Transient occurence © 2006 Teseq Specifications subject to change without notice. All trademarks recognised. 691-006A Teseq AG Nordstrasse 11F 4542 Luterbach Switzerland Tel: +41 (0)32 681 40 40 Fax: +41 (0)32 681 40 48 E & OE: Whilst great care has been taken in preparing this data, Teseq AG cannot be responsible in any way for any errors or omissions. Standards are subject to change and it is strongly recommended that before any tests are carried out, the latest issue of the standard is obtained from the relevant standards body. www.teseq.com Surge - IEC 61000-4-5 ESD - IEC 61000-4-2 Amplitude density spectra Peak transient amplitude Transient occurrence in the real world The data shown here are taken from a study carried out in Germany in the mid- 1980s. Around 3,400 hours of recording captured 28,000 transients at 40 different measuring points. The transients were measured between live and protective earth of TN-type 220/380V supply networks. Transient characteristics did not vary much between industrial, business, domestic or laboratory locations, although the total number of transients was much greater in the industrial locations than the others. The data show that: the relative rate of occurrence of a given transient varies roughly proportionally to the inverse of the cube of its peak amplitude; the rate of rise (dv/dt) of the transient increases roughly proportionally to the square root of its peak amplitude, as does its rise time; the energy measure of a transient is more or less constant up to 200V and then increases roughly proportionally to the square of its peak amplitude at higher voltages; this suggests that the waveshape of transients is fairly constant over a range of amplitudes. For peak voltages above 1kV, the number of recorded transients was insufficient to give a high degree of statistical coverage. Reference: , J J Goedbloed, IEEE Transactions on EMC, Vol EMC-29 No 2, May 1987, pp 104-115 Transients in Low-Voltage Supply Networks V max V ms 2 V/ns 100% 10% 1% 0.1% 0.01% 100V 1kV 3kV 20 18 16 14 12 10 8 6 4 2 0 1000 10 Median energy measure S (industrial locations) V max 2 V max Median dv/dt (industrial locations) 1/V max 3 Relative no.of transients (all locations) Schaffner Test standard Peak V Voltage Voltage Peak I Current Current Number of 2050 module r t d t r t d pulses PNW2050 IEC 61000-4-5 1.2/50μs combination wave AC power line-to-line each polarity AC power Limited by additional 10 in series line-to-earth Other lines, Limited by additional 40 in series line-to-earth PNW2051 ITU-T (CCITT) 10/700μs wave K.17, .20 Transverse and 0.5 –5kV 10μs 700μs 12.5 –125A Defined by circuit components 10, polarity reversed longitudinal between pulses PNW2053B FCC Telephone line type A (high energy) Part 68 metallic 800V min 10μs max 560μs min 100A min 10μs max 560μs min 1 each polarity longitudinal 1500V min 10μs max 160μs min 200A min 10μs max 160μs min Telephone line type B (low energy) metallic 1000V min 9μs ±30% 720μs ±20% 25A min 5μs ±30% 320μs ±20% 1 each polarity longitudinal 1500V min 9μs ±30% 720μs ±20% 37.5A min 5μs ±30% 320μs ±20% Power line phase-neutral 2500V min 2μs max 10μs min 1000A min 2μs max 10μs min 3 each polarity IEC and other surge specifications 2kA ±10% 8μs ±20% 20μs ±20% Minimum 5 t 4kV ±10% 1.2μs ±30% 50μs ±20% 0.25 0.5 period between surge pulses determined by EUT protection capability For AC lines, synchronise surges to peaks (both polarities) ... ...and zero crossings Surge application ground reference plane is not essential, provided care is taken with earth connections, except for tests to shielded lines physically isolate the EUT, disconnect it from other equipment where possible and insulate the whole setup to prevent flashover synchronise each surge to the peak of the AC supply waveform to give maximum stress, and to the zero crossing to induce maximum follow-on energy in case this occurs: five negative and five positive applications each at 0°, 90°, 180° and 270° phases are required in most cases all lower test levels must also be satisfied – increase the stress voltage in steps up to the maximum, to check that the protective devices do not allow upset or damage at lower levels of applied voltage despite satisfactorily clamping high levels replace protective devices after testing if the EUT is to be re-used, in case of degradation; if tests done faster than one pulse per minute cause failure due to damaged protective devices, testing at one pulse per minute prevails during the test 0.5 0.3 0.9 1.0 Open circuit voltage waveform at the output of the generator, no CDN connected V/V pk t d T t = 1.2 s ±30% t = 50 s ±20% r d μ μ Rise time t = 1.67 · T r The combination wave t r (NOT TO SCALE) t ( s) μ undershoot 30% max 0.5 0.1 0.9 1.0 Short circuit current waveform at the output of the generator I/I pk T t d t r Rise time t = 1.25 · T r t = 8 s ±20% t = 20 s ±20% r d μ μ t ( s) μ undershoot 30% max coupling decoupling AC, DC and 3-phase supply surge coupling SA, SB: line selection (SA switched to successive lines, line-to-earth test) SA SB line to line | line to earth 1018 F µ 9F µ L1 L2 L3 N PE coupling/decoupling network (only L3, N and PE for single-phase supplies) CDN 110 (single phase) CDN 113 (3-phase) surge generator o/p floating L = 1.5mH mains supply input V S 2EUT L1 L2 L3 N PE Signal line and shielded cable surge coupling SA, SB: line select (SA switched to successive lines, line-to-earth test) SA SB line to line/ line to earth capacitive coupling/ arrestor coupling 400.5 F µ coupling/decoupling network for unshielded, lines unbalanced coupling/decoupling network for unshielded, lines balanced surge generator o/p floating PE 0 1 2 3 4 protection circuits protection circuits ancillary equipment ancillary equipment 20mH 20mH EUT unshielded, balanced lines unshielded, unbalanced lines shielded lines mains supply V S 2surge generator o/p earthed protective earth normally connected but must be isolated for surges on shielded lines far end earthed directly 2nd EUT shielded cable under test length 20m, or maximum allowed by EUT spec, bundled as necessary safety isolating transformer needed for surges on shielded lines L N E V S 2V S surge generator o/p earthed 1.2/50 s or 10/700 s generator as required µ µ 0 = line to earth 1–4 = line to line = 90V gas discharge tube surge arrestor IEC 61000-4-5: parallel combination of resistors to give: ITU-T K.20: resistors 25 each – 40 , 1.2/50 s surge – 25 , 10/700 s surge µ µ 1.2/50 s generator µ 1.2/50 s generator µ coupling to EUT's metallic enclosure or direct to shielded cable ground plane S1 * * Switch S1 is permanently in position 0 if testing to the second edition of IEC 61000-4-5 (no line-to-line coupling) body capacitance hand capacitance path of ESD current through victim equipment return path via ground discharge to victim Points of application Application method Non-earthed apparatus Number of discharges Mode of application Test levels – all points that are accessible to the user in normal operation; not necessarily pins of open connectors nor points accessible only during maintenance or servicing – contact discharge is preferred, air discharge is used where contact cannot be applied; both direct discharges to the EUT, and indirect discharges to the coupling plane(s), are required – should be deliberately discharged between each pulse, e.g. via connection of bleed resistor or by air ionisation – normally ten in each polarity to each point of application – EN 55024 requires a total of 200, 50 at each point – test generator must be perpendicular to the surface of the EUT; for air discharge, the tip must approach the EUT as fast as possible without causing mechanical damage; for contact, the tip must touch the EUT before the discharge switch is operated – all lower test levels must also be satisfied, i.e. if the test specification is 6kV contact, then 2kV and 4kV must also be applied The discharge event Applying the ESD test series inductance and resistance low impedance return connections from generator to GRP, routed away from EUT bleed resistor connections to coupling planes (470K at each end) indirect application to HCP horizontal coupling plane (HCP) 1.6 x 0.8m at least 0.1m larger than EUT on all sides direct application to EUT wooden table 0.8m high table-top EUT insulated from HCP ground reference plane (GRP) min. 1m , projecting >0.5m beyond EUT or HCP 2 vertical coupling plane (VCP) 0.5 x 0.5m indirect application to VCP 10cm VCP 10cm indirect application to VCP 10cm high insulating pallet direct application to EUT Floor-standing EUT > 1m between EUT and any other conducting structure > 1m between EUT and any other conducting structure ESD test set-up for table-top and floor-standing EUTs safety earth MHz MHz kHz -60 0.001 -40 0.01 -20 0.1 0 1 dB As µ µAs 0 10 -6 20 10 -5 40 10 -4 60 0.001 80 0.01 100 0.1 120 1 dB Vs µ Vs 10/700 s telecom 1.2/50 s surge (combination) 0.5 s/100kHz ring 5/50ns EFT µ µ µ Solid lines are calculated from the Fourier transform of the waveform equations given below; dotted lines are envelopes as shown in Annex B of IEC 1000-4-1: 1992 All waveforms have a peak value of 1kV ESD For calibrated current waveform at 4kV indicated voltage Amplitude density spectra of test pulses Equations Source: IEEE C62.41: 1991, except ESD: IEC 61000-4-2 draft Ed 2 ESD current waveform (4kV indicated voltage, t in ns) Surge voltage 1.2/50 s waveform (t in s) EFT 5/50ns waveform (t in ns) 0.5 s/100kHz ring waveform (t in s, = 2 ·10 rad/s) µ µ µ µ ω π 5 Vt V t t p () . exp . exp . = 1037 1 0 407 68 22 Vt V t t p () . exp . exp . = 127 1 35 55 6 ( ) Vt V t t t p () . exp . exp . cos = 159 1 0 533 9 788 ω + + + = 37.8 t exp 12 t 1 12 t 20.7 2 t exp 1.3 t 1 1.3 t 55 I(t) 1.8 1.8 1.8 1.8 1 10 100 1 1 10 10 100 100 1GHz 1GHz Energy content peak open circuit voltage (indicated voltage, ESD) kV energy W peak open circuit voltage kV Surge Ring energy measure S Vs 2 Joules Transient energy The energy content of transients and surges is not simple to define. The actual energy stored in the test generator is not all dissipated in the load. That proportion which is, depends on the ratio of the load and generator impedances. In general, a load such as a surge suppressor will be non-linear and will also have a time or frequency dependence. The "energy measure" of a given waveform can be described by which gives the energy that would be delivered by that voltage waveform into a 1 resistor, whether or not the generator is capable of this (i.e., assuming zero output impedance). These figures are shown in the lower graph opposite. Alternatively, the actual energy delivered by the generator into a defined resistive load can be calculated. For the ESD and EFT waveforms, these can be the calibration loads of 2 and 50 respectively. For the surge and ring waves, a load which matches the output impedance can be chosen, and the voltage or current waveform is delivered* into this resistance with half the open circuit (or short circuit, for current) amplitude. In these cases the energy in Joules (watt seconds) is shown in the upper graph and is given by where and are the open circuit voltage and short circuit current waveforms, respectively. These graphs are for comparative purposes only – the real energy delivered to a particular EUT can only be calculated if the load impedance and characteristics, and the actual waveshape applied to this load, are known accurately. The symbols on the graphs represent test levels 1 to 4 as defined in each standard. V(t) I(t) * This simplifying assumption is not found in practice as the current and voltage waveforms vary depending on the load impedance. S V t dt T = 2 0 () W R Vt dt T = 1 2 2 0 () W R It dt T = () 2 2 0 Energy versus test level 100 100 10 10 1 1 0.1 0.1 0.01 0.01 0.001 10 -3 10 -4 10 -5 10 -6 0.5 1 2 4 6 8 10 Surge – 1.2/50μs V, 2Surge – 1.2/50μs V, 12 Surge – 1.2/50μs V, 42 Surge – 8/20μs I, 2 Ring – 12 Ring – 30 Ring – 200 EFT – single pulse EFT – 1 second of bursts ESD into 2 0.5 1 2 4 EFT – single pulse EFT – 1 sec. of bursts EFT - IEC 61000-4-4 L1 L1 L2 (L2) L3 (L3) N PE N PE to safety earth Burst generator NSG3025 V B 50C = 33nF short, direct connection to ground plane – NB test generator should rest on GRP to achieve least possible inductance of link L > 100 H + ferrite µ EUT signal ports excess length folded (not coiled), 0.1m from GRP cable length 0.5m ±5cm length < 1m h G coupling clamp generator connected to end nearest EUT 10cm cable to auxiliary equipment protected by decoupling network coupling clamp at least 0.5m from other conductive structures EUT at least 0.5m from other conductive structures (including generator and coupling clamp) Common mode coupling only (2nd edition IEC 61000-4-4) external coupling h = 10 ±1 cm for both floor-standing and table-top equipment (2nd edition IEC 61000-4-4) G = grounding connection for EUT according to manufacturer's specification, length stated in test plan ground reference plane (GRP), min. 1 x 1m, projecting > 0.1m beyond EUT and clamp EFT burst test set-up and coupling cable length 0.5m ±5cm, 10cm above GRP 0.5 0.1 0.9 V = 1.0 PK V and waveshape are calibrated into a 50 load with a voltage level half the open circuit value ±10%, and into a 1000 load with a voltage level 5% lower than open circuit PK t (ns) t d t r t (ms) repetition frequency 5kHz or 100kHz ±20% burst duration 15ms at 5kHz 0.75ms at 100kHz * (75 pulses) 15ms ±20% for 5kHz 0.75ms ±20% for 100kHz * 300ms ±20% * t (ms) Asynchronous with power supply * NB these parameters are specified in the standard, but other values may be programmed for development testing Duration of each burst application 1 minute, both polarities mandatory Repetitive bursts Single burst of pulses Individual pulse V B t = 5ns ±30% t = 50ns ±30% for 50 50ns +100ns –15ns for 1000 r d IEC 61000-4-4: 2004 Electrical fast transient burst Waveform specifications Severity level Test voltage Test voltage (environment) (contact) (air) 1 (35% RH, antistatic) 2kV 2kV 2 (10% RH, antistatic) 4kV 4kV 3 (50% RH, synthetic) 6kV 8kV 4 (10% RH, synthetic) 8kV 15kV synthetic Relative humidity % Charge voltage kV 8kV 2kV 4kV 15kV air discharge severity levels Charge voltage versus RH and environmental materials typical ringing waveform ESD generator equivalent circuit Contact discharge stray capacitance Current at indicated voltage of 4kV: calibrated currents vary as ratio of indicated voltage, rise time remains constant t wool anti-static IEC 61000-4-2 Electrostatic discharge specification V Air discharge V ideal cal waveform R C R : 50–100M C R : 330 D C : 150pF D R C C D C D R D R D I = 15A ±10% PK 8A ±30% 4A ±30% t = 0.7–1ns r 30ns 60ns I Calibration waveform 25 0 50 75 100 0 5 10 15 Ring wave - IEC 61000-4-12 Ring wave application Generator Minimum Application output repetition impedance Z period 12 10s EUT supply ports connected to major feeders Application between communication ports on cabinets interconnected with 10m long screened data comms cables 30 6s EUT supply ports connected to outlets 200 1s I/O ports, unless the test involves protection devices or filters, in which case 12 or 30 is applicable A minimum of 5 positive and 5 negative transients are to be applied, both line to ground (common mode, simultaneously between all terminals and ground) and line to line (differential mode), and/or between cabinets (communication ports) IEC 61000-4-12 Ring wave t ( s) µ open circuit voltage f = 100kHz peak amplitude 60% of previous 10–90% rise time 0.5 s µ 1 0.5 0 -0.5 -1 ±10% 0 10 20 30 40 coupling decoupling (attenuation >30dB differential mode, >20dB common mode) AC, DC and 3-phase supply ring wave coupling SA–SD: line selection (switched between different lines, line-to-line test) SA SB SC SD 1 = line to earth 2,3 = line to line L1 L1 L2 L2 L3 L3 N N PE* PE EUT coupling/decoupling network (only L3, N and PE for single-phase supplies) surge generator output floating mains supply input V S 1 2 3 1 2,3 impedance depending on test requirement C C C C coupling capacitor C: 0.5 F for generator Z = 200 > 3 F for generator Z = 30 > 10 F for generator Z = 12 µ µ µ Ground reference plane (GRP) min 1m x 1m, projecting > 0.1m beyond EUT and auxiliary equpt * if no GRP is used, the protective earths for the EUT and surge generator must both be connected directly to the CDN earth terminal cabinet * see note re. GRP 1m safety earth Floor-standing EUT must be placed over a GRP using a 0.1m insulating support Table-top EUT may or may not* use a GRP; if present, the GRP is placed on top of a 0.8m high table and the EUT is insulated from it by 0.5mm thick material EUT must be at least 0.5m from other conducting structures System 2050 + PNW 2056 Z Generic and product standards L-L = line to line; L-E = line to earth. Always check the appropriate standard for detailed applicability Standard Scope ESD EFT-burst Surge EN 61000-6-1: 2001 EN 61000-6-2: 2005 EN 55014-2: 1997 + A1: 2001 EN 55020: 2002 EN 55024: 1998 EN 50130-4: 1995 + A2: 2003 EN 61326-1: 2006 EN 61547: 1995 + A1: 2000 EN 300386 Residential, commercial & light industrial generic Industrial generic Household appliances etc. Broadcast receivers etc. Information technology equip- ment Fire, intruder and social alarm systems Measurement, control and lab equipment, min. requirements General lighting equipment Telecom network equipment, immunity only Telecom centres Not telecom centres 4kV contact, 8kV air to EN 61000-4-2 4kV contact, 8kV air to IEC 61000-4-2 4kV contact, 8kV air to EN 61000-4-2 4kV contact, 8kV air to EN 61000-4-2 4kV contact, 8kV air to IEC 61000-4-2 6kV contact, 8kV air to EN 61000-4-2 4kV contact, 4kV air to IEC 61000-4-2 4kV contact, 8kV air to IEC 61000-4-2 4kV contact, 4kV air to EN 61000-4-2 6kV contact, 8kV air to EN 61000-4-2 1kV AC power, 0.5kV DC power > 10m, signal and functional earth > 3m to EN 61000-4-4 2kV AC power, DC power > 3m, 1kV signal and functional earth > 3m to IEC 61000-4-4 1kV AC power, 0.5kV DC power, signal and control > 3m to EN 61000-4-4 1kV AC power to EN 61000-4-4 1kV AC power, 0.5kV DC power, signal and telecom > 3m to IEC 61000-4-4 2kV AC mains supply, 1kV other supply/signal lines to EN 61000-4-4 1kV AC & DC power, 0.5kV I/O signal/ control > 3m to IEC 61000-4-4 1kV AC power, 0.5kV DC power, sig- nal and control > 3m to IEC 61000- 4-4 1kV AC power, 0.5kV DC power, out- door signal and indoor signal > 3m to EN 61000-4-4 1kV AC power and DC power > 3m, 0.5kV outdoor signal and indoor signal > 3m to EN 61000-4-4 1kV L-L, 2kV L-E on AC power input; 0.5kV L-L & L-E DC power > 10m, to EN 61000-4-5 1kV L-L, 2kV L-E on AC power; 0.5kV L-L & L-E DC power connected to a distribution network; 1kV L-E signal > 30m, to IEC 61000-4-5 1kV L-L, 2kV L-E on AC mains, to EN 61000-4-5 Not required 1kV L-L, 2kV L-E on AC mains, 0.5kV L-E on DC power with outdoor cables, to IEC 61000-4-5; 1.5kV 10/700μs on signal/telecom ports with outdoor cables, to ITU-T K recs. 1kV L-L, 2kV L-E on AC mains supply; 1kV L-E other supply/signal lines, to EN 61000-4-5 0.5kV power L-L, 1kV power & long distance I/O signal/control L-E to IEC 61000-4-5 0.5kV L-L, 1kV L-E on AC power, to IEC 61000-4-5 0.5kV L-L, 1kV L-E on AC power; 0.5kV L-E indoor signal lines > 10m, 1kV on outdoor signal lines, to EN 61000-4-5 1kV L-L, 2kV L-E on AC power; 0.5kV L-E indoor signal lines > 10m, 1kV L-E on outdoor signal lines, to EN 61000-4-5 Transient immunity testing 4 of a series of wallchart guides formerly Schaffner Test Systems Teseq AG Teseq AG Teseq AG Teseq AG Teseq AG Teseq AG Teseq AG Teseq AG Teseq AG

Transient occurence Surge - IEC 61000-4-5 ESD - IEC 61000 … · Transient occurence © 2006 Teseq ... PNW2050 IEC 61000-4-5 1.2/50µs combination wave ... Surge voltage 1.2/50 s

  • Upload
    doanthu

  • View
    230

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Transient occurence Surge - IEC 61000-4-5 ESD - IEC 61000 … · Transient occurence © 2006 Teseq ... PNW2050 IEC 61000-4-5 1.2/50µs combination wave ... Surge voltage 1.2/50 s

Transient occurence

© 2006 Teseq Specifications subject to change without notice.

All trademarks recognised.

691-006A

Teseq AGNordstrasse 11F4542 LuterbachSwitzerlandTel: +41 (0)32 681 40 40Fax: +41 (0)32 681 40 48

E & OE: Whilst great care has been taken in preparing this data, Teseq AG cannot be responsible in any way for any errors or omissions.Standards are subject to change and it is strongly recommended that before any tests are carried out, the latest issue of the standard is obtained from the relevant standards body.

www.teseq.com

Surge - IEC 61000-4-5 ESD - IEC 61000-4-2

Amplitude density spectra

Peak transient amplitude

Transient occurrence in the real world The data shown here are taken from a study carried out in Germany in the mid-1980s. Around 3,400 hours of recording captured 28,000 transients at 40 different measuring points. The transients were measured between live and protective earth of TN-type 220/380V supply networks. Transient characteristics did not vary much between industrial, business, domestic or laboratory locations, although the total number of transients was much greater in the industrial locations than the others.

The data show that:

the relative rate of occurrence of a given transient varies roughly proportionally to the inverse of the cube of its peak amplitude;the rate of rise (dv/dt) of the transient increases roughly proportionally to the square root of its peak amplitude, as does its rise time;the energy measure of a transient is more or less constant up to 200V and then increases roughly proportionally to the square of its peak amplitude at higher voltages; this suggests that the waveshape of transients is fairly constant over a range of amplitudes.

For peak voltages above 1kV, the number of recorded transients was insufficient to give a high degree of statistical coverage.

Reference: , J J Goedbloed, IEEE Transactions on

EMC, Vol EMC-29 No 2, May 1987, pp 104-115

Transients in Low-Voltage Supply Networks

Vmax

V ms2

V/ns

100%

10%

1%

0.1%

0.01%100V 1kV 3kV

201816141210

86420

1000

10

Median energy measureS (industrial locations)

Vmax2

√Vmax

Median dv/dt(industrial locations)

1/Vmax3

Relative no.of transients(all locations)

Schaffner Test standard Peak V Voltage Voltage Peak I Current Current Number of

2050 module r td tr td pulses

PNW2050 IEC 61000-4-5 1.2/50µs combination wave

AC power – –line-to-line each polarity

AC power Limited by additional 10Ω in seriesline-to-earth

Other lines, Limited by additional 40Ω in seriesline-to-earth

PNW2051 ITU-T (CCITT) 10/700µs waveK.17, .20

Transverse and 0.5 –5kV 10µs 700µs 12.5 –125A Defined by circuit components 10, polarity reversed

longitudinal between pulses

PNW2053B FCC Telephone line type A (high energy)Part 68

metallic 800V min 10µs max 560µs min 100A min 10µs max 560µs min 1 each polarity

longitudinal 1500V min 10µs max 160µs min 200A min 10µs max 160µs min

Telephone line type B (low energy)

metallic 1000V min 9µs ±30% 720µs ±20% 25A min 5µs ±30% 320µs ±20% 1 each polarity

longitudinal 1500V min 9µs ±30% 720µs ±20% 37.5A min 5µs ±30% 320µs ±20%

Power line

phase-neutral 2500V min 2µs max 10µs min 1000A min 2µs max 10µs min 3 each polarity

IEC and other surge specifications

2kA ±10% 8µs ±20% 20µs ±20% Minimum 5

t

4kV ±10% 1.2µs ±30% 50µs ±20% 0.25 0.5

period between surge pulses determined by EUT protection capability

For AC lines, synchronise surges to peaks (both polarities) ... ...and zero crossings

Surge application∗

ground reference plane is not essential, provided care is taken with earth connections, except for tests to shielded linesphysically isolate the EUT, disconnect it from other equipment where possible and insulate the whole setup to prevent flashoversynchronise each surge to the peak of the AC supply waveform to give maximum stress, and to the zero crossing to induce maximum follow-on energy in case this occurs: five negative and five positive applications each at 0°, 90°, 180° and 270° phases are required in most casesall lower test levels must also be satisfied – increase the stress voltage in steps up to the maximum, to check that the protective devices do not allow upset or damage at lower levels of applied voltage despite satisfactorily clamping high levelsreplace protective devices after testing if the EUT is to be re-used, in case of degradation; if tests done faster than one pulse per minute cause failure due to damaged protective devices, testing at one pulse per minute prevails

during the test

0.5

0.3

0.9

1.0Open circuit voltage waveform atthe output of the generator,no CDN connected

V/Vpk

td

T t = 1.2 s ±30% t = 50 s ±20%r

d

µµ

Rise time t = 1.67 · Tr

The combination wave

tr

(NOT TO SCALE)

t ( s)µ

undershoot 30% max

0.5

0.1

0.9

1.0

Short circuit current waveformat the output of the generator

I/Ipk

T

td

tr Rise time t = 1.25 · Tr

t = 8 s ±20%t = 20 s ±20%r

d

µµ

t ( s)µ

undershoot 30% max

coupling

decoupling

AC, DC and 3-phase supply surge coupling

SA, SB: line selection(SA switched to successivelines, line-to-earth test)

SA SB

line to line | line to earth

10Ω18 Fµ

9 Fµ

L1

L2

L3

N

PE

coupling/decoupling network(only L3, N and PE for single-phase supplies)

CDN 110 (single phase)CDN 113 (3-phase)surge generator

o/p floating

L = 1.5mH

mainssupplyinput

VS

EUT

L1

L2

L3

N

PE

IEC 61000-4-5 surge test

Signal line and shieldedcable surge coupling

SA, SB: line select(SA switched to successive lines,line-to-earth test)

SA SB

line to line/line to earth

capacitive coupling/arrestor coupling

40Ω0.5 Fµ

coupling/decoupling network for unshielded,

linesunbalanced

coupling/decoupling networkfor unshielded, linesbalanced

surge generatoro/p floating

PE

01

23

4

protectioncircuits

protectioncircuits

ancillaryequipment

ancillaryequipment

20mH

20mHEUT

unshielded,balancedlines

unshielded,unbalancedlines

shieldedlines

mainssupply

VS

2Ω surge generatoro/p earthed

protective earthnormally connectedbut must be isolatedfor surges onshielded lines

far end eartheddirectly

2nd EUT

shielded cable under test –length 20m, or maximumallowed by EUT spec,bundled as necessary

safety isolatingtransformerneeded forsurges onshielded lines

L

N

E

VS

VS

surge generatoro/p earthed

1.2/50 s or 10/700 sgenerator as required

µ µ

0 = line to earth1–4 = line to line

= 90V gas discharge tube surge arrestor

IEC 61000-4-5: parallel combination of resistors to give:

ITU-T K.20: resistors 25 eachΩ

– 40 , 1.2/50 s surge– 25 , 10/700 s surge

Ω µΩ µ

1.2/50 sgenerator

µ

1.2/50 sgenerator

µ

coupling to EUT'smetallic enclosure ordirect to shielded cable

ground plane

S1 *

* Switch S1 is permanentlyin position 0 if testing to thesecond edition of IEC 61000-4-5(no line-to-line coupling)

bodycapacitance

handcapacitance

path of ESD currentthrough victim equipment

return path via ground

dischargeto victim

Points of application

Application method

Non-earthed apparatus

Number of discharges

Mode of application

Test levels

– all points that are accessible to the user in normal operation; not necessarily pins of open connectors nor points accessible only during maintenance or servicing

– contact discharge is preferred, air discharge is used where contact cannot be applied; both direct discharges to the EUT, and indirect discharges to the coupling plane(s), are required

– should be deliberately discharged between each pulse, e.g. via connection of bleed resistor or by air ionisation

– normally ten in each polarity to each point of application – EN 55024 requires a total of 200, 50 at each point

– test generator must be perpendicular to the surface of the EUT; for air discharge, the tip must approach the EUT as fast as possible without causing mechanical damage; for contact, the tip must touch the EUT before the discharge switch is operated

– all lower test levels must also be satisfied, i.e. if the test specification is 6kV contact, then 2kV and 4kV must also be applied

The discharge event Applying the ESD test

seriesinductanceandresistance

low impedancereturn connectionsfrom generatorto GRP, routedaway from EUT

bleed resistor connectionsto coupling planes (470Kat each end)

indirectapplicationto HCP

horizontal couplingplane (HCP) 1.6 x 0.8mat least 0.1m larger thanEUT on all sides

direct application to EUT

wooden table0.8m high

table-top EUTinsulated fromHCP

ground reference plane (GRP)min. 1m , projecting >0.5m beyond EUT or HCP

2

verticalcouplingplane (VCP) 0.5 x 0.5m

indirectapplicationto VCP

10cm

VCP

10cm

indirectapplicationto VCP

10cm highinsulatingpallet

directapplicationto EUT

Floor-standing EUT

> 1m between EUTand any otherconducting structure

> 1m between EUTand any otherconducting structure

ESD test set-up for table-top and floor-standing EUTs

safetyearth

MHz

MHzkHz

-600.001

-400.01

-200.1

01

dB Asµ

µAs

010-6

2010-5

4010-4

600.001

800.01

1000.1

1201

dB Vsµ

Vs

10/700 s telecom

1.2/50 s surge (combination)

0.5 s/100kHz ring

5/50ns EFT

µ

µ

µ

Solid lines are calculated from the Fourier transform of the waveform equations given below; dotted lines are envelopes as shown in Annex B of IEC 1000-4-1: 1992

All waveforms have a peak value of 1kV

ESD

For calibrated current waveform at 4kV indicated voltage

Amplitude density spectra of test pulses

EquationsSource: IEEE C62.41: 1991, except ESD: IEC 61000-4-2 draft Ed 2

ESD current waveform (4kV indicated voltage, t in ns)

Surge voltage 1.2/50 s waveform (t in s)

EFT 5/50ns waveform (t in ns)

0.5 s/100kHz ring waveform (t in s, = 2 ·10 rad/s)

µ µ

µ µ ω π5

V t V t tp( ) . exp

.exp

.= ⋅ ⋅ −

1037 10 407 68 22

V t V t tp( ) . exp

.exp

.= ⋅ ⋅ −

127 13 5 55 6

( )V t V t t tp( ) . exp.

exp.

cos= ⋅ ⋅ −−

⋅159 1

0 533 9 788ω

+

⋅+

+

⋅=37.8

texp

12t1

12t

20.72texp

1.3t1

1.3t

55I(t) 1.8

1.8

1.8

1.8

1 10 100 1

1

10

10

100

100

1GHz

1GHz

Energy content

peak open circuit voltage (indicated voltage, ESD) kV

energy W

peak open circuit voltage kV

Surge

Ring

energymeasure S

V s2

Joules

Transient energy

The energy content of transients and surges is not simple to define. The actual energy stored in the test generator is not all dissipated in the load. That proportion which is, depends on the ratio of the load and generator impedances. In general, a load such as a surge suppressor will be non-linear and will also have a time or frequency dependence.

The "energy measure" of a given waveform can be described by

which gives the energy that would be delivered by that voltage waveform into a 1 resistor, whether or not the generator is capable of this (i.e., assuming zero output impedance). These figures are shown in the lower graph opposite.

Alternatively, the actual energy delivered by the generator into a defined resistive load can be calculated. For the ESD and EFT waveforms, these can be the calibration loads of 2 and 50 respectively. For the surge and ring waves, a load which matches the output impedance can be chosen, and the voltage or current waveform is delivered* into this resistance with half the open circuit (or short circuit, for current) amplitude. In these cases the energy in Joules (watt seconds) is shown in the upper graph and is given by

where and are the open circuit voltage and short circuit current waveforms, respectively.

These graphs are for comparative purposes only – the real energy delivered to a particular EUT can only be calculated if the load impedance and characteristics, and the actual waveshape applied to this load, are known accurately.

The symbols on the graphs represent test levels 1 to 4 as defined in each standard.

Ω

Ω Ω

V(t) I(t)

* This simplifying assumption is not found in practice as the current and voltage waveforms vary depending on the load impedance.

S V t dtT

= ∫ 2

0

( )

WR

V t dtT

= ⋅

∫1

2

2

0

( ) W R I t dtT

= ⋅

∫ ( )

2

2

0

Energy versus test level100

100

10

10

1

1

0.1

0.1

0.01

0.01

0.001

10-3

10-4

10-5

10-6

0.5 1 2 4 6 8 10

Surge – 1.2/50µs V, 2Ω

Surge – 1.2/50µs V, 12

Surge – 1.2/50µs V, 42

Surge – 8/20µs I, 2

Ring – 12

Ring – 30

Ring – 200EFT – single pulseEFT – 1 second of bursts

ESD into 2

Ω

Ω

Ω

Ω

Ω

Ω

Ω

0.5 1 2 4

EFT – single pulse

EFT – 1 sec. of bursts

EFT - IEC 61000-4-4

L1L1

L2(L2)

L3(L3)

N

PE

N

PE

to safetyearth

Burst generator NSG3025

VB

50Ω

C = 33nF

short, direct connectionto ground plane – NBtest generator should reston GRP to achieve leastpossible inductance of link

L > 100 H + ferriteµ

EUT

signalports

excess length folded (not coiled), 0.1m from GRP

cable length 0.5m±5cm

length < 1m

hG

coupling clamp

generator connected to end nearest EUT

10cm

cable to auxiliaryequipment protected bydecoupling network

coupling clampat least 0.5m fromother conductivestructures

EUT at least 0.5m fromother conductive structures(including generator andcoupling clamp)

Common mode coupling only(2nd edition IEC 61000-4-4)

externalcoupling

h = 10 ±1 cm for both floor-standing andtable-top equipment (2nd edition IEC 61000-4-4)

G = grounding connection for EUT according to manufacturer's specification, length stated in test plan

ground referenceplane (GRP), min.1 x 1m, projecting> 0.1m beyondEUT and clamp

EFT burst test set-up and coupling

cable length 0.5m±5cm, 10cm above

GRP

0.5

0.1

0.9

V = 1.0PKV and waveshape are calibratedinto a 50 load with a voltage levelhalf the open circuit value ±10%,and into a 1000 load with a voltagelevel 5% lower than open circuit

PKΩ

Ω

t (ns)

td

tr

t (ms)

repetition frequency 5kHz or 100kHz ±20%

burst duration15ms at 5kHz0.75ms at 100kHz *(75 pulses)

15ms ±20% for 5kHz0.75ms ±20% for 100kHz *

300ms ±20% *

t (ms)

Asynchronous withpower supply

* NB these parametersare specified in thestandard, but othervalues may be programmed fordevelopment testing

Duration of each burst application 1 minute, both polarities mandatory≥

Repetitivebursts

Singleburst ofpulses

IndividualpulseVB

t = 5ns ±30%t = 50ns ±30% for 50 50ns +100ns –15ns for 1000

r

d ΩΩ

IEC 61000-4-4: 2004Electrical fast transient burstWaveform specifications

Severity level Test voltage Test voltage(environment) (contact) (air)

1 (35% RH, antistatic) 2kV 2kV

2 (10% RH, antistatic) 4kV 4kV

3 (50% RH, synthetic) 6kV 8kV

4 (10% RH, synthetic) 8kV 15kV

synthetic

Relative humidity %

ChargevoltagekV

8kV

2kV

4kV

15kV

air dischargeseverity levels

Charge voltage versus RH and environmental materials

typical ringing waveform

ESD generator equivalent circuit

Contact discharge

straycapacitance

Current at indicated voltage of 4kV:calibrated currents vary as ratio of indicated voltage,rise time remains constant

t

woolanti-static

IEC 61000-4-2 Electrostatic discharge specification

V

Air discharge

V

ideal calwaveform

RC

R : 50–100MC Ω

R : 330D Ω

C : 150pFD

RC

CD

CD

RD

RD

I = 15A ±10%PK

8A ±30%

4A ±30%

t = 0.7–1nsr30ns 60ns

I

Calibration waveform

250 50 75 1000

5

10

15

Ring wave - IEC 61000-4-12

Ring wave application

Generator Minimum Applicationoutput repetitionimpedance Z period

12 10s EUT supply ports connected to major feedersApplication between communication ports on cabinets interconnected with 10m long screened data comms cables

30 6s EUT supply ports connected to outlets

200 1s I/O ports, unless the test involves protection devices or filters, in which case 12 or 30 is applicable

Ω

Ω

ΩΩ Ω

A minimum of 5 positive and 5 negative transients are to be applied, both line to ground (common mode, simultaneously between all terminals and ground) and line to line (differential mode), and/or between cabinets (communication ports)

IEC 61000-4-12 Ring wave

t ( s)µ

opencircuitvoltage

f = 100kHz

peak amplitude 60% of previous

10–90%rise time0.5 sµ

1

0.5

0

-0.5

-1

±10%

0 10 20 30 40

coupling

decoupling(attenuation >30dBdifferential mode,>20dB common mode)

AC, DC and 3-phase supply ring wave coupling

SA–SD: line selection(switched between differentlines, line-to-line test)

SA SB SC SD

1 = line to earth2,3 = line to line

L1L1

L2L2

L3L3

NN

PE*PE

EUT

coupling/decoupling network(only L3, N and PE for single-phase supplies)

surge generatoroutput floating

mainssupplyinput

VS

12

3

12,3

impedance depending ontest requirement

C C C C

coupling capacitor C:0.5 F for generator Z = 200> 3 F for generator Z = 30> 10 F for generator Z = 12

µ Ωµ Ωµ Ω

Ground referenceplane (GRP)min 1m x 1m,projecting > 0.1mbeyond EUT and auxiliary equpt

* if no GRP is used, the protectiveearths for the EUT and surgegenerator must both be connecteddirectly to the CDN earth terminal

cabinet

* see note re. GRP

1m

safety earth

Floor-standing EUT mustbe placed over a GRP using a 0.1m insulating support

Table-top EUT may or may not*use a GRP; if present, the GRPis placed on top of a 0.8m hightable and the EUT is insulatedfrom it by 0.5mm thick material

EUT must be at least 0.5m fromother conducting structures

System 2050+ PNW 2056

Z

Generic and product standards

L-L = line to line; L-E = line to earth. Always check the appropriate standard for detailed applicability

Standard Scope ESD EFT-burst Surge

EN 61000-6-1: 2001

EN 61000-6-2: 2005

EN 55014-2: 1997 + A1: 2001

EN 55020: 2002

EN 55024: 1998

EN 50130-4: 1995 + A2: 2003

EN 61326-1: 2006

EN 61547: 1995 + A1: 2000

EN 300386

Residential, commercial & light industrial generic

Industrial generic

Household appliances etc.

Broadcast receivers etc.

Information technology equip-ment

Fire, intruder and social alarm systems

Measurement, control and lab equipment, min. requirements

General lighting equipment

Telecom network equipment, immunity only

Telecom centres

Not telecom centres

4kV contact, 8kV air to EN 61000-4-2

4kV contact, 8kV air to IEC 61000-4-2

4kV contact, 8kV air to EN 61000-4-2

4kV contact, 8kV airto EN 61000-4-2

4kV contact, 8kV air to IEC 61000-4-2

6kV contact, 8kV air to EN 61000-4-2

4kV contact, 4kV air to IEC 61000-4-2

4kV contact, 8kV air to IEC 61000-4-2

4kV contact, 4kV air to EN 61000-4-2

6kV contact, 8kV air to EN 61000-4-2

1kV AC power, 0.5kV DC power > 10m, signal and functional earth > 3m to EN 61000-4-4

2kV AC power, DC power > 3m, 1kV signal and functional earth > 3m to IEC 61000-4-4

1kV AC power, 0.5kV DC power, signal and control > 3m to EN 61000-4-4

1kV AC power to EN 61000-4-4

1kV AC power, 0.5kV DC power, signal and telecom > 3m to IEC 61000-4-4

2kV AC mains supply, 1kV other supply/signal lines to EN 61000-4-4

1kV AC & DC power, 0.5kV I/O signal/control > 3m to IEC 61000-4-4

1kV AC power, 0.5kV DC power, sig-nal and control > 3m to IEC 61000-4-4

1kV AC power, 0.5kV DC power, out-door signal and indoor signal > 3m to EN 61000-4-4

1kV AC power and DC power > 3m, 0.5kV outdoor signal and indoor signal > 3m to EN 61000-4-4

1kV L-L, 2kV L-E on AC power input; 0.5kV L-L & L-E DC power > 10m, to EN 61000-4-5

1kV L-L, 2kV L-E on AC power; 0.5kV L-L & L-E DC power connected to a distribution network; 1kV L-E signal > 30m, to IEC 61000-4-5

1kV L-L, 2kV L-E on AC mains, to EN 61000-4-5

Not required

1kV L-L, 2kV L-E on AC mains, 0.5kV L-E on DC power with outdoor cables, to IEC 61000-4-5; 1.5kV 10/700µs on signal/telecom ports with outdoor cables, to ITU-T K recs.

1kV L-L, 2kV L-E on AC mains supply; 1kV L-E other supply/signal lines, to EN 61000-4-5

0.5kV power L-L, 1kV power & long distance I/O signal/control L-E to IEC 61000-4-5

0.5kV L-L, 1kV L-E on AC power, to IEC 61000-4-5

0.5kV L-L, 1kV L-E on AC power; 0.5kV L-E indoor signal lines > 10m, 1kV on outdoor signal lines, to EN 61000-4-5

1kV L-L, 2kV L-E on AC power; 0.5kV L-E indoor signal lines > 10m, 1kV L-E on outdoor signal lines, to EN 61000-4-5