YB-O SeriesPrefabricated Secondary Substations

您贴心的配电专家Hezong power serves the world

Page 2: YB-O Series

2 1

YB-O Series

Overview .................................................................. 2Quality ...................................................................... 3Standard Compliant .................................................. 3Applications .............................................................. 4Model Name ............................................................. 4YB-O Typical Solution............................................... 5Layout Overview....................................................... 6Special Field Solution ............................................... 7Technical Parameters ............................................... 8Recommendation ..................................................... 9Medium Voltage Switchgear ................................... 10Low Voltage Switchgear ..........................................11Transformer ............................................................ 12Enclosure ............................................................... 21Typical Solution ...................................................... 22Dimension .............................................................. 27Distribution Automation Terminal ............................ 28Optional automated devices ................................... 29Foundation ............................................................. 30Transportation and Lifting ....................................... 31Inspection and Commissioning ............................... 32Maintenance and Upgrade ..................................... 32Ordering Instructions .............................................. 33

CONTENT

Page 3: YB-O Series

2 3

YB-O Series

Quality

Overview

YB-O series prefabricated secondary substation is designed in accordance with IEC62271-202 standards, which includes a distribution transformer, medium voltage switchgear, low voltage switchgear, connections and associated equipment in a compact unit. The YB-O is designed keeping in mind high levels of personal safety and aesthetics as they are often located in highly dense and urban centers.

All components are housed in an enclosure, which protects the equipment against environmental hazards and unauthorized access. The enclosure is typically divided into three sections or compartments - medium voltage switchgear, low voltage switchgear and distribution transformer.

The standard degree of protection of YB-O is IP33D, which is in accordance with IEC 60529 standards.

This YB-O can be operated in harsh environments ● Ambient temperature: -25◦C~+45◦C (extreme low up to -40◦C) ● Relative humidity: monthly average ≤ 90%, daily average ≤95% ● Altitude: ≤2000 m ● Seismic intensity: 8 degrees

YB-O is manufactured in accordance with HeZong's stringent quality and environmental (ISO 9001 and ISO 14001) standards.

Personnel safetyAll live parts in the YB-O range are protected against unintentional contact by means of lockable doors. Cable connections and fuses in the medium voltage compartment are also protected against unintentional contact. Anti-contact protection is tested in accordance with IEC62271-202. Clinched or screwed connections form electrical connections with all of the station's metal parts. The channel steel frame is bolted to the structure. The result is a fully earthed enclosure, providing a high level of personnel safety.

ProtectionThe substation is often exposed to moisture, condensation and dirt. In coastal locations, sea salt in the air which is in contact with the surface of open, insulated surfaces can cause leaking current, which can result in a flashover. Accordingly, the YB-O is designed and fabricated using material and equipment capable of withstanding harsh climatic and operational conditions.

● IEC 60071-1-2006: Insulation co-ordination - Part 1: Definitions, principles and rules

● IEC 62271-1: High-voltage switchgear and control gear - Part 1: Common specifications

● IEC 62271-100: High-voltage switchgear and control gear - Part 100: Alternating-current circuit-breakers

● IEC 62271-102: High-voltage switchgear and control gear - Part 102: Alternating current disconnectors and earthing switches

● IEC 62271-103: High-voltage switchgear and control gear - Part 103: Switches for rated voltages above 1kV up to and including 52 kV

● IEC 62271-105: High-voltage switchgear and control gear - Part 105: Alternating current switch-fuse combination for rated voltages above 1 kV up to and including 52 kV

● IEC 62271-200: 2011: High-voltage switchgear and control gear - Part 200: AC metal-enclosed switchgear and control gear for rated voltages above 1 kV and up to and including 52 kV

● IEC 62271-202: High-voltage switchgear and controlgear - Part 202: High-voltage/ low-voltage prefabricated substation

● IEC 61869-1: Instrument transformers - Part 1: General requirements

● IEC 60529: Degrees of protection provided by enclosures (IP code)

● IEC 60076-1: Power transformers - Part 1: General

● IEC 60947-1: Low-voltage switchgear and controlgear - Part 1: General rules

● IEC 62262: Degrees of protection provided by enclosures for electrical equipment against external mechanical impacts (IK code)

Standard Compliant

Page 4: YB-O Series

4 5

YB-O Series YB-O typical solutionApplications

YB-O is designed for the following applications. ● Industries ● Wind power plants ● Solar power plants ● Railways ● Commercial centers ● Urban residential complexes ● Mining and industrial applications ● In high humidity, high temperature and low temperature areas; in

environments with the risks of salt spray corrosion, chemical/industrial waste corrosion (from chemical plants, oil refining factories etc.) and also in dust prone areas.

YB-O - □ / □ - □

Maximum power(kVA)HV rated voltage(kV)LV rated voltage(kV)YB-O series prefabricated secondary substation

Model name

For example: ● YB-O - 12 / 0.4 - 800 means ● HV rated voltage : 12kV ● LV rated voltage: 0.4kV ● Transformer capacity: 800kVA

● YB-O - 24/0.4 - 1000(400) means ● HV rated voltage:24kV ● LV rated voltage:0.4kV ● Transformer capacity: 1*1000kVA and 1*400kVA

YB-O series

YB-O series

YB-O series

● One 3-way and one 4-way MV switchgear provide a hand-in-hand ring main connection

● One 2-way MV switchgear provides a terminal solution

Page 5: YB-O Series

6 7

YB-O Series Special field solution

YB-O series provides flexible layout for HV/LV/Transformer as follow:

● Non-walk-in type. Operated from the outside. Access to the foundation will be from outside of YB-O

● Walk-in type. Operated from the inside. Access to the foundation from inside YB-O

● Legend

Low voltage Medium voltage Distributionswitchgear switchgear transformer

YB-O series offer specific designs for different applications.

YB-O series street lamp solution ● Transformer capacity less than 500 kVA ● Intelligent street lamp controller, the street lamp will be automatically

adjusted according to different seasons ● Reactive compensation for LV side ● Metering function for HV side

YB-O series movable type ● Can be operated in harsh environments ● Temporary or emergency power supply ● Cable compartment inside, easily connect to source and load

YB-O series railway solution ● Two 3-way MV RMU with top mounted PT ● Two dry-type transformers ● Two sets LV switchgear with auto transfer function

Non-walk-in type A Non-walk-in type B

Accesstofoundation

Walk-in type A

Accesstofoundation

Accesstofoundation

Walk-in type B Walk-in type C

Page 6: YB-O Series

8 9

YB-O Series

Transformer capacity(kVA)

Primary current10kV/20kV(A)

HV cableHV fuse10kV/20kV(A)

Secondary current(A)

LV main breaker(A)

Capacitance compensation

Recommended capacito

Capacitor circuit current(A)

50 2.89/1.44

50mm2

10/3.15 72.17 100 7.5~15 kvar 5 kvar *2 14.4380 4.62/2.31 10/6.3 115.47 125 12~24 kvar 5 kvar *3 21.65100 5.77/2.89 16/6.3 144.34 200 15~30 kvar 10 kvar *3 43.3125 7.22/3.61 16/6.3 180.43 250 18.8~37.5 kvar 10 kvar *4 57.74160 9.24/4.62 25/10 230.95 315 24~48 kvar 10 kvar *5 72.17200 11.55/5.77 25/10 288.68 400 30~60 kvar 10 kvar *6 86.61250 14.43/7.22 25/16 360.85 630 37.5~75 kvar 15 kvar *5 108.26315 18.19/9.09 40/16 454.68 630 48~94.5 kvar 15 kvar *6 129.91400 23.1/11.55 40/25 577.37 800 60~120 kvar 15 kvar *8 173.21500 28.87/14.43 50/25 721.71 1000 75~150 kvar 15 kvar *10 216.51630 36.37/18.19 50/25 909.35 1250 94.5~189 kvar 15 kvar *12 259.82800 46.19/23.1

70mm2

80/40 1154.73 1600 120~240 kvar 15 kvar *16 346.421000 57.74/28.87 80/40 1443.42 2000 150~300 kvar 15 kvar *20 433.031250 72.17/36.09 125/50 1804.27 2500 188~375 kvar 15 kvar *24 519.63

Transformer capacity(kVA)

Primary current (A) HV cable

HV fuse(A)

Secondary current0.4kV / 0.69kV(A)

LV main breaker0.4kV / 0.69kV(A)

Capacitance compensation

Recommended capacitor

Capacitor circuit current0.4kV / 0.69kV(A)

100 1.65

35mm2

6 144.34/83.68 200/125 15~30 kvar 10 kvar *3 43.3/25.10125 2.06 10 180.43/104.60 250/200 18.8~37.5 kvar 10 kvar *4 57.74/33.47160 2.64 10 230.95/133.88 315/200 24~48 kvar 10 kvar *5 72.17/41.84200 3.30 16 288.68/167.36 400/250 30~60 kvar 10 kvar *6 86.61/50.21250 4.12 16 360.85/209.20 630/315 37.5~75 kvar 15 kvar *5 108.26/62.76315 5.20 16 454.68/263.58 630/400 48~94.5 kvar 15 kvar *6 129.91/75.31400 6.60 16 577.37/334.71 800/630 60~120 kvar 15 kvar *8 173.21/100.41500 8.24 25 721.71/418.38 1000/630 75~150 kvar 15 kvar *10 216.51/125.51630 10.40 25 909.35/527.16 1250/800 94.5~189 kvar 15 kvar *12 259.82/150.62800 13.20 25 1154.73/669.42 1600/1000 120~240 kvar 15 kvar *16 346.42/200.821000 16.48 40 1443.42/836.76 2000/1250 150~300 kvar 15 kvar *20 433.03/251.031250 20.62 40 1804.27/1045.96 2500/1600 188~375 kvar 15 kvar *24 519.63/301.24

Technical parameter

High voltage switchgear

Rated voltage 12/24kV 40.5kVRated current 630A/1250A 630ARated frequency 50Hz1min power frequency withstand voltage

Phase to phase, phase to ground 42/65kV 95kVAcross isolating distance 48/79kV 118kV

Lightning impulsewithstand voltage

Phase to phase, phase to ground 75/125kV 185kVAcross isolating distance 85/145kV 215kV

Rated short-time withstand current 20kA/4s 20kA/4sRated peak withstand current 50kA 50kAIP degree IP67(SF6 tank)/IP4X

Low voltage switchgear

Rated voltage 380V/660VRated current 100~4000ARated short-time withstand current 30kA/1sRated peak withstand current 63kARated current for feeder 10~4000AFeeder quantity l~12Reactive compensation capacity 15~30% of transformerIP degree IP30

TransformerTap changer ±2x2.5%, ±5%Connection type D,ynll or Y,yn0

Enclosure

Rated class of enclosure(Temperature rising degree) 10KRated maximum power 2500kVANoise level ≤45dBIK degree IK10IP degree IP33D

Technical Parameters Recommendation

10(20)/0.4 kV transformer

*. If transformer capacity over than 1250 kVA, please contact HeZong

35/0.4(0.69) kV transformer

Page 7: YB-O Series

10 11

YB-O Series Medium voltage switchgear

TPS6 series SF6 insulated switchgear is a completely sealed system with a stainless steel tank containing all working parts and switching functions. A sealed stainless steel tank with stable atmospheric conditions ensures reliability and safety of not only the equipment and personnel handling the equipment but also for the environment.

Transformer protectionTPS6 offers a choice between a load break switch-fuse combination or vacuum circuit breaker in combination with relay for transformer protection. The load break switch-fuse combination offers optimal protection against short circuit currents, while the circuit-breaker with relay offers better protection against low over-currents. Circuit-breaker with relay is always recommended for higher rated transformers.

Fuse-links selectionTPS6 fuses are designed and tested according to IEC 60282-1. While inserting the fuse into the canister, the striker-pin must always face outwards against the fuse holder.

The dimensions of the fuse-links can also be in accordance with DIN 43625 and the length of the fuse canister is based on the use of fuse-links with a length of 292 mm(12kV) or 442 mm(24kV) or 537mm(40.5kV).

TPS6 provides two standard protection relays for circuit breaker

ST260E Self powered relayST260E is a CT powered numerical feeder protection relay, designed for the protection of utility and industrial power systems, where auxiliary power is not available or cannot be guaranteed.

Features: ● Input from 3 phases current input for Conventional 1A or 5A CT ● Non-directional over current protection, 3 stages ● Non- directional earth-fault protection, 2 stages

ST280G advanced relayST280G is a comprehensive feeder relay for protection and measuring.

Features: ● Non-directional over current protection, 3 stages ● Non- directional earth-fault protection ● Three-phase under voltage protection ● Overload protection ● Re-close operation ● Three-phase current measurement ● Three-phase voltage measurement ● Power monitoring with P, Q, S, power factor, frequency ● RS-485 communication port

*. Other protection relay please contact HeZong

Low voltage switchgear

HDG and HGJ ● HDG and HGJ series low voltage switchgear are designed by HeZong for YB-

O. They are fixed type with modular design ● HDG is used for main incoming and feeder panels, HGJ is used for capacitor

panel ● All live parts including MCCB are mounted inside the switchgear and

instruments on the front door, the door can be opened by a special key only ● Operating from outside possible

MNS ● MNS Low voltage switchgears can be used for YB-O as LV part. They are of

the withdrawal type with a maximum of 9 feeders in one panel ● The busbar is on top of the switchgear; all live parts are mounted inside and

operated from outside ● Circuit breaker can be moved out only in open position ● Modular design provides good interchangeability

Panel mounted type ● The panel mounted type is an economic solution for low voltage part for

YB-O which is without LV enclosure and with all live parts mounted in LV compartment directly and sealed by the YB-O's door

*. Other low voltage solution please contact HeZong

Page 8: YB-O Series

12 13

YB-O Series Transformer

The YB-O can be supplied with a pre-installed transformer. Two types of transformers can be supplied; Oil-immersed transformer and dry type transformer.

There are three types of oil-immersed and two types of dry type transformers that can be used in YB-O.

Feature of oil-immersed transformer: ● Lower no-load loss ● Economy ● Corrugated cooling surfaces provide well heat dispersion ● Larger capacity

Features of dry type transformer: ● Flame retardant materials ● Smaller size, lighter ● Gas or oil free ● Intelligent cooling system ● Environment friendly

Transformer capacity (kVA)

Rated voltageConnection No-load

loss (W) Load loss (W) (75oC)

Short-circuit impedance (%)

No-load current (%)High voltage

(kV)Tap changer (%)

Low voltage (kV)

30

66.31010.511

±5%or±2×2.5%

0.40.69

Yyn0orDyn11

100 630/600

4.0

2.3

50 130 910/870 2.0

63 150 1090/1040 1.9

80 180 1310/1250 1.9

100 200 1580/1500 1.8

125 240 1890/1800 1.7

160 280 2310/2200 1.6

200 340 2730/2600 1.5

250 400 3200/3050 1.4

315 480 3830/3650 1.4

400 570 4520/4300 1.3

500 680 5410/5150 1.2

630 810 6200

4.5

1.1

800 980 7500 1.0

1000 1150 10300 1.0

1250 1360 12000 0.9

1600 1640 14500 0.8

2000 1940 178005.5

0.7

2500 2300 20500 0.6

Transformer parameters

S11-M series Oil-immersed transformer

Transformer

Page 9: YB-O Series

14 15

YB-O Series

Transformer capacity (kVA)

Rated voltageConnection No-load

loss (W) Load loss (W) (75oC)

Short-circuit impedance (%)

No-load current (%)High voltage

(kV)Tap changer (%)

Low voltage (kV)

30

10±5% or±2×2.5%

0.40.69

Yyn0orDyn11

80 630/600

4.0

0.3

50 100 910/870 0.24

80 130 1310/1250 0.22

100 150 1580/1500 0.21

160 200 2310/2200 0.19

200 240 2730/2600 0.18

250 290 3200/3050 0.17

315 340 3830/3650 0.16

400 410 4520/4300 0.16

500 480 5410/5150 0.16

630 570 6200

4.5

0.15

800 700 7500 0.15

1000 830 10300 0.14

1250 970 12000 0.13

1600 1170 14500 0.12

S13-M·RL series Oil-immersed transformer

Transformer

Transformer capacity (kVA)

Rated voltage

Connection

Class 2 Class 1No-load current (%)

Short- circuit imped ance (%)

High voltage (kV)

Tap changer (%)

Low voltage (kV)

No-load loss(W)

Load loss (W)(75oC) No-load

loss(W)

Load loss (W)(75oC)

Dyn11 YynoDyn11 Yyno

30

66.31010.5

±5%or±2×2.5%

0.40.69

Yyn0orDyn11

33 630 600 33 565 540 1.7

4.0

50 43 910 870 43 820 785 1.3

63 50 1090 1040 50 980 935 1.2

80 60 1310 1250 60 1180 1125 1.1

100 75 1580 1500 75 1420 1350 1

125 85 1890 1800 85 1700 1620 0.9

160 100 2310 2200 100 2080 1980 0.7

200 120 2730 2600 120 2455 2340 0.7

250 140 3200 3050 140 2880 2745 0.7

315 170 3830 3650 170 3445 3285 0.5

4.0400 200 4520 4300 200 4070 3870 0.5

500 240 5410 5150 240 4870 4635 0.5

630 320 6200 320 5580 0.3

4.5

800 380 7500 380 6750 0.3

1000 450 10300 450 9270 0.3

1250 530 12000 530 10800 0.2

1600 630 14500 630 13050 0.2

S(B)H15/ S(B)H16 series amorphous alloy Oil-immersed transformer

Transformer

*. Other parameter please contact HeZong

Page 10: YB-O Series

16 17

YB-O Series

SCB10 series dry type transformer

Transformer

Transformer capacity (kVA)

Rated voltageConne ction

No-load loss (W)

Load loss (W) (120oC)

Load loss (W) (75oC)

Short- circuit impeda nce (%)

No-load current (%)

Sound pressure leve (Lpadb)

High voltage (kV)

Tap changer (%)

Low voltage (kV)

30

66.36.61010.511

±5%or±2X2.5%

0.40.69

Yyn0orDyn11

190 710 620

4.0

2.3 63

50 270 1000 870 2.2 63

80 370 1380 1205 1.7 65

100 400 1570 1370 1.7 65

125 470 1850 1615 1.5 66

160 540 2130 1860 1.5 66

200 620 2530 2210 1.3 67

250 720 2760 2410 1.3 67

315 880 3470 3030 1.1 69

400 980 3990 3485 1.1 69

500 1160 4880 4260 1.1 70

630 1340 5880 5135 0.9 71

630 1300 5960 5205

6.0

0.9 71

800 1520 6960 6080 0.9 72

1000 1770 8130 7100 0.9 72

1250 2090 9690 8460 0.9 74

1600 2450 11730 10245 0.9 75

2000 3050 14450 12620 0.7 77

2500 3600 17170 14995 0.7 78

Transformer capacity (kVA)

Rated voltageConne ction

No-load loss (W)

Load loss (W) (120oC)

Load loss (W) (75oC)

Short- circuit impeda nce (%)

No-load current (%)

Sound pressure leve (Lpadb)

High voltage (kV)

Tap changer (%)

Low voltage (kV)

30

66.36.61010.511

±5%or±2X2.5%

0.40.69

Yyn0orDyn11

170 710 620

4.0

2.3 63

50 240 1000 870 2.2 63

80 330 1380 1205 1.7 65

100 360 1570 1370 1.7 65

125 420 1850 1615 1.5 66

160 480 2130 1860 1.5 66

200 550 2530 2210 1.3 67

250 640 2760 2410 1.3 67

315 790 3470 3030 1.1 69

400 880 3990 3485 1.1 69

500 1040 4880 4260 1.1 70

630 1200 5880 5135 0.9 71

630 1170 5960 5205

6.0

0.9 71

800 1360 6960 6080 0.9 72

1000 1590 8130 7100 0.9 72

1250 1880 9690 8460 0.9 74

1600 2200 11730 10245 0.9 75

2000 2740 14450 12620 0.7 77

2500 3240 17170 14995 0.7 78

SCB11 series dry type transformer

Transformer

Page 11: YB-O Series

18 19

YB-O Series

Transformer capacity(kVA)

Rated voltageConne ction

No-load loss (W)

Load loss (W) (75oC)

Short- circuit impeda nce (%)

No-load current(%)

High voltage (kV)

Tap changer (%)

Low voltage (kV)

50

20223335

±5%or±2×2.5%

0.40.69

Yyn0orDyn11

210 1270/1210

6.5

2.0

100 290 2120/2020 1.8

125 340 2500/2380 1.7

160 360 2970/2830 1.6

200 430 3500/3330 1.5

250 510 4160/3960 1.4

315 610 5010/4770 1.4

400 730 6050/5760 1.3

500 860 7280/6930 1.2

630 1040 8280 1.1

800 1230 9900 1.0

1000 1440 12150 1.0

1250 1760 14670 0.9

1600 2120 17550 0.8

24/35kV Oil-immersed transformer

Transformer

*. Other parameter please contact HeZong

Transformer capacity (kVA)

Rated voltageConne ction

No-load loss (W)

Load loss (W) Short-circuit impedance (%)

No- load current (%)

High voltage (kV)

Tap changer (%)

Low voltage (kV)

B (100oC) F (120oC) H (145oC)

50

202224

±5%or±2×2.5%

0.40.69

Yyn0orDyn11

380 1230 1300 1390

6.0

2.4

100 600 1980 2100 2250 2.2

160 750 2470 2600 2800 1.8

200 820 2950 3100 3310 1.8

250 940 3440 3600 3910 1.6

315 1080 4100 4300 4600 1.6

400 1280 4900 5100 5460 1.4

500 1500 5800 6100 6500 1.4

630 1700 6880 7200 7750 1.2

800 1950 8230 8700 9300 1.2

1000 2300 9720 10300 11000 1.0

1250 2650 11500 12150 13000 1.0

1600 3100 13780 14600 15650 1.0

2000 3600 16300 17250 18500 0.8

2500 4300 19350 20400 21800 0.8

24kV dry type transformer

Transformer

Page 12: YB-O Series

20 21

YB-O Series

Transformer capacity (kVA)

Rated voltageConne ction

No-load loss (W)

Load loss (W) Short-circuit impedance (%)

No- load current (%)

High voltage (kV)

Tap changer (%)

Low voltage (kV)

B (100oC) F (120oC) H (145oC)

50

333538.5

±5%or±2×2.5%

0.40.69

Yyn0orDyn11

500 1420 1500 1600

6.0

2.8

100 700 2080 2200 2350 2.4

160 880 2790 2960 3170 1.8

200 980 3300 3500 3750 1.8

250 1100 3750 4000 4280 1.6

315 1310 4480 4750 5080 1.6

400 1530 5360 5700 6080 1.4

500 1800 6570 7000 7450 1.4

630 2070 7650 8100 8700 1.2

800 2400 9000 9600 10250 1.2

1000 2700 10400 11000 11800 1.0

1250 3150 12700 13400 14300 0.9

1600 3600 15400 16300 17400 0.9

2000 4250 18100 19200 20500 0.9

2500 4950 21700 23000 24600 0.9

40.5kV dry type transformer

Transformer

*. Other parameter please contact HeZong

A IP33D enclosure is used for YB-O.

The materials that can be selected could be of stainless steel, cold-rolled steel plate, galvanized aluminum zinc plate or GRC.

The color can be selected from a choice of military green(RAL6005) or ice grey(RAL7032).

Features: ● Compact structure, small floor area, convenient transportation, simple to

operate ● Maze composite structure of the door make sure good ventilation and

heat dispersion ● The frame is made by channel steel and angle iron, to ensure the structure is firm ● Double-decker roof provides good heat insulation and heat preservation ● Automatic lighting device with the opening door ● All doors open outward and over than 90 degree with limiting stopper ● The door handle is covered and lockable

*.Any other requirement please contact HeZong

Enclosure

Page 13: YB-O Series

22 23

YB-O Series

Solution H01 H02Medium voltage switchgear

TPS6-KT Manual Motor operation TPS6-KKT Manual Motor operation

Single line diagram

Fuse kV/ A SFLDJ—12kV/ A

Current transformerPotential transformer

Solution H04 H05Medium voltage switchgear

TPS6-KW Manual Motor operation TPS6-KKW Manual Motor operation

Single line diagram

Fuse

Current transformerPotential transformer

Typical solution

Medium voltage switchgear typical solution

Solution H03 H04Medium voltage switchgear

TPS6-K+M+T Manual Motor operation TPS6-KT Manual Motor operation

Single line diagram

Fuse kV/ A kV/ A

Current transformer LZZBJ9

Potential transformer JDZ

Typical solution

Medium voltage switchgear typical solution

Solution H07Medium voltage switchgear

TPS6-K+M+W Manual Motor operation

Single line diagram

Fuse

Current transformer LZZBJ9

Potential transformer JDZ

Optional Optional Optional

VV

Optional Optional

Optional Optional Optional

VV

Optional

Page 14: YB-O Series

24 25

YB-O Series Typical solution

Low voltage switchgear typical solutionIncomer solution

Feeder solution

Solution L01 L02 L03 L04Low voltage switchgear Incomer Incomer Incomer Incomer

Single line diagram

Description

Incoming circuit breaker Incoming disconnector Incoming circuit breaker Incoming disconnector

Metering Incoming circuit breaker Measuring Incoming circuit breaker

Measuring Metering Measuring

Measuring

Solution L05 L06 L07 L08Low voltage switchgear Feeder Feeder Feeder Feeder

Single line diagram

Description

Feeder circuit breaker Feeder circuit breaker Feeder disconnector Feeder disconnector

Measuring Feeder circuit breaker Feeder circuit breaker

Measuring

.. .. .. ..

Solution L09 L10 L11 L12Low voltage switchgear Reactive compensation Reactive compensation Reactive compensation Reactive compensation

Single line diagram

Description

Fuse-switch-disconnector Fuse-switch-disconnector Fuse-switch-disconnector Disconnector

Measuring Measuring Measuring Measuring

Surge arrester Surge arrester Surge arrester Surge arresterMicro circuit breaker Contactor

Fuse and contactor Thermal relay Fuse intelligent switch Intelligent capacitor

Self-healing low-voltage shunt capacitor

Self-healing low-voltage shunt capacitor

Self-healing low-voltage shunt capacitor

Typical solution

Low voltage switchgear typical solutionReactive compensation solution

Page 15: YB-O Series

26 27

YB-O Series

Solution DX02Low voltage switchgear Incomer Feeder Reactive compensation

Typical single line diagram

Description

Incoming circuit breaker Feeder disconnector Disconnector

Incoming circuit breaker Feeder circuit breaker Measuring

Metering Measuring Surge arrester

Measuring Intelligent capacitor

Typical solution

Solution DX01Low voltage switchgear Incomer Feeder Reactive compensation

Typical single line diagram

Description

Incoming circuit breaker Feeder circuit breaker Disconnector

Metering Measuring Measuring

Measuring Surge arrester

Intelligent capacitor

Low voltage switchgear typical solution

Type DimensionEnclosure dimension(length x width x height)

Configuration

M01 3000 x 2000 x 2300

Maximum 630 kVA transformerMaximum 4 HV panelsLV solution: DX01Weight: 1450 kg

M02 2700 x 2000 x 2300

Maximum 630 kVA transformerMaximum 4 HV panelsLV solution: DX01Weight: 1380 kg

M03 3300 x 2400 x 2300

Maximum 1250 kVA transformerMaximum 4 HV panelsLV solution: DX01Weight: 1680 kg

M04 4100 x 2400 x 2300

Maximum 1250 kVA transformerMaximum 4 HV panelsLV solution: DX02Weight: 2000 kg

P01 3000 x 2100 x 2300

Maximum 630 kVA transformerMaximum 3 HV panelsLV solution: DX02Weight: 1420 kg

Dimension

Dimension12kV Non-walk-in type

*.24kV and 40.5kV YB-O please contact HeZong*. Walk-in type YB-O please contact HeZong

950 1300 750

2000HV TR LV

950 1300 450

2000HV TR LV

950 1550 800

2400HV TR LV

950 1550 1600

2400HV TR LV

2000 1000

1350

750

HVTR

LV

..

..

Page 16: YB-O Series

28 29

YB-O Series Distribution Automation Terminal

HZD300 series ● HZD300 series integration distr ibution automation terminal is

manufactured by HeZong ● HZD300 series distribution automation terminal provides voltage and

current measurement, digital input and output, communication port and standard protocol

● HZD300 can be used for both MV and LV switchgears

EM600 series ● EM600 series can be mounted on each module's LV panel and used as a

feeder terminal unit ● EM600 series distribution automation terminal provides voltage and

current measurement, digital input and output, communication port and standard protocol

Distribution transformer supervisory terminal unit (TTU) ● A TTU can be used for transformer real-time monitoring with P, Q, S,

power factor, frequency. Calculate distortion ratio of current harmonic ● A TTU can also provide communication function

Optional automated devices

Fault indicator ● The short-circuit and earth fault indicator is designed for distribution

network. The instrument is provided with three short-c i rcui t current transformers and one earth fault current transformer. The overcurrent is indicated by a red LED

● The fault indicator provides a range from 7s to 8hr automatic resetting time selection

Smoke alarm ● The smoke alarm normally installed on the roof of YB-O, in case of a fire or

smoke inside the YB-O, can be enable the electronic speaker which will make a loud buzzing and also a signal will be sent for remote monitoring.

Cable thermal detecting device ● HZT100 is used to detect the temperature of the cables ● The reading will be shown on the screen. If the cable is overheated, it

will be indicated by a red LED, and also a signal can be used for remote monitoring

Transformer thermal detecting device ● The device is used to detect the oil and winding temperature of the

transformer. It can send a signal to trip the upstream switch for protecting the transformer

Page 17: YB-O Series

30 31

YB-O Series Foundation

Non-walk-in type

Notes: 1. The connections in YB-O from HV to transformer and from transformer to LV are finished inside enclosure. 2. Please consider the door open if any protective guard around YB-O is needed. 3. For walk-in type, please contact HeZong

Transportation and lifting

Transportation ● YB-O can be carried by a forklift for short distances. Please make sure

the Forklift's maximum rated load capacity

● There are 4 davits inside the bottom bracket of YB-O normally hidden inside, can be pulled out for enabling the YB-O be lifted by a crane. The lifting frame which is designed for YB-O is used to prevent the damage of the YB-O's surface and roof

● A chain rope is needed to be used to fix the YB-O on a truck for long distance transportation. The davits can also be used to help fixing the YB-O on the truck

Page 18: YB-O Series

32 33

YB-O Series

User's name

Contact Phone/fax

Filled by Date Transformer technical information1 Rated capacity ___________ kVA

2 Rated voltage □10/0.4kV □20/0.4kV □35/0.69kV□other______

3 Rated frequency □50Hz □other______4 Tap changer □±2*2.5% □±5% □other______

5 Oil-immersed transformer

□S11-M □S13-M·RL □S(B)H15□S(B)H16 □other______

6 Dry type transformer □SCB10 □SCB11 □other______HV technical information1 Solution H_____ □other______2 Fuse SFLDJ__A □other______3 Other requirement:LV technical information

1 Main switch

□No

□Yes

□Under voltage protection□Fixed type□Withdrawable type□other______

2 Meter

□No

□Yes

□Reserve space□Standard□Multi-functional Energy-meter□other______

3 Feeder solution L_____ □other______Reactive compensation

1Reactive compensation solution

L_____ □other______

2 Capacitor __________kvarEnclosure

1 Type □Non-walk-in type A □Non-walk-in type B □other______□Walk-in type A □Walk-in type B □Walk-in type C

2 Color □RAL6005 □RAL7032 □other______

3 Material □Stainless steel □Cold-rolled steel sheet□Galvanized aluminum zinc plate □GRC □other______

Optional items1 Fault indicator □Qty:______ □Not equipped

2 Distribution automation devices □HZD300 series □EM600 series Qty:______

Inspection and commissioning

● While opening the door of HV or LV rooms, make sure the door is held by the limiting stopper

● Make sure all fuses are installed correctly

● Before closing the incoming panel, make sure that all switches are in the correct position

● Low voltage breakers can be motor-operated or operated by a handle

● By setting the correct value, the Reactive compensation panel will achieve automatic close/open operation

● Make sure that the corresponding HV panel is in open or earthing position before entering the transformer room

● The ratio between the high voltage and low voltage of the transformer can be adjusted by the tapping connection changer

● Make sure the secondary wiring connections are correct

● Make sure all devices are installed correctly and reliably

● Make sure all instruments are working in appropriate position

● Make sure all doors are locked while leaving the enclosure

Maintenance ● Regularly inspect the surface of the enclosure, any damages that may

need to be fixed should be fixed as soon as possible to avoid rusting on the surface

● Regularly inspect all operating parts and instruments, and make sure all parts are working correctly

● If an Oil-immersed transformer is used in YB-O, the analysis of the oil sample needs to be done once a year at least

● After the tripping, the fault should be fixed before closing switch

● Once a fuse is blown, all the three fuse-links need to be changed

Upgrade ● If any HV switchgear, LV switchgear or transformer need(s) to be changed

or upgraded, the roof of YB-O is removable, and all the works can be completed within a limited time

Maintenance and Upgrade

Ordering instructions

Page 19: YB-O Series