Page 188 2007-08 Copyright © Siemens AG 2007. All rights reserved. PTD SE PTI Author: G. Ziegler Transformer Protection

Transformer Protection - SIEMENS

Embed Size (px)

Citation preview

Page 1: Transformer Protection - SIEMENS

Page 188 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Transformer Protection

Page 2: Transformer Protection - SIEMENS

Page 189 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Transformer: Function principle and equivalent circuits

12211 wIwIwI ⋅=⋅+⋅ µ

At load and short-circuit: '2,1II <<µ2211 wIwI ⋅=⋅

'21 σσ XXTKX +='2U1U '21 II ='21 RRTKR +=

Equivalent electromagnetic circuit

1R '2R1σX '2σX

µX1U µI1I '2I '2U

Equivalent electric circuit

Φ

w1

U1 U2

I1w2 I2

σ1Φ σ2Φ

TKR TKX

Page 3: Transformer Protection - SIEMENS

Page 190 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Rated power

MVA

850

600

300

300

40

16

6.3

0.63

Ratio

kV/kV

850/21

400/230

400/120

230/120

110/11

30/10.5

30/10.5

10/0.4

No-load magnetizing current % In

0.2

0.25

0.1

0.1

0.1

0.2

0.2

0.15

Short-circuit voltage % UN

17

18.5

19

24

17

8.0

7.5

4.0

Typical Transformer data

Page 4: Transformer Protection - SIEMENS

Page 191 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Transformer Inrush current

Source: Sonnemann, et al.: Magnetizing Inrush phenomena in transformer banks, AIEE Trans., 77, P. III, 1958, pp. 884-892

Inrush-current of a single phase transformer

Fluxφ φ

IRush

U

tIm

φRem

Page 5: Transformer Protection - SIEMENS

Page 192 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

mTI

mRI

RI

SI

mCmRR III ⋅−⋅=61

65

mTImRISI ⋅−⋅−=61

61

mRmTT III ⋅−⋅=61

65

TI

Oscillogram:

Inrush currents of a Y-∆-transformerNeutral of Y-winding earthed

DIRI

SI

CI

Source: Sonnemann et al. : Magnetizing Inrush phenomena in transformer banks, AIEE Trans., 77, P. III, 1958, pp. 884-892

RI

SI

TI

Page 6: Transformer Protection - SIEMENS

Page 193 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

20

40

60

80

100

90O 180O 270O 360O

17,5%

)1(

)(

m

m

II ν

)1(

)2(

m

m

II

)1(

)3(

m

m

II

240O

B B

360O

Width of base B

Inrush current : Content of 2nd und 3rd harmonic

%

Page 7: Transformer Protection - SIEMENS

Page 194 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Inrush currents of a three-phase transformerrecorded with relay 7UT51

Page 8: Transformer Protection - SIEMENS

Page 195 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

N

Rush

I

I

Rated transformer power in MVA

Transformer Inrush current:Amplitude and time constant

Rated power time constant in MVA in seconds

0,5....1,0 0,16....0,2

1,0 10 0,2 .....1,2

>10 1,2 ....720

5 10 50 100 500

6

10

2

4

8

12

Page 9: Transformer Protection - SIEMENS

Page 196 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Sympathetic Inrush

Wave form: Transient currents:

1I

2I

Current circulating between transformers

TI t

I

G

SR SX

1I 2ITI

Transformer being closed

T1

T2

Transformer already closed

G

1I

2I

TI

resistance

2I

1I

TI

T1 T2

Page 10: Transformer Protection - SIEMENS

Page 197 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Transformer overfluxing

Deduction of wave form Harmonic content

U/Un

0,5

1,5

1,0

BUGauß410×

15105 AIm

Im

t0 10 20 ms

100 120 140 160%

20

4060

80100

0

I150/I50

I250/I50

I350/I50

I50/InTr

%

Page 11: Transformer Protection - SIEMENS

Page 198 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

IRIr

Vector group adaptation with matching CTsCurrent distribution with external ph-ph fault

87T87T 87T

1/3

IS

IT

I1

I2

I3

R

S

r

s

t

Is

It

13

G

T

Page 12: Transformer Protection - SIEMENS

Page 199 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

1/387T87T 87T

Sg

Tg R0 S0 T0

Rm

Tm

Sm Rg

sm

IT=3

30O30O

rm

tm tgsg

rg

3=tI

tm

tg

rg

rm

3=rI

IR

IS

IT

I1

I2

I3

R

S

T

r

s

t

Ir

Is

ItG

Yd1

Vector group adaptation with matching CTsCurrent distribution with external ph-E fault

Page 13: Transformer Protection - SIEMENS

Page 200 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

L1

L2

L3

L1

L2

L3

G

∆Ι∆Ι ∆Ι

Traditional I0-elimination with matching CTsCurrent distribution in case of an internal earth fault

• Sensitivity only 2/3 IF!

•Non-selective fault indication!

!

Page 14: Transformer Protection - SIEMENS

Page 201 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Traditional I0-correction with matching CTsCurrent distribution with external ph-E fault

A

B

C

a

b

c

G

87T87T 87T

3/1

Page 15: Transformer Protection - SIEMENS

Page 202 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

A

B

C

a

b

c

G

87T87T 87T

3/1

Traditional I0-correction with matching CTsCurrent distribution with internal ph-E fault

Page 16: Transformer Protection - SIEMENS

Page 203 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Digital protectioncontains:

Adaptation to

• Ratio UA / UB

• Vector group

IB1

IB2

IB3L3

IA1

IA2

IA3

∆I ∆I∆I

L2

L1

UA

(110 kV)

UB

(20 kV)

7UT6

Transformer differential protection, connection

Software replica of matching transformers

Page 17: Transformer Protection - SIEMENS

Page 204 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

I0-elim.

Com-parison

∆I

IRISIT

Ir**Is**It**

IR*IS*IT*

Ir*Is*It*

Vectorgroupadapt.

Norm

Norm

JR-secJS-secJT-sec

Jr-prim

Js-prim

Jt-prim

JR-prim

JS-prim

JT-prim

Jr-secJs-secJt-sec

CT 1 CT 2W1 W2

I0-elim.

IrIsIt

1-NU3NS

W1TransfN⋅

=−−I2-NU3

NSW2TransfN

⋅=−−I

secsecsecRJ

1secsecsecRJ

W1-TransfNI1 CTPrimNI

TISIRI

−−−

⋅−=

−−−

⋅−

−−=

TJSJCTk

TJSJ

sect

secs2CT

sect

secsJJk

JJ

−− ⋅=⋅=secrsecr

W2-TransfN

2 CTPrimN

t

s

r JJ

II

III

Digital transformer protectionAdaptation of currents for comparison (1)

Page 18: Transformer Protection - SIEMENS

Page 205 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

I0-elim.

Com_parison

∆I

IRISIT

Ir**Is**It**

IR*IS*IT*

Ir*Is*It*

Vectorgroup adapt.

Norm

Norm

JR-secJS-secJT-sec

Jr-prim

Js-prim

Jt-prim

JR-prim

JS-prim

JT-prim

Jr-secJs-secJt-sec

CT 1 CT 2W1 W2

I0-elim.

IrIsIt

( )TISIRI31

0I ++⋅=

0ITI*TI0ISI*SI0IRI*RI

−=−=

−=

( )tIsIrI31

0I ++⋅=

0ItI*tI0II*sI0IrI*rI

−=

−=

−=

s***

110011101

31

******

tIsIrI

tIsIrI

⋅−

−−

=

Example Yd5:

******

***

tIsIrI

TISIRI

TISIRI

+=

−∆−∆−∆

Digital transformer protectionAdaptation of currents for comparison (2)

Page 19: Transformer Protection - SIEMENS

Page 206 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Input data:•n times 30O vector group number

(only for 2nd and 3rd winding, 1st winding is reference)

•UN (kV) Rated winding voltage

•SN (MVA) rated winding power

•INW (A) Primary rated CT current

•Line or BB direction of CT neutral

•Elimination / I0-treatmentCorrection / without

•Side XX Assignment input for REF

•INW S (A) Primary rated current of neutral CT

•Neutral CT Earth side connection to relay: Q7 or Q8?

minmax

minmaxN UU

UU2U+⋅

⋅=

At windings with tap changer:

Winding 1 (reference) is normally:

•High voltage side

Adaptation of currents for comparison Relay input data

Page 20: Transformer Protection - SIEMENS

Page 207 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Yd5

SN = 100 MVAUN2= 110 kVUN1= 20 kV

600/1 A3000/5 A

2.400 A7621 A

∆I

W2 W1

1 A

5 A

Digital transformer protectionCurrent adaptation, Example (1)

Page 21: Transformer Protection - SIEMENS

Page 208 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

525A110kV3

100MVAW1TrafoNI =

⋅=−−

4,57A4525600

NormI

A 4,024006001

sek-TS,R,J

=⋅=

=⋅=

357,4357,42

357,4

04,570

211121112

31

*tI*sI*rI

⋅−=−⋅−−

−−−−

⋅=

2887A20kV3

100MVAW2TrafoNI =

⋅=−−

A34,5734,428873000

NormI

A 34,43132003000

1sek-tr,s,J

=⋅=

=⋅=

3/57,43/57,42

3/57,4

0357,4

357,4

110011101

31

******

−⋅

−=−⋅

−−

−=

tIsIrI

000

34,5734,5734,57234,572

34,5734,57

**tI*TI**sI*SI**rI*RI

TAISAIRAI

===

−⋅+⋅−

=+=+=+

=−

=−

=−

110-kV-side20-kV-side

I0-elimination: Vector group adaptation: Yd5

Digital transformer protectionCurrent adaptation, Example (2)

Page 22: Transformer Protection - SIEMENS

Page 209 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

7UT6 Operating characteristic

1

2

3

4

1 2 3 4 5 6 7 8 9 10 11

Stable operation

Slope 1

Slope 2

I DIFF >>

5

6

7

8

Istab / In

I DIFF

= I STAB

00

9I1 I2

IDIFF = |I1+ I2|

IStab = |I1| + |I2|

7UT6

Additional stabilisation for high Is.c.

IDiff/ In

I DIFF >

Tripping area

Page 23: Transformer Protection - SIEMENS

Page 210 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

I0- elimination necessary at all windings with earthed neutral or with grounding transformer in the protection rangeEarth fault sensitivity reduced to 2/3 ! Incorrect fault type indication!

I0- correction provides full earth current sensitivity and correct phase selective fault type indication, however requires CT in the neutral-to-earth connection of the transformer.

As an alternative, earth differential protection can be used to enhance earth fault sensitivity.

I0-elimination / correction: Summary

Page 24: Transformer Protection - SIEMENS

Page 211 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Source: P.M. Anderson: Power System Protection, McGraw-Hill and IEEE Press (Book)

Transformer winding to earth faultSolid earthed neutral

h⋅UR

UR

IFIK

Infeed side

IF

IK

200 40 60 80 100

2

4

6

8

10

IFper unit

Short-circuited winding part h in %

Page 25: Transformer Protection - SIEMENS

Page 212 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

E

RF R

UhI ⋅=

Fn

nFK I

UUhI

wwhI ⋅

⋅⋅=⋅

⋅=

31

2

1

2ERRU

nUnUhKI ⋅⋅⋅=

12

312

Source: P.M. Anderson: Power System Protection, McGraw-Hill and IEEE Press (Book)

h⋅UR

RE

UR

IFIK

Infeed side

Short-circuited winding part h in %

MaxII

50

020 40 60 80 100

100%

IF

IK

Transformer winding to earth faultResistance or reactance earthed neutral

Page 26: Transformer Protection - SIEMENS

Page 213 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Location of the earth fault h in %20 40 60 80 100

Grid

Transformer winding to earth faultEarth fault in the delta winding

1

2

3

4

5 20%0%

R

33,3%

50%

100%

x In

IKIK

Page 27: Transformer Protection - SIEMENS

Page 214 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

IPx In

IF , IKx In

Short-circuited winding part h in %

IF

IK

Transformer winding short-circuit

Source: Protective Relays, Application Guide, GEC Alstom T&D, 1995

100

80

60

40

20

05 10 15 20 25

2

4

6

8

10

IF

IK

Page 28: Transformer Protection - SIEMENS

Page 215 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

I>

∆ IEI0* I0**

IN

IRISIT

Restricted earth fault protection of relay 7UT6

Extended operating area:

Basic operating area:

NI

IsetOpIif ≥

Op II *0=

restr IIIII **0

*0

**0

*0 +−−=

TSR IIIII 0**

0 3=++==

for ( ) 0**0

*0

0 90/90 +≤≤− IIϕ

for ( ) 0**0

*0

0 270/90 +≤≤+ IIϕ

I *0

IrestrOPIif ≥

restrOp IkII 0*0 −= ·

Page 29: Transformer Protection - SIEMENS

Page 216 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Restricted earth fault protection of 7UT6Operating characteristic (2)

k0 =2ϕ Limit=110O

( )*0

**0 /IIϕ

180O 120O 110O 100O 90O 80O 70O 60O 50O

External fault

130O

K0 ϕ Limit

1.0 130

1.4 120

2.0 110

4.0 100

∞ 90

1II

*0

**0 =

Σ=

N

PhII

4

3

2

1

set-0

*0

I I

0O

Internal fault

Page 30: Transformer Protection - SIEMENS

Page 217 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

0

20

40

60

80100

120

140

160

180

200

220

240

260 280

300

320

340

2

1.6

1.2

0.8

0.4

0

*)*/I*(Ie**0I

*0I 00ϕ⋅

+1

BlockingTripping

K0= 4K0= 2

K0= 1.4

K0= 1

ϕ

Restricted earth fault protection of 7UT6Polar characteristic

Page 31: Transformer Protection - SIEMENS

Page 218 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Restricted earth fault protection 87N (7UT6)Application aspects

Increased sensitivity with earth faults near winding neutralPreferably used in case of resistance or reactance neutral earthingSensitive to turns short-circuitI0 / IN amplitude and angle comparison2nd harmonic stabilisedCan protect a separate shunt reactor or neutral earthing transformer in addition to the two winding transformer differential protectionNot applicable with autotransformers! (as only one stabilising input at transformer terminal side, -- high impedance principle to be used in this case.

Page 32: Transformer Protection - SIEMENS

Page 219 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

∆IE>IN

IrIsIt

∆IE>

IR

IS

IT

ZE

Transformer HI-earth fault protection

Page 33: Transformer Protection - SIEMENS

Page 220 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

IrIsIt

87

IRISIT

87 87

HI differential protection of an autotransformer

Page 34: Transformer Protection - SIEMENS

Page 221 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

IN

IrIsIt

∆I>

IRISIT

HI earth fault protection of an autotransformer

Page 35: Transformer Protection - SIEMENS

Page 222 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Transformer tank protection 64T: Principle

Insulated

IE>

Page 36: Transformer Protection - SIEMENS

Page 223 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Transformer Protectionwith

Siemens SIPROTEC7UT6

7UT612

Transformer protection, Relay design

Page 37: Transformer Protection - SIEMENS

Page 224 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

YN yn0 d5RST

ϑ>(2)

I>>,I>t

ϑ>(1) ∆ITE ∆IT

Digital transformer protection relay 7UT613:Current inputs and integrated protective functions

Page 38: Transformer Protection - SIEMENS

Page 225 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Relay 7UT6: Application examples

Two winding transformer

Three winding transformer

Busbars

G ∆I

Generator / Motor

∆I

Shunt Reactor

∆I

∆I ∆I

∆I

Transformer bank (1-1/2-LS)

∆I

Page 39: Transformer Protection - SIEMENS

Page 226 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

1

2

3

4

1 2 3 4 5 6 7 8 9 10 11

Restraining area

slope = 1/2 of 1606

pick-up limit (left border line) = (1618 )

slope 1

(1606)

slope 2

(foot p

oint= 1607, s

lope = 1608 )

I DIFF >> (1604)

5

6

7

8

Istab / In

I DIFF

= I STAB

00

9I1 I2

IDIFF = |I1+ I2|

IStab = |I1| + |I2|

Tripping area

7UT61

Add-on restraint for high ISC

IDiff/ In

I DIFF >(1603)

7UT6Operating characteristic

Page 40: Transformer Protection - SIEMENS

Page 227 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Advantages of digital transformer differential protection

High stability against c.t. saturation provided by integrated saturation detector and add-on stabilisation

High stabile against inrush currents due to advanced filter technology (Fourier analysis) and optional cross-blocking function

High stability against over-excitation ( 5th harmonic blocking)

Short tripping time - typically 1.5 cycles

High set ∆I fast tripping < 1 cycle

Sensitive earth differential protection against interturn faults and earth faults near winding neutral

Integral ratio and vector group adaptation (no external auxiliary CTs required)

Integral thermal overload protection

External start of fault recording (e.g. by gas pressure relays)

Page 41: Transformer Protection - SIEMENS

Page 228 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Transformer differential protection∆I> Rush-stabilised (2nd harmonic)Stabilised against overfluxing (5th harmonic)∆I>> high set element, non-stabilised

Thermal overload protection

Time overcurrent protection (IT or DT)

Earth current differential protection (7UT613)

Tank protection (7UT613)

49-149-2

50/5150HS

87T

87N

64T

7UT6Integrated protection functions

Page 42: Transformer Protection - SIEMENS

Page 229 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Application examples

Page 43: Transformer Protection - SIEMENS

Page 230 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Protection of a two winding transformer

7SJ600

W2 (US)

W1 (OS)

49

87T

51

50 51

52 52

52

52

7UT512

Bu

W2

W1

Page 44: Transformer Protection - SIEMENS

Page 231 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Protection of a three winding transformer

7UT513

52

52

W1

W3

49-1

87T

49-2

51

7SJ600

50 51

W3W2

W1

Load

Bu

W2

Page 45: Transformer Protection - SIEMENS

Page 232 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

W1

W2

7SJ600

W2 (US)

W1 (OS)

49-1

87T

50 51

52 52

52

52

51

87TE

7UT513

Restricted earth fault protectionfor a two winding transformer

ZE

Bu

Page 46: Transformer Protection - SIEMENS

Page 233 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Protection of an autotransformer

3YLoad

52

52

4987TL

51

87TH

505151BF

7VH600 7UT513

597SJ600

7SJ6007RW600

50BF

51N

7SJ600

5051

51N

50BF

52

Bu

Page 47: Transformer Protection - SIEMENS

Page 234 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

Protection of a large transformer bank

3Load 52

4987TL

51

49

87TH

7SA6

7VH6 (3)7UT513

59N

7SJ67SJ67RW6

50BF

50BF4921

52

51BF21

7SA6

51N

52 52

Page 48: Transformer Protection - SIEMENS

Page 235 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

52

52

G ∆IG

∆IT

52

G ∆IG

∆IT

52

G ∆IG

∆IT

52

G

∆IT

Differential protection of generation units

Page 49: Transformer Protection - SIEMENS

Page 236 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

52

52

G ∆IG

∆IT

52

∆IT

*)

*) same ratio as generator CTs

Auxiliaries

Differential protection of generation units (2)

Page 50: Transformer Protection - SIEMENS

Page 237 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

ΘCu ΘOil

C1 C2

Rth1 Rth2

PCu PFe

ΘAmb

Legend:PCu: Winding losses (I2·R)

PFe: Core and tank losses

Rth1: Thermal resistance Copper-Oil

Rth2: Thermal resistance Oil-Air (cooling medium)

C1: Winding thermal capacity

C2: Thermal capacity of Oil, Core and tank

ΘCu: Winding copper temperature

ΘOil: Oil temperature

ΘAmb.: Ambient temperature

Thermal protection of transformers

Lifetime of insulation depends on the

winding Hot-spot temperature.

6 OC higher temperature increases the aging of the insulation by the factor 2!

Page 51: Transformer Protection - SIEMENS

Page 238 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

7SA6: Temperature monitoring

Two thermo-devices can be connected to the serial service interfaceMonitoring of up to 12 measuring points (6 per thermo-device)One input is reserved for hot spot monitoring (measurement of oil temperature)Thermistors: Pt100, Ni100 or Ni120

RS485 Interface

The the upper oil temperature is directly measured by the use of thermoelement.The hot spot temperature is calculated by the relay using the thermal model Cu-Oil:

Oil -Temp.

( )OilCuTh

2

Th

Cu 1IrI1

dtd

Θ−Θ⋅τ

−⎟⎠⎞

⎜⎝⎛⋅

τ=

Θ I = actual transformer currentIr = rated transformer currentτth =time constant of the winding

Page 52: Transformer Protection - SIEMENS

Page 239 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

7UT6: Temperature monitoring with hot spot calculation (1)Example: Natural cooling

HVLV

Oil -Temp.

YgrOh kHΘΘ ⋅+= Θh= hot spot temperature

Θh= oil temperature

Hgr=hot-spot-to-oil temperature gradient

k= load factor I/In

Y= winding exponent

98)/6(Θ2C98at AginghΘat AgingV h −=°

=

∫ ⋅⋅−

=2

1

T

T12

dtVTT

1L

Aging rate:

Mean value of aging during a fixed time interval:

98O is reference for the aging of Cellulose insulation

Page 53: Transformer Protection - SIEMENS

Page 240 2007-08Copyright © Siemens AG 2007. All rights reserved.

PTD SE PTIAuthor: G. Ziegler

1.622V 98)/6(10298)/6(Θh ≈== −−

C1021.152373kHΘΘ 1.6Ygroh °=⋅+≈⋅+=

ΘhΘo

t

[°C]98°C

Θh Hot spot temp.

1.6

102°C

1.15

73°C

k (I/In)

108°Ck,V,L

V (relative aging) L (mean value of V)

Θo oil temp. (from thermo-device)

(L)

7UT6: Temperature monitoring with hot spot calculation (2)Example: Natural cooling