40
User’s and installation manual UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series from 160 to 300kVA EK449A01

UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

User’s and installation manual

UNINTERRUPTIBLE POWER SUPPLYSLC ELITE MAX Series from 160 to 300kVA

EK449A01

Page 2: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 2 -

Page 3: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 3 -

SAFETY WARNINGS . .............................................................................................. 6

User’s manual, installation and start up. ................................................................ 4-39

Page 4: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 4 -

Contents

I. SYMBOLOGY USED IN THIS MANUAL AND/OR EQUIPMENT.

II. SAFETY WARNINGS .

III. APPLICATIONS AND USES.

1.- General information.1.1.- General description of the UPS.1.1.1.- UPS applications.1.1.2.- Power and back up time.1.1.3.- Safety and easy use.1.2.- Configuration and optional devices.1.2.1.- Standard configuration.1.2.2.- Battery cabinet.1.2.3.- Transformer cabinet.1.2.4.- Remote communication card.1.2.5.- UPS management software.1.2.6.- Remote panel.1.2.7.- Remote E.P.O. button.1.3.- Operating principle.1.3.1.- UPS block diagram.1.3.2.- Input, power module and output.1.3.3.- Control and auxiliary circuits.1.3.4.- Batteries.1.3.5.- Manual bypass.1.3.6.- Frontal panel.

2.- INSTALLATION STANDARDS.

2.1.- General information.2.2.- Reception and identification.2.3.- Storing.2.4.- UPS location.2.5.- Location features.2.6.- Predisposition and mains connection.2.7.- Auxiliary connections of the UPS.2.7.1.- Remote communication card.2.7.2.- Remote panel.2.7.3.- UPS monitoring software.2.7.4.- Remote E.P.O. button.2.8.- Main earthing protection.

3.- CONTROL PANEL.

3.1.- Introduction.3.2.- Menu 1: Status and alarms display.3.2.1.- UPS failure.3.3.- Menu 2: Measurements display.3.4.- Menu 3: UPS controls.

Page 5: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 5 -

3.5.- Menu 4: Guided procedures.3.6.- Menu 5: Panel configuration.3.7.- Menu 6: Data logger display.3.8.- Menu 7: Service.

4.- OPERATION.4.1.- Introduction.4.2.- Power switches.4.3.- Guided procedures.4.4.- UPS start up instructions.4.5.- Instructions for transferring to manual bypass.4.6.- Instructions for transferring from manual bypass to normal running.4.7.- Instructions for complete UPS shutdown.4.8.- Emergency Power Off (E.P.O.).4.9.- Instructions to start up the UPS in ECONOMY mode.4.10.- Instructions for transferring to manual bypass in ECONOMY mode.4.12.- Instructions for complete UPS shutdown in ECONOMY mode.4.13.- Battery management of the UPS.4.14.- Battery test settings.

5.- UPS IN PARALLEL.5.1.- Predisposition of the system.

6.- EQUIPMENT WITH FAILURES.6.1.- Generic alarms.6.2.- Fire principle.6.3.- Failures depending on the load type.

7.- SCHEDULED MAINTENANCE.7.1.- Yearly maintenance (or half-yearly in some critical cases).7.2.- Scheduled part replacement.

Page 6: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 6 -

I. SYMBOLOGY USED IN THIS MANUAL AND/OR EQUIPMENT.

«Warning» symbol. Carefully read the indicated paragraph and take the indicated prevention measures.

«Danger of electrical discharge» symbol. Pay special attention to this both in the indication on the device and thatof the paragraphs referred to in this Instructions Manual.

«Main protective earting terminal» symbol. Connect the earth cable from the installation to this terminal.

«Protective earth bonding terminal» symbol. Connect the load or loads and the batteries in case ou cabinet to the strip.

«Notes of information» symbol.

Preservation of the Environment.The presence of this symbol in the product or in their associate documentation indicates that, when concluding its cycleof useful life, this won’t be disposed with the domestic residuals.To avoid the possible damages to the environment, please separate this product from other residuals and recycle it suitably.The users can contact with their provider or with the pertinent local authorities to be informed on how and where they cantake the product to be recycled and/or dispose correctly.

II. SAFETY WARNINGS .

The described UPS in this Operating Manual, has been designed, manufactured and commercialised in accordance with thestandard UNE-EN ISO 9001 of Quality Assurance. The CE marking states the conformity with the CEE Directives by means ofthe following harmonised standards:

• EN-IEC 62040-1-2. Uninterruptible Power Suppply (UPS). Part 1-1: General safety requirements for UPS used in accessibleareas by workers.

• EN-IEC 60950-1. IT equipments. Safety. Part 1:General requirements.

• EN-IEC 62040-2. Uninterruptible Power Supply (UPS). Part 2: Electromagnetic Compatibility Prescriptions (EMC).

• EN-IEC 62040-3. Uninterruptible Power Supply (UPS). Part 3: Specification of the operating methods and test requirements.

It is excluded the responsability of the manufacturer in case of any modification or intervention made by the client.

• Together with the equipment and this «User’s manual», it is supplied the «Safety instructions» related with this product (Seedocument EK266*08). Before proceeding to the installation or start up, check that both information are available, otherwiserequest them. It is a must to comply the «Safety instructions», being legally responsible the user as for their observance. Oncethey are read, keep them for future consults that can arise.

III. APPLICATIONS AND USES.

Due to the different applications and standards involved in each case, the manufacturer recommends not to sell the product if theend use is not known. The responsability in those applications with wrong UPS operating or unsuitable use of itself that can causea risk of human life danger, will be of the seller only. The manufacturer will not accept any responsability over the caused damagesor wrong applications.

Page 7: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 7 -

1.- GENERAL INFORMATION.

1.1.- General description of the UPS.

This UPS is built in a metallic structure, where the electronic power is located in and we have access to it through the frontal door.The external covers of the equipment can be removed completely in order to guarantee an easy start up from any point in front ofany event.In the right frontal door, it is located the user interface panel, for controlling and managing the UPS.Due to the high power rate of the UPS, it doesn’t have any battery string inside; they are located in one or several cabinets.The cooling system of the equipment is based on a hydraulic system (made of water and glycol) and forced cooling, the air is takenfrom the baseboard of the UPS and exhausted through the frontal cooling grids placed in the exchanger stage, and located on thefrontal left side of the equipment.

1.1.1.- UPS applications.

This new UPS has been designed to supply stabilized and filtered voltage to sophisticated electronic devices (particularly to datacentres), which must have a power supply free of voltage and frequency fluctuations. Among them there are: hospitals, policestations, highway tunnels, broadcasting stations, banks, technical offices, etc.

1.1.2.- Power and back up time.

Thanks to its modular configuration, the power rates of this series are between 160 KVA and 300 KVA.It is not foreseen any internal battery string, so to achieve the wanted back up time is needed the use of additional cabinets them.

1.1.3.- Safety and easy use.

All the controls are properly insulated and disconnected from hazardous voltages.The control for overloads and overtemperatures guarantee an immediate intervention, in case one of them occurs during itsoperation.Through the frontal panel, the end-user can visualize the status of the UPS and make transference and shutdowns manoeuvres inan easy way . See chapter 3.There is the possibility to connect one or more external E.P.O. buttons (not supplied). Thanks to them, in case of fire, it is possibleto control the complete UPS shutdown. See chapter 2.7.4.The UPS monitoring can be remotely managed in an easy way either through a personal computer with a specific communicationsoftware(optional), or through a remote panel, optional too, they are essential in case of unattended places. See chapters1.2.5–1.2.6.

1.2.- Configuration and optional devices.

1.2.1.- Standard configuration.

The standard configuration is to assemble the UPS in only one cabinet, which will have the same dimensions in all the possibleconfigurations and sizes:

- Six pulses: 160 – 300 kVA- Twelve pulses: 160 – 300 KVA- Twelve pulses + THD filter: 160 – 300 KVA

Page 8: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 8 -

1.2.2.- Battery cabinet.

Under request, the UPS can be supplied with the suitable batteries to have the wanted back up time.The batteries are built in a separate cabinet and they have their own protection and breaking devices.Due to their external location, it is a must to foresee their protection.

1.2.3.- Transformer cabinet.

The galvanic isolation transformer is built in a separate cabinet (output -rectifier mains -bypass mains) for specific uses.The standard transformer is three phase/three phase with ratio 1:1, but it can be supplied with different ratio, depending on thecustomer needs.

1.2.4.- Remote communication card.

The UPS can be monitored through theremote communication card (CS0098).This monitoring can be done either througha PC with a specific software connectedto CN3, or through the dry contactslocated in the terminal strip M1. Thesystem already has a remotecommunication card and a slot to placean optional one, if it is requested (formore information, see chapter 2.7.-Auxiliary connections of the UPS).

1.2.5.- UPS management software.

The monitoring software Generex “UPS MANAGEMENT” allows tocommunicate the UPS with a PC or with an IT network, which runsunder Windows, Win-NT, Novell, OS2, Dec or Lynux platforms.This software allows the control of one or several UPS used in thesame IT network (LAN) of personal computers (For more information,see chapter 2.7.- Auxiliary connections of the UPS).

1.2.6.- Remote panel.

The remote panel allows displaying the operation of the UPS remotely,by repeating the status of the main stages with LED indicators andan acoustic alarm. (For more information, see chapter 2.7.- Auxiliaryconnections of the UPS).

1.2.7.- Remote E.P.O. button.

The remote E.P.O. button is a safety system that allows shuttingdown the UPS completely in case of an emergency. (For moreinformation , see chapter 2.7.- Auxiliary connections of the UPS).

Page 9: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 9 -

1.3.- Operating principle.

The described UPS is an On-line double conversion equipment with automatic bypass according with the European standardEN62040-3. This kind of UPS makes a double conversion of the input voltage in a continuous way and without any interruption.

As the loads are not connected directly to the mains there are not interferences transfer to them; also, the double conversionguarantees a stabilized energy, both voltage and frequency, which is the ideal for the correct operation of the critical loads.

When the input voltage is out of the permissible range of the equipment or there is a black out, the load is fed from the energy storedin the batteries.The system is provided with an automatic bypass; in case of UPS fault or overload, the bypass connects the critical loads to thebypass mains directly, which allows to restore the normal operating conditions of power supply without any interruption. See figure1.3.1.

1.3.1.- UPS block diagram.

BYPASS MANUAL / MANUALBYPASS

BYPASS MANUAL / MANUALBYPASS

LINEA BYPASS / BYPASS LINE

LINEA BYPASSBYPASS LINE

ENTRADA REDMAINS INPUT

RECTIFICADOR - CONVERTIDOR STEPUP RECTIFIER - STEP UP CONVERTER

INVERSORINVERTER

INTERRUP TOR ESTÀTICOSTATIC SWITCH

SALIDA - CARGAOUTPUT - LOAD

CARGADOR DEBATERÍAS

BATTERY CHARGER

ARMARIO DE BATERÍASBATTERY CABINET

1.3.2.- Input, power module and output.

From the input terminals, the mains is connected through the MAINS INPUT I1 switch to the power module.During a mains failure or it is out of the permissible UPS range, the step-up rectifier module, makes the DC/DC conversion from thebattery and in case of restoring it makes the AC/DC conversion from the mains (normal operation).

After, the direct current supplies the inverter module, which is in charge of inverting the DC to alternating current making it suitablefor the load requirements.The last module is the automatic bypass; it connects, in normal operation, the filtered and regenerated energy from the invertermodule to the loads. In case of UPS fault or overload, the UPS output will transfer to the bypass line; in this situation, the mainsis in charge of feeding the loads. Once the fault, which has provoked the transference to bypass, is solved, the static switchtransfers back the load to the inverter automatically.Through the UPS OUTPUT SWITCH I4, the loads are supplied in a filtered, regenerated and stabilized way. See diagram 1.3.1.

Page 10: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 10 -

1.3.3.- Control and auxiliary circuits.

The control logic is in a specific card (CS0090) and it is equal to “the intelligence” of the UPS. It is in charge of managing theoperation of the rectifier step-up, inverter and bypass from the comparison, in phase, of the signs detected by the power module.Also the control logic manages three additional cards: the battery charger, the auxiliary power supply and the communicationinterface.

The battery charger guarantees the perfect recharging of those external battery strings that are connected to the UPS. Thecommunication interface takes the signals from the control logic and they are converted to the foreseen protocol for the UPS frontalpanel and relay card. Contrary to it, the communication interface sends the criteria coming from the frontal panel (forced transferto bypass) and/or from the relay card (E.P.O.) to the control logic, doing at the same time, the transference of the UPS to the bypassline and/or shutting down the UPS immediately, respectively.

The communication interface can control a part from the standard relay card an additional one, which is optional.The auxiliary power supply feds all the PCB’s and electronic parts of the UPS.

1.3.4.- Batteries.

The battery supplies energy to the system when the mains is out of range or there is a black out. In the rest of cases, the batterycharger module recharges that battery in a constant way to leave it ready again.

1.3.5.- Manual bypass.

The use of the manual bypass is foreseen for those cases that the UPS must be excluded from the loads and they must still besupplied from the mains(example: UPS shutdown, fault,...). It is a circuit, which is turned on/off through the MANUAL BYPASSSWITCH I4 and it is located in the frontal part of the UPS. For more information, see chapter 4. In normal running, this switch isin off position with a safety mechanical lock (it is padlocked).

1.3.6.- Frontal panel.

The UPS is controlled through the frontal panel, and it is possible to manage the controls, visualize and reboot the alarm circuits.The panel has an LCD that allows displaying the UPS operating, the load status and any measurement (see chapter 3).

Page 11: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 11 -

2.- INSTALLATION STANDARDS.

2.1.- General information.

This chapter describes both the installation modes of the system and the description of the following topics:

2.2.- Reception and identification.2.3.- Storing.2.4.- UPS location.2.5.- Location features.2.6.- Predisposition and mains connection.2.7.- Auxiliary connections of the UPS.2.8.- Main earthing protection.

2.2.- Reception and identification.

After removing the packing, inspect the UPS and battery cabinet visually (inside and outside) to detect possible damages inthe unit due to the transport. If there is any damage in the structure, it is convenient to claim to the transport agency or dealerimmediately. Also, it is convenient to compare the supplied good with the delivery invoice.In the door of the equipment there is the adhesive tag label with the type, power and serial number of the equipment.

2.3.- Storing.

If the equipment is not installed immediately, it must be stored in a environment protected from high humidity and heat sources(from +5 to +40 °C, non-condensing humidity lower than 95%).

When the battery cabinet is also supplied, it is a must to assure that the period time between the last recharge of the batteries andthe next one will not be higher than 6 months. Once this period is overcame, the UPS will be connected to the mains and startedup provisionally, during the needed time in order to recharge the batteries .

2.4.- UPS location.

All the sizes and configurations of this series have been designed with the same structure. Their mechanical features are describedin the tables 2.4 a-b-c.

The dimensions and weight are different due to the liquid-air exchanger of the equipment.

For its handling, remind you that the equipment, less in those particular agreements, it is sent and joined with the exchanger,therefore it is necessary to take note of the dimensions and weight of the used version.

The cabinet, without the packing, can be transported with the help of a forklift, either from the front or from the side, and movedtill the installation location.Remind you, that the UPS has bottom entry cable (on the right and under the baseboard support ) (fig. 2.4).

Page 12: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 12 -

Tab.2.4c

DIMENS ION SD x W x K

160 570200 600250 630300 630

DIMENS ION SD x W x K

160 720200 720250 870300 870

DIMENS ION SD x W x K

160 780200 780250 990300 990

SIX PHASE VERSION

800 x 1240 x 1800

POW ER (kVA) W EIGHT (K g .)

T HREE PHASE VERSION

800 x 1240 x 1800

SIX PHASE VERSION

800 x 1240 x 1800

POW ER (kVA) W EIGHT (K g .)

POW ER (kVA) W EIGHT (K g .)

Page 13: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 13 -

In the Fig.2.4, it is showed the fixing bars and hardwiring of the cables.

If the UPS is seen from the front, the entry cable is done from the bottom right side, and we can access by removing the sidecover.All the cables enter through the bottom window, as it is showed in the figure 2.4 (side view).

2.5.- Location features.

The UPS installation site must be clean and with a contamination degree of 2 (IEC); also, it must be able to exhaust the heatproduced by the equipment, according to the heat losses stated in the table 2.5a.

Fig. 2.4

MAIN INPUT SWITCH

OUTPUT LOAD

BYPASS INPPUT SWITCH

EARTH BAR

ENTRY CABLE

POS - NEG BATTERY

Page 14: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 14 -

If the installation has battery cabinet too, the location must guarantee a cooling equal or higher than the one stated in the table 2.5b

Likewise, remind that the average lifetime of the batteries is related with their operating temperature, the recommended one isaround 20°C.(In case the 20º C are overcame, per each 10°C over, the “battery lifetime” is reduced in 50%.)

2.6.- Predisposition and mains connection.

To make the connection to the mains, it is recommended a solution like the one stated in the diagram 2.6a. The switches B-C-Dare circuit breakers without earth leakage protection or, in case it is needed, with a leakage current higher than 500mA, delayedand ready to support loads with DC component (RCD type B).

Diagram 2.6a

Bypass estandarStandard bypass Carga / Load

Red principalStandard mains

BYPASS DEMANTENIMIENTO

MAINTENANCEBYPASS

PAN

EL D

E D

ISTR

IBU

CIÓ

N /

DIS

TRIB

UTI

ON

Red principalStandard mains

Bypass estandarStandard bypass

BYPASS DE MANTENIMIENTOMAINTENANCE BYPASS

BYPASS

LÍNEA DE BYPASSBYPASS LINE

ENTRADAINPUT

SALIDAOUTPUT

BATERÍA 1 / BATTERY 1

ARMARIO DE BATERÍAS / BATTERY CABINET

SAIUPS

Tab.2.5b

Spare air for 15 Spare air for 30 Spare air for 1minutes (m³/h) hour (m³/h) minutes (m³/h)

10 19 3213 26 4216 32 5219 39 62

Spare air fot the hydrogen of the batteries

Tab.2.5a

H e at lo s s e s w i th H e at lo s s e s w ith o u te x ch an g e e xch an g e

1 6 0 8 ,2 3 ,52 0 0 9 ,9 4 ,12 5 0 1 2 ,8 5 ,33 0 0 1 5 ,5 6 ,5

P O W ER

N o m . P o w e r

Page 15: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 15 -

The manoeuvres devices and all power connections of the UPS must be able to support the currents stated in the tab. 2.6,in a permanent way.

If it were necessary, prepare, a backfeed protection to be installed in the UPS distribution board as it is showed in the circuitdiagram 2.6b

¡ATTENTION!IT IS A MUST TO INSTALL EXTERNALLY TO THE UPS, AT THE MAINS INPUT, A CONTACTOR A PART FROMTHE PROTECTION CIRCUIT BREAKER, IN ORDER TO PROTECT AGAINST BACKFEED VOLTAGES, IN ACCORD-

ANCE WITH THE TABLE 2.6 AND THE FOLLOWING CIRCUIT DIAGRAM:

Diagram 2.6b

Inpu

t.

UPS.

R

S

T

N

Out

put.

R

S

T

N

Bypa

ss.

U

V

W

N

Automatic bacfeed protection at theinput, external to the UPS

(EN-IEC 62040-1-1 parágrafo 5.1.4).

Tab.2.6

160 305 242 242 350200 369 302 302 438250 449 378 378 547300 530 454 454 600

Output (A) Battery discharge (A)UPS Power (kVA) Mains input (A) Bypass input (A)

Page 16: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 16 -

BYPASS( )

Before connecting the UPS, check:

- The voltage and frequency values of the mains are the same ones as in the nameplate pasted in the internal side of the UPSdoor (input voltage, operating frequency, etc.).

- Main earthing of the installation is done in accordance with the IEC standard or with the local regulations.

After that, proceed to install the four poles circuit breakers, upstream and downstream of the UPS (see Fig.2.6b) with the followingfeatures:

- The size must be equal or higher than the one stated in the nameplate located in the internal side of the UPS door (KVA).- Their features must in accordance with the IEC standards or with the local regulations for circuit breakers with characteristic

“C”.- The connections must done, in accordance with the local standards for electrical installations, by using flexible cables with

a minimum cross section as they are stated in the following table:

Fig. 2.6c

¡WARNING!BEFORE CONNECTING THE UPS, BE SURE THAT THE CABLES BETWEEN THE MAINS AND BYPASS INPUT

WITH THE DISTRIBUTION BOARD ARE NOT LIVE. LIKEWISE, THE BATTERY SWITCH MUST ALSO BEOPENED. LASTLY, PUT THE WARNING LABELS IN THE DISTRIBUTION BOARD AND BATTERY CABINET TO

AVOID ACCIDENTAL MANEOUVRES.

CABLE FIXING BARSUPS OUTPUT

LOAD

INPUTMAINS

INPUTBYPASSMAINS

Page 17: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 17 -

2.7.- Auxiliary connections of the UPS.

The communication cards are placed over the UPS switches.

The standard configuration is based on remote communication card (CS0098) and one slot ready to located the SNMP card.

There is the possibility, under request, to install an additional and optional remote communication card (CS0098) (fig.2.7.1a).

The connection of these cards is located in the rear side of the UPS (fig.2.7.1b)

2.7.1.- Remote communication card.

This card allows the connection of the UPS with several external devices.The card has a terminal strip with dry contacts (M1) where it can connected the following: a remote panel (chapter.2.7.2),acoustic buzzers or visual indicators or signalling systems

Through other two contacts (CN1), it is possible to connect one or more remote E.P.O. buttons (chapter 2.7.4).

Lastly, the equipment can be connected to a PC with its corresponding monitoring software through a DB9 connector (CN3)

160 2 x 70 242 2 x 50 350200 2 x 95 302 2 x 70 438250 2 x 150 378 2 x 95 547300 2 x 185 454 2 x 120 600

P (kVA) Ø A.C. (mm²) I A.C. (A) Ø D.C. (mm²) I D.C. (A)

Page 18: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 18 -

(chapter 2.7.3).

2.7.2.- Remote panel.

It is connected to the UPS through the terminal strip M1 located in the remotecommunication card (CS0098)(connection diagram fig. 2.7.2a). This device allowscontrolling remotely the main stages of the UPS (represented with led indicators).Likewise, the acoustic alarm can be silenced through the key 5.

LED description:

1)UPS ON green led.Turned ON, means the correct operation of the UPS; turned OFF, means,that there is one or more alarms in the inverter stage (acoustic alarm on).

2)ON BATTERY yellow led.Turned ON, means the UPS is in battery mode (acoustic alarm on).

3)LOW BATTERY red led.

Fig. 2.7.1a

EXTERAL CONNECTION OF THE COMMUNICATION PBC

Low battery voltage

Mains fault

Maintenance bypass

Inverter ON

1

2

3

4

5

6

78

910

1112

CN1

JP1

M12

1

EPO

CN3

26

738495

1

RX

T X

Fig. 2.7.1b

Fig. 2.7.2b

M1

Page 19: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 19 -

Turned ON, means an imminent discharge of the battery (acoustic alarm on).

4)ON BYPASS yellow led.Turned ON, means that the load is supplied from the bypass (acoustic alarm on).

5)ALARM SILENCE key.It allows silencing the acoustic alarm.

6)Green Led .

Turned ON, means the correct power supply of the remote panel.

2.7.3.- UPS monitoring software.

Through a computer with this software installed, it is possible to control all the UPS status. This computer must be connected tothe UPS with the supplied specific cable.For more information about the software installation and using, see its corresponding manual.

2.7.4.- Remote E.P.O. button.

Pay special attention to the connection of the buttons for the E.P.O. function (emergency power off). That connection is based onseveral closed dry contacts in rest state (Fig.2.7.4), and when they are turned on they are opened shutting down the UPS makinga break in the load feeding. The external E.P.O. buttons must be connected to the terminal CN1 of the PCB CS0098. In case the

Fig. 2.7.2a

2

6

73

8

4

9

5

1

2

1

4

3

5

12V-12A

K1

DB9

Male connector

Relay PCB

121110987654321

M1

12345678

M1

UPS Remote panel

Low batteryUPS ONBypass onMains statusCommon

External power supply

11296

2-5-8-11

12345

Relay PCB UPS Remote panel

Fig. 2.7.2a

NC = Normally closed

Page 20: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 20 -

external E.P.O. button is not added, there must be a cable jumper JP1 instead . (enclosed in a circle in the fig.2.7.1a).

2.8.- Main earthing protection.

The input earth cable must be connected to the earth stud of the UPS. That cable must be the first one to be connected. It is betterto place an anti-rust between the earth stud and the contact board to extend the life of the contact.

¡WARNING!IF THE EARTHING IS UNSUITABLE, THE STAFF COULD SUFFER ELECTRICAL DISCHARGES OR

TO PROVOKE A FIRE.

Page 21: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 21 -

All the cabinets and accessories must be earthed in accordance with the current standards.

3.- CONTROL PANEL.

3.1.- Introduction.

The control panel is in the frontal side of the UPS, which is used to monitor its general and battery status and the correspondingalarms in a easy way.That control panel is based in a LCD panel that shows the operating status, measurements and alarms, and by an E.P.O. buttonlocated in the bottom-right side.The LCD panel shows text messages and operating parameters in a LCD screen of 4 rows with 20 characters per each one.The screens are organised in 7 multilevel menus , which can be selected by using the keys placed under the LCD panel.

In the left side of the LCD, there are two LEDs, one is green labelled as “NORMAL” and the other one is red labelled as “ALARM”.

The behaviour of both LED is summarized in the table 3.1a.

During the normal operating and to identify the UPS master, in case of parallel systems, the green LED blinks.

Tab 3.1a

STATUS UPS OK ACTIVE ALARM DEACTIVE ALARMGREEN LED ON OFF ONRED LED OFF ON BLINKING

Key ESCAllow silenci theacoustic alarm

Key MENUAllow escaping

from the selectedmenu.

Figure 3-1b LCD panel composition

Key BACK Key NEXT

Allow moving from one menu to another. If bothare pressed together is the ENTER function.

Page 22: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 22 -

LCD control panel

During the normal operating of the UPS, the control panel shows, through several messages, the operating status of each stage that ismaking up the system. In this way, the user receives the information on eventual failures of the system in real time (acoustic alarm).

The table 3-1b summarizes all the available menus.

It is possible to move through the described 7 menus in the table 3-1b by using the keys NEXT(>) or BACK(<).

By pressing simultaneously the keys NEXT(>) and BACK(<), the control ENTER (< >) is selected and the selection isconfirmed, and accessing to the next level.To come back to the previous level, the key MENU must be pressed.

Each alarm signal in the LCD panel goes with an acoustic alarm (buzzer), that can be silenced by pressing the key ESC (seefigure 3-1b).

When the UPS is turned ON, it is showed the menu N. 4 “GUIDED PROCEDURES” automatically and the start up procedure isshowed.In this moment, the user can decide to continue with the guided procedure by following the proposed visual indications tillthe system is completed started up, or to execute different operations through the key MENU.

If the user doesn’t make any action, after three minutes, the menu N1 “STATUS AND ALARMS DISPLAY” isdisplayed.

3.2.- Menu 1: Status and alarms display.

This menu shows in the first row of the message, the texts UPS IN OPERATION (if the UPS is normal operating), or UPSALARM (if the UPS shows an alarm condition). Find below the meaning of the messages:

Tab 3.1b

MENU Nº NOTES

Status and alarms displaying 1If any key is not pressed after 3 minutes, this menu isactivated again.

Measurements displaying 2 It is possible to visualize the values of all measurementsUPS controls 3 Inverter Start up/shutdown, static switch, battery testGuided procedures 4 It is showed when the equipment is started up.Panel sett ings 5 Date/time/battery test/language settingData logger displaying 6 Displays the alarm data loggerServices 7 Destined for Service and Technical Support

Page 23: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 23 -

UPS in normal operating mode3.2.1.- UPS failure.

In case of UPS failure, the status screen is replaced by the alarm ones.

There is a message informing the user about the occurred failure type and the buzzer is turned on but it can be silenced bypressing the key ESC. When the key ENTER (< >) is pressed a signal list is showed to help the user to understand themeaning of the alarm. The keys <BACK or NEXT> allow moving through the list. When the alarm condition disappears, the

UPS ALARM ALARM CAUSE

< ENTER>

< BACK or NEXT>

Tab 3

MESSAGE MEANING

CORRECT MAINS / OUT OF RANGEThe input mains is present but the voltage is out of thespecified range

CORRECT BYPASS LINE / OUT OF RANGEThe bypass line mains is present but the voltage is outof the specified range

CORRECT BATTERY VOLTAGE The battery voltage is inside the specified rangeINVERTER ON The inverter is ON and it is in normal operatingINVERTER-BYPASS SYNCHRONISED /NOT SYNCHRONISED

Indication of the synchronism status between theinverter and bypass

LOAD ON INVERTER The inverter feds the load

LOAD ON BYPASSThe bypass feds the load. It is a temporary situation of20 seconds due an overload detection.

UPS MASTER It controls the UPSs connected in parallelUPS SLAVE It is controlled by another UPS in parallel.

Page 24: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 24 -

3.3.- Menu 2: Measurements display.

To access to this screen press the key ENTER in “2.Measurements display” of the main menu. In this way the user can check,by moving with the keys < or >, the value of the following electrical measurements:

V phase/neutral = phase to neutral voltage of the input mains.V phase/phase = phase to phase voltage of the input mains.Input currents = currents of the three input phases.V out phase/neutral = phase to neutral voltage of the UPS output.Output currents = output currents to the load.Battery V,I = battery voltage and current.Supplied power KVA = power supplied by the UPS.Frequency= output frequency of the UPS.% back up timeTemperature = ambient / rectifier heatsink / inverter heatsink / bypass heatsink / liquid cooling / batteries.

LCD panel goes back to the main screen.Next there is a list with all the alarms and helping messages.

A L AR M A M E S S A G E M E AN IN G

INV E R T E R O FF T he loa d is no t supp lied by the inve rte r, so a b rea k c a n ha ppen .

O V E RLO A DT he inve rte r is shu tdow n due to a n ove rloa d a nd t he loa ds a re st illsupp lied .

S T A T IC S W IT C H B LO C K E DA fte r 3 frust ra ted au tom at ic a t tem pts from bypass t o inve rte r, theU PS b loc ks t he sta t ic sw it c h in the bypa ss line posit ion .

B A T T E R Y FA U LTB A T T E R Y T E S T FA U LT

It is d isp la yed , w hen the ba t te ry test is no t O K , due t o a nyreason .

LO W B A T T E R Y A LA R MW hen the ba t te ry vo lta ge rea c hes 440V , the U PS w a rns t he use rstha t the ba t te ry is low . A t 400V the U PS is shu tdow n .

S T A T IC S W IT C H FA U LT O ne o r m ore ou t pu t pha ses a re m issedM A NU A L B YPA S S E NA B LE D It is d isp la yed w hen the m a nua l bypa ss is t u rned on .

INPU T M A INS O U T O F R A N GET he inpu t m a ins is ou t o f the U PS ra nge , it c a n be h ighe r o r low erthan t he spec ified range , o r a m a in fau lt .

B YPA S S LIN E O U T O F R A N GET he bypa ss line is ou t o f the U PS ra nge , it c a n be h ighe r o r low ertha n the spec ified ra nge , o r a m a in fa u lt o r a w rong p ha sesequenc e .

E M E R GE NC Y U PS S H U T D O W N It is d isp la yed w hen the E .P .O bu t t on is p ressed .

B A T T E R Y C H A R GE R FA U LT It is d isp la yed w hen the ba t te ry c ha rge r is fa u lty o r d isc onnec ted .PA R A LLE L C O M M U NIC A T IO N D A T AFA U LT

It is d isp la yed w hen the re is no t da t a in te rc ha ng ing be t w een theU PS s in pa ra lle l. It c a n be e it he r a m issing o r w rong c onnec t ion .

Page 25: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 25 -

After 3 minutes of inoperation, the LCD panel will display the menu 1 STATUS AND ALARMS DISPLAY.3.4.- Menu 3: UPS controls.

By means of this menu we can give orders to the UPS.After 3 minutes of no operation, the LCD panel will display the menu 1 STATUS AND ALARMS DISPLAY.

3.5.- Menu 4: Guided procedures.After 3 minutes of no operation, the LCD panel will display the menu 1 STATUS AND ALARMS DISPLAY.

3.6.- Menu 5: Panel configuration.

MESSAGE MEANING

4,1 UPS START UP The user is guided to start up the equipment.4,2 UPS SHUTDOWN The user is guided to shutdown the equipment.4,3 MANUAL BYPASS ACTIVATION The user is guided to shutdown the UPS and bypass line. The loads are still fed with

no interruption through the manual bypass.4,4 MANUAL BYPASS DEACTIVATION The user is guided to restart up the UPS , the loads are still fed with no interruption

from the manual bypass.

MESSAGE MEANING

3,1 INVERTER ON3,2 INVERTER OFF

3,3 LOAD TRANSFERRED TO INVERTER With this message, when the key ENTER is pressed, the load is transferred frombypass to inverter.

3,4 LOAD TRANSFERRED TO BYPASS With this message, when the key ENTER is pressed, the load is transferred frominverter to bypass.

3,5 BATTERY TEST START With this message, when the key ENTER is pressed, an automatic battery test willstart, which will take 30 seconds.

With this message, when the key ENTER is pressed, the user can start up orshutdown the inverter in a permanent way. It is needed for starting up the inverterand after a shutdown due to a permanent overload.

MESSAGE MEANING

5,1 Date setting Allow setting the current date by using the arrows to increase or decrease thenumbers.

5,2 Time setting Allow setting the current time by using the arrows to increase or decrease thenumbers.

5,3 Battery test setting Allow setting the automatic battery test by choosing the weekday, the number ofweek between one test and the next one, and the time in the day when it must bedone.

5,4 Language settingAllow choosing the language among: Spanish, English, French, German and Italian

Page 26: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 26 -

After 3 minutes of no operation, the LCD panel will display the menu 1 STATUS AND ALARMS DISPLAY.3.7.- Menu 6: Data logger display.

In this menu the end-user can check the last 1.024 events / alarms in chronological order.By selecting 6.EVENTS DATA LOGGER in the main menu and after that selecting DATA LOGGER, the data logger is displayed.The screen will show the date and time of the last event.The log list can be checked using the keys <BACK or NEXT>.At any position of the log list, by pressing MENU, the LCD panel will come back to the MAIN MENU.

To delete all the events and alarms, the submenu DELETE DATA LOGGER must be selected and after that press<ENTER>.

After 3 minutes of no operation, the LCD panel will display the menu 1 STATUS AND ALARMS DISPLAY.

3.8.- Menu 7: Service.

The control PCB can be connected to a notebook computer through optical fiber. This way, the Service and Technical Support candiagnose or set the parameters of the UPS. To make this procedure or to check the software version of the signalling, we mustenter into the menu 7. SERVICE MODE. This menu is protected, by a password that denies the access to not authorised personal.

Page 27: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 27 -

After 3 minutes of no operation, the LCD panel will display the menu 1 STATUS AND ALARMS DISPLAY.4.- OPERATION.

4.1.- Introduction.

This chapter describes all the control devices of the UPS at the user disposal to use the system properly. The UPS can be runningunder one of the following operating modes:

• Normal mode. The UPS feeds the load. The UPS is running normally and uses the input mains to fed the loads and torecharge the batteries. This operating mode guarantees the non-interrupted power supply to the loads.

• Internal automatic bypass mode. The load is fed by the mains. In case of failure and/or inverter overload, the powersupply of the loads is guaranteed thanks to the bypass line (reserve). This operating mode doesn’t guarantee the non-interrupted power supply to the loads.

• Maintenance bypass mode. The UPS is shutdown. The load is connected directly to the mains through the maintenanceor emergency bypass line. This operating mode doesn’t guarantee the non-interrupted power supply to the loads.

• Battery mode. The UPS feds the load. The UPS is running and uses the batteries to fed the loads because there is a mainsfailure. This operating mode guarantees the non-interrupted power supply of the loads till the end of autonomy.

4.2.- Power switches.

The power switches of the UPS are located behind the right front door and they have been installed vertically in the followingorder (see fig. 4.3):

• Input mains switch (I1): It connects the UPS with the input mains.

• Output switch (I4): It connects the UPS with the critical loads.

• Input bypass switch (reserve) (I2): It connects the UPS with the bypass mains (reserve).

• Manual bypass switch (I3): It allows excluding the UPS by keeping the LOADS fed the mains. It is protected by amechanical lock (padlock) to avoid accidental manoeuvers.

All the power switches of the UPS have been described less the battery one, which is located in the battery cabinet, outfrom the UPS cabinet.To isolate the equipment completely from hazardous voltages, the battery SWITCH must be turned OFF, althoughit is not located in the cabinet.Likewise, remind you that there are charged capacitors inside the converters stages, therefore you must wait

¡ATTENTION!THE HORIZONTAL POSITION OF THE LEVER MEANS SWITCH TURNED OFF, THE VERTICAL POSITION

(MOVE TO CLOCKWISE) OF THE LEVER MEANS SWITCH TURNED ON

Page 28: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 28 -

for 10 minutes before accessing to the internal pars of the equipment.

The fig. 4.3 shows the switches in OFF position:4.3.- Guided procedures.

If this menu is selected, the following operations can be done:

-UPS start up.-UPS shutdown.-Manual bypass activation.

I1 INPUT MAINSSWITCH

I4 OUTPUT UPSSWITCH

I2 INPUT BYPASSSWITCH

I3 MANUAL BYPASSSWITCH

Fig. 4.3

¡ATTENTION!All the operations described in the below paragraphs must be done by authorised electrical and/or

trained personal.

Page 29: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 29 -

-Transfer from manual bypass to normal operating mode of the UPS.Depending on the selection, the LCD panel will show all the instructions to be executed by the user to make a correctprocedure of the selected option.The user will be guided through several messages that mean all the manoeuvres that must be done with the power switchesof the UPS and the instructions in the LCD panel that must be activated.At the end of each operation, if everything has been done correctly, there will be a message confirming the right operation.

It is possible to make the above operations without applying the guided procedures; in this case, escape from the menu“GUIDED PROCEDURES” and follow the instructions of the following paragraphs.

4.4.- UPS start up instructions.

By means of this procedure the UPS achieves its normal operating mode.Before continuing, check that the system and all the electrical connections have been controlled by authorised personal andthe external power switches are closed .

Check that the MANUAL BYPASS SWITCH I3 is in OFF position and it is mechanical locked (padlocked).

BE SURE OF THAT THE PHASE ROTATIONS OF THE INPUT AND BYPASS MAINS ARE CORRECT.

See fig. 4.3 to know the meaning of each switch.

Once all the above points are checked, we will proceed to start up the system as follows:

1. Turn on the BYPASS MAINS SWITCH (RESERVE) I2.The LCD panel and the control of the UPS starts to run (to disable the guided procedures, which is proposed by default bythe UPS and to have access to the normal operating mode, press the key MENU).If the power supply of the bypass mains (reserve) is correct, the fans of the heat exchanger are turned on.

2. Turn on the OUTPUT SWITCH of UPS I4.This way, the loads connected to the OUTPUT of the UPS are fed.

3. Turn on the INPUT MAINS SWITCH I1.Wait for 10 seconds; after that the rectifier will start up with a walk-in time in order to pre-charge the internal capacitorsavoiding any overcurrent at the input mains.The LCD will show the message INVERTER SHUTDOWN.

4. Start up the inverter.By means of the menu 3. UPS COMMANDS, select the Inverter ON and press ENTER.

5. Check the transference from bypass line to inverter.Wait for 30 seconds; after that, the static switch will do the automatic transference of the load from the bypass line toinverter.Check the correct operating, by observing that the green led of the control panel is ON.

6. Battery connection.After checking that the battery connection has been done in the right polarity, turn on the SWITCH of the battery board, andit will connect the battery with the UPS.

Now the equipment is in normal operating mode, and it is able to guarantee the continuity of power supply to the LOADS.

Page 30: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 30 -

Simulate a mains failure and restore it in order to check the right operating of the UPS/Battery system.

remind you that the SYSTEM WILL NEVER BE STARTED UP WITH THE BATTERY CONNECTED. 4.5.- Instructions for transferring to manual bypass.

If for any maintenance or other reasons, the power supply of the critical loads must be done from the mains directly , byexcluding the UPS, to do operations of control or maintenance in it, follow the following steps:

1. Select the menu 3. UPS COMMANDS.Select “transfer load to bypass” and press ENTER. From now on the loads are fed from the bypass line (reserve) directly.

2. Inverter shutdown.By means of the menu 3 UPS COMMANDS, select Inverter OFF and press ENTER. By doing it, the inverter is shutdown andthe non-interrupted power supply to the loads is not guaranteed.

3. Turn on the MANUAL BYPASS I3.Remove the padlock or any other mechanical lock from the switch and turn it on.

4. Turn off the INPUT MAINS SWITCH I1.

5. Turn off the INPUT BYPASS SWITCH (RESERVE) I2.The loads are fed from the mains directly, through the manual Bypass .

6. Turn off the OUTPUT SWITCH I4.

The above operation will be done by turning off and on the input mains SWITCH.

¡ATTENTION!The described start up procedure must always be respected. In particular,

From now on the UPS doesn’t have any hazardous voltages, less in both the input /output terminals, whichare protected with a cover, and the DC and AC capacitors of the inverter, which have energy during some

minutes and to access to them a metallic panel must be removed.

Page 31: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 31 -

7. Disconnect the battery.4.6.- Instructions for transferring from manual bypass to normal running.

To restore the normal operating from the loads are supplied through the manual bypass, follow the following steps:

1. Turn on the INPUT BYPASS SWITCH (RESERVE) I2.Now, the bypass (reserve) line is checked and if it is correct, the LCD panel and the control of the UPS is activated and readyto operate.The LCD panel will be turned on automatically and will show the menu GUIDED PROCEDURES; after that, escape bypressing the key MENU.

2. Turn on the OUTPUT SWITCH I4.

3. Turn off the MANUAL BYPASS SWITCH I3.From now on, the loads are supplied from the bypass (reserve) line. Put back the mechanical lock in the manual bypassswitch I3.

4. Turn on the INPUT MAINS SWITCH I1.Wait for 10 seconds; after that the rectifier will start up with a walk-in time in order to pre-charge the internal capacitorsavoiding any overcurrent at the input mains.The LCD will show the message INVERTER SHUTDOWN.

5. Start up the inverter.By means of the menu 3. UPS COMMANDS, select the Inverter ON and press ENTER.

6. Check the transfer from bypass line to inverter.Wait for 30 seconds; after that, the static switch will do the automatic transference of the load from the bypass line toinverter.Check the correct operating, by observing that the green led of the control panel is ON.

7. Battery connection.After checking that the battery connection has been done in the right polarity, turn on the SWITCH of the battery board, and

it will connect the battery with the UPS.4.7.- Instructions for complete UPS shutdown.

If for any maintenance or other reasons, the system must be shutdown completely and leaving the loads without powersupply, follow the following steps:

1. Select the menu 3. CONTROL MODE.Select the option “transferring the load to the bypass (reserve) line” and press ENTER. The loads are fed from the bypassline (reserve) directly .

2. Inverter shutdown.By means of the menu 3 UPS COMMANDS, select Inverter OFF and press ENTER. By doing it, the inverter is shutdown and

¡ATTENTION!The battery and battery switch must always be connected to the UPS at the end of the start up procedure,

because it can cause system malfunctioning.

Page 32: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 32 -

the non-interrupted power supply to the loads is not guaranteed.3. Turn off the OUTPUT SWICTH I4.

The loads are not fed.

4. Turn off the INPUT BYPASS (RESERVE) SWITCH I2.

5. Turn off the INPUT MAINS SWITCH I1.

6. Turn off the Battery switch.4.8.- Emergency Power Off (E.P.O.).

The emergency shutdown has as a target to shutdown the UPS completely in case it is needed by turning off the staticswitch, both the one of the mains and the one of the inverter. This way, the loads are not supplied.Obviously, inside the UPS there are still hazardous voltages.

4.9.- Instructions to start up the UPS in ECONOMY mode.

This procedure must be done to put in service the UPS. It will be started up without any power supply.

Before proceeding, be sure that the system and all the electrical connections have been checked by authorised personal andthe external switches are all turned on.

Check the MANUAL BYPASS SWITCH I3 is turned OFF and mechanically locked (padlocked).

BE SURE THAT THE PHASE ROTATION OF THE INPUT AND BYPASS MAINS ARE CORRECT.

See fig. 4.3 to know the meaning of each switch.

Once the above steps are checked, the system can be started up in Economy mode as follows:

1. Turn on the INPUT BYPASS SWITCH (RESERVE) I2.The LCD panel and the control of the UPS starts to run (to disable the guided procedures, which is proposed by default bythe UPS and to have access to the normal operating mode, press the key MENU).If the power supply of the bypass mains (reserve) is correct, the fans of the heat exchanger are turned on.

2. Turn on the OUTPUT SWITCH of UPS I4.This way, the loads connected to the OUTPUT of the UPS are fed.

3. Turn on the INPUT MAINS SWITCH I1.Wait for 10 seconds; after that the rectifier will start up with a walk-in time in order to pre-charge the internal capacitorsavoiding any overcurrent at the input mains.

From now on the UPS doesn’t have any hazardous voltages, less in both the input /output terminals, whichare protected with a cover, and the DC and AC capacitors of the inverter, which have energy during some

minutes and to access to them a metallic panel must be removed.

Page 33: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 33 -

The LCD will show the message INVERTER SHUTDOWN.4. Start up the inverter.

By means of the menu 3. UPS COMMANDS, select the Inverter ON and press ENTER. Check the correct operating, byobserving that the green led of the control panel is ON.

5. Battery connection.After checking that the battery connection has been done in the right polarity, turn on the SWITCH of the battery board, andit will connect the battery with the UPS.

Now the equipment is in normal operating mode, and it is able to guarantee the continuity of power supply to the LOADS.

Simulate a mains failure and restore it in order to check the right operating of the UPS/Battery system.

The above operation will be done by turning off and on the input mains SWITCH, which is located in the upper part of the UPS.4.10.- Instructions for transferring to manual bypass in ECONOMY mode.

If for any maintenance or other reasons, the power supply of the critical loads must be done from the mains directly , byexcluding the UPS, to do operations of control or maintenance in it, follow the following steps:

1. Inverter shutdown.By means of the menu 3 UPS COMMANDS, select Inverter OFF and press ENTER. By doing it, the inverter is shutdown andthe non-interrupted power supply to the loads is not guaranteed.

2. Turn on the MANUAL BYPASS I3.Remove the padlock or any other mechanical lock from the switch and turn it on.

3. Turn off the INPUT MAINS SWITCH I1.

4. Turn off the INPUT BYPASS SWITCH (RESERVE) I2.The loads are fed from the mains directly, through the manual Bypass .

5. Turn off the OUTPUT SWITCH I4.

The described start up procedure must always be respected. In particular, remind you that the SYSTEMWILL NEVER BE STARTED UP WITH THE BATTERY CONNECTED.

Page 34: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 34 -

6. Disconnect the battery.4.11.- Instructions for transferring from manual bypass to ECONOMY mode. .

To restore the normal operating from the loads are supplied through the manual bypass, follow the following steps:

1. Turn on the INPUT BYPASS SWITCH (RESERVE) I2.Now, the bypass (reserve) line is checked and if it is correct, the LCD panel and the control of the UPS is activated and readyto operate.The LCD panel will be turned on automatically and will show the menu GUIDED PROCEDURES; after that, escape bypressing the key MENU.

2. Turn on the OUTPUT SWITCH I4.

3. Turn off the MANUAL BYPASS SWITCH I3.From now on, the loads are supplied from the bypass (reserve) line. Put back the mechanical lock in the manual bypassswitch I3.

4. Turn on the INPUT MAINS SWITCH I1.Wait for 10 seconds; after that the rectifier will start up with a walk-in time in order to pre-charge the internal capacitorsavoiding any overcurrent at the input mains. The LCD will show the message INVERTER SHUTDOWN.

5. Start up the inverter.By means of the menu 3. UPS COMMANDS, select the Inverter ON and press ENTER. Check the correct operating, byobserving that the green led of the control panel is ON.

6. Battery connection.After checking that the battery connection has been done in the right polarity, turn on the SWITCH of the battery board, and

From now on the UPS doesn’t have any hazardous voltages, less in both the input /output terminals, whichare protected with a cover, and the DC and AC capacitors of the inverter, which have energy during some

minutes and to access to them a metallic panel must be removed.

¡ATTENTION!The battery and battery switch must always be connected to the UPS at the end of the start up procedure,

because it can cause system malfunctioning.

Page 35: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 35 -

it will connect the battery with the UPS.4.12.- Instructions for complete UPS shutdown in ECONOMY mode.

If for any maintenance or other reasons, the system must be shutdown completely and leaving the loads without powersupply, follow the following steps:

1. Inverter shutdown.By means of the menu 3 UPS COMMANDS, select Inverter OFF and press ENTER. By doing it, the inverter is shutdown andthe non-interrupted power supply to the loads is not guaranteed.

2. Turn off the OUTPUT SWICTH I4.The loads are not fed.

3. Turn off the INPUT BYPASS (RESERVE) SWITCH I2.

4. Turn off the INPUT MAINS SWITCH I1.

5. Turn off the battery switch.

4.13.- Battery management of the UPS.

A part from the battery voltage and current readings, which are displayed in the menu 2. MEASUREMENTS DISPLAY, it ispossible to make a battery test without breaking the power supply to the LOADS, although they are damaged.In fact, the test controls the rectifier bridge located at the input stage to reduce the DC output voltage of the converter till thethreshold when the battery discharge starts; if it is correct, at 2 V/cell, it will start to supply current. Otherwise, there will bedisplayed an alarm “BATTERY TEST FAULT”. In this situation, call to the Service centre.

4.14.- Battery test settings.

The user can do the battery test at any moment by selecting in the menu “3.UPS COMMANDS” and pressing ENTER in“BATTERY TEST”. The test takes 30 seconds. There is the possibility to set a periodic battery test by following these steps:

1. Select the menu “PANEL SETTINGS“ by pressing ENTER.2. Select “BATTERY TEST SETTING” by pressing ENTER.

Using the arrows and ENTER, starting from the left, can be selected the weekday to make the test, the number of weeksbetween one test and the following one (from 1 to 99 – IMPORTANT: the week 0 means a non-executed automatic test) andthe timetable of day to do it.

From now on the UPS doesn’t have any hazardous voltages, less in both the input /output terminals, whichare protected with a cover, and the DC and AC capacitors of the inverter, which have energy during some

minutes and to access to them a metallic panel must be removed.

Page 36: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 36 -

5.- UPS IN PARALLEL.

5.1.- Predisposition of the system.

The installation of more than one UPS in parallel needs one or more than one distribution boards. The board type guaranteesdifferent operating levels depending on the complexity of the adopted solution. Next, it is described the standard solution,usually suggested, that guarantees the operability of the total system (fig.5.1).

It has been foreseen the cross section of all power supply cables of each equipment, the feedback cross section cable andthe battery protection.

Likewise, it is advisable to install a general bypass in the system, with a functional blocking. This blocking is needed to avoidpossible damages to the system.

The stated solution allows checking all the operations during the installation and maintenance periods of each equipment.

The general manual bypass allows isolating the complete system with no-interruption in the feeding of the loads.The complexity of the system makes that the status of each UPS must be supervised through a remote panel or SNMP. See chapter1.2.4.

Fig. 5.1

Red principal / Standardmains

Red bypass / Standard bypass

PANEL DE DISTRIBUCIÓNDISTRIBUTION PANEL

BYPASS

CargaLoad

BYPASSMantenimientoMaintenanceBYPASS

BYPASS

Línea

de BY

PASS

BYPA

SS Li

ne

ENTRADAINPUT

SALIDAOUT

BATERÍA nBATTERY n

ARM ARIO BATERÍASBATTERY CABINET

BYPASSMantenimientoMaintenanceBYPASS

BYPASS

Línea

de BY

PASS

BYPA

SS Li

ne

ENTRADAINPUT

SALIDAOUT

BATERÍA 2BATTERY 2

ARM ARIO BATERÍASBATTERY CABINET

BYPASSMantenimientoMaintenanceBYPASS

BYPASS

Línea

de BY

PASS

BYPA

SS Li

ne

ENTRADAINPUT

SALIDAOUT

BATERÍA 1BATTERY 1

ARM ARIO BATERÍASBATTERY CABINET

Page 37: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 37 -

6.- EQUIPMENT WITH FAILURES.

6.1.- Generic alarms.

In case of faults in the UPS, the screen, by default, will be replaced by one alarm message, which can be one of the following:

When the UPS has failures that can’t be solved, it is not able to guarantee the non-interrupted power supply to the loads. Therefore, it isbetter to make the EMERGENCY BYPASS manoeuvre and leave the equipment isolated and shutdown, before calling the Service andTechnical Support.

In case of parallel equipments, the UPS with faults is excluded from the parallel operation, however it must be isolated byturning off the OUTPUT SWITCH and shutting down the equipment. Next call to the Service and Technical Support.In case of temperature alarms, be sure that there is not any cooling liquid leakage (liquid level alarm in the LCD panel). In caseof liquid leakage, the equipment must be shutdown and isolated, and transferring it to maintenance bypass. Call to theService and Technical Support.

6.2.- Fire principle.

In case of fire, remind you that CO2 or dust extinguisher must be used only. The equipment must be shutdown completelyand transferred to maintenance Bypass, and the battery switch must be turned off.

In case of parallel equipments, the OUTPUT SWITCH of that UPS must be turned off immedately and the rest of the switchestoo, including the battery one.

ALARM MESSAGE CAUSE ACTION

INVERTER SHUTDOWN Initial start up Start up the inverter.Permanent overload Check the output.

OVERLOAD Continuous overload at the UPSoutput

Check the load at the UPS output and the start upthe inverter.Check that there is not any short-circuit at theoutput.

OVERLOAD BATTERY FAULT High inrush loads at the UPS output. Check the load at the UPS output and start up theinverter again.

Three frustrated attempts have beendone for transferring to inverter

BATTERY TEST FAULT Wrong battery test Check the batteries.Check the battery fuses.

LOW BATTERY ALARM Low battery voltage. The inverter willbe shutdown soon.

Shutdown the non-critical loads, which areconnected to the UPS.

STATIC SWITCH FAULT One or more phases are missed Check the SCR of the bypass.Check the external connections of the bypass.

MANUAL BYPASS ENABLED UPS in maintenanceINPUT MAINS OUT OF RANGE The switch is turned off. Check the mains voltage and the position of the

switches.BYPASS LINE OUT OF RANGE The input phase rotation is wrong. Check the bypass line voltage.

There is a mains fault. Check the phase rotation of the mains.EMERGENCY UPS SHUTDOWN The E.P.O has been activated. Restart up the UPS.

Turn on the switches and the battery fuses.Wait t ill the LCD panel is off completely.After that put the UPS on again.

BATTERY CHARGER FAULT The battery charger is faulty or notconnected.

Call to Service and Technical Support

PARALLEL COMMUNICATION DATAFAULT

The equipment has been excluded dueto lack of communicat ion.

Call to Service and Technical Support

Page 38: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 38 -

6.3.- Failures depending on the load type.

Frequently some wrong operations are attributed to the UPS, meanwhile, in fact, they are normal reaction in front of faultyloads or installations.Next, it is described the most common situations:

• The load of the UPS is still receiving power supply from the bypass mains although the inverter is running properly: Itdepends on a high inrush current, which makes a high dropping voltage, and if it is reiterated, provokes the transfer of theload to bypass.The system, after three consecutive attempts to transfer back to inverter, the static switch is blocked into the bypass linein order to protect the inverter. Therefore, the load current must be checked, and eliminate that load which makes thoseovercurrents.The reiterated inrush current can’t be higher than 2,5 times of the root mean square value.

• The OUTPUT voltage accuracy of the UPS is bad: It can be due to unbalanced loads or those loads that provokes distortion.

7.- SCHEDULED MAINTENANCE.

The UPS needs, along of its useful life, some scheduled maintenance cycles in order to maintain the reliablity of operatingand efficiency.The scheduled maintenance must be done by the UPS dealer company or by a specialised company, recommended by thedealer company.

7.1.- Yearly maintenance (or half-yearly in some critical cases).

The yearly maintenance has the following actions and checking:

• Equipment cleaning.• Interface and control PCBs cleaning.• Checking the bolt torque and the electrical connections (UPS and battery).• Checking the cooling efficiency.• Cleaning and checking the efficiency of the liquid-air exchanger.• Checking the no leakage of cooling liquid.• Checking the inverter output wave.• Checking the output voltage/frequency.• Synchronisation checking.• Signalling, alarms and E.P.O. operation checking.• LCD panel calibration with a calibrated instrument.• Checking the operating of the manual and automatic controls.• Checking the operating of the transfer circuits.• Mains failure test in the UPS to check the battery efficiency and the correct operation of the battery charger.

7.2.- Scheduled part replacement.

• In a triennial period the axial 120x12 mm and centrifugal fans must be replaced.• In a biennial period the cooling liquid must be replaced.• In four years period the power electrolytic capacitors and cooling pump must be replaced.• Every six years the power AC capacitors must be replaced .

Important: The battery replacement, will depend on the type used, therefore it will depend on the batterymanufacturer instructions.

Page 39: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 39 -

Page 40: UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series …

- 40 -

08460 PalautorderaTel. +34 93 848 24 00

[email protected]

salicru.com