Vitodens300 WB3A 49 66kW Service

Embed Size (px)

Citation preview

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    1/132

    VIESMANN Service instructionsfor heating engineers

    Vitodens 300Type WB3A , 49 and 66 kWGas fired wall mounted condensing boiler natural gas and LPG version

    See applicability on the last page

    VITODENS 300

    5692 550 GB 5/2004 Please keep safe

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    2/132

    Please follow these safety instructions closely to prevent accidents andmaterial losses.

    Safety instructions explained

    Danger This symbol warns against therisk of injury.

    ! Important informationThis symbol warns against therisk of material losses andenvironmental pollution.

    NoteDetails identified by the words "Note" contain additional information.

    Warranty

    All war ranty rights are void if theseservice instructions are not observed.

    Target group

    These service instructions are exclu-sively designed for qualified person-nel.Work on gas equipment must only becarried out by a registered gas fitter.Only approved contractors may mod-ify this equipment for countries other than those designated on the typeplate. That contractor will thenarrange for the relevant approval inthat country.Electrical work must only be carriedout by a qualified electrician.The system must be commissioned bythe system installer or a qualified per-son authorised by the installer.

    Regulations

    Observe the following during servicework:& all legal instructions regarding the

    prevention of accidents,& the TRGI, TRF and special regula-

    tions, e.g. those of the BDH,& all legal instructions regarding

    environmental protection,& the Code of Practice by relevant

    trade associations and all local reg-ulations.

    If you notice a smell of gas

    Danger Escaping gas can cause explo-sions which may lead to ser-ious injury.& Do not smoke. Prevent

    naked flames and sparks.Never switch electrical lightsor equipment.

    & Open windows and doors.& Close the gas shut-off valve.& Remove all personnel from

    the danger zone.& Observe the safety regula-

    tions of your local gas sup-plier which can be found onthe gas meter.

    & Notify your heating contrac-tor from outside the building.

    Safety instructions

    2

    Safety instructions

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    3/132

    If you smell flue gas

    Danger Flue gas may lead to life-threa-tening poisoning.& Shut down the heating sys-

    tem.& Ventilate the boiler room.& Close all doors leading to the

    living space.

    Repair work

    It is not permitted to carry out repairson parts that fulfil a safety function.Use only original Viessmann spareparts, or equivalent parts that havebeen approved by Viessmann.

    Service work on the heating system

    & Isolate the system from mains sup-ply, e.g. by removing a separatefuse or by means of a mains electri-cal isolator, and check that it is nolonger 'live'.

    & Safeguard the system againstunauthorised reconnection.

    & When using gas as fuel, also closethe main gas shut-off valve and

    safeguard against unauthorisedreopening.

    Ancillary components, spare andwearing parts

    ! Important informationComponents which are nottested with the heating system,the installation of non-approved spare parts andunauthorised conversion maylead to damage to the heatingsystem, which may affect their function and limit our warranty.For conversions or replace-ments, use only original partsfrom Viessmann or those whichare approved by Viessmann.

    Safety instructions (cont.)

    3

    Safety instructions

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    4/132

    Initial start-up, inspection, maintenanceSteps - initial start-up, inspection and maintenance ..................................... 5Further details regarding the individual steps .............................................. 7

    CodingCode 1........................................................................................................ 38Code 2........................................................................................................ 42Resetting the coding to the delivered condition ........................................... 62

    Service scansService level summary ................................................................................ 63

    Temperatures, boiler coding card and brief scans ....................................... 64Checking outputs (relay test) ...................................................................... 68Scanning operating conditions and sensors ................................................ 70

    TroubleshootingCalling up fault code history ........................................................................ 73Call up current fault codes .......................................................................... 73Checking and acknowledging faults ............................................................ 75Repairs ...................................................................................................... 85

    Function descriptionConstant temperature control units ............................................................. 95Weather-compensated control units ............................................................ 96Extensions for external connections (accessory) ......................................... 98Control functions ........................................................................................ 102

    DesignsConnection and wiring diagrams internal connections .............................. 107Connection and wiring diagrams external connections.............................. 109

    Parts lists .................................................................................................. 111

    Commissioning/service reports ............................................................... 118

    Specification ............................................................................................. 124

    CertificatesDeclaration of conformity ............................................................................ 125Manufacturer's certificate according to the 1st BImSchV [Germany]............. 126

    Keyword index .......................................................................................... 127

    Index

    4

    Index

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    5/132

    For further instructions on individual steps, see pages indicated

    Commissioning steps

    Inspection steps

    Maintenance steps Page

    ! ! ! 1. Filling the heating system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2. Venting the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

    3. Venting the heating system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 4. Filling the siphon with water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 5. Checking the electrical mains connection 6. Language selection (if required) - only for the

    weather-compensated control units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 7. Setting the time and date (if required) - only for

    weather-compensated control units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 8. Checking the gas type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 9. Changing the gas type (see separate installation

    instructions) 10. Function sequence and possible faults . . . . . . . . . . . . . . . . . . . . . . . 10 11. Checking static and supply pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 12. Checking the CO 2 settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 13. Setting the max. output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 14. Checking all connections on the primary and DHW

    side for leaks 15. Checking the burner (recording values on

    page 118 of commissioning report) 16. Checking the balanced flue system for soundness

    (annular gap check) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 17. Removing the burner and checking the burner

    gasket (replace gasket every two years) . . . . . . . . . . . . . . . . . . . . . . 18 18. Checking the burner gauze assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 19. Checking and adjusting the ignition and ionisation

    electrodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    Steps - initial start-up, inspection and maintenance

    5

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    6/132

    Commissioning stepsInspection steps

    Maintenance steps Page

    ! ! ! 20. Cleaning the combustion chamber/heating

    surfaces and installing the burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 21. Checking the condensate drain and cleaning the

    siphon . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 22. Checking the neutralising system (if installed)

    23. Checking the diaphragm expansion vessel andsystem pressure

    24. Checking the function of all safety valves 25. Checking tightness of electrical connections 26. Checking all gas equipment for soundness at

    operating pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 27. Checking the ionisation current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 28. Checking the external LPG safety valve (if

    installed) 29. Matching the control unit to the heating system . . . . . . . 24 30. Connecting the control unit to the LON system

    (only for weather-compensated control units) . . . . . . . . . . 31 31. Implementing a user check (in conjunction with

    the LON system) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 32. Adjusting heating curves (only for weather-

    compensated control units) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 33. Instructing the system user . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

    34. Scanning and resetting the "Maintenance" display 37

    Steps - initial start-up, inspection and maintenanc . . . (cont.)

    6

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    7/132

    Filling the heating system1. Check the charge pressure of the

    diaphragm expansion vessel.

    2. Close the gas shut-off valve.

    3. ! Important informationUnsuitable fill water increases the level of depos-its and corrosion and may

    lead to boiler damage.& Thoroughly flush the entire

    heating system prior to fill-ing with water.

    & Only use fill water of pota-ble quality.

    & Soften fill water harder than 20 dH (3.58 mmol/l).For suitable means of water softening, see theVitotec pricelist.

    & An ant i-freeze additive sui-table for heating systemscan be mixed with the fillwater.

    Fill the heating system via the boi-ler fill & drain valve A (minimumsystem pressure > 0.8 bar).

    4. Close the boiler fill & drainvalve A .

    Further details regarding the individual steps

    7

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    8/132

    Venting the boiler 1. Close the shut-off valves on the

    heating water side.

    2. Connect the drain hose to the boiler fill & drain valve B .

    3. Open valves A and B , and ventat mains pressure, until no sound of escaping air can be heard.

    4. Close valves A and B , and openthe primary shut-off valves.

    Venting the heating system

    1. Close the gas shut-off valve andstart the control unit.

    2. Activate the venting program viacoding address 2F:1.

    NoteTo call up code 1 and for setting thecoding address, see page 38.For function and sequence of theventing program, see page 103.

    3. Check the system pressure.

    Further details regarding the individual steps (cont.)

    8

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    9/132

    Filling the siphon with water 1. Remove the retaining clip and

    siphon A .

    2. Fill the siphon with water.

    3. Fit siphon A and secure with theretaining clip.

    Language selection (if required) - only for the weather-com-pensated control units

    1. Press c .

    2. Select the required languagewith b .

    3. Confirm with d .

    Setting the time and date (if required) - only for weather-com-pensated control units

    NoteDuring commissioning, or after prolonged time out of use, it may be necessary to set the time and date.

    1. Press D .

    2. Set the correct time with a / b .

    3. Confirm with d ; Date will then bedisplayed.

    4. Set the current date with a / b .

    5. Confirm with d .

    Further details regarding the individual steps (cont.)

    9

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    10/132

    Checking the gas type

    ! Important informationThe natural gas version cannot beconverted to LPG.

    1. Enquire about the gas type andWobbe index (Wo) from your localmains gas or LPG supplier.

    Note

    In the delivered condition, Vito- dens 300 is set up for natural gas E or LPG P.Natural gas E version:The boiler can be operated in theWobbe index range 12.0 to16.1 kWh/m 3 (43.2 to 58.0 MJ/m 3 ).LPG P version:The boiler can be operated in theWobbe index range 21.4 to22.5 kWh/m 3 (76.9 to 81.0 MJ/m 3 ).

    2. Compare the gas category (gastype) and gas group with the detailson the label on the gas train andthe cap plate.

    3. If these details do not match thefuel provided, the burner must beconverted according to the detailsprovided by the mains gas or theLPG supplier.

    See separate conversion kitinstallation instructions.

    After conversion from& Natural gas E or LPG P to nat-

    ural gas LLThe boiler can be operated in theWobbe index range 10.0 to13.1 kWh/m 3 (36.0 to 47.2 MJ/ m 3 ).

    & LPG P to natural gas EThe boiler can be operated in theWobbe index range 12.0 to16.1 kWh/m 3 (43.2 to 58.0 MJ/ m 3 ).

    4. Set the gas type via codingaddress 1E at the control unit.

    NoteTo call up code 1 and for setting thecoding address, see page 38.

    5. Record the gas type in the servicereport on page 118.

    Function sequence and possible faults

    For further details regarding faults, see page 75.

    Further details regarding the individual steps (cont.)

    10

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    11/132

    Display screen RemedyControl unitissues heatdemand

    No Set value

    Yes

    Fan startsNo

    After approx .51 seconds

    Check cables andplug-in connec-tionsFault

    F9

    Yes

    Differential pres-sure sensor enables start(0.75 V acrossterminals X8.5and X8.6)

    No After approx .51 seconds

    Check fan cablesand fan plug-inconnections,check fan

    FaultE6

    YesIgnition No Fault Check the ignition

    module (controlvoltage 230 Vacross plugs X2.1and X2.2)

    F4

    Yes

    Gas combination

    valve opens

    No Fault Check the gas

    train (control vol-tage 230 V) andgas supply pres-sure

    F4

    Yes

    Further details regarding the individual steps (cont.)

    11

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    12/132

    Ionisation cur-rent builds(higher than5 A) No

    Fault Check electrodeadjustment andgas pipe for air-locks

    Symbol A F4

    Yes

    Operational bur-ner

    Stops below setboiler tempera-ture and restarts

    Check flue gassystem for sound-ness (flue gas

    recirculation),check gas flowpressure

    Checking static and supply pressure

    Danger Higher CO emissions can lead to poisoning.Measure the CO value before and after any work on gas equipment toprevent any health hazards and to ensure the perfect operational condi-tion of the system.

    Operation with LPG Flush the LPG tank twice during commissioning/replacement. Thoroughly vent the tank and gas lines after flushing.

    Further details regarding the individual steps (cont.)

    12

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    13/132

    1. Close the gas shut-off valve.

    2. Release the screw inside test nip-ple PE A on the gas combinationvalve , but do not remove, and con-nect the pressure gauge.

    3. Open the gas shut-off valve.

    4. Check the static pressure; it shouldbe a max. of 57.5 mbar. Record the

    actual value in the service report.

    5. Start up boiler.

    NoteDuring commissioning, the boiler can enter a fault state because of airlocks in the gas pipe. After approx. 5 seconds, press E toreset the burner.

    6. Check the supply (flow) pressure; itshould be& 20 mbar for natural gas,& 50 mbar for LPG.

    NoteUse suitable test equipment with aresolution of at least 0.1 mbar tomeasure the supply pressure.

    Record the actual value in the ser-vice report.Take the action shown in the table.

    Further details regarding the individual steps (cont.)

    13

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    14/132

    Supply (flow)pressure for nat-ural gas

    Supply (flow)pressure for LPG

    Remedy

    Below 17.4 mbar Below 42.5 mbar Do not start up. Notify your mains gas or LPG supplier.

    17.4 to 57.5 mbar 42.5 to57.5 mbar

    Start up boiler.

    Above 57.5 mbar Above 57.5 mbar Install a separate gas governor down-stream of the system and regulate thepressure to 20 mbar for natural gas or 50 mbar for LPG.Notify your mains gas

    or LPG supplier.

    7. Shut down the boiler, close the gasshut-off valve, remove the pressuregauge, and close test nipple Awith the screw.

    8. Open the gas shut-off valve andstart the boiler.

    Danger Gas escaping from the testnipple leads to a risk of explosion.Check test nipple A for soundness.

    Checking the CO 2 settings

    Vitodens 300 is factory-set for natural gas E or LPG P. The natural gas E versioncan be converted to natural gas LL using a conversion kit. The LPG P versioncan be converted to natural gas E or LL using a conversion kit.During commissioning or maintenance, check the CO 2 level at the boiler adap-tor.

    NoteThe MatriX burner for Vitodens 300 is preset for the entire gas group. Therefore,the burner requires no further setting or adjustment.

    Subject to the Wobbe index, the CO 2 content fluctuates between

    Further details regarding the individual steps (cont.)

    14

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    15/132

    & 6.6 to 10.0 % for natural gas E& 7.0 to 10.0 % for natural gas LL and& approx. 10.0 % for LPG P.

    Compare the actual CO 2 value with the above CO 2 value ranges for the indivi-dual gas groups (check the gas group with your mains gas or LPG supplier).If the actual CO 2 value deviates by more than 1 % for natural gas or 0.5 % for LPG, proceed as follows:& Check whether the correct gas restrictor has been installed.& Check the balanced flue system for soundness, see page 17.

    1. Connect a flue gas analyser at theflue gas aperture A on the boiler adaptor.

    2. Open the gas shut-off valve, com-mission the boiler and create a heatdemand.

    3. Select the lower rated output.

    Constant temperature control units:& Press both keys 9 and d simul-

    taneously, until the display shows1.

    Weather-compensated controlunits:& Press both keys 9 and d simul-

    taneously until the display shows"Relay test".

    & With a / b in the display, select"Basic load".

    4. Check the CO 2 content. Should theactual value deviate by more than1 % from the above range, imple-ment steps from page 15 (possiblyreplace the burner).

    5. Enter actual values into the serv icereport.

    Further details regarding the individual steps (cont.)

    15

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    16/132

    6. Set the upper rated output.

    Constant temperature control units:& With a / b in the display, select

    2.

    Weather-compensated controlunits:& With a / b in the display, select

    "Full load".

    7. Check the CO 2 content. Should theactual value deviate by more than1 % from the above range, imple-ment steps from page 15 (possiblyreplace the burner).

    8. After testing, press d .

    9. Enter actual values into the servicereport.

    Setting the max. output

    NoteThe max. output can be limited for heating operation . You can limit the output via the modulation range.

    1. Start up boiler.

    2. Press both K and F simulta-neously until 100 flashes on thedisplay, (equals 100 % of the ratedoutput) and A appears. Onweather-compensated controlunits, the display additionallyshows "Max. output".

    3. With a / b select the requiredvalue in % of rated output as max.output.

    4. Confirm the set value with d .

    5. Record the settings for max. outputon the additional type plateincluded with the technical docu-mentation. Affix the type plate nextto the original type plate on top of the boiler.

    NoteThe output can also be limited for DHW loading. For this, change coding address 6F in code 2.

    Further details regarding the individual steps (cont.)

    16

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    17/132

    Checking the balanced flue system for soundness (annular gap check)

    A Combustion air aperture

    For balanced flue systems testedtogether with the gas fired wallmounted boiler, some Federal States(e.g. Northrhein-Westphalia) waivethe requirement for a soundness test(overpressure test) during commis-sioning by the flue gas inspector.For such cases we recommend that

    your heating contractor carries out asimple soundness test during theinitial start-up of your system. For this, it would be sufficient to check theCO 2 concentration in the combustionair at the annular gap in the balancedflue pipe.The flue pipe is deemed to be sound,if the CO 2 concentration of the com-bustion air is no higher than 0.2 % or the O 2 concentration is at least20.6 %.If actual CO 2 values are higher or O 2values are lower, carry out a pressuretest on the flue pipe at a static pres-sure of 200 Pa.

    Further details regarding the individual steps (cont.)

    17

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    18/132

    Removing the burner and checking the burner gasket(replace gasket every two years)

    1. Switch OFF the control unit ON/ OFF switch and the mains electricalsupply.

    2. Close the gas shut-off valve andsafeguard against reopening.

    3. Pull electrical cables from fan

    motor A , differential pressure sen-sor B , gas valve C , ionisationelectrode D , ignition electrodesE and earth F .

    4. Release gas connection pipe Gfixing screws and fittings.

    5. Release six nuts H and removethe burner.

    ! Important informationPrevent damage to the wiremesh.Never rest the burner on thegauze assembly.

    6. Check the burner gasket (see partslist) for damage.Generally, replace the burner gas-ket every two years .

    Further details regarding the individual steps (cont.)

    18

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    19/132

    Checking the burner gauze assemblyReplace the burner gauze assembly if the wire mesh is damaged.

    1. Remove electrodes A .

    2. Turn thermal insulation ring Bclockwise and remove.

    3. Release the eight Torx screws Cand remove the burner gauze

    assembly D .

    4. Remove the old gauze assemblygasket E .

    5. Insert a new burner gauze assem-bly with a new gasket, and securewith eight Torx screws.

    NoteTorque: 4.5 Nm

    6. Refit the thermal insulation ring B .

    Checking and adjusting the ignition and ionisation electro-des

    A Ionisation electrode B Ignition electrodes

    Further details regarding the individual steps (cont.)

    19

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    20/132

    1. Check the electrodes for wear andcontamination.

    2. Clean the electrodes with a smallbrush (not with a wire brush) or emery paper.

    ! Important informationWire meshdo not damage.

    3. Check all clearances. If the gapsare not as specified or the electro-des are damaged, replace andalign the electrodes together withnew gaskets. Tighten the electrodefixing screws with 2 Nm.

    Further details regarding the individual steps (cont.)

    20

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    21/132

    Cleaning the combustion chamber/heating surfaces andinstalling the burner

    1. If required, clean combustionchamber A and heatingsurfaces B with a brush or flushwith water.

    ! Important informationScratches on parts whichare in contact with flue

    gases can lead to corrosion.Only use plastic brushes andNOT wire brushes.

    Apply a solvent-/potassium-freecleaning agent if residues remain:& Remove soot deposits with alka-

    line cleaning agents with addi-tional surfactants (e.g. Fauch600).

    & Remove coatings and surfacediscolouration (yellow-brown)with slightly acidic, chloride-freecleaning agents based on phos-phoric acid (e.g. Antox 75 E).

    & Thoroughly flush with water.

    NoteFauch 600 and Antox 75 E are sup- plied by:Hebro Chemie GmbH Rostocker Strae 40 D 41199 Mnchengladbachc : Intec Bassersdorf AGGrindelstrasse 12 PostfachCH-8303 Bassersdorf

    2. Install the burner and torque nutsdiagonally with 4.5 Nm.

    Further details regarding the individual steps (cont.)

    21

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    22/132

    3. Secure the gas supply pipe with anew gasket.

    4. Check the gas connections for soundness.

    Danger Escaping gas leads to a riskof explosion.Check all fittings for sound-ness.

    5. Connect the electrical cables/leadsto each corresponding component.

    Checking the condensate drain and cleaning the siphon

    1. Check at the siphon, that the con-densate can freely drain.

    2. Remove the retaining clip and thesiphon.

    3. Clean the siphon.

    4. Fit the siphon and secure with theretaining clip.

    Checking all gas equipment for soundness at operating pres-

    sureDanger Escaping gas leads to a risk of explosion.Check gas equipment for soundness.

    Further details regarding the individual steps (cont.)

    22

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    23/132

    Checking the ionisation current

    A Adaptor line (available as acces-sory)

    B Control unit cable

    1. Remove the cable and connect thetest equipment.

    2. Set the upper rated output.

    Constant temperature control units:& Press K and d simultaneously

    for at least 2 seconds.& With a / b in the display, select

    2.

    Weather-compensated controlunits:& Press K and d simultaneously

    for at least 2 seconds.& With a / b in the display, select

    "Full load".

    NoteThe minimum ionisation current should be at least 5 A as soon asthe flame is established (approx. 2 - 3 seconds after opening the gastrain).

    3. If the ionisation current is < 5 A\;& Check the electrode gap, see

    page 19.& Check the control unit power sup-

    ply.

    4. After testing, press d .

    5. Record the actual value in the ser-vice report.

    Further details regarding the individual steps (cont.)

    23

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    24/132

    Matching the control unit to the heating systemNoteThe control unit must be matched to the system equipment. Various systemcomponents are automatically recognised by the control unit, and codes areautomatically set.& For selection of an appropriate design, see the following diagrams.& For coding steps, see page 38.

    System design 1

    With/without DHW heating with 1 heating circuit without mixer

    ! Outside temperature sensor (onlyfor weather-compensated controlunits)or

    lH Vitotrol 100 (only for constanttemperature control units)

    % Cylinder temperature sensor s Heating circuit pump

    sA Cylinder loading pump (connec-tion via external extension H1)

    sK Cylinder loading pump (connec-tion via internal extension H1 or H2)

    A Internal extension H1 or H2or External extension H1

    Further details regarding the individual steps (cont.)

    24

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    25/132

    Required coding AddressFunction relay of the internal extension: Cylinder loadingpump

    53:3

    System design 2

    With/without DHW heating with 1 heating circuit with mixer and systemseparation

    ! Outside temperature sensor ? Flow temperature sensor % Cylinder temperature sensor s Heating circuit pumpsA Cylinder loading pump (connec-

    tion via external extension H1)sK Cylinder loading pump (connec-

    tion via internal extension H1 or H2)

    lH Power supplyaVG KM BUS

    A Internal extension H1 or H2or External extension H1

    B Extension kit for 1 heating circuitwith mixer

    C Maximum temperature controller (underfloor heating)

    D Heating circuit pump (sec-ondary)

    E Heating circuit pump (primary)F Heat exchanger for system

    separationG Expansion vessel

    Further details regarding the individual steps (cont.)

    25

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    26/132

    Required coding Address1 heating circuit with mixer & with DHW cylinder 00:4& without DHW cylinder 00:3Function relay of the internal extension: Cylinder loadingpump

    53:3

    System design 3

    With/without DHW heating with low loss header, 1 heating circuit withoutmixer and 1 heating circuit with mixer

    ! Outside temperature sensor ? Flow temperature sensor % Cylinder temperature sensor s Heating circuit pump or boiler

    circuit pumpsA Cylinder loading pump (connec-

    tion via external extension H1)lH Power supplyaVG KM BUS

    A External extension H1B Low loss header C Extension kit for 1 heating circuit

    with mixer D Maximum temperature controller

    (underfloor heating)

    Further details regarding the individual steps (cont.)

    26

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    27/132

    E Heating circuit pump heating cir-cuit with mixer F Heating circuit pump heating cir-

    cuit without mixer (connectionvia external extension H1)

    Required coding Address

    Further details regarding the individual steps (cont.)

    27

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    28/132

    System design 4

    With/without DHW heating with 3 or more heating circuits with mixer andlow loss header

    ! Outside temperature sensor ? Flow temperature sensor % Cylinder temperature sensor s Heating circuit pump or boiler cir-

    cuit pumpsA Cylinder loading pump (connec-

    tion via external extension H1)

    sK Cylinder loading pump (connec-tion via internal extension H1 or H2)

    f Power supplygS Mixer motor A Internal extension H1 or H2

    or External extension H1

    B Low loss header

    Further details regarding the individual steps (cont.)

    28

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    29/132

    C Vitotronic 050D Maximum temperature controller (underfloor heating)

    E Heating circuit pumpF Mixer motor

    Required coding AddressFunction relay of the internal extension: Cylinder loadingpump

    53:3

    Further details regarding the individual steps (cont.)

    29

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    30/132

    System design 5

    Multi-boiler system with/without DHW heating with several heating circuitswith mixer and low loss header

    ! Outside temperature sensor ? Flow temperature sensor heat-

    ing circuits? / Flow temperature sensor / low

    loss header % Cylinder temperature sensor s Heating circuit pump or boiler

    circuit pumpsA Cylinder loading pump

    f Power supplygS Mixer motor aVG KM BUSA Low loss header B Vitotronic 333C Maximum temperature control-

    ler (underfloor heating system)D Heating circuit pumpE Mixer motor

    Further details regarding the individual steps (cont.)

    30

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    31/132

    Required coding AddressMulti-boiler system with Vitotronic 333 01:2

    NoteCodes for multi-boiler system, seeVitotronic 333 installation and operat- ing instructions.

    Connecting the control unit to the LON system (only for weather-compensated control units)

    The LON communication module (accessory) must be plugged in.

    Installation instructionsLON communication module

    NoteData transfer via the LON system can take 2 to 3 minutes.

    Setting up LON user numbers

    Adjust the user number via codingaddress 77 (see below).

    In a LON system, the same number cannot be allocated twice.

    Updating the LON user list

    Only possible, if all users are connected, and the control unit is encoded as faultmanager (code 79:1).

    1. Press L and d simultaneouslyfor approx. 2 seconds. User checkinitiated (see page 32).

    2. Press e . The user list is updatedafter approx. 2 minutes. User check completed.

    Single boiler system with Vitotronic 050 and Vitocom 300

    Further details regarding the individual steps (cont.)

    31

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    32/132

    Boiler controlunit Vitotronic 050 Vitotronic 050 Vitocom

    User no. 1Code 77:1

    User no. 10Code 77:10

    User no. 11Set code 77:11

    User no. 99

    Control unit isfault manager *1Code 79:1

    Control unit is notfault manager *1Code 79:0

    Control unit is notfault manager *1Code 79:0

    Control unit isfault manager

    Sent time via LONCode 7b:1

    Time received viaLONSet code 81:3

    Time received viaLONSet code 81:3

    Time receivedvia LON

    Transmit outsidetemperature viaLONSet code 97:2

    Outside tempera-ture is received viaLONSet code 97:1

    Outside tempera-ture is received viaLONSet code 97:1

    Fault monitoringLON user code9C:20

    Fault monitoringLON user code9C:20

    Fault monitoringLON user code9C:20

    Implementing a user check (in conjunction with the LON sys-tem)

    Communication with the system devices connected to the fault manager istested with a user check.Preconditions:& The control unit must be encoded as fault manager (code 79:1).& The LON user number must be encoded in all control units (see page 31).& The fault manager user list must be up to date (see page 31).

    Further details regarding the individual steps (cont.)

    32

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

    *1In each heating system, only one Vitotronic may be encoded as fault manager.

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    33/132

    A Consecutive list number B User number

    1. Press L and d simultaneouslyfor approx. 2 seconds. User checkinitiated.

    2. Select the required user with aand b .

    3. Activate checking with d ."Check " flashes until its comple-tion. The display and all key illumi-nations of the selected user flash

    for approx. 60 seconds.& "Check OK " flashes during com-

    munication between bothdevices.

    & "Check not OK " flashes if thereis no communication betweenboth devices. Check LON con-nection.

    4. For checking further users, proceedas for items 2 and 3.

    5. Press L and d simultaneouslyfor approx. 1 second. User checkcompleted.

    Adjusting heating curves (only for weather-compensatedcontrol units)

    The heating curves illustrate the rela-tionship between the outside tem-perature and the boiler water or theflow temperature. To put it simply: thelower the outside temperature, thehigher the boiler water or flow tem-perature. The room temperature,again, depends on the boiler water or the flow temperature.

    Settings in the delivered condition:& Slope = 1.4& Level = 0

    Generally, the slope of the heatingcurve lies& in the range of A for underfloor

    heating systems,& in the range of B for low tempera-

    ture heating systems (according tothe Energy Savings Order [Ger-many]).

    Further details regarding the individual steps (cont.)

    33

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    34/132

    Changing slope and level

    A Changing the slopeB Changing the level

    1. Modify the slope in code 1 with cod-ing address d3 (see page 38).Value adjustable from 0.2 to 3.5.

    2. Modify the slope in code 1 with cod-ing address d4 (see page 38).Value adjustable from 13 to +40 K.

    Further details regarding the individual steps (cont.)

    34

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    35/132

    Adjusting the set room temperature

    Standard room temperature:

    1. Select a heating circuit:& Press a .

    1 r flashes on the display.& Select heating circuit A1 (heating

    circuit without mixer):Press d .

    & Select heating circuit M2 (heating

    circuit with mixer): Press a . 2 r flashes on the display. Press d .

    Example 1: Modifying the standardroom temperature from 20 C to 26 C

    A Boiler water or flow temperaturein C

    B Outside temperature in CC Set room temperature in CD Heating circuit pump OFFE Heating circuit pump ON

    2. Adjust the set day temperature withrotary selector ts .The value will be automaticallyadopted after approx. 2 seconds. Accordingly, the heating curve isadjusted along the set room tem-perature axis, which results in mod-ified start/shutdown characteristicsof the heating circuit pumps, if theheating circuit pump logic is acti-vated.

    Further details regarding the individual steps (cont.)

    35

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    36/132

    Reduced room temperature:

    1. Select a heating circuit:& Press a .

    1 r flashes on the display.& Select heating circuit A1 (heating

    circuit without mixer):Press d .

    & Select heating circuit M2 (heatingcircuit with mixer): Press a . 2 r flashes on the display. Press d .

    Example 2: Modifying the reducedroom temperature from 5 C to 14 C.

    A Boiler water or flow temperaturein C

    B Outside temperature in CC Set room temperature in CD Heating circuit pump OFFE Heating circuit pump ON

    2. Call up the set night temperaturewith E .

    3. Change this value with a and b .

    4. Confirm the set value with d .

    Instructing the system user

    The system installer must hand the operating instructions to the system user and instruct them in the operation of the system.

    Further details regarding the individual steps (cont.)

    36

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    37/132

    Scanning and resetting the "Maintenance" displayThe red fault indicator flashes when the limits set via coding address 21 and 23have been reached. As regards the operating interface display:& For constant temperature control units, the hours run (subject to setting) or

    the given time interval and the clock symbol flashes.& For weather-compensated control units "Maintenance" flashes.

    NoteSet code 24:1 and then code 24:0, if maintenance is implemented before main- tenance is displayed; the set maintenance parameters for hours run and interval

    are then reset to 0.

    1. Press c .Maintenance scan is activated.

    2. Scan maintenance messageswith a or b .

    3. Press d , for weather-compen-sated control units also confirm thedisplay "Acknowledge: Yes"with d ."Maintenance" is cancelled fromthe display and the red fault indica-tor continues to flash.

    Note An acknowledged maintenancemessage can be redisplayed by pressing d (approx. 3 seconds).

    After maintenance has been carriedout

    1. Reset code 24:1 to 24:0.The red fault indicator is extin-guished.

    NoteIf coding address 24 is not reset, anew "Maintenance" message will be displayed on Monday at 07:00 h.

    2. If required:& Press c .& Reset burner hours run, burner

    starts and consumption (seepage 70).

    & Press c .

    Further details regarding the individual steps (cont.)

    37

    Initial start-up, inspection, maintenance

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    38/132

    Call up code 11. Press K and L simultaneously

    for approx. 2 seconds.

    2. Select the required coding addresswith a or b ; the address flashes.Confirm with d ; the value flashes.

    NoteCodes are displayed in plain text

    on weather-compensated control units. Codes, which are not rele- vant because of the equipment level of your heating system or because of settings of other codes,will not be displayed.

    3. Change this value with a and b ;confirm with d . The display brieflyshows "adopted", then the addressflashes again. Select additionaladdresses (if required) with aor b .

    4. Press K and L simultaneouslyfor approx. 1 second.

    Code 1

    38

    Coding

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    39/132

    SummaryCodes

    Coding inthe asdeliveredconditionAddress:value

    Function mode CodingchangeAddress:value

    Possible change

    System design00:1 System version 1:

    1 heating circuit withoutmixer A1, without DHWheating

    00:2 System version 1:1 heating circuit withoutmixer A1, with DHW heat-ing

    00:3 System version 2, 4, 5:1 mixer circuit M2, with-out DHW heating

    00:4 System version 2, 4, 5:1 mixer circuit M2, withDHW heating

    00:5 System version 3:1 heating circuit withoutmixer A1 and 1 mixer cir-cuit M2, without DHWheating

    00:6 System version 3:1 heating circuit withoutmixer A1, 1 mixer circuitM2 with DHW heating

    Single and multi-boiler system01:1 *1Single boiler system 01:2 Mult i-boiler system with

    Vitotronic 333Max. boiler temp.06:... Maximum limit of the

    boiler water tempera-ture, defaulted by theboiler coding card

    06:20to06:127

    Maximum limit of the boi-ler water temperaturewithin the rangesdefaulted by the boiler

    Code 1 (cont.)

    39

    Coding

    5 6 9 2 5 5 0 G B

    *1Only for constant temperature control units.

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    40/132

    Coding inthe asdeliveredconditionAddress:value

    Function mode CodingchangeAddress:value

    Possible change

    Gas type1E:0 Natural gas operation,

    defaulted by the boiler coding card

    1E:1 LPG operation, defaultedby the boiler coding card

    Venting/filling

    2F:0 Venting program dis-abled

    2F:1 Venting program enabled2F:2 Filling program enabled

    User no.77:1 LON user number 77:2

    to77:99

    LON user number, adjus-table from 1 to 99:1 - 4 = boiler 5 = cascade10 - ... = Vitotronic 05099 = Vitocom

    Note Allocate each number only once.

    DHW priority A1 A2:2 DHW cylinder prior ity

    applicable to heatingcircuit pump and mixer

    A2:0 Without cylinder prior ityfor heating circuit pump

    DHW priority M2 A2:2 DHW cylinder prior ity

    applicable to heating

    circuit pump and mixer

    A2:0 Without DHW cylinder priority applicable to

    heating circuit pump andmixer A2:1 DHW cylinder prior ity

    only applicable to mixer A2:3to A2:15

    Modulating DHW cylinder priority

    Summer econ. A1 A5:5 *1With heating circuit

    pump logic function A5:0 Without heating circuit

    pump logic function

    Code 1 (cont.)

    40

    Coding

    5 6 9 2 5 5 0 G B

    *1Only for weather-compensated control units.

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    41/132

    Coding inthe asdeliveredconditionAddress:value

    Function mode CodingchangeAddress:value

    Possible change

    Summer econ. M2 A5:5 *1With heating circuit

    pump logic function A5:0 Without heating circuit

    pump logic functionMin. flow temp. A1C5:20 Electronic limit of the

    minimum flow tempera-ture: 20 C

    C5:1

    toC5:127

    Minimum limit adjustable

    from 1 to 127 C

    Min. flow temp. M2C5:20 Electronic limit of the

    minimum flow tempera-ture: 20 C

    C5:1toC5:127

    Minimum limit adjustablefrom 1 to 127 C

    Max. flow temp. A1C6:75 *1Electronic maximum

    flow temperature limit at75 C

    C6:1toC6:127

    Maximum limit adjustablefrom 1 to 127 C

    Max. flow. temp. M2C6:75 *1Electronic maximum

    flow temperature limit at75 C

    C6:1toC6:127

    Maximum limit adjustablefrom 1 to 127 C

    Slope A1d3:14 *1Heating curve slope =

    1.4d3:2tod3:35

    Heating curve slopeadjustable from 0.2 to 3.5(see page 33)

    Slope M2d3:14 *1Heating curve slope =

    1.4d3:2to

    d3:35

    Heating curve slopeadjustable from 0.2 to 3.3

    (see page 33)Level A1d4:0 *1Heating curve level =

    0d4: 13tod4:40

    Heating curve leveladjustable from 13 to 40(see page 33)

    Level M2d4:0 *1Heating curve level =

    0d4: 13tod4:40

    Heating curve leveladjustable from 13 to 40(see page 33)

    Code 1 (cont.)

    41

    Coding

    5 6 9 2 5 5 0 G B

    *1Only for weather-compensated control units.

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    42/132

    Calling up code 21. Press L and G simultaneously

    for approx. 2 seconds; confirmwith d .

    2. Select the required coding addresswith a or b ; the address flashes.Confirm with d ; the value flashes.

    3. Change this value with a and b ;confirm with d . The display brieflyshows "adopted", then the addressflashes again. Select additionaladdresses (if required) with aor b .

    4. Press L and G simultaneouslyfor approx. 1 second.

    Overall summary

    The coding addresses are grouped in accordance with the following functionranges . The respective function range is displayed.Scroll through the ranges in the following sequence with a or b .

    Function range Coding addressesSystem design 00 and 01Boiler/burner 06 to 54DHW 56 to 73General 76 to 9FBoiler circuit (heating circuit A1 withoutmixer)

    A0 to F7

    Mixer circuit (heating circuit M2 with mixer) A0 to F7

    NoteCodes, which are not relevant because of the equipment level of your heating system or because of settings of other codes, will not be displayed.For heating systems with 1 heating circuit without mixer and 1 heating circuit with mixer, initially the possible coding addresses A0 to F7 are scrolled for theheating circuit without mixer A1, then those for the heating circuit with mixer M2.

    Code 2

    42

    Coding

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    43/132

    Codes

    Coding inthe asdeliveredconditionAddress:value

    Function mode CodingchangeAddress:value

    Possible change

    System design00:1 System design 1:

    1 heating circuit withoutmixer A1, without DHWheating

    00:2 System design 1:1 heating circuit withoutmixer A1, with DHW heat-ing

    00:3 System design 2, 4, 5:1 mixer circuit M2, with-out DHW heating

    00:4 System design 2, 4, 5:1 mixer circuit M2, withDHW heating

    00:5 System design 3:1 heating circuit without

    mixer A1 and 1 mixer cir-cuit M2, without DHWheating

    00:6 System design 3:1 heating circuit withoutmixer A1, 1 mixer circuitM2 with DHW heating

    01:1 *1Single boiler system 01:2 Mult i-boiler system withVitotronic 333

    Boiler/burner 06:... Maximum limit of the

    boiler water tempera-ture, defaulted by theboiler coding card

    06:20to06:127

    Maximum limit of the boi-ler water temperaturewithin the rangesdefaulted by the boiler

    07:1 *1Boiler number inmulti-boiler systems

    07:2to07:4

    Boiler number 2 to 4 inmulti-boiler systems

    1E:0 Natural gas operation,defaulted by the boiler coding card

    1E:1 LPG operation, defaultedby the boiler coding card

    Code 2 (cont.)

    43

    Coding

    5 6 9 2 5 5 0 G B

    *1Only for constant temperature control units.

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    44/132

    Coding inthe asdeliveredconditionAddress:value

    Function mode CodingchangeAddress:value

    Possible change

    21:0 No maintenance indica-tionBurner

    21:1to21:100

    The number of hours runbefore the burner shouldbe serviced is adjustablefrom 100 to 10000 hours(each step represents

    100 hours)23:0 No time interval for bur-

    ner maintenance23:1to23:24

    Time interval adjustablefrom 1 to 24 months

    24:0 No "Maintenance" dis-play

    24:1 "Maintenance" display(the address is automati-cally set and must bemanually reset after maintenance has beencompleted)

    25:0 *1No recognition of out-side temperature sen-sor or remotemonitoring

    25:1 Recognition of outsidetemperature sensor andfault monitoring

    28:0 No burner interval igni-tion

    28:1 The burner is forced ONonce every 24 hours

    2E:0 Without external exten-sion

    2E:1 Inc luding ex ternal exten-sion (automatical adjust-ment on connection)

    2F:0 Venting program dis-abled

    2F:1 Venting program enabled2F:2 Filling program enabled

    30:1 Internal variable speedcirculation pump (auto-matic adjustment)

    30:0 Internal circulation pumpwithout variable speed(e.g. temporarily for ser-vice)

    31:65 Set speed of the inter-nal circulation pumpwhen operated as boiler circuit pump 65 %,defaulted by the boiler coding card

    31:0to31:100

    Set speed adjustablefrom 0 to 100 %

    Code 2 (cont.)

    44

    Coding

    5 6 9 2 5 5 0 G B

    *1Only for constant temperature control units.

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    45/132

    Coding inthe asdeliveredconditionAddress:value

    Function mode CodingchangeAddress:value

    Possible change

    32:0 Signal "External lock-out" on circulationpumps: All pumps arecontrolled

    32:1to32:15

    Signal "External lockout"on circulation pumps:See the following table

    Coding Internalcircula-tion pump

    Heating cir-cuit pumpHeating cir-cuit withoutmixer

    Heating circuitpumpHeating circuitwith mixer

    Cylinder loadingpump

    0 Controlfunct.

    Control funct. Control funct. Control funct.

    1 Controlfunct.

    Control funct . Control funct. OFF

    2 Controlfunct.

    Control funct. OFF Control funct.

    3 Controlfunct.

    Control funct. OFF OFF

    4 Controlfunct.

    OFF Control funct. Control funct.

    5 Controlfunct.

    OFF Control funct. OFF

    6 Controlfunct.

    OFF OFF Control funct.

    7 Control

    funct.

    OFF OFF OFF

    8 OFF Control funct. Control funct. Control funct.9 OFF Control funct. Control funct. OFF10 OFF Control funct. OFF Control funct.11 OFF Control funct. OFF OFF12 OFF OFF Control funct. Control funct.13 OFF OFF Control funct. OFF14 OFF OFF OFF Control funct.15 OFF OFF OFF OFF

    Code 2 (cont.)

    45

    Coding

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    46/132

    Coding inthe asdeliveredconditionAddress:value

    Function mode CodingchangeAddress:value

    Possible change

    Boiler/burner 34:0 Signal "External

    demand" on circulationpumps: All pumps arecontrolled

    34:1to34:23

    Signal "External demand"on circulation pumps:See the following table

    Coding Internalcirculationpump

    Heating cir-cuit pumpHeating cir-cuit withoutmixer

    Heating cir-cuit pumpHeating cir-cuit withmixer

    Cylinder loading pump

    0 Controlfunct.

    Controlfunct.

    Control funct. Control funct.

    1 Controlfunct.

    Controlfunct.

    Control funct. OFF

    2 Controlfunct.

    Controlfunct.

    OFF Control funct.

    3 Controlfunct.

    Controlfunct.

    OFF OFF

    4 Controlfunct.

    OFF Control funct. Control funct.

    5 Controlfunct.

    OFF Control funct. OFF

    6 Controlfunct.

    OFF OFF Control funct.

    7 Controlfunct. OFF OFF OFF

    8 OFF Controlfunct.

    Control funct. Control funct.

    9 OFF Controlfunct.

    Control funct. OFF

    10 OFF Controlfunct.

    OFF Control funct.

    11 OFF Controlfunct.

    OFF OFF

    12 OFF OFF Control funct. Control funct.

    Code 2 (cont.)

    46

    Coding

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    47/132

    Coding Internalcirculationpump

    Heating cir-cuit pumpHeating cir-cuit withoutmixer

    Heating cir-cuit pumpHeating cir-cuit withmixer

    Cylinder loading pump

    13 OFF OFF Control funct. OFF14 OFF OFF OFF Control funct.15 OFF OFF OFF OFF16 ON Control

    funct.Control funct. Control funct.

    17 ON Controlfunct.

    Control funct. OFF

    18 ON Controlfunct.

    OFF Control funct.

    19 ON Controlfunct.

    OFF OFF

    20 ON OFF Control funct. Control funct.21 ON OFF Control funct. OFF22 ON OFF OFF Control funct.23 ON OFF OFF OFF

    Coding inthe asdeliveredconditionAddress:value

    Function mode CodingchangeAddress:value

    Possible change

    Boiler/burner 50:0 Alternative control

    (automatic adjustmentupon recognition of the

    operating interface)

    50:1 Constant temperaturecontrol units

    50:3 Weather-compensated

    control units52:0 Without flow tempera-ture sensor for low lossheader

    52:1 With flow temperaturesensor for low lossheader (automatic adjust-ment upon recognition)

    Code 2 (cont.)

    47

    Coding

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    48/132

    Coding inthe asdeliveredconditionAddress:value

    Function mode CodingchangeAddress:value

    Possible change

    53:1 Function relay 2 of theinternal extension:DHW circulation pump

    53:0 Function relay 2: Centralfault

    53:2 Function relay 2: Externalheating circuit pump(heating circuit without

    mixer)53:3 Function relay 2: External

    cylinder loading pump54:0 Without solar control

    unit54:1 With Vitosolic 10054:2 With Vitosolic 200 (auto-

    matic adjustment onrecognition)

    Domestic hot water 56:0 DHW temperature

    adjustable from 10 to60 C

    56:1 DHW temperature adjus-table from 10 to 95 C(only for gas fired boilers)Observe the max. per-missible DHW tempera-ture

    58:0 Without auxiliary func-tion for DHW loading

    58:1to58:95

    Input of set DHW value 2;adjustable from 1 to95 C (observe codingaddress 56)

    59:0 DHW cylinder loading:Starting point -2.5 KStopping point +2.5 K

    59:1to59:10

    Starting point adjustablefrom 1 to 10 K below theset value

    5b:0 DHW cylinder directlyconnected to the boiler 5b:1 DHW cylinder connecteddownstream of the lowloss header

    60:10 *1During DHW loading,the boiler water tem-perature is up to 20 Khigher than the setDHW temperature

    60:5to60:25

    The difference betweenthe boiler water tempera-ture and the set DHWtemperature is adjustablefrom 10 to 50 K

    Code 2 (cont.)

    48

    Coding

    5 6 9 2 5 5 0 G B

    *1Only for weather-compensated control units.

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    49/132

    Coding inthe asdeliveredconditionAddress:value

    Function mode CodingchangeAddress:value

    Possible change

    62:2 Circulation pump with 2minutes run-on time

    62:0 Circulation pump withoutrun-on

    62:1to62:15

    Run-on time adjustablefrom 1 to 15 minutes

    63:0 *1Without auxiliaryfunction for DHW load-ing

    63:1 Additional function: 1 xdaily

    63:2to63:14

    Every 2 to every 14 days

    63:15 2 x daily65:... Information regarding

    the type of diverter valve (not adjustable)

    65:0 Without diverter valve65:1 Diverter valve by Viess-

    mann65:2 Diverter valve by Wilo65:3 Diverter valve by Grund-

    fos67:40 In conjunc tion with Vito-

    solic solar control unit:Set DHW value 3

    67:0to67:60

    DHW set value adjusta-ble from 0 to 60 C

    6C:100 Set speed internal DHWloading pump 100 %

    6C:0to6C:100

    Set speed adjustablefrom 0 to 100 %

    6F:100 Max. output duringDHW loading 100 %,defaulted by the boiler

    coding card

    6F:0to6F:100

    Max. output during DHWloading adjustable from 0to 100 %

    71:0 *2DHW circulationpump: On according toDHW time program

    71:1 OFF during DHW loadingto set value 1

    71:2 ON during DHW loadingto set value 1

    72:0 *2DHW circulationpump: ON according totime program

    72:1 OFF during DHW loadingto set value 2

    72:2 ON during DHW loadingto set value 2

    Code 2 (cont.)

    49

    Coding

    5 6 9 2 5 5 0 G B

    *1Only for constant temperature control units.*2 Only for weather-compensated control units.

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    50/132

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    51/132

    Coding inthe asdeliveredconditionAddress:value

    Function mode CodingchangeAddress:value

    Possible change

    80:1 With 5 seconds' timedelay for fault message;message will be issued,if a fault persists for atleast 5 seconds

    80:0 Without time delay80:2to80:199

    Time delay adjustablefrom 10 to 995; 1 step =5 s

    81:1 Automatic summer/win-ter changeover

    81:0 Manual summer/winter changeover

    81:2 The application of theradio clock module will berecognised automatically

    81:3 Accept time via LON88 :0 Temperature display in

    Celsius88 :1 Temperature display in

    Fahrenheit90:128 Time constant for calcu-

    lating the adjusted out-side temperature21.3 hours

    90:0to90:199

    Fast (low values) or slow(high values) matching of flow temperature subjectto set value if the outsidetemperature changes;1 step = 10 min

    91:0 *1No external operatingmode changeover viaexternal extension

    91:1 External heating programchangeover applies toheating circuit withoutmixer

    91:2 External heating programchangeover applies toheating circuit with mixer

    91:3 External heating programchangeover applies toheating circuit withoutmixer and heating circuitwith mixer

    95:0 Without Vitocom 100communication inter-face

    95:1 With Vitocom 100 com-munication interface;automatic recognition

    Code 2 (cont.)

    51

    Coding

    5 6 9 2 5 5 0 G B

    *1Only for weather-compensated control units.

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    52/132

    Coding inthe asdeliveredconditionAddress:value

    Function mode CodingchangeAddress:value

    Possible change

    97:0 *1The outside tempera-ture of the sensor con-nected to the controlunit is utilised internally

    97:1 Outside temperature isadopted by the LON BUS

    97:2 The outside temperatureof the sensor connectedto the control unit will be

    utilised internally andtransmitted via LON BUSto any connected Vitotro-nic 050.

    98:1 Viessmann systemnumbers (in conjunctionwith monitoring of sev-eral systems via Vito-com 300)

    98:1to98:5

    System number adjusta-ble from 1 to 5

    9b:70 Minimum set boiler water temperature incase of externaldemand

    9b:1to9b:127

    Set temperature adjusta-ble from 1 to 127 C

    9C:20 *1Monitoring LON usersWhen there is noresponse from a user,values defaulted insidethe control unit continueto be used for a further 20 minutes. Only thenwill a fault message betriggered.

    9C:0 No monitoring9C:5to9C:60

    Time adjustable from 5 to60 minutes

    9F:8 *1Differential tempera-ture 8 K; only in con- junction with a mixer circuit

    9F:0to9F:40

    Differential temperatureadjustable from 0 to 40 K

    Boiler circuit, mixer circuit A0:0 *1Without remote con-

    trol A0:1 With Vitotrol 200 (auto-

    matic recognition) A0:2 With Vitotrol 300 (auto-

    matic recognition)

    Code 2 (cont.)

    52

    Coding

    5 6 9 2 5 5 0 G B

    *1Only for weather-compensated control units.

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    53/132

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    54/132

    Parameters Heating circuit pumpAddress A3:... ON at OFF at-9 -10 C -8 C-8 -9 C -7 C-7 -8 C -6 C-6 -7 C -5 C-5 -6 C -4 C-4 -5 C -3 C-3 -4 C -2 C-2 -3 C -1 C-1 -2 C 0 C0 -1 C 1 C1 0 C 2 C2to15

    1 Cto14 C

    3 C

    16 C

    Coding inthe asdeliveredconditionAddress:value

    Function mode CodingchangeAddress:value

    Possible change

    Boiler circuit, mixer circuit A4:0 *1With frost protection A4:1 No fros t protection,

    adjustment only possibleif code A3:-9 is selected.

    NoteWhen selecting a valuebelow 1 C there will be a

    risk of pipes outside thethermal insulation envel- ope of the house freez- ing-up. The standby mode, in particular,should be observed, e.g.during holidays.

    Code 2 (cont.)

    54

    Coding

    5 6 9 2 5 5 0 G B

    *1Only for weather-compensated control units.

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    55/132

    Coding inthe asdeliveredconditionAddress:value

    Function mode CodingchangeAddress:value

    Possible change

    A5:5 *1With heating circuitpump logic function(economy circuit): Heat-ing circuit pump OFF, if the outside temperature

    (AT) is 1 K higher thanthe set room tempera-ture (RT Set ) AT > RT Set +1 K

    A5:0 Without heating circuitpump logic function

    A5:1to A5:15

    With heating circuit pumplogic function: Heatingcircuit pump OFF, if (see

    the following table)

    Parameter addressA5:...

    With heating circuit pump logic function: Heatingcircuit pump OFF, if

    1 AT > RTSet +5 K2 AT > RTSet +4 K3 AT > RTSet +3 K4 AT > RTSet +2 K5 AT > RTSet +1 K6 AT > RTSet7to

    AT > RT Set -1 K

    15 AT > RT Set - 9 K

    Code 2 (cont.)

    55

    Coding

    5 6 9 2 5 5 0 G B

    *1Only for weather-compensated control units.

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    56/132

    Coding inthe asdeliveredconditionAddress:value

    Function mode CodingchangeAddress:value

    Possible change

    Boiler circuit, mixer circuit A6:36 *1Extended economy

    circuit inactive A6:5to A6:35

    Extended economy cir-cuit enabled, i.e. the bur-ner and heating circuitpump will be switched

    OFF, and the mixer willbe closed at a variablevalue, which is adjustablebetween 5 and 35 C plus1 C. This value is basedon the adjusted outsidetemperature, comprisingthe actual outside tem-perature and a time con-stant, which takes thecooling down of an aver-age building into consid-eration.

    A7:0 *1Without mixer econ-omy function

    A7:1 With mixer economyfunction (extended heat-ing circuit pump logic):Heating circuit pump alsoOFF, if the mixer wasclosed for longer than20 minutes. Heatingpump ON,& if the mixer changes to

    control modeor

    & after cylinder loading(for 20 min.)or

    & if there is a risk of frost.

    Code 2 (cont.)

    56

    Coding

    5 6 9 2 5 5 0 G B

    *1Only for weather-compensated control units.

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    57/132

    Coding inthe asdeliveredconditionAddress:value

    Function mode CodingchangeAddress:value

    Possible change

    A8:1 *1Heating circuit M2(mixer circuit) creates ademand for the internalcirculation pump

    A8:0 Heating circuit M2 (mixer circuit) creates nodemand for the internalcirculation pump

    A9:7 *1With pump idle per-iod: Heating circuitpump OFF in case of set value modification(by changing the oper-ating mode or changingthe set room tempera-ture)

    A9:0 *1Without pump idle per-iod

    A9:1to A9:15

    With pump idle time,adjustable from 1 to 15

    b0:0 *1With remote control:Heating mode/reducedmode: Weather-com-pensated *2

    b0:1 Heating mode: Weather-compensatedReduced mode: Withroom temperature hook-up

    b0:2 Heating mode: With roomtemperature hook-upReduced mode: Weather-compensated

    b0:3 Heating mode/reducedmode: With room tem-perature hook-up

    b2:8 With remote control unitand for the heating cir-

    cuit, heating with roomtemperature hook-upmust be encoded:Room influence factor 8*2

    b2:0 Without room influenceb2:1

    tob2:64

    Room influence factor

    adjustable from 1 to 64

    Code 2 (cont.)

    57

    Coding

    5 6 9 2 5 5 0 G B

    *1Only for weather-compensated control units.*2 Change the coding for the heating circuit without mixer A1 or for mixer circuit M2, if the

    remote control unit affects that heating circuit.

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    58/132

    Coding inthe asdeliveredconditionAddress:value

    Function mode CodingchangeAddress:value

    Possible change

    b5:0 *1With remote control:Without room tempera-ture-dependent heatingcircuit pump logic func-tion *2

    b5:1tob5:8

    Heating circuit pumplogic function - see thefollowing table

    Parameter address b5:...

    With heating circuit pump logic function: Heating cir-cuit pump OFF, if

    1: active RT Actual > RT Set + 5 K; passive RT Actual < RT Set + 4 K2: active RT Actual > RT Set + 4 K; passive RT Actual < RT Set + 3 K3: active RT Actual > RT Set + 3 K; passive RT Actual < RT Set + 2 K4: active RT Actual > RT Set + 2 K; passive RT Actual < RT Set + 1 K5: active RT Actual > RT Set + 1 K; passive RT Actual < RT Set6: active RT Actual > RT Set ; passive RT Actual < RT Set - 1 K7: active RT Actual > RT Set - 1 K; passive RT Actual < RT Set - 2 K8: active RT Actual > RT Set - 2 K; passive RT Actual < RT Set - 3 K

    Coding inthe asdeliveredconditionAddress:value

    Function mode CodingchangeAddress:value

    Possible change

    Boiler circuit, mixer circuit

    C5:20 *1

    Electronic limit of theminimum flow tempera-ture: 20 C

    C5:1toC5:127

    Minimum limit adjustablefrom 1 to 127 C

    C6:74 *1Electronic limit of themaximum flow tempera-ture: 74 C

    C6:0toC6:127

    Maximum limit adjustablefrom 1 to 127 C

    d3:14 *1Heating curve slope =1.4

    d3:2to

    Heating curve slopeadjustable from 0.2 to 3.5

    Code 2 (cont.)

    58

    Coding

    5 6 9 2 5 5 0 G B

    *1Only for weather-compensated control units.*2 Change the coding for the heating circuit without mixer A1 or for mixer circuit M2, if the

    remote control unit affects that heating circuit.

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    59/132

    Coding inthe asdeliveredconditionAddress:value

    Function mode CodingchangeAddress:value

    Possible change

    d3:35 (see page 33)d4:0 *3Heating curve level =

    0d4: 13tod4:40

    Heating curve leveladjustable from 13 to 40(see page 33)

    d5:0 *3The external operat-ing mode changeover changes the heatingprogram to "Constantoperation with reducedroom temperature"

    d5:1 The external operating

    mode changeover changes the heating pro-gram to "Constant opera-tion with standard roomtemperature"

    E1:1 *3With remote control:Set day value is adjus-table at the remote con-trol unit from 10 to30 C

    E1:0 Set day value adjustablefrom 3 to 23 C

    E1:2 Set day value adjustablefrom 17 to 37 C

    E2:50 *3With remote controlunit and for the heatingcircuit, heating withroom temperature hook-up must be encoded:No display correction of the actual room tem-perature

    E2:0toE2:49

    Display correction 5 Kor Display correction 0.1 K

    E2:51toE2:99

    Display correction +0.1 Kor Display correction +4.9 K

    E5:0 *3Without variablespeed circuit pump

    E5:1 With variable speed cir-cuit pump; automaticrecognition

    E6:65 *3Max. speed of thevariable speed pump =

    65 % of max. speed instandard mode

    E6:0toE6:100

    Maximum speed adjusta-ble from 0 to 100 % of max. speed

    E7:30 *3Min. speed of the vari-able speed pump =30 % of max. speed

    E7:0toE7:100

    Minimum speed adjusta-ble from 0 to 100 % of max. speed

    E8:1 *3Min. speed subject tothe setting in codingaddress E9

    E8:0 Speed subject to the set-ting in coding address E7

    Code 2 (cont.)

    59

    Coding

    5 6 9 2 5 5 0 G B

    *3 Only for weather-compensated control units.

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    60/132

    Coding inthe asdeliveredconditionAddress:value

    Function mode CodingchangeAddress:value

    Possible change

    E9:45 *1Speed of the variablespeed pump = 45 % of max. speed in reducedmode

    E9:0toE9:100

    Speed adjustable from 0to 100 % of max. speed

    Mixer circuit

    F1:0 Screed drying functiondisabled*1

    F1:1toF1:5

    Screed drying functionadjustable in accordancewith 5 optional tempera-ture time profiles (seepage 104)

    NoteObserve the screed dry- ing supplier's instruc- tions.

    Observe DIN 4725-2 or local regulations. Thereport to be provided bythe heating contractor must contain the follow-ing heat-up details:& Heat-up data with

    respective flow tem-peratures

    & Max. flow temperatureachieved

    & Operating conditionand outside tempera-ture during handover.

    The function continuesafter power failure or after the control unit hasbeen switched OFF. Theheating program rwwill be started, after the

    Code 2 (cont.)

    60

    Coding

    5 6 9 2 5 5 0 G B

    *1Only for weather-compensated control units.

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    61/132

    Coding inthe asdeliveredconditionAddress:value

    Function mode CodingchangeAddress:value

    Possible change

    screed-drying functionhas been completed or if the address is manuallyset to 0.

    F1:6

    toF1:15

    Constant flow tempera-

    ture 20 C

    F2:8 *2Time limit for partyoperation 8 hours or external operatingmode changeover viapush button *3

    F2:0 No time limit for partymode

    F2:1toF2:12

    Time limit adjustable from1 to 12 hours *3*3

    F5:12 Run-on time of the inter-nal circulation pump inheating mode

    F5:0 No run-on time of theinternal circulation pump

    F5:1toF5:20

    Run-on time of the inter-nal circulation pumpadjustable from 1 to20 minutes

    F6:0 *4In "DHW only" operat-ing mode, the internalcirculation pump is per-manently OFF

    F6:1toF6:24

    In "DHW only" operatingmode, the internal circu-lation pump will bestarted 1 to 24 times per day for 10 minutesrespectively

    F6:25 In "DHW only" operatingmode, the internal circu-

    lation pump is perma-nently ONF7:0 *4In "Standby mode",

    the internal circulationpump is permanentlyOFF

    F7:0 In "Standby mode", theinternal circulation pumpis permanently OFF

    F7:1to

    In "Standby mode", theinternal circulation pump

    Code 2 (cont.)

    61

    Coding

    5 6 9 2 5 5 0 G B *2 Only for weather-compensated control units.

    *3 In heating program rw , the party mode ends automatically when changing over tooperation with standard room temperature.

    *4Only for constant temperature control units.

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    62/132

    Coding inthe asdeliveredconditionAddress:value

    Function mode CodingchangeAddress:value

    Possible change

    F7:24 will be started 1 to 24times per day for 10 minutes respectively

    F7:25 *5In "Standby mode", theinternal circulation pump

    is permanently ON

    Resetting the coding to the delivered condition

    1. Press L and G simultaneouslyfor approx. 2 seconds.

    2. Press e .Confirm "Basic setting? Yes"with d .With a or b , you can select"Basic setting? Yes" or "Basic set-ting? No".

    Code 2 (cont.)

    62

    Coding

    5 6 9 2 5 5 0 G B

    *5 Only for constant temperature control units.

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    63/132

    Function Key combination Exit PageTemperatures, boiler cod-ing card and brief scans

    Press K and G simulta-neously for approx.2 seconds

    Press d 64

    Relay test Press K and d simulta-neously for approx.2 seconds

    Press d 68

    Max. output (heatingmode)

    Press K and F simulta-neously for approx.2 seconds

    Press d 16

    Operating condition Press c Press c 70Maintenance scan c (if "Maintenance"

    flashes)Press d

    Adjusting the display con-trast

    Press d and b simulta-neously; display darkens

    Press d and a simulta-neously; display becomeslighter

    Fault history Press G and d simulta-neously for approx.2 seconds

    User check (in conjunc-tion with LON system)

    Press L and d simulta-neously for approx.2 seconds

    Emissions test functionS

    Press F and E simulta-neously for approx.2 seconds

    Press Fand Esimulta-neously

    Coding level 1Plain text display

    Press K and L simulta-neously for approx.2 seconds

    Press Kand Lsimulta-neously

    38

    Coding level 2Numerical display

    Press L and G simulta-neously for approx.2 seconds

    Press Land Gsimulta-neously

    42

    Max. output in heatingmode

    Press K and F simulta-neously for approx.2 seconds

    Press Kand Fsimulta-neously

    16

    Service level summary

    63

    Service scans

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    64/132

    Weather-compensated control units1. For two heating circuits select

    heating circuit:& Press a .

    1 r flashes on the display.& Select heating circuit A1 (heating

    circuit without mixer):Press d .

    & Select heating circuit M2 (heatingcircuit with mixer):

    Press a . 2 r flashes on the display. Press d .

    2. Press K and G simultaneouslyfor approx. 2 seconds.

    3. Select the required scan with aand b .

    4. Press d .

    The following values can be scanned, subject to the actual equipment level:

    & Slope A1 Level A1& Slope M2 Level M2& Adj . outside temp.& Outside temp., actual

    The adjusted outside temperature can be reset

    to the current outside temperature with e .& Boiler temp., set& Boiler temp., actual& DHW temp., set& DHW temp., actual& DHW outlet temp., actual& DHW outlet temp., set& Flow temperature, set& Flow temperature, actual

    Heating circuit with mixer Heating circuit with mixer

    & Mixed flow temp., set& Mixed flow temp., actual

    Low loss header Low loss header

    & Boiler coding card& Brief scan 1

    toBrief scan 8

    Temperatures, boiler coding card and brief scans

    64

    Service scans

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    65/132

    Display screenBrief scan

    Boiler codingcard

    N/A N/A X X X X

    1 Software versionControl unit

    VersionBoiler (EEPROM)

    VersionBurner control unit(EEPROM)

    2 System design 1 to

    6indication in accor-dance with the rele-vant design

    Display

    KM BUSusers

    Max. demand temperature

    3 N/A SoftwareversionPro-gram-ming unit

    SoftwareversionMixer exten-sion kit

    SoftwareversionSolar controlunit

    SoftwareversionLONsystem

    SoftwareversionExt. exten-sion

    4 Software versionBurner control unit

    TypeBurner control unit

    Boiler type

    5 0: No ext.demandor oper-atingmodechange-over 1: Ext.demandor oper-atingmodechange-over pre-sent

    0: Noext.blocking1: Ext.blockingpresent

    N/A External hook-up 0 to 10 V,displayed in %

    6 Number of LONusers

    SoftwareversionThirdpartycontrol-ler

    Max. output,displayed in %

    Temperatures, boiler coding card and brief scans (cont.)

    65

    Service scans

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    66/132

    Display screenBrief scan

    Heating circuit 1(boiler circuit A1)

    Heating circuit 2(mixer circuit M2)

    7 N/A N/A Remotecontrol0: excl.1: Vito-

    trol

    2002: Vito-trol300

    SoftwareversionRemotecontrol

    Remotecontrol0: excl.1: Vito-

    trol

    2002: Vito-trol300

    SoftwareversionRemotecontrol

    Internal circulationpump

    Heating circuit pumpboiler circuit A1

    Heating circuit pumpmixer circuit M2

    8 Variablespeedpump0: excl.1: Wilo

    2: Grun-dfos

    SoftwareversionVariablespeedpump

    Variablespeedpump0: excl.1: Wilo

    2: Grun-dfos

    SoftwareversionVariablespeedpump

    Variablespeedpump0: excl.1: Wilo

    2: Grun-dfos

    SoftwareversionVariablespeedpump

    Constant temperature control units

    1. Press K and G simultaneouslyfor approx. 2 seconds.Scanning enabled.

    2. Select the required scan with aand b .

    3. Press d .Scanning is completed.

    Temperatures, boiler coding card and brief scans (cont.)

    66

    Service scans

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    67/132

    Display screenBrief scan

    0 Systemdesign,indicationin accor-dance withthe design

    Software versionControl unit

    SoftwareversionUser inter-face

    1 Software

    versionSolar panel

    Software version

    Burner control unit

    Software

    versionExt. exten-sion

    Software

    versionCascademodule

    E 0: No ext.demand or operatingmodechange-over 1: Ext.demand or

    operatingmodechange-over pre-sent

    0: No ext.blocking1: Ext.blockingpresent

    External hook-up 0 to 10 V,displayed in %

    3 Set boiler temperature at the boiler temperature sensor

    A Highest demand temperature4 Burner control unit type Boiler type5 Set cylinder temperature at the cylin-

    der temperature sensor (currentvalue)

    b Max. heating output in %C Boiler coding card (hexa-decimal)c Version

    Equipment (EEPROM)VersionBurner control unit(EEPROM)

    Temperatures, boiler coding card and brief scans (cont.)

    67

    Service scans

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    68/132

    Display screenBrief scan

    d Variablespeedpump0: excl.1: Wilo2: Grund-

    fos

    SoftwareversionVariablespeed pump

    Checking outputs (relay test)

    Weather-compensated control units

    1. Press K and d simultaneouslyfor approx. 2 seconds.Relay test enabled.

    2. Select the relay outputs with aand b .

    3. Press d .Relay test is completed.

    Subject to the actual equipment level, the following relay outputs can be con-trolled:

    Display DescriptionBasic load Burner modulation lower outputFull load Burner modulation upper outputHeating valve Diverter valve set to heating modeValve central pos. Changeover valve in central position (fill)DHW valve Diverter valve set to DHW modeInt. pump ON Int. pump/output 20 ONClose mixer Mixer extensionOpen mixer Mixer extensionHeating circ. pump M2 ON Mixer extensionOutput int. Internal extensionHeating circ. pump A1 ON Ext. extensionCylinder loading pump ON Ext. extensionDHW circ. pump ON Ext. extensionCentral fault display ON Ext. extension

    Temperatures, boiler coding card and brief scans (cont.)

    68

    Service scans

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    69/132

    Display DescriptionSolar pump ON Vitosolic

    Constant temperature control units

    1. Press K and d simultaneouslyfor approx. 2 seconds.Relay test enabled.

    2. Select the relay outputs with aand b .

    3. Press d .Relay test enabled.

    Subject to the actual equipment level, the following relay outputs can be con-trolled:

    Display Description1 Burner modulation lower output2 Burner modulation upper output3 Diverter valve set to heating mode4 Valve in central position5 Valve set to DHW mode6 Internal pump/output 20 ON10 Output sK internal extension11 Heating circuit pump A1 external extension12 Cylinder loading pump external extension13 DHW circulation pump external extension14 Central fault external extension

    Checking outputs (relay test) (cont.)

    69

    Service scans

    5 6 9 2 5 5 0 G B

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    70/132

    Weather-compensated control units1. Select a heating circuit:

    & Press a .1 r flashes on the display.

    & Select heating circuit A1 (heatingcircuit without mixer):Press d .

    & Select heating circuit M2 (heatingcircuit with mixer): Press a . 2 r flashes on the display. Press d .

    2. Press c .

    3. Select the required operating con-dition scan with a or b .

    4. Press c .

    Heating circuits A1 and M2Operating condition display(subject to system equip-ment level)

    Description

    User no. Encoded user no. in the LON systemHoliday program Displayed only if a holiday program has been

    set upDate of departure DateDate of return DateOutside temperature, ... C Actual valueBoiler temperature, ... C Actual valueFlow temperature, ... C Actual value (only for heating circuit M2)Standardroom temperature, ... C

    Set value

    Room temperature, . .. C Actual valueExt. set room temp., ... C If external hook-upDHW temperature, ... C Actual DHW temperature

    Solar DHW temp. , . .. C Actual valueCollector temperature, ... C Actual valueMixed flow temp., ... C Actual value, only with low loss header Burner, ...h *1 Hours runBurner starts, ... *1*1 Actual valueSolar energy Displayed in kW/hTimeDate

    Scanning operating conditions and sensors

    70

    Service scans

    5 6 9 2 5 5 0 G B

    *1Reset hours run and burner starts after maintenance has been completed. You can reset the hours run to 0 by pressing e .

  • 8/10/2019 Vitodens300 WB3A 49 66kW Service

    71/132

    Operating condition display(subject to system equip-ment level)

    Description

    Burner OFF or ONInt. pump OFF or ON Output 20Int. output OFF or ON Internal extens ionHeating pump OFF or ON Ext