

    TEES continued 

     Consult price sheet for Made to Order items andfor minimum order quantities.

    611Tee C x C x C – Wrot continued  APPROX. DIMENSIONS  NET WT. INCHES  NOM. SIZE LBS. C F G

      5 8.29 227 /32 227 /32 313 /32

      5 x 5 x 4 7.09 27 /32  29 /32  33 /16

      5 x 5 x 3 5.91 125 /32 125 /32  33 /16

      5 x 5 x 2 1/2 5.90 15 /16  15 /16  33 /16

      5 x 5 x 2 5.29 11 /16  11 /16  33 /16

      5 x 5 x 1 1/2 4.87 11 /32  11 /32  33 /16

      5 x 5 x 1 1/4 4.50 11 /16  11 /16  33 /16

      5 x 5 x 1 4.20 9 /16  9 /16  33 /16

      5 x 4 x 5 8.53 227 /32 429 /32 313 /32

      5 x 4 x 4 8.17 21 /4  417 /32  33 /8

      5 x 2 x 5 9.47 23 /4  51 /16  31 /2

      6 13.50 39 /32  39 /32  41 /32

      6 x 6 x 5 11.67 225 /32 225 /32  41 /32

      6 x 6 x 4 10.17 29 /32  29 /32  311 /16

      6 x 6 x 3 8.92 125 /32 125 /32 311 /16

      6 x 6 x 2 1/2 8.11 117 /32 117 /32  33 /4

      6 x 6 x 2 7.78 19 /32  19 /32  311 /16

      6 x 6 x 1 1/2 6.86 1 1 311 /16

      6 x 6 x 1 1/4 6.66 29 /32  29 /32  311 /16

      6 x 6 x 1 7.19 9 /16  9 /16  311 /16

      6 x 6 x 3/4 7.18 9 /16  9 /16  49 /16

      6 x 6 x 1/2 7.17 9 /16  9 /16  411 /16

      6 x 4 x 6 16.60 33 /16  51 /8  41 /8

      6 x 4 x 1 1/2 9.62 15 /16  215 /16  33 /4

      8 36.81 41 /16  41 /16  51 /32

      8 x 8 x 6 27.86 31 /16  31 /16  51 /8

      8 x 8 x 5 24.90 225 /32 225 /32 415 /16

      8 x 8 x 4 22.26 21 /16  21 /16  43 /4

      8 x 8 x 3 20.01 19 /16  19 /16  43 /4

      8 x 8 x 2 1/2 19.02 15

     /16  15

     /16  43

     /4  8 x 8 x 2 18.01 11 /16  11 /16  43 /4

    NOTE: Tee sizes are read Run x Run x Outlet.

    611-2Fitting Tee C x Ftg x C – Wrot  APPROX. DIMENSIONS  NET WT. INCHES  NOM. SIZE LBS. B C F

      1/2 0.07 11 /32  3 /8  7 /16

      3/4 0.15 115 /32  1 /2  17 /32

    711-5Drop Tee C x C x C – Cast  APPROX. DIMENSIONS  NET WT. INCHES  NOM. SIZE LBS. A C

      1/2 0.16 3 /8  7 /16

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    85/294

      A H E A D O F T H E F L O W® www.nibco.com

    NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455

    www.nibco.com20

    Revision 5/1/08

    712Tee C x C x F – Cast  APPROX. DIMENSIONS  NET WT. INCHES  NOM. SIZE LBS. E F G

      3/8 0.11 11 /16  7 /16  7 /16

      1/2 0.14 13 /16  7 /16  7 /16

      3/4 0.33 1 21 /32  21 /32

      1 0.54 11 /4  7 /8  7 /8

      1 1/2 1.08 15 /8  11 /8  11 /8

      2 1.74 17 /8  13 /8  13 /8

      1/2 x 1/2 x 1/4 0.16 13 /16  1 /2  1 /2

      1/2 x 1/2 x 3/8 0.15 13 /16  1 /2  1 /2

      1/2 x 1/2 x 3/4 0.23 15 /16  11 /16  11 /16

      3/4 x 3/4 x 3/8 0.23 7 /8  1 /2  1 /2

      3/4 x 3/4 x 1/2 0.24 57 /64  17 /32  17 /32

      1 1/4 x 1 1/4 x 1/2 0.49 11 /4  9 /16  9 /16

      1 1/4 x 1 1/4 x 3/4 0.55 15 /16  11 /16  11 /16

      1 1/4 x 1 1/4 x 1 0.66 17 /16  7 /8  7 /8

      1 x 1 x 1/2 0.34 11 /8  9 /16  9 /16

      1 x 1 x 3/4 0.42 13 /16  11 /16  11 /16

      1 1/2 x 1 1/2 x 1/2 0.62 13 /8  9 /16  9 /16

      1 1/2 x 1 1/2 x 3/4 0.70 17 /16  11 /16  11 /16

      1 1/2 x 1 1/2 x 1 0.79 11 /2  13 /16  13 /16

      2 x 2 x 1/2 0.97 15 /8  17 /32  17 /32

      2 x 2 x 3/4 1.10 111 /16  11 /16  11 /16

      2 x 2 x 1 1.23 13 /4  13 /16  13 /16

      1/4 0.08 13 /16  9 /32  9 /32

      1 1/4 0.76 17 /16  1 1

      3/8 x 3/8 x 1/4 0.12 11 /16  7 /16  7 /16

      3/4 x 1/2 x 3/4 0.28 1 21 /32  11 /16

      3/4 x 3/4 x 1 0.40 11 /8  7 /8  7 /8

    712-5Drop Tee C x C x F – Cast  APPROX. DIMENSIONS  NET WT. INCHES  NOM. SIZE LBS. A C E

      1/2 0.25 3 /8  9 /16  7 /8

      3/4 0.38 1 /2  21 /32  1

    713Tee C x C x M – Cast  APPROX. DIMENSIONS  NET WT. INCHES  NOM. SIZE LBS. E F

      1/2 0.15 13 /32  7 /16

      3/4 0.29 19 /32  9 /16

    714Tee C x F x C – Cast  APPROX. DIMENSIONS  NET WT. INCHES  NOM. SIZE LBS. C E S

      1/2 0.18 7 /16  9 /16  7 /8

      1/2 x 3/4 x 1/2 0.27 7 /16  9 /16  13 /16  3/4 0.31 9 /16  11 /16  1

      3/4 x 1/2 x 3/4 0.26 9 /16  9 /16  15 /16

      1 0.52 23 /32  13 /16  11 /4

      1 x 3/4 x 1 0.43 23 /32  23 /32  13 /16

      1 x 1/2 x 1 0.42 3 /4  3 /4  11 /8

      1 1/4 0.70 7 /8  1 113 /32

      1 1/4 x 3/4 x 1 1/4 0.62 7 /8  7 /8  17 /32

      1 1/4 x 1/2 x 1 1/4 0.56 7 /8  7 /8  13 /16

      1 1/2 1.00 1 11 /8  19 /16

      1 1/2 x 3/4 x 1 1/2 0.88 1 1 113 /16

      2 1.72 11 /4  13 /8  17 /8

      2 x 3/4 x 2 1.57 11 /4  11 /4  2

      2 x 1/2 x 2 1.58 11 /4  11 /4  2

    TEES continued 

     Consult price sheet for Made to Order items andfor minimum order quantities.

     TRAPS

    698

    Suction Line P-TrapC x C – WrotA major application of this fitting is on thesuction line of a refregeration compressor.The line is looped, by use of the Suction LineP-Trap, to the floor prior to being run verticallyupwards to prevent the drainage of oil back to thecompressor during shut down periods. AdditionalP-Traps are used for each 20' or riser pipe. thisprevents high velocity build-up as the oil or liquidbegins to return to the compressor during thisshut down period.

      APPROX. DIMENSIONSNET WT. INCHES

      NOM. SIZE LBS. C D J K

      1/2 0.36 53 /8  3 3 6

      5/8 0.45 53 /8  27 /8  3 6

      3/4 0.58 53 /8  23 /4  3 

    6

      1 0.92 51 /4  221 /32  3 6

      1 1/4 1.16 53 /8  27 /8  33 /4  61 /8

      1 1/2 2.32 75 /8  35 /8  5 9

      2 3.93 8 35 /8  6 97 /16

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    86/294

  • 8/20/2019 tran ac units2305 00-001 HVAC Submittals_1

    87/294

      A H E A D O F T H E F L O W® www.nibco.com

    NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455

    www.nibco.com

    39

    Revision 5/1/08

    TYPES OF JOINTS

    Flared Joint — The principle of the flared joint was first developedfor copper tube plumbing in 1928 by NIBCO. The flared type joint iswholly a mechanical means of joining copper tubes. The tube nut isplaced over the end of the copper tube to be joined; the tube endthen is flared out at an approximate 45 degree angle by a flaring tool.The flared end is then drawn up by the tube nut so the inside surface

    is tightly secured against the ball seat of the fitting. This joint canbe readily dismantled at any time and is, in effect, a type of unionconnection. Its use is generally restricted to soft (annealed) coppertubes since hard drawn tubes would be subject to splitting whenflared (if the ends were not previously annealed). The flared endsof NIBCO Flared Fittings are produced to the requirements of ASMEB16.26, “Cast Copper Alloy Fittings for Flared Copper Tube.”

    Solder Joint — NIBCO pioneered the development ofthe solder joint and its application to the field of copper tubepiping. Today the solder joint is widely adopted, as evidenced bythe majority of cities and states that have written codes to includecopper tube and solder joints as desirable for general plumbing,water lines, vent, stack, waste and drain lines, as well as other uses

    in industry. Testing has shown that often the solder joint has greaterstrength than the tubes being joined, depending upon the solderingalloy selected. While the method of preparing a solder joint is anexacting art to insure a full strength joint, it can be readily masteredby skilled tradesmen. It is for this reason — to insure the public ofthe protection afforded by properly prepared joints — that NIBCOproducts are marketed through the reputable sources of supply to thepiping trades. Important procedures for preparing a solder joint aregraphically illustrated in this catalog on page 48.

    Brazed Joint — This type of joint has long been used wherever andwhenever critical situations have been encountered in copper piping.The joint itself is completed much in the same manner as the solderjoint; however, considerably more heat and several refinements of

    technique require separate procedures that are described further inthis catalog on pages 49-50.

    Threaded Ends — To adapt copper tube to equipment havingNational Standard Pipe Taper (NPT) threads or to add copper tube toexi