UNIVERSITI TEKNIKAL MALAYSIA MELAKA THE AIRBORNE FUNGI CONTAMINANT IN LIBRARY CENTRE AT UNIVERSITI TEKNIKAL MALAYSIA MELAKA (UTeM): ASSESSMENT ON THE HVAC SYSTEM This report submitted in accordance with requirement of the Universiti Teknikal Malaysia Melaka (UTeM) for the Bachelor Degree of Engineering Technology (Refrigeration and Air-Conditioning Systems) (Hons.) by NUR ATIQAH KHAIRIAH BINTI GHAZALI B071110305 920418-04-5348 FACULTY OF ENGINEERING TECHNOLOGY 2015

UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

Embed Size (px)

Citation preview

Page 1: UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

UNIVERSITI TEKNIKAL MALAYSIA MELAKA

THE AIRBORNE FUNGI CONTAMINANT IN LIBRARY

CENTRE AT UNIVERSITI TEKNIKAL MALAYSIA

MELAKA (UTeM): ASSESSMENT ON THE HVAC SYSTEM

This report submitted in accordance with requirement of the Universiti Teknikal

Malaysia Melaka (UTeM) for the Bachelor Degree of Engineering Technology

(Refrigeration and Air-Conditioning Systems) (Hons.)

by

NUR ATIQAH KHAIRIAH BINTI GHAZALI

B071110305

920418-04-5348

FACULTY OF ENGINEERING TECHNOLOGY

2015

Page 2: UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

UNIVERSITI TEKNIKAL MALAYSIA MELAKA

BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA

TAJUK: The Airborne Fungi Contaminant in Library Centre at Universiti Teknikal Malaysia Melaka (UTeM): Assessment on the HVAC System

SESI PENGAJIAN: 2014/15 Semester 2 Saya NUR ATIQAH KHAIRIAH BINTI GHAZALI mengaku membenarkan Laporan PSM ini disimpan di Perpustakaan Universiti Teknikal Malaysia Melaka (UTeM) dengan syarat-syarat kegunaan seperti berikut:

1. Laporan PSM adalah hak milik Universiti Teknikal Malaysia Melaka dan penulis. 2. Perpustakaan Universiti Teknikal Malaysia Melaka dibenarkan membuat salinan

untuk tujuan pengajian sahaja dengan izin penulis. 3. Perpustakaan dibenarkan membuat salinan laporan PSM ini sebagai bahan

pertukaran antara institusi pengajian tinggi.

4. **Sila tandakan ( )

SULIT

TERHAD

TIDAK TERHAD

(Mengandungi maklumat yang berdarjah keselamatan atau kepentingan Malaysia sebagaimana yang termaktub dalam AKTA RAHSIA RASMI 1972)

(Mengandungi maklumat TERHAD yang telah ditentukan oleh organisasi/badan di mana penyelidikan dijalankan)

Alamat Tetap:

No. 25, Jalan AU1C/3K,

Taman Keramat Permai,

54200, Kuala Lumpur.

Tarikh: ________________________

Disahkan oleh:

Cop Rasmi: Tarikh: _______________________

** Jika Laporan PSM ini SULIT atau TERHAD, sila lampirkan surat daripada pihak berkuasa/organisasi berkenaan dengan menyatakan sekali sebab dan tempoh laporan PSM ini perlu dikelaskan sebagai SULIT atau TERHAD.

Page 3: UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

iii

DECLARATION

I hereby, declared this report entitled “The Airborne Fungi in Library Centre at

Universiti Teknikal Malaysia Melaka (UTeM): Assessment on the HVAC System”

is the results of my own research except as cited in references.

Signature : ………………………………………….

Author’s Name : …………………………………………

Date : …………………………………………

Page 4: UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

iv

APPROVAL

This report is submitted to the Faculty of Engineering Technology of UTeM as a

partial fulfillment of the requirements for the degree of Bachelor of Engineering

Technology (Refrigeration and Air-Conditioning Systems) (Hons.). The member

of the supervisory is as follow:

………………………………

(Project Supervisor)

Page 5: UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

v

ABSTRAK

Mikrob bawaan udara telah dikesan menjadi salah satu pencemaran utama yang

membawa keapada kualiti udara dalaman yang rendah. Kajian ini bertujuan untuk

menkaji tahap pencemaran kulat di dalam pusat perpustakaan kampus utama

Universiti Teknikal Malaysia Melaka (UTeM). Pencemaran udara ditentukan melalui

kaedah pemendapan dengan menggunakan Malt Extract Agar (MEA). Jumlah purate

kepekatan kulat untuk keseluruhan bangunan perpustakaan adalah 324 CFU/m³.

kepekatan kulat juga ditentukan pada setiap aras tingkat di mana, tingkat tanah

mempunyai kepekatan kulat pada 131 CFU/m³, tingkat satu dengan 695 CFU/m³ dan

tingkat dua dengan 79 CFU/m³. Dapatan ini menunjukkan bahawa pusat

perpustakaan mempunyai tahap latar belakang yang signifikan dengan pencemaran

kulat. Pemilik bangunan mestilah sedar akan status penyelenggaraan bangunan untuk

melindungi penghuni dari segi keselamatan dan masalah kesihatan.

Page 6: UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

vi

ABSTRACT

Airborne microbe has been detected to been one of major contaminant that lead to

poor indoor air quality. This study intended to investigate the level of fungal

contaminant in the library center of main campus of Universiti Teknikal Malaysia

Melaka (UTeM). The fungal contaminant is determined by using sedimentation

method with the use of Malt Extract AGAR (MEA). The total mean of concentration

of fungal for the whole library building is 324 CFU/m³. The fungal concentration

also determined in each level where ground floor has concentration of 131 CFU/m³,

first floor with 695 CFU/m³ and second floor with 79 CFU/m³. These findings

indicates that the library center do have some significant background level of fungal

contaminant. The building owner should be aware to their building maintenance

status to protect the occupant from safety and health problem.

Page 7: UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

vii

DEDICATION

This project report is dedicated to my parents and family who have supported me all

the way since the beginning of my studies.

A special feeling of gratitude to my loving parents, Ghazali B. Md Isa and Zaiton

Harun who have given me words of encouragement push me into finishing this

project report.

My sister, Siti Noor Hasanah, who always giving me advice in confronting the

problems and always give me moral support, I dedicate this project report to you.

I also dedicate this dissertation to my friends who have supported and encourage me

throughout the process. I will always appreciate all they have done, especially to my

group mate of final year project who’s always been there for me whenever I

encounter problems in completing this project.

Finally, this thesis is dedicated to all those who believe in the richness of learning

and also the people in my life who touch my heart. Without their love and support, I

would not have made it to where I am today.

Page 8: UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

viii

ACKNOWLEDGEMENT

I would never have been able to finish my project report without the guidance of my

committee members, help from my friends and support from my family.

I would like to express my deepest gratitude to my supervisor, Mr Azwan Bin Aziz

for his excellent guidance, caring, patience and providing me with an excellent

atmosphere for doing research. I would like also to thank him as he gave me facilities

to incubate my samples.

Aside from that, I would like to give appreciation to the National Institue of

Occupational Safety and Health (NIOSH) staff workers especially Miss Zuhairah and

Madam Suhaili as they give me knowledge on how to handle the sampling and

disposing of the plate.

Apart from that, I would also like to thank my friends for helping me with the

sampling and measurement of data for this project.

Lastly, I would also want to thank my parents, sisters and my brothers as they always

stay behind my back and support me with their best wishes.

Page 9: UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

ix

TABLE OF CONTENT

Abstrak v

Abstract vi

Dedication vii

Acknowledgement viii

Table of Content ix

List of Tables xii

List of Figures xiv

List Abbreviations, Symbols and Nomenclatures xv

CHAPTER 1: INTRODUCTION 1

1.1 Background of Study 1

1.2 Problem Statement 4

1.3 Objective of the Study 5

1.3.1 The Main Objective of the Study 5

1.3.2 The Specific Objective of the Study 5

1.4 Scope 6

CHAPTER 2: LITERATURE REVIEW 7

2.1 Pollutants in Indoor Environment 7

2.1.1 Bioaerosols 8

2.1.2 Fungal Concentration in Indoor Environment 9

2.1.3 Fungi 10

2.1.3.1 Taxonomy 10

2.1.3.2 Health Hazards of Indoor Fungi 12

2.1.3.3 Factor Affecting Fungal Growth 12

2.1.3.4 Microbial Air Sampling 13

2.2 Indoor Air Quality 14

2.2.1 Factors Affecting Indoor Air Quality 14

2.2.2 Temperature 16

Page 10: UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

x

2.2.3 Humidity 16

2.2.4 Air Velocity 16

2.2.5 Carbon Monoxide 17

2.2.6 Airborne Particles 17

2.2.7 Health Effects of ETS 18

2.2.8 Health Effect of SBS 18

2.2.9 Legionnaire’s Disease 19

CHAPTER 3: METHODOLOGY 20

3.1 Study Design 20

3.2 Data Collection 22

CHAPTER 4: RESULTS AND DISCUSSION 30

4.1 Descriptive Findings of the Variables 30

4.2 Physical Parameter Result 36

4.2.1 Air Temperature 36

4.2.2 Relative Humidity 37

4.2.3 Air Movement 38

4.2.4 Dust Level 39

4.2.5 Fungal Concentration 40

4.3 Selection of Statistical Test 41

4.4 Comparison of Variables with Recommended 42

Exposure Limit and Standard

4.4.1 Compliance Status 42

4.5 Relation Between Indoor Fungi Concentration With Temperature, 43

Relative Humidity, Air Velocity and Dust Level

4.6 Comparison of Fungi Concentration with Recommended 45

Maximum Exposure of Limit and standard

4.7 Association Between Fungi Concentration with Temperature, 45

Relative Humidity, Air Velocity and Dust Level

Page 11: UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

xi

CHAPTER 5: CONCLUSION AND FUTURE WORK 48

5.1 Summary of the Research 48

5.1.1 Objective of the Research 48

5.1.2 Research Methodology 49

5.1.3 Results 49

5.2 Conclusion 50

5.3 Recommendation 51

5.4 Future Works 51

REFERENCES 52

APPENDICES 57

A-1 Floor plan for Administration Unit 57

A-2 Workspace for Administration Unit 57

A-3 Floor plan for automation Unit 58

A-4 Workspace for Automation Unit 58

A-5 Floor plan for Circulation Unit 59

A-6 Workspace for Circulation Unit 59

A-7 Floor plan for Media and Referencing Unit 60

A-8 Workspace for Media and Referencing Unit 60

A-9 Floor plan for Indexing Unit 61

A-10 Workspace for Indexing Unit 61

A-11 Floor plan for Acquisition Unit 62

A-12 Workspace for Acquisition Unit 62

B-1 Walkthrough inspection checklist ICOP IAQ 2010 page 1 63

B-2 Walkthrough inspection checklist ICOP IAQ 2010 page 2 64

B-3 Walkthrough inspection checklist ICOP IAQ 2010 page 3 65

B-4 Walkthrough inspection checklist ICOP IAQ 2010 page 4 66

B-5 Walkthrough inspection checklist ICOP IAQ 2010 page 5 67

B-6 Recommended minimum number of sampling points for indoor 68

air quality assessment ICOP IAQ 2010 page 40

Page 12: UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

xii

B-7 Letter for appointment 69

B-8 Letter for appointment 70

B-9 Letter for appointment 71

B-10 Letter for appointment 72

Page 13: UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

xiii

LIST OF TABLES

3.1

3.2

List of apparatus

Acceptable range for specific physical parameters ICOP IAQ

2010

21

25

3.3

List of indoor air contaminants and the acceptable limits ICOP

IAQ (2010)

25

4.1

Descriptive data of temperature, relative humidity, dust level, air

velocity and fungi concentration

31

4.2

4.3

4.4

4.5

4.6

4.7

4.8

4.9

4.10

4.11

4.12

Descriptive data of temperature in each level and hour

Descriptive data of relative humidity in each level and hour

Descriptive data of air velocity in each level and hour

Descriptive data of dust level in each level and hour

Descriptive data of presence of fungi in each unit

Descriptive data of viable colony, mean viable, fungi

concentration and mean fungi concentration

Comparison of the variables with the ICOP standard

Descriptive data of the variables in each level

Normality test of Shapiro-Wilk

Compliance results on the variables

Correlation test between variables

31

32

32

33

33

34

34

35

41

43

44

Page 14: UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

xiv

LIST OF FIGURES

3.1 Airborne microbe sampling flow chart 24

3.2

3.3

3.4

3.5

3.6

3.7

3.8

3.9

3.10

3.11

Implemented of monitoring sequence

Sampling of fungal

Fungal growth after 5 days

Fungal growth after 5 days

Fungal growth after 5 days

Sampling of fungal

Sampling of IAQ

Sampling of IAQ

Conceptual framework of the study

Research protocol

26

27

27

27

27

27

27

27

28

29

4.1 Graph of temperature vs hours 36

4.2 Graph of relative humidity vs hours 37

4.3

4.4

4.5

4.6

Graph of air movement vs hours

Graph of dust level vs hours

Graph of fungal concentration vs units

Graph of fungal concentration vs level of floor

38

39

40

41

Page 15: UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

xv

LIST OF ABBREVIATIONS, SYMBOLS AND

NOMENCLATURE

AC - Air Conditioning

ANOVA - Analysis of Variance

BRI - Building Related Illness

CFU - Colony Forming Unit

CH2HO - Formaldehyde

CO - Carbon Monoxide

CO2 - Carbon Dioxide

COP - Code of Practice

ETS - Environmental Tobacco Smoke

F - F Test (ANOVA)

HVAC - Heating, Ventilating and Air Conditioning

IAQ - Indoor Air Quality

ICOP - Industrial Code of Practice

MEA - Malt Extract Agar

O2 - Oxygen

PM - Particulate Matter

SBS - Sick Building Syndrome

SD - Standard Deviations

TLV - Threshold Limit Value

VOC - Volatile Organic Compound

> - More than

< - Less than

Page 16: UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

1

In this chapter, introduction to this project will be briefly discussed for the

reader to get the brief idea of this whole project. The background of study of this

project will be added in this chapter, which will explain generally the topics of

this subject. The problem statements of this project study are also stated which it

explains the problem that needs to be solved and be the main reason why this

study is conducted. The objectives of this study will also be stated which

included the general and specific objectives. This chapter also explains the scope

of this study.

1.1 Background of Study

The use of air conditioning system in our daily life is a common need nowadays.

Almost every building in every country installs air conditioning system and it is used

almost throughout their day either during working hours or even in their home to

provide comfort. As Malaysia has only one season, and the climate in Malaysia is hot

and humid throughout the year, peoples in this country only need to be conditioned

with fresh air, and does not need heated air. Unlike these countries, there are

countries that consist of many more seasons up to four seasons. For this type of

condition, the people in those countries are rather to install types of air conditioning

system that could provide not just only air conditioning but also heating. This heating

INTRODUCTION

CHAPTER 1

Page 17: UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

2

of air can be used during their winter season. While, air conditioning is preferable

used during summer season.

The function of Heating Ventilating and Air Conditioning (HVAC) is to control the

temperature, humidity and also the quality of air depends on the chosen condition.

The system needs to transfer heat and moisture in and out of the air and also controls

the air pollutant either by removing it to the outside air or blending it to the

acceptable level. Exposed to a long exposure of indoor air pollution may cause health

effects to the occupants (Zainal Abidin et al., 2013). There are many types of air

pollutant that produced in the building itself, such as volatile organic compounds

(VOC), airborne microorganism, formaldehyde (CH2HO), particulate matter (PM),

radon, asbestos, and combustion gases and by-products. However, in previous

studies, it is found that airborne microbe is one of the major contaminant that

contributes to the problem of poor indoor air quality (IAQ) (Zainal Abidin et al.,

2013). Airborne contaminants can fall into categories of chemical hazards, physical

hazards, biological hazards, and ergonomic hazards. In this study, researcher will

focus into the study on biological hazard which is the level or the quantity of fungal

contaminates in air conditioning (AC) system only. In the indoor environment, we

can find a wide variety of fungi (molds, or yeasts) which includes bacteria, viruses

and amoeba (Zainal Abidin et al., 2013).

Fungal is hazardous to health as it can cause allergens which is a substance that can

cause allergic reactions, irritants, and in some case it can cause potentially toxic

substance which is mycotoxins (EPA, 2010). Allergies may happen if someone is in

contact with the fungal spore, and the allergic responses may include hay fever-type

symptoms, such as sneezing, running nose, red eyes and skin rash (dermatitis) (EPA,

2010). The types of fungi that are reported to cause allergy are Ascomycota,

Basidiomycota, or anamorphic fungi (Khan and Karuppayil, 2012). Fungi can grow

its population in any types of condition either natural or synthetic materials,

especially if they are hygroscopic or wet (Khan and Karuppayil, 2012).

People nowadays are living hectic lifestyles, where we always busy with our works

and kept working in a same place for hours. It is common for a normal person to

Page 18: UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

3

breath an amount of air ranges from 10 000 to 30 000 liter of air (Zainal Abidin et

al., 2013). Thus, it is important for us to keep and to ensure that the air we breathe is

clean from any types of pollutant that may harmful to our health. The sick building

syndrome (SBS) term is commonly used when health disturbances are related to IAQ

(Ross et al., 2004). When an environment is exposed to the indoor air pollution,

health hazards such as allergy, infections and toxicity may pose up (Khan and

Karuppayil, 2012). The most common sign of SBS is the person will feels headaches,

pressure on the head and throbbing, and feelings of tiredness (Khan and Karuppayil,

2012).

The ignorance of the duty in cleaning and checking out of the HVAC systems may

allow microbial growth, which causes rhinitis, bronchitis, pharyngitis, pneumonia,

conjunctivitis and keratitis in the users (Ross et al., 2004). These kinds of infections

may be life threatening, and to control these infections from occurring is proving to

be difficult even when air filtration is installed in places (Weaver et al., 2009). It is

estimated that over 90% of the time is spent in indoor environments in developed

countries and this may contribute to SBS (Li et al., 2007). As a preventive ways of

those unwanted problems from occurring, the government in Malaysia has develop a

guidelines of code of practice which is entitled “Code of Practice on Indoor Air

Quality” (COP-IAQ) developed on 2005 by Department of Occupational safety and

Health (DOSH) as a guideline for the building manager in managing the conditions

of the building to a suitable state with human adaptation.

Thus, the importance of this study is to create awareness on the importance of

maintaining the IAQ of a building and also preventing any SBS from occurring. This

study also been carried out to give knowledge to people out there as the study of

fungal in AC system is not many being carried out especially in the library. The

presence of books, furniture, carpets and people in the building would contribute to

the level of fungal contaminant and also the level of IAQ parameters. The purpose of

this study is to determine the airborne fungi in the HVAC system in the UTeM

Library. This study will be conducted to see the evidence of poor HVAC ducting

system that can caused fungi contaminant in the system.

Page 19: UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

4

Thus, the aim of this study is to determine the level of the airborne fungal

contaminant and IAQ parameter (air temperature, percentage of relative humidity, air

velocity, carbon dioxide, carbon monoxide, total volatile organic compound, and

suspended particulate matter) and their relationship with the poor AC ducting

system.

1.2 Problem Statement

The HVAC system is a common thing in our life nowadays, yet there are lacks of

evidence of the impact of these systems on human health (Weaver et al., 2009).

People nowadays are also lacking of awareness of the importance of conducting the

maintenance of cleaning the AC system. Lots of building with AC system installed in

is always being left without periodical or proper maintenance. Thus, when an AC

system in being left for a long time without being cleaned, some of the IAQ

parameters may cause the existence of fungal growth due to high humidity in the

system. A high humidity would cause a growth of fungi in the system. As mention

earlier, fungi are hazardous to health. A high level of dust in the air would also

contribute to health problems as dust particles could blend in the air and when

breathe it could enter the respiratory parts and lead to further health problems such as

asthma. As dust particles, fungi spores can also be flown over by the air and if

breathed in, it would cause a very crucial health problem such as allergy and fever.

The fungal growth must be prevented and the way to prevent it is that we must make

sure that the condition of the AC system must be free from any conditions that may

lead to fungal growth such as wet or leaking. Thus, this procedure must be included

in the maintenance of the AC system. The SBS may appear if the occupants of the

building are exposed too long to the hazards. Thus, the researcher will intend to

prove these two parameters which are fungal growth in the system and also IAQ

level in the building which is probably due to low maintenance of the AC ducting

system. This study is conducted in the library as the building has cooling tower

which is important for the AC system and if there is leaking, it may cause fungal

growth. Apart from that, library center has a large volume of occupant entering and

Page 20: UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

5

stay in the building for a specific time, thus making the study easier as to compare

with the time exposed to the AC system. in a study, it is also stated that the highest

fungal counts were recorded at research laboratories and library (Awad and Farag,

1999).

Thus, there is evidence saying that library is a place that has fungal growth.

According to Ambu et al. (2008) the code of practice (COP) that developed in 2005

act as a safe guard the well-being of building occupants. However, the

implementation of this COP is not mandatory, therefore, the set objectives of

developing the COP is not successfully achieved. Thus, this study is also conducted

to inform people or the building manager in the importance of maintaining the IAQ

parameters in the AC system and also in keeping the AC system in proper condition.

1.3 Objectives of the study

The objective included main and specific objective of this study. The objectives

become the main reason and the relevant why the researcher conduct this study. The

conclusion of the study would also be based on these objectives.

1.3.1 The Main Objective of the Study

To determine the level of airborne fungal contaminant along with IAQ parameter and

their relationship with the poor AC ducting system.

1.3.2 The Specific Objectives of the Study

1. To calculate the total quantity of fungi found in the UTeM’s library AC system.

Page 21: UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

6

2. To identify the IAQ parameter (air temperature, percentage of relative humidity,

air velocity, carbon dioxide, carbon monoxide, total volatile organic compound,

and suspended particulate matter) of the UTeM’s library AC system.

3. To correlate the IAQ parameters (air temperature, percentage of relative

humidity, air velocity, carbon dioxide, carbon monoxide, total volatile organic

compound, and suspended particulate matter) with the AC system and fungal

growth.

1.4 Scope

This study will focuses on the airborne fungi contaminant in Library Centre at

Universiti Teknikal Malaysia Melaka (UTeM) with Assessment on the AC system.

This library is a three floor building and has six units of working place. Thus, this

study will cover all the AC system in each floor of that building. This study involves

the data collection data of the fungal concentration. Apart from that, the researcher

will also find the IAQ parameter of the building. All the collected data will then be

compared with the Industrial Code of Practice on Indoor Air Quality (ICOP-IAQ

2010) standard to check whether the building do comply with the standard or not and

then proceed to be related to the AC system conditions. Some general question will

be asked to the occupants about their awareness of the problem as further

information for this study.

Page 22: UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

7

A literature review is a critical look at the existing research or case study that

have significant to the proposed project. The existing research, then will be

summarized, interprets and critically evaluates in order to establish current

knowledge of a subject. The literature review is done by consulting others work

in order to see and investigate the problem of the research task. Articles, books,

journals and other sources relevant to the particular issues, areas of research or

theory have been surveyed in conducting this literature review. The literature

review is important in a research because it is needed to give the reader what

knowledge and ideas have been established on topic, what the strength and

weakness of the study. The aim of the literature review is to provide a

justification of the proposed research project, indicating how it will be different

from the published study and to develop an argument or case for study based on

literature review.

2.1 Pollutants In Indoor Environments

Exposure to indoor air pollution is becoming a serious issue on public health

problems of a wide variety of nonindustrial settings such as residences, offices,

schools, hospitals and vehicles. This issue is due to that most people spending their

working time in indoor environments (Ismail et al., 2010). It is estimated that over

90% of the time is spent in indoor environments in developed countries and this may

contribute to SBS (Li et al., 2007; TSI-IAQ Handbook, 2011).

LITERATURE REVIEW

CHAPTER 2

Page 23: UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

8

According to TSI-IAQ Handbook (2011), there are several types of pollutants that

affect air quality which include biological (bacteria, fungi, viruses, molds, pollen,

animal hair, dander and excrement), chemical (cleaners, solvents, fuels, adhesives,

various combustion by-products and emissions from furnishing floor and wall

coverings), and particles and aerosols (dust, construction activities, printing,

photocopying, manufacturing processes, smoking, combustion and some chemical

actions in which vapors condense to form particles). The air pollutants in the indoor

environment or buildings, that can be found are volatile organic compound (VOC),

airborne microorganism, formaldehyde (CH2HO), particulate matter (PM), radon,

asbestos, and combustion gases, and by-products (Zainal Abidin et al., 2013). In a

previous study, it was found that various abiotic agents like dust, particulate matter,

wall coverings, synthetic paints, glue, polishes, and VOC may contribute to indoor

pollution and may cause SBS (Chao et al., 2002; Horner, 2003). In the indoor

environment, we can find a wide variety of fungi (molds, or yeasts) which includes

bacteria, viruses and amoeba (Zainal Abidin et al., 2013). Many buildings

experienced with fungal breakouts, and in previous study, it is found that this

complaint mostly occurs in libraries (Schneider, 2004).

2.1.1 Bioaerosols

The term bioaerosols defines airborne material that is or was living, such as mold,

and bacteria, parts of living organisms and animal feces (EPA, 1991). In a previous

study, the collecting samples of fungi is conducted during winter, this is due that

during this season, there is wide use of environment insulation, which probably

increases the number of bioaerosols in indoor air, coinciding with high levels of

respiratory infections (Ross et al., 2004). According to a study, biological

contaminants are often found in areas that provide food and moisture or water

(Zainal Abidin et al., 2011). Meanwhile, any other areas where dust collects may

accumulate biological contaminants or even bedding, carpet, wood material, and

furniture stuffing (Zainal Abidin et al., 2011). Huang et al., (2010) states in his study

that biological aerosols cannot be captured by filter as the particles would stuck at

Page 24: UNIVERSITI TEKNIKAL MALAYSIA MELAKAeprints.utem.edu.my/15353/1/THE AIRBORNE FUNGI...UNIVERSITI TEKNIKAL MALAYSIA MELAKA BORANG PENGESAHAN STATUS LAPORAN PROJEK SARJANA MUDA TAJUK:

9

the filter and eventually it would re-enter the air stream when the velocity of the filter

pores increase, thus increasing the drag force of the particles collected on the filter.

2.1.2 Fungal Concentration In Indoor Environment

In previous study, it is stated that fungal studies have mainly focused on spores, yeast

cells, and fragments of these propagules and hyphae that are airborne or established

from air (Adams et al., 2013). Zainal Abidin et al. (2013) found in his research that

the concentrations of total fungi in non-carpeted office at different phases of building

commissioning shows that the concentrations fell within e range of 0 till 760

CFU/m³. From his study, he also concluded that the office setting without carpet

yield low result of airborne microorganism furthermore reduce the risk of health

problems due to unwanted exposure. From Ross et al. (2004), the results of the study

shows that the genera Aspergillus and Epicoccum were found in all the air indoor

sample and air outdoor samples of the four sites (public auditorium, hospital,

company and shopping center).

From the results of a previous research, the researcher found that the reported

microbe count vary within the building levels area depending on the cleanliness from

the dust residual on that level, the outdoor and indoor air movement either

mechanical or natural and type of flooring used whether carpet or not (Zainal Abidin

et al., 2011). According to ICOP-IAQ (2010), the standards acceptable limit of

fungal concentration in indoor environment is 1000 CFU/m³.

It is found that during fall and summer, both the indoor and outdoor fungal

population is the highest and lowest during winter and spring. This is because the

higher outdoor concentrations in the summer and fall may reflect higher temperatures

and humidity and causing increases in microbiological activities during these periods

(Shelton et al., 2002). The culture of fungi in a study shows that the number of fungi

colonies present was assessed the third and fifth days of incubation, and the number

of colony forming units was determined per m³ of air (CFU/m3 air) (Ross et al.,