Spring ICC 2012 WIRING REQUIREMENTS FOR NFPA 130

(SUBWAY TUNNELS AND STATIONS) AND NFPA 502 (ROAD TUNNELS)

James Conrad Technical Manager Marmon Innovation and Technology

Page 2: Wiring Requirements

Agenda

Review NFPA 130 (Standard for Fixed Guideway Transit and Passenger Rail Systems)

Review NFPA 502 (Standard for Road Tunnels, Bridges, and Other Limited Access Highways)

Where do we go from here

Page 3: Wiring Requirements

130

NFPA 130 Standard for

Fixed Guideway Transit and

Passenger Rail Systems

2010 Edition

Page 4: Wiring Requirements

Patco Subway System

Page 5: Wiring Requirements

NFPA 130

1.2 Purpose.

The purpose of this standard shall be to establish minimum requirements that will provide a reasonable degree of safety from fire and its related hazards in fixed guideway transit and passenger rail system environments.

Page 6: Wiring Requirements

NFPA 130 4.2 Goal. 4.2.1 The goal of this standard shall be to provide an environment for occupants of fixed guideway and passenger rail system elements that is safe from fire and similar emergencies to a practical extent based on the following measures: (1) Protect occupants not intimate with the initial fire development (2) Maximize the survivability of occupants intimate

with the initial fire development

Page 7: Wiring Requirements

EURO TUNNEL FIRE 1996

Page 8: Wiring Requirements

EURO TUNNEL FIRE 1996

Page 9: Wiring Requirements

NFPA 130

Minimal Requirements Electrical Wiring Chapter 5 Stations Chapter 6 Trainways Chapter 7 Ventilations Chapter 8 Vehicles Chapter 11 Control and Communication

System Functionality, Reliability, and Availability

Page 10: Wiring Requirements

NFPA 130

Minimal Requirements Electrical Wiring All wiring shall conform to NEC

Except for traction power

Rated for 75⁰ C for fire-rated cables Rated for 90⁰ C all other cables Rated for wet location Installed in armor or raceway

Except radio antennas and ancillary area

Page 11: Wiring Requirements

NFPA 130

Minimal Requirements Electrical Wiring …listed as being resistant to the spread of

fire and shall have reduced smoke emissions NFPA 262 – Plenum test FT4/IEEE 1202 and ST-1/LS UL 1685

Page 12: Wiring Requirements

NFPA 130

Emergency Lighting, Emergency Communication and Emergency Power for Ventilation must be able to survive a fire Chapter 5 Stations Chapter 6 Trainways Chapter 7 Ventilations

Page 13: Wiring Requirements

Chapter 6 – Trainways (Tunnels) 6.3.3.2.8 The emergency lighting and communications circuits shall be protected from physical damage by system vehicles or other normal system operations and from fires in the system for a period of not less than 1 hour. The circuits shall be protected from ASTM E119 fire conditions by any of the following: (1) Suitable embedment or encasement (2) Routing external to the interior underground portions of the system facilities (3) Diversity in system routing (such as separate redundant or multiple circuits separated by a 1-hour fire barrier) so that a single fire or emergency event will not lead to a failure of the system (4) Use of a listed fire-resistive cable system with a minimum 1-hour rating in accordance with 6.3.3.2.10 (UL 2196)

Page 14: Wiring Requirements

Patco Subway System

Page 15: Wiring Requirements

502

NFPA 502 Standard for

Road Tunnels, Bridges, and

Other Limited Access Highways

2011 Edition

Page 16: Wiring Requirements
Page 17: Wiring Requirements
Page 18: Wiring Requirements

NFPA 502 Chapter 12

12.1.1 The electrical systems shall support life safety operations, fire emergency operations, and normal operations. 12.1.2 Emergency circuits installed in a road tunnel and

ancillary areas shall remain functional for a period of not less than 1 hour for the anticipated fire condition, meeting one of the following methods:

Page 19: Wiring Requirements
Page 20: Wiring Requirements
Page 21: Wiring Requirements
Page 22: Wiring Requirements

NFPA 502 Chapter 12

(1) A fire-resistive cable listed for 2 hours in accordance with ANSI/UL 2196 or other equivalent internationally recognized standards to 950°C (1742°F) when approved by the AHJ.

(2) Circuits embedded in concrete or protected by a 2-

hour fire barrier system in accordance with UL 1724. The cables or conductors shall be thermoset and shall be suitable to maintain functionality at the temperature within the embedded conduit or fire barrier system.

Page 23: Wiring Requirements

NFPA 502 Chapter 12 12.2 Wiring Methods.

12.2.1 All wiring materials and installations shall conform to NFPA 70 except as herein modified in this standard.

12.2.1.1 All cables and conductors shall be of the moisture resistant and heat-resistant types with temperature ratings that correspond to the conditions of application.

12.2.1.2 All cables and conductors shall be listed for use in wet locations.

Page 24: Wiring Requirements

NFPA 502 Chapter 12

12.2.1.3 All cables and conductors used in road tunnels shall be resistant to the spread of fire and shall have reduced smoke emissions by one of the following methods:

(1) All wires and cables shall be listed and shall comply

with the FT4/IEEE 1202 exposure requirements for cable char height, total smoke released, and peak smoke release rate of ANSI/UL 1685.

Page 25: Wiring Requirements

NFPA 502 Chapter 12

(2) Wires and cables listed as having adequate fire-resistant and low smoke-producing characteristics, by having a flame travel distance that does not exceed 1500 mm (4.9 ft), generating a maximum peak optical density of smoke of 0.5 and a maximum average optical density of smoke of 0.15 when tested in accordance with NFPA 262.

Page 26: Wiring Requirements

NFPA 502 Chapter 12

12.2.1.4 All cables and conductors used in road tunnels shall emit less than 2 percent acid gas when tested in accordance with MIL-C 24643 or in accordance with an equivalent internationally recognized standard approved by the AHJ.

Page 27: Wiring Requirements

NFPA 502 Chapter 12

12.3 Installation Methods.

12.3.1 All wiring shall be protected by means of metallic armor/sheath, metal raceway, electrical duct banks embedded in concrete …..

Page 28: Wiring Requirements

NFPA 502 Chapter 12

12.3.2 All wiring, raceways, equipment, and supports installed in a road tunnel and ancillary areas shall meet the following:

(1) PVC coatings of any type shall not be permitted on

exposed metallic armor/sheath, raceways, equipment, or supports.

Page 29: Wiring Requirements

Tunnel Wiring

NFPA 130 & 502 require cable To be listed for wet location.

Is the typical UL 12 week test enough? Be resistant to the spread of fire and shall have

reduced smoke emissions - IEEE/1202 and UL 1685 or NFPA 262

502 requires minimal acid gases Should 130 have to same requirement?

Page 30: Wiring Requirements

Tunnel Wiring

NFPA 130 & 502 cable requirements: Circuits must survive a fire.

NFPA 130 – 1 hour per UL 2196 @ 1700⁰ F NFPA 502 - 2 hour per UL 2196 @ 1850⁰ F

Is this the right test for this type of fire?

Page 31: Wiring Requirements

Where do we go from here

Long term water testing for low voltage cable? Acid gas testing – is this the right test for

conductive gas? Fire test standard that matches the fire

conditions for tunnel fires?

Page 32: Wiring Requirements

Questions