Download pdf - AS220_PR_E_Manual UK.pdf

Transcript
Page 1: AS220_PR_E_Manual UK.pdf

AS220 Single phase Smart Meter

Product manual

Document name AS220_PR_E.doc Document revision: Revision 1.9 Date of version: 02.02.2010

Page 2: AS220_PR_E_Manual UK.pdf

Page 2 of 67

Product manual 1.9 AS220

COPYRIGHT NOTICE Copyright © 2009 by ELSTER GmbH. All rights are reserved. No part of this document may be reproduced, transmitted, processed or recorded by any means or form, electronic, mechanical, photographic or otherwise, translated to another language, or be released to any third party without the express written consent of ELSTER GmbH.

Printed in Germany

NOTICE The information contained in this document is subject to change without notice. ELSTER shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing, performance, or use of this material. For further information, see the following referenc es: ELSTER companies web side: http://www.elster.com ELSTER electricity meter web side: http://www.elstermetering.com

Page 3: AS220_PR_E_Manual UK.pdf

Page 3 of 67

Product manual 1.9 AS220

Content 1 Overview........................................... ................................................................................. 6

1.1 System overview ............................................................................................................ 6 2 Referenced documents............................... ...................................................................... 7 3 Application ........................................ ................................................................................ 8

3.1 Essential features of the alpha meter AS220.................................................................. 8 3.1.1 High accuracy ........................................................................................................ 8 3.1.2 Integrated communication module ......................................................................... 8 3.1.3 Integrated load profile ............................................................................................ 8 3.1.4 Readout during power outage................................................................................ 8 3.1.5 Anti Tampering features......................................................................................... 8 3.1.6 Configuration ......................................................................................................... 8

4 General description ................................ .......................................................................... 9 4.1 Enclosure ....................................................................................................................... 9 4.2 Power supply................................................................................................................ 10 4.3 Readout during power outage ...................................................................................... 10 4.4 Model variants .............................................................................................................. 10

4.4.1 Direct connected meter (DIN version) .................................................................. 10 4.4.2 Direct connected meter (BS version).................................................................... 10

5 Measured value acquisition......................... ................................................................... 11 5.1 Measuring module........................................................................................................ 11 5.2 Measuring principle ...................................................................................................... 12

5.2.1 Active demand and energy calculation................................................................. 12 5.2.2 Reactive demand and energy calculation............................................................. 12 5.2.3 Theft resistant measurement (always run positive) .............................................. 12

6 Display Control .................................... ........................................................................... 13 6.1 Display ......................................................................................................................... 13

6.1.1 Back lightened display ......................................................................................... 13 6.2 Display Modes.............................................................................................................. 15 6.3 Scroll mode .................................................................................................................. 16 6.4 Display test mode......................................................................................................... 16 6.5 A-button menu.............................................................................................................. 16

6.5.1 Standard mode (Menu Option "Std-dAtA") ........................................................... 16 6.5.2 Second Standard mode (Menu Option "Abl-dAtA") .............................................. 16 6.5.3 Load profile mode (Menu option „P.01“)............................................................... 17 6.5.3.1 Date selection for the day block ........................................................................... 17 6.5.3.2 Load profile values of the selected day ................................................................ 17

6.6 Flow chart of different display modes............................................................................ 17 7 Demand reset ....................................... ........................................................................... 20 8 Identifier system and data readout lists ........... ............................................................. 21

8.1 Standard data readout list............................................................................................. 21 8.2 Service list - second data readout list ........................................................................... 22 8.3 OBIS formatted read and write operations.................................................................... 22

9 Tariff characteristics............................. .......................................................................... 23 9.1 General remarks........................................................................................................... 23 9.2 Energy tariff control ...................................................................................................... 23 9.3 Maximum demand tariff control..................................................................................... 23

9.3.1 Synchronization of the demand period ................................................................. 24 9.4 Delta register values..................................................................................................... 25 9.5 Real time clock............................................................................................................. 25

Page 4: AS220_PR_E_Manual UK.pdf

Page 4 of 67

Product manual 1.9 AS220

9.5.1 General characteristics of the real time clock....................................................... 25 9.5.2 Correction of the RTC.......................................................................................... 25 9.5.3 Battery backup..................................................................................................... 26 9.5.3.1 Internal battery..................................................................................................... 26 9.5.3.2 External battery.................................................................................................... 26 9.5.4 Internal tariff table ................................................................................................ 27 9.5.5 Future / deferred tariff table.................................................................................. 27

10 Load profile of billing data....................... ..................................................................... 28 10.1.1 Features of the load profile storage...................................................................... 28 10.1.2 Depiction of load profile in the data telegram ...................................................... 29

11 Setting parameters................................. ....................................................................... 30 12 Inputs / Outputs................................... .......................................................................... 31

12.1 Interfaces.................................................................................................................... 31 12.1.1 Optical interface................................................................................................... 31 12.1.2 Interface to the comms module ............................................................................ 31

12.2 Electronic output......................................................................................................... 31 12.2.1 Electronic control output....................................................................................... 31 12.2.2 Electronic pulse output......................................................................................... 31

12.3 Overload Control ........................................................................................................ 32 13 Security functions ................................. ........................................................................ 33

13.1 Error messages .......................................................................................................... 33 13.1.1 Certification relevant alarms................................................................................. 33 13.1.2 Non Certification relevant alarms ......................................................................... 33 13.1.3 Diagnostic messages........................................................................................... 34

13.2 Terminal cover removal detection............................................................................... 35 13.3 Main cover removal detection..................................................................................... 35 13.4 Magnetic tamper detection ......................................................................................... 35 13.5 Reverse run detection................................................................................................. 35 13.6 Basic log file ............................................................................................................... 36

13.6.1 Characteristic of the log file.................................................................................. 36 13.6.2 Certified log file .................................................................................................... 36 13.6.3 Log file format ...................................................................................................... 36 13.6.4 Readout modes of the log file by using R5 / R6 - commands ............................... 37

13.7 Second log file – storing meter configurations ............................................................ 37 13.8 Standard register data list........................................................................................... 38 13.9 Data integrity .............................................................................................................. 38 13.10 Security protection against reprogramming............................................................... 39 13.11 Display of meter status information’s ........................................................................ 40 13.12 Summarize of Anti Tampering features..................................................................... 41

13.12.1 Terminal cover opening detection ........................................................................ 41 13.12.2 Main cover opening detection .............................................................................. 41 13.12.3 Magnetic field detection ....................................................................................... 41 13.12.4 Reverse run detection.......................................................................................... 41 13.12.5 Always run positive measurement........................................................................ 41 13.12.6 Detection of anti creep conditions ........................................................................ 41 13.12.7 Security concept .................................................................................................. 41 13.12.8 Logfile .................................................................................................................. 41

14 Instrumentation measurement ........................ ............................................................. 42 14.1 Instantaneous power quality parameters .................................................................... 42 14.2 Instantaneous power quality counters......................................................................... 42 14.3 Load profiling of power quality parameters ................................................................. 43

15 Integrated connect / disconnect relay .............. ........................................................... 44

Page 5: AS220_PR_E_Manual UK.pdf

Page 5 of 67

Product manual 1.9 AS220

15.1 Remote connect / disconnect...................................................................................... 44 15.2 Load limiting function.................................................................................................. 44

16 Communication module............................... ................................................................. 45 16.1 AM100 module – GSM/GPRS .................................................................................... 45 16.2 AM700 module – RS485 + DLMS protocol support..................................................... 46

17 Calibration and test ............................... ........................................................................ 47 17.1 Calibration .................................................................................................................. 47 17.2 Accuracy test using a test bench ................................................................................ 47 17.3 Manufacturer specific test mode ................................................................................. 47 17.4 Simplified test mode ................................................................................................... 48 17.5 Simple creep and anti-creep test ................................................................................ 48 17.6 Checksum display ...................................................................................................... 48

18 User program....................................... .......................................................................... 49 18.1 Reading and configuration tool alphaset..................................................................... 49

19 Installation and start-up.......................... ...................................................................... 50 19.1 Installation and general function control...................................................................... 50 19.2 Installation check using the meter display................................................................... 51 19.3 Installation recommendations ..................................................................................... 52

20 Type key........................................... .............................................................................. 53 21 Name plate ......................................... ............................................................................ 55 22 Technical data of the AS220........................ ................................................................. 56 23 OBIS identifiers of AS220 .......................... ................................................................... 57

23.1 Identifiers for measuring values.................................................................................. 57 23.1.1 Power Measuring................................................................................................. 57 23.1.2 Energy Measuring................................................................................................ 59 23.1.3 Instantaneous Values .......................................................................................... 60 23.1.4 Supervision Data.................................................................................................. 60

23.2 General Purpose Objects ........................................................................................... 61 23.2.1 Objects, that OBIS-identifier starts with “0”........................................................... 61 23.2.2 Objects, that OBIS-identifier starts with “C”.......................................................... 62 23.2.3 Objects, that OBIS-identifier starts with “96”......................................................... 63 23.2.4 Objects, that OBIS-identifier starts with “P” .......................................................... 63 23.2.5 Objects, that OBIS-identifier starts with “F” .......................................................... 63

24 Dimensions of AS220................................ .................................................................... 64 24.1 Outside dimension of AS220 (BS standard)................................................................ 64 24.2 Terminal block of AS220 meter (BS standard)............................................................ 65 24.3 Outside dimension of AS220 (DIN standard) .............................................................. 66 24.4 Terminal block of AS220 meter (DIN standard)........................................................... 67

Page 6: AS220_PR_E_Manual UK.pdf

1 Overview Page 6 of 67

Product manual 1.9 AS220

1 Overview

1.1 System overview The document describes the basic features of the AS220 meter designed for Smart Meter Applications. It includes information’s about:

• Application

• Basic description of the meters

• Data acquisition

• Controls and displays

• Identifier System

• Tariff structure

• Setting parameters

• Outputs

• Communication modules

• Integrated connect / disconnect relay, remotely controlled

• Security features

• Calibration and test

• Installation and start-up

• User tools for reading and configuring of the meter

Page 7: AS220_PR_E_Manual UK.pdf

2 Referenced documents Page 7 of 67

Product manual 1.9 AS220

2 Referenced documents Title Version Date VDEW requirements V2.0 for electronic electricity meters V2.0 12.1997

Electricity metering – data exchange for meter reading, tariff and load control – part 21

EN 62056-21 06.2002

Electricity metering – data exchange for meter reading, tariff and load control – part 61:

Object Identification System (OBIS)

EN 62056-61 06.2002

Electricity metering equipment (AC) – general requirements, test and test conditions – part 11

EN 62052-11 02.2003

Electricity metering equipment (AC) – general requirements, test and test conditions – part 21:

Static meters for active energy, (classes 1 and 2)

EN 62053-21 01.2003

Electricity metering equipment (AC) – general requirements, test and test conditions – part 23:

Static meters for reactive energy, (classes 2 and 3)

EN 62053-23 01.2003

Electricity metering equipment (AC) – Part 1: general requirements, test and test conditions – Metering equipment (classes indexes A, B and C):

Static meters for reactive energy, (classes 2 and 3)

EN 50470-1 2006

Electricity metering equipment (AC) – Part 3: Particular requirements – Static meters for active energy (classes indexes A, B and C):

Static meters for reactive energy, (classes 2 and 3)

EN 50470-3 2006

Elektrizitätszähler in Isolierstoffgehäusen für unmittelbaren Anschluß bis 60 A Grenzstrom; Hauptmaße für Wechselstromstromzähler

DIN 43857 Teil 1

09.78

Dimension of electricity meters BS 7856 1996

Page 8: AS220_PR_E_Manual UK.pdf

3 Application Page 8 of 67

Product manual 1.9 AS220

3 Application New requirements dependant from legislation and EU energy saving directives are dominating the European meter market. Smart Metering stands not only for the reading of electricity meters. With this approach the frequently reading of gas and water meters is included. With the remote metering the standardization process become more and more important. With the adaptation of the well proven A220 meter to the specific Smart Metering requirements, like modular communication, integrated connect/disconnect relay, etc. the new AS220 meter match these new requirements respectively. This manual describes the feature set of the following firmware versions of the AS220:

• FW 8.00

3.1 Essential features of the alpha meter AS220

3.1.1 High accuracy Digital measured-value processing with a digital signal processor (DSP) and high sample rate for accurate, flexible measured-value processing in all 4 quadrants.

3.1.2 Integrated communication module With the integrated communication module the AS220 meter can be used for Smart Metering application. The comms module contents a GSM/GPRS communication for remote metering. Additionally with a wireless M-Bus communication gas- and water-meters can be readout using the 868MHz frequency

3.1.3 Integrated load profile The meter offers an integrated load profile with up to 8 channels.

3.1.4 Readout during power outage By pushing the display button the meter is able to display all billing data even if the main power is absent. Furthermore all register data can be readout by the optical interface.

3.1.5 Anti Tampering features The meter supports a lot of anti tampering features. For example the removal of the terminal and main cover will be registered and stored in a log file with time&date information.

3.1.6 Configuration User-friendly readout and configuration tool alphaSet, enabling users to define their own different function variants. The same tool can be used for all ELSTER meters (AS220, A220, A1350, A1500, A2500).

Page 9: AS220_PR_E_Manual UK.pdf

4 General description Page 9 of 67

Product manual 1.9 AS220

4 General description

4.1 Enclosure The AS220 meter enclosure is available in 2 versions and exceeds the following standards:

• DIN 43857, part 2

• BS 7856 The enclosure has the flowing features:

• The meter cover is secured by 2 certification relevant seals

• The case is double insulated to protective class II.

• The case provides an ingress protection rating of IP54.

• The base with its integral terminal block is moulded in glass-filled polycarbonate.

• The top fixing centers are provided, one internal and one external

• The terminal cover is moulded in light beige colored polycarbonate.

• The terminal cover provides the possibility for cut-outs

• The terminal cover can be sealed for limit access to the main meter connections

• Under the terminal cover an exchangeable battery can be fixed

• The main cover is moulded in tinted, clear polycarbonate

• The metal ring of the optical port is fixed under the main cover

Page 10: AS220_PR_E_Manual UK.pdf

4 General description Page 10 of 67

Product manual 1.9 AS220

4.2 Power supply The meter's power supply is a capacitive power supply for dedicated nominal voltage level from 220V–240V (-20% .. +15%). The power supply is designed to withstand an over voltage >440V for longer than 12 hours.

4.3 Readout during power outage The behaviour of the AS220 during power outage is described below

• Readout using the display After pressing the alternate button the LCD will be switched ON. The segment test will be displayed first. After pressing the alternate button again the next data of the standard data readout list will be displayed for about 10s. The LCD will be switched OFF after the following events:

- Without pressing the push button within 10s. - At reaching the end of the standard data readout list

• Readout by optical port

After pressing the alternate button the LCD will be switched ON. After the segment test will be displayed the standard data readout list of the meter can be read by the optical port. At the end of the communication the LCD will be switched OFF.

By using the exchangeable battery the readout feature is available even if the meter is not powered for longer than 4 years, depending on the number of readouts without main power.

4.4 Model variants The alpha Meter is available in several different model variants.

4.4.1 Direct connected meter (DIN version)

- 220V .. 240V, 5/60A class 1 or 2 - 220V .. 240V, 5/100A class 1 or 2

4.4.2 Direct connected meter (BS version)

- 220V .. 240V, 20/100A class 1 or 2 - 220V .. 240V, 5/100A class 1 or 2

Page 11: AS220_PR_E_Manual UK.pdf

5 Measured value acquisition Page 11 of 67

Product manual 1.9 AS220

5 Measured value acquisition

5.1 Measuring module The measuring module (Fig. 1) comprises a shunt for the current transformation, a voltage divider plus a highly integrated customized circuit (ASIC). The analog measured variables obtained are digitized in the ASIC and fed to a downstream digital signal processor, which uses them to compute the active or reactive powers plus the corresponding energies, and forwards energy-proportional pulses to the tariff module. By using both digital multiplication and integration, significant advantages can be achieved in terms of measuring stability and flexibility. The scanning frequency has been selected so as to ensure that the electrical energy contained in the harmonics is acquired with the specified class accuracy.

Microcontroller

timer tariff clock

battery EEPROM

Display

Control output

Control input

LED- pulse

optical interface

electrical interface

Max reg. 1 Tariff control

push button

U 1

Max reg. 2 Loadprofil Logfile

U 1,

, I 1

2

ASIC

+P

-P

+Q

-Q

Measuring module

Tariff module

power supply Input/Output module

Shunt

Voltage divider

Fig. 1: Functional schematics of the AS220 meter

Page 12: AS220_PR_E_Manual UK.pdf

5 Measured value acquisition Page 12 of 67

Product manual 1.9 AS220

5.2 Measuring principle The alpha Meter's basic hardware can be used to acquire the following measured variables: - Active demand (+P), - Active demand (-P), - Reactive demand (Q1, Q2, Q3, Q4 or +Q=Q1+Q2 and –Q=Q3+Q4) - Apparent demand (+S, -S)

5.2.1 Active demand and energy calculation The active power is obtained by multiplying the current and voltages values in accordance with Equation (1): p(t) = u(t) * i(t) (1)

5.2.2 Reactive demand and energy calculation The AS220 reactive energy measurement is implemented according the phase shift method. The reactive energy calculation is done by using a 900 phase shift between voltage and current and a following multiplication of voltage and current according eq. 1.

5.2.3 Theft resistant measurement (always run posit ive) The AS220 can be ordered with an optional theft resistant measurement that records negative energy flow as positive energy flow. This feature can be used to deter power theft or minimize the effects of improper meter wiring. The following equation shows how total active power is calculated using theft-resistant measurement. P = |+/-P| Theft-resistant measurement applies of registration of active, reactive or apparent energy. Instrumentation values, including active energy +P and –P, are also signed normally. Therefore, instrumentation can be used to investigate the meter service wiring, while the theft-resistant measurement guarantees that active energy is properly registered. Operation of the LCD energy direction indicators is modified by the theft-resistant measurement. With the theft-resistant option, the –P arrow is not used. The +P arrow signals all positive or negative active energy flow. The following figures shows how the energy direction indicators appear for negative active and reactive power when using standard measurement and theft-resistant measurement.

Standard active energy measurement theft resistan t measurement

-P-Q

+P-Q

Page 13: AS220_PR_E_Manual UK.pdf

6 Display Control Page 13 of 67

Product manual 1.9 AS220

6 Display Control

6.1 Display The LCD has the following format:

• LCD size: 47mm x 28mm

• Digit size: 8mm x 3,6mm The digits for the LC display of the AS220 you will find in Fig 2:

No. Description 1 Identifier

2 Error indicator

3 Unit of measuring quantity

4 Measuring quantity

5 Energy direction indicator

6 Energy Tariff information

7 Demand tariff indication

Fig. 2 LC display of the AS220

6.1.1 Back lightened display The display can optionally be back lightened to be readable under dark reading conditions. The back-lightened display will be activated for 2 minutes by pressing the alternate button. This feature will be available even if the meter is not connected to the main power.

3

2 7 6

1

4

5

Page 14: AS220_PR_E_Manual UK.pdf

6 Display Control Page 14 of 67

Product manual 1.9 AS220

The display consists of the following items: Operating display The definitions for import and export of energy have been agreed in terms of the load reference arrow system (VZS). For defining the transmission direction of active and reactive power, the specifications of the load reference arrow system likewise apply. The VZS assumes that the power utility's contracting party is importing energy (+A) from the supply grid. Display of activated tariff The tariffs T1 to T4 and M1 to M2 switched on at any one time are continuously displayed. In addition, the following applies: Arrow to the right: Indicator for positive active power

Arrow to the left: Indicator for negative active power

Arrow pointing upwards: Indicator for positive reactive power

Arrow pointing downwards: Indicator for negative reactive power

The relevant symbols will flash when the meter is not programmed to measure this energy direction. The symbols for the measured variable involved have been switched off if the power is below the device's start-up threshold. Identifier and value range All digits are separated by dots (OBIS separator or decimal point). Time particulars (h, min, sec) are separated by colons, date particulars (year, month, day) by the top dots of the colons. Alarm Indicator Alarm indicator: This indicator will be displayed if any error message of the meter

occurs (F.F, F.F.1, F.F.2)

Page 15: AS220_PR_E_Manual UK.pdf

6 Display Control Page 15 of 67

Product manual 1.9 AS220

6.2 Display Modes The following principles apply for display control: Alternate button

• pressing briefly (<2s) switches to the next list value or menu option • pressing for longer (2s < t < 5s) either activates the menu options currently being

displayed or causes preceding values to be skipped • pressing the alternate button for longer (>5 s) returns you from any display mode back

into the scroll mode (rolling display)

Further principles:

• The display control and the edit function for settable values are handled by means of "single-hand operator control" in conformity with the stipulations of the VDEW -Specification, i.e. it is never necessary to operate more than one control at any one time.

• Depiction of the different values on the display in the various display modes can be parameterized.

• The default status for the display is the operating display. A change from the operating display to the "Menu [A]-key" (i.e. call or load profile).

• From standard, second or load profile call mode you jump back into the operating display through the end-of-list identifier, or automatically if no control is operated within a defined time of 30 minutes, for example, or if the alternate button has been pressed for longer than 5 s.

• The end of a list is designated in the display with the word "End" in the value range. Different operating modes for the display:

• Scroll Mode

• Display test

• Call mode "Menu alternate button" - Standard call mode ("Std-dAtA" , displaying all the list's register contents) - Second call mode ("Abl-dAtA" , displaying all the list's register contents) - Load profile call mode ("P.01" , displaying load profile values) - Log file call mode ("P.98" , displaying of log file data)

Page 16: AS220_PR_E_Manual UK.pdf

6 Display Control Page 16 of 67

Product manual 1.9 AS220

6.3 Scroll mode The operating display is the standard display function. The measured values involved are dis-played in rolling mode, with the data relevant to billing being displayed for a configurable duration (e.g. 10 s). While a measured value is actually being displayed, then it will not be updated in the scroll mode.

6.4 Display test mode

Pressing the alternate button (<5 s) causes the meter to switch over from rolling display to display test mode, in which all segments on the display are activated. The display test mode is retained from approx. 3 seconds after the alternate button is released. During the display test mode, you can press the alternate button to switch to the "A-button menu"

6.5 A-button menu The first value displayed in the menu list is the single-call menu option entitled "Std-dAtA". Every time you press the alternate button briefly again, more menu options as available will be displayed, e.g. the load profile "P.01" or the second alternate list “Abl-dAtA” . For purposes of menu option selection, the alternate button must be held down for at least 2 s. If the time limit after the last touch on the button has been reached (this can be parameterized in a range from 1 min to 2 h) or the alternate button has been kept depressed for not less than 5 s, the meter will automatically switch over to the scroll mode. While a measured value is being displayed in this mode, it will be updated in the display once a second.

6.5.1 Standard mode (Menu Option "Std-dAtA") The first value displayed in the call list is the Identifier and the content of the function error. Every time the alternate button is pressed again, further data will be displayed. In order to call up data more quickly, existing preceding values can be skipped and the value following the preceding values can be displayed. You do this by keeping the alternate button pressed down for longer than 2 s. If the time limit after the last touch on the button has been reached (this can be parameterized in a range from 1 min to 2 h) or the alternate button has been kept depressed for not less than 5 s, the meter will automatically switch over to the operating display. Extending the time limit gives you an option for testing the meter without any software tools, since the LED will flash either for +P, -P, +P/-P or Q1.. Q4, etc., depending on the measured variable being displayed (active or reactive power consumption). The final value in the call list is the end-of-list identifier, which is designated in the display's value range by the word "End" .

6.5.2 Second Standard mode (Menu Option "Abl-dAtA")

Furthermore the meter supports second standard data list (“Abl-dAtA”). The handling of this list is the same as described in chapter 4.5.1. The main difference between the 2 lists is that the “Abl-dAtA” list can be set without breaking the certification seal (see chapter 7.2).

Page 17: AS220_PR_E_Manual UK.pdf

6 Display Control Page 17 of 67

Product manual 1.9 AS220

6.5.3 Load profile mode (Menu option „P.01“)

6.5.3.1 Date selection for the day block The first value displayed in the list is the date of the most recent available day block in the load profile. Every time the alternate button is pressed briefly (<2 s) again, the display will show the preceding available day in the load profile. If the alternate button is pressed for >2 s, then for precise analysis of the day block selected the day profile will be displayed in increments of the demand integration period, provided no events have led to the demand integration period being cancelled or shortened. If the time limit after the last touch on the button has been reached (this can be parameterized in a range from 1 min to 2 h) or the alternate button has been kept depressed for not less than 5 s, the meter will automatically switch over to the operating display. The final value in the call list is the end-of-list identifier, which is designated in the display's value range by the word "End" .

6.5.3.2 Load profile values of the selected day Display of the day block selected begins by showing the oldest load profile values stored on this day (the value stored at 0.00 h is assigned to the preceding day), beginning with the lowest OBIS Identifier from left to right (time, Channel 1 value, .. Channel n value). Every time the alternate button is pressed briefly (<2 s) again, the next available measured value for the same demand integration period will be displayed. Once all the period's measured values have been displayed, they are followed by the data of the next available demand period. The last value in the call list is the end-of-list identifier, which is designated in the display's value range by the word "End" and which appears after the final load profile value of the day selected. If the alternate button is pressed for >2 s, the meter will switch back to the day block previously selected from the date list. If the time limit after the last touch on the button has been reached (this can be parameterized in a range from 1 min to 2 h) or the alternate button has been kept depressed for not less than 5s, the meter will automatically switch over to the operating display.

6.6 Flow chart of different display modes

Scroll mode

(rolling display)

[A]- button pressed short or long

[A]-button menu

[A]-button pressed short or long

Display test mode

Fig. 3 Different display modes

Page 18: AS220_PR_E_Manual UK.pdf

6 Display Control Page 18 of 67

Product manual 1.9 AS220

[A]-button

menu

Display"Std-dAtA"

Display"P.01"

Displayend of list

load profile mode

Standard modepress [A]-button short

press [A]-button short

press [A]-button short

press [A]-button short

press [A]-button long

Fig. 4 A-button menu

Fig. 5 Single call display

pres s [A ]-but ton s hortpres s ed k urz betätigt

pres s [A ]-but ton long

se lec t nextvalue/previous value

d isplays elec ted va lue

se lec t next value, ignore

previous values

dis play 1. value of the s tandard lis t

S tandard m ode

Page 19: AS220_PR_E_Manual UK.pdf

6 Display Control Page 19 of 67

Product manual 1.9 AS220

load profile mode

calculate date of current day

selecttime&date ofday day before

displaytime&date

calculate data of 1.register period of

selected time&date

select nextregister period

displaydata of current reg.

period

press [A]-button short

press [A]-button long

press [A]-button long

press [A]-button short

Fig. 6 Load profile data display

Page 20: AS220_PR_E_Manual UK.pdf

7 Demand reset Page 20 of 67

Product manual 1.9 AS220

7 Demand reset The demand reset of all energy/demand register can be executed by:

• an internal signal from the integrated clock

• a demand reset request through one of the data interfaces The demand reset of the meter possesses the following characteristics:

a) The demand reset disable time can be parameterized from 1 min to 45 days.

Disable times for a new demand reset by triggering a reset through...

1 2 3 4

1 ... interfaces (optical, electrical) t1 0 0 0 2 ... external control 0 t1 t1 t1 3 ... internal RTC of the meter 0 t1 t1 t1

b) The demand reset disable time can be configured to be cancelled by a power failure.

c) If during an activated demand reset disable another reset is executed through the optical or electrical data interface, then on the display all segments show the letter “E”.

d) The demand reset counting mechanism can run either from 0..99 or from 1..12, to corres- pond to the months of a year. The number of the reset counting mechanism simultaneously serves as an auxiliary Identifier for the preceding values.

1-1:1.2.1 0.134 kW 1-1:1.2.1*05 0.230 kW 1-1:1.2.1*04 0.212 kW

e) The counting of the historical data reset is counting with the highest reset counter at first (see item f). Optionally the meter can be programmed, that “*1 is always the last demand reset. If there is the next reset, *1 value goes to *2 and so on.

f) Resetting via the data interface is safeguarded by a password and/or terminal cover opening

g) During the test mode every demand reset will be performed always directly without delay.

h) A demand reset can be carried out on a daily, monthly or yearly base.

i) After power up the AS220 meter checks whether an automatic reset has to be executed during the power outage time. In that case the demand reset lockout time will not be started.

j) Optionally it is possible to configure the meter in a way, that the meter accepts only one demand reset during one month.

k) Up to 3 automatic demand resets in one month can be programmed.

Page 21: AS220_PR_E_Manual UK.pdf

8 Identifier system and data readout lists Page 21 of 67

Product manual 1.9 AS220

8 Identifier system and data readout lists The alpha Meter's Identifier system can be parameterized by the user, with a total of 3 Identifier digits provided for the display and the readout over the optical and electrical interfaces. The user has the option for using an own identifier system but to follow the international standardization the OBIS Identifier system (EN 62056-61) is recommended (see appendix, chapter 20).

8.1 Standard data readout list In the attached table you will find a sample of the standard data readout list of a meter with active and reactive and demand measurement and 2 tariffs. The standard data readout list contains all billing data. OBIS-identifier Format on the display Length Designation F.F XXXXXXXX 8 Error condition 0.0.0 XXXXXXXX 8 Identification number 0.0.1 XXXXXXXX 8 Additional Identification 0.1.0 XX 2 Demand reset counter 0.9.1 hh:mm:ss 8 Current time 0.9.2 JJ-MM-TT 8 Current date 1.2.1 XXX.XXX 6 Cumulative demand, tariff 1 1.2.2 XXX.XXX 6 Cumulative demand, tariff 2 1.4.0 XXX 3 Actual time of the demand period X.XXX 4 actual demand of the period 1.6.1 X.XXX 4 Demand, tariff 1 1.6.1.VV X.XXX Demand, tariff 1, historical value 1.6.2 X.XXX 4 Demand, tariff 2 1.6.2.VV X.XXX 4 Demand, tariff 2, historical value 1.8.1 XXXXX.XX 7 +A, active energy, tariff 1 1.8.1.VV XXXXX.XX 7 +A, active energy, tariff 1,

historical value 1.8.2 XXXXX.XX 7 +A, active energy, tariff 2 1.8.2.VV XXXXX.XX 7 +A, active energy, tariff 2,

historical value 3.8.1 XXXXX.XX 7 +R, reactive energy, tariff 1 3.8.1.VV XXXXX.XX 7 +R, reactive energy, tariff 1,

historical value 3.8.2 XXXXX.XX 7 +R, reactive energy, tariff 2 3.8.2.VV XXXXX.XX 7 +R, reactive energy, tariff 2,

historical value C.3 XXXXXXXX 8 Status of input / outputs C.4 XXXXXXXX 8 Status of internal signals Remark: All parameters of the standard data readout lists can only be changed by breaking the certification seal of the meter:

Page 22: AS220_PR_E_Manual UK.pdf

8 Identifier system and data readout lists Page 22 of 67

Product manual 1.9 AS220

8.2 Service list - second data readout list In the attached sample table you will find a sample of a service data readout list of a meter. All parameters of this list can be changed without breaking the certification seal. Only a password is required.

OBIS-identifier Format on the display Length Designation 31.7 X.XXX 6 Current phase L1 32.7 XXX.X 6 Voltage phase L1 33.7 X.XX 6 Power factor phase L1 1.7 XXX.X 6 Active demand, +P, total

C.7.1 XX 2 Number of outages in phase L1 C.52 XXXXXX 6 Start date of last power outage C.53 XXXXXX 6 Start time of last power outage C.54 XXXXXX 6 End date of last power outage C.55 XXXXXX 6 End date of last power outage

8.3 OBIS formatted read and write operations The table below provides information on which single registers and OBIS Identifier can be read or written. The "R5" and "W5" commands defined in conformity with EN62056-21 are used for this purpose:

ODIS -identifier

Significance Commands R5 / R6 / W5

Remarks

P.01 Read / Erase load profile yes / yes / yes P.98 Read / Erase operating

log file yes / yes / yes

0.9.1 Read time yes / no / no 0.9.1 Set time no / no / yes 0.9.2 Read date yes / no / no 0.9.2 Set date no / no / yes

Table 1: Register for OBIS-formatted read and write functions Remark: In addition, the "R5" command can be used to read out individually all the registers contained in the readout list.

Page 23: AS220_PR_E_Manual UK.pdf

9 Tariff characteristics Page 23 of 67

Product manual 1.9 AS220

9 Tariff characteristics

9.1 General remarks The tariff module of the alpha meter processes the counting pulses provided by the measuring module, monitors the integrated communication modules, and operates the meter's interfaces. Depending on the meter parameterization involved, all or only some of the functions described below will be supported. Furthermore it is possible to use a separate tariff source for the energy and the demand tariffs.

9.2 Energy tariff control Overall, the meter provides 6 energy register sets for acquiring the following quantities:

• Imported and export active energy +A and -A

• Reactive energies R1 .. R4 of the 4 energy quadrants

• Combination of reactive energies, e.g. +R=R1 + R2

• Apparent energy a) Internal tariff control using internal clock See Section 9.5.4 b) External tariff control using communication inte rface

The energy and demand tariffs can be controlled by the optical or electrical interface or the communication module.

9.3 Maximum demand tariff control The block demand calculation is provided for up to 4 separate programmable maximum registers for active, reactive or apparent calculation. The total parameters provided for the block demand measurement are as follows:

• Duration of the maximum period: 15 min (configurable in the range of 1..60 min) • Up to 4 separate maximum registers each with 4 maximum tariffs M1..M4 and 4

cumulative counting mechanisms (*) • Input variables for the 4 maximum values are user-selectable, e.g. +P/Q1, +P/+Q/+S • Maximum tariffs and energy tariffs are independent of each other • Temporary maximum demand measurements • Overlapping maximum demand measurements • Each maximum value is assigned a time stamp • Saving up to 15 preceding-month values

a) Internal demand tariff control using internal cl ock See Section 9.5.4 b) External tariff control using communication inte rface

The demand and tariffs can be controlled by the optical or electrical interface too.

Page 24: AS220_PR_E_Manual UK.pdf

9 Tariff characteristics Page 24 of 67

Product manual 1.9 AS220

9.3.1 Synchronization of the demand period The integration period for the meter's maximum measurement function can be synchronized in a number of different, configurable ways: • Power failure a) Integration period is ended b) Integration period is not ended • Power recovery a) A new integration period is started, and terminated synchronous- ly with the device time b) Depending on the duration of the interruption, either the integration period ongoing at the time of the power failure will be continued, or a new (and perhaps shortened) integration period will be begun. The end of the integration period is always specified by the IP raster. • Energy tariff change a) Energy tariff is switched over, and the integration period is affected if energy and power are not being jointly controlled b) The tariff is changed after a time-delay, and synchronized with the integration period raster specified by the device clock, if it has not occurred synchronously • Demand tariff change a) The power tariff will be changed immediately, the ongoing integration period switched over, and a new integration period started b) The tariff is changed after a time-delay, and synchronized with the integration period raster specified by the device clock, if it has not occurred synchronously • Demand Reset a) Ongoing integration period is ended, new integration period is started with the beginning of the new billing period b) The reset is accepted as preparation, but not actually executed until the next time the time filed in the device comes round (this does not apply for resets with the reset button or through the optical interface) • Setting device clock a) Setting the device clock causes the demand integration period to be terminated prematurely. The following integration period is terminated synchronously with the device time, and may be shortened if the resetting has not been synchronized so as to harmonize with the integration period raster.

Page 25: AS220_PR_E_Manual UK.pdf

9 Tariff characteristics Page 25 of 67

Product manual 1.9 AS220

9.4 Delta register values A Delta value or counting mechanism increment is the energy value, which has accumulated as a preceding value since the last demand reset. In comparison to the register reading, the Delta value represents the energy of the variable measured between two defined points in time. In the AS220 meter, Delta values and register readings can be displayed in parallel. When Delta values are displayed and read out, they are identified with their own Identifier, distinguishable from the meter readings.

9.5 Real time clock 9.5.1 General characteristics of the real time cloc k

The AS220 RTC (real-time clock) possesses the following characteristics:

• The time basis is derived from the internal oscillator with an accuracy of <5ppm (<+/- 0.5s per day).

• The energy for the running reserve is supplied by an internal battery (>5 years backup time).

• After the running reserve has been exhausted, the device clock will start after power up with the time and date information of the last power outage. An associated error identifier can be read out.

• Time and date can be set by using the optical or electrical interface.

• The real-time clock supplies the time stamp for all events inside the meter, such as time stamp for maximum measurement, time stamp for voltage interruptions, etc.

• It has been specified that two-digit year figures from 90 up to and including 99 are assigned to the twentieth century. Two-digit year figures in the range from 0 to 89 will be linked to the twenty-first century.

• If the real-time clock stops running the meter can be set to a predefined tariff.

9.5.2 Correction of the RTC There are several options for correcting the RTC clock of the meter. "Correcting" in this context means "synchronization" of the device clock, i.e. the clock's deviation lies in the range of 1% of the demand period. In this case, a running integration period will not be restarted. If the deviation is greater than this specified value, we speak of "setting" , i.e. the clock is synchronized and the integration period restarted.

Page 26: AS220_PR_E_Manual UK.pdf

9 Tariff characteristics Page 26 of 67

Product manual 1.9 AS220

9.5.3 Battery backup

9.5.3.1 Internal battery To keep the RTC of the meter running the AS220 owns an onboard soldered battery, which is located on the PCB under the main cover of the meter. The features of the battery are:

• Nominal voltage: 3,6V • Nominal capacity: 0,22Ah • Life time: >10 years (nominal conditions) • Shelf time for RTC: >4-5 years (nominal conditions)

9.5.3.2 External battery As an further option the meter can be equipped with an external, replaceable battery which is located under the terminal cover of the meter (see fig. 8). With this external battery the RTC running and readout without power feature works as listed below: - internal supercap: keeps the RTC running and supports the readout of the meter without

Main power in the first 12h of power outage

- internal battery: keeps the RTC running and supports the readout of the meter without Main power after the supercap is empty (4-5 years)

- external battery: the additional external battery keeps the RTC running and supports the readout of the meter without main power after the supercap is empty (>7 years):

Fig. 7 Location of the exchangeable battery

Page 27: AS220_PR_E_Manual UK.pdf

9 Tariff characteristics Page 27 of 67

Product manual 1.9 AS220

9.5.4 Internal tariff table The internal tariff table can be used to control tariff switchover functions at specified times of the day. The switching times are here defined by the switching table. For up to 4 different day types (e.g. workday, Saturday, Sunday, Holiday), different switching tables can be specified. In addition, up to 4 seasons can be defined, with an option for having different switching tables in each of the seasons concerned. The maximum possible number of switching tables is thus: 4 day types * 4 seasons =16 switching tables Example of a switching table:

- Switching table applies for Season 1 (1 Jan - 31 March) - Within Season 1, the switching table applies on workdays only - Switching times:

06:00 T1,M1 operative 22:00 T2,M2 operative, etc.

For the "Holiday" day type, the meter incorporates a Holiday table, where a year's fixed and movable Holidays can be entered. The parameters for the integrated clock can be read off at the meter's display using a switching number. Besides tariff control, the integrated lock timer is also used to form the maximum integration period and the time stamps for maximum demand, load profile and logbook (Fig. 9).

maximum integration period

Switching times

time stamps for maxima,load profile, logfile

Load relay control

synchronization of maximum integration period

up to 4 day types

up to 4 seasons

leap year

oszillator or main frequency clock time basis

summer-/wintertime

movable holidays

Fig. 9 Functionality of integrated clock

9.5.5 Future / deferred tariff table The meter can optionally be programmed with a second internal tariff table, which has the identical structure than tariff table described in chapter 9.7.4. The future tariff table can be programmed with a fixed date (at 00:00), where the tariff table will be activated automatically. The tariff table 1 will be overwritten and the internal tariff control of the meter will only be done by this second tariff table. This feature is very useful for future tariff changes.

Page 28: AS220_PR_E_Manual UK.pdf

10 Load profile of billing data Page 28 of 67

Product manual 1.9 AS220

10 Load profile of billing data By using the internal load profile storage the actual demand or energy over a selectable period (1...60min) can be stored. At the end of the storage capacity the oldest value of the load profile will be overwritten by the actual one. With the load profile memory approved by the PTB, load profile memory contents are interrogated and output in conformity with the VDEW requirements. The contents of the output data records are formatted in terms of their data structure in con-formity with EN 62056-61 (OBIS). The load profile memory possesses the following characteristics:

• Number of channels: 1-8 • Measuring quantities: +P, -P, Q1, Q2, Q3, Q4, +Q, -Q, +S, -S • Memory depth: small load profile storage

- 30 days for 1 channel (15min period) large load profile

- 260 days for 1 channel (15 min period) Remark: the size of the load profile storage decreases with the number of channels The following types of measuring values can be stor ed in the load profile storage:

• Demand values per period • Energy values per period • Energy Register every period

10.1.1 Features of the load profile storage • Load profiles are read out using the formatted "R5" command, which causes a load profile

formatted with OBIS to be output. The reply generated by the meter here is given as a self-sufficient telegram.

• Recorded profiles can be deleted using the "W5 " command defined to supplement DIN EN 62056-21

Please note: erasing the load profile memory will automatically erase the log file. • If the meter does not support the OBIS Identifier requested, it will return this as an echo

response. The part contained in the reply telegram between the two brackets (which function as separators) is omitted completely.

• If in conjunction with the load profile readout there is no entry in the inquiry for the OBIS Identifier of a measured value, the meter will respond with all available measured values in its profile.

• If the meter does not incorporate an internal device clock, then the following data will be output instead of the time stamp:

- for the date of the string: "999999" (OBIS Format: D6) - for the time of the string: "999999" (OBIS Format: Z6) - for the time stamp of the string "999999999999" • The telegram formed as the reply corresponds to the form specified in OBIS. It contains in

the "Address" field of the first data record the OBIS Identifier of the first load profile excerpt of the reply. This is followed, in accordance with the definition specified in OBIS, by a

Page 29: AS220_PR_E_Manual UK.pdf

10 Load profile of billing data Page 29 of 67

Product manual 1.9 AS220

header-specific number of bracketed additional values, to which are appended the likewise bracketed elements of the load profile excerpt.

• If in the interval specified there is more than one section of the load profile, then a new header will be inserted for each such section. The formation of new profile headers during load profile transfer is explained with the events and status changes coded in the first 8 bits (Bits 7 to 0) of the profile status word. The time stamp in the header is assigned not to the transactions, but to the formation of the first profile value.

• The overall length of the telegram answered will depend on the size of the interval desired. The time stamps in the reply telegram are of the "ZSTs13" type. Output of the telegram's data always begins with the oldest interrogated value.

• If the order includes a request for a time range for which there are no entries, the meter will respond with "P.01 (ERROR)”.

• If the order requests a Identifier which the meter does not support, the meter will merely supply the values for the Identifier it does know.

10.1.2 Depiction of load profile in the data tele gram KZ (ZSTs13) (S) (RP) (z) (KZ1)(E1) .. (KZz)(Ez) (Mw1) ... (Mwz) | <- header of load profile entry -> | <- Meas. value of load profile -> | * KZ OBIS-Identifier "P.01" * ZSTs13 Time stamp of the oldest measured value * S Profile status word

Bit Significance b7 Power failure b6 Power recovery b5 Change of time/date b4 Demand reset b3 Seasonal switchover (summer/winter time) b2 Measure value disturbed b1 Running reserve exhausted b0 Fatal device error

* RP Demand integration period in minutes * z Number of different measured values in one demand integration period * KZn Identifier of the measured values (without tariff particulars or preceding- value Identifier) * E1 Units of measured values * Mwn Measured values

Page 30: AS220_PR_E_Manual UK.pdf

11 Setting parameters Page 30 of 67

Product manual 1.9 AS220

11 Setting parameters The setting parameters can be changed by the optical or electrical interface without breaking the certification seal. They are safeguarded by:

- password - and/or removal of the terminal cover (optional)

The following parameters can be changed:

• Date and time (Formatted command) • Juncture for summer/winter changeover (Formatted command) • Maximum reset (Formatted command) • Duration of demand reset lockout time • Parameters for integrated clock timer

- switching times - special days, holidays - season - summer/winter changeover

• Activation of tariff switchover by - internal clock timer - external tariff terminals

• Activation of maximum demand reset by - internal clock timer - external tariff terminals

• Display control - scroll time for the operating display - maximum dwell duration of a value on the display - all parameters of second display data list “Abl-dAtA”

• Power utility password • Property Number • Meter address and meter identification in conformity with EN62056-21 • Communication baud rate for optical and electrical interface • Activation of setting mode

- through password protection • Threshold for overload control • Passwords

- for setting mode via data interface - for OBIS write commands ("W5" commands)

• Time base of the meter - internal oscillator

• instantaneous measurement of network parameters (current, voltage, ..) - enable disable parameters - assignment to service list

• profile of instantaneous measurement - enable disable parameters - readout options

Page 31: AS220_PR_E_Manual UK.pdf

12 Inputs / Outputs Page 31 of 67

Product manual 1.9 AS220

12 Inputs / Outputs

12.1 Interfaces Different interfaces like optical or electrical interfaces are available for reading or configuring the meter. Using one of these interfaces the meter can be readout by a handheld unit or PC in combination with an optical probe or by connection the meter to a modem for AMR purposes. The data protocol is implemented according Mode C of the EN62056-21 protocol. The communication baud rates are configurable.

12.1.1 Optical interface Electrical characteristics: as per EN62056-21 Protocol: as per EN62056-21 Baud rate: max. 9600 baud

12.1.2 Interface to the comms module Electrical characteristics: DIN 66348 Protocol: as per EN62056-21 Baud rate: max. 9600 Baud

12.2 Electronic output The AS220 meter provides 1 electronic S0 outputs acc. DIN 43864. The electronic output can be used either as control output (see chapter 12.2.1) or as pulse output (see chapter 12.2.2).

12.2.1 Electronic control output The assignment of the control output is user-configurable:

• Energy tariff information • Maximum demand tariff M1-M2 information • Maximum demand reset • Alarm indication • End of interval • Overload conditions • Power outage • Reverse run detection

12.2.2 Electronic pulse output The assignment of the pulse output to the individual measured variables is user-configurable:

• Active energy +A (import) • Active energy -A (export) • Reactive energy R1 • Reactive energy R2 • Reactive energy R3 • Reactive energy R4 • Combinations of measured variables, such as +R=R1+R2 • Apparent energy

Page 32: AS220_PR_E_Manual UK.pdf

12 Inputs / Outputs Page 32 of 67

Product manual 1.9 AS220

12.3 Overload Control With the AS220 it is possible to use a control output for load control opportunities. After exceeding a predefined threshold an output contact can be closed (opened). The number of overload exceeds can be counted and/or stored in a log file. The user can define 2 different thresholds for one control output.

a) The format of the selectable overload threshold and the demand are the same. b) At the begin of the period the output contact will be opened (closed) c) The output contact will be closed (opened) under the following conditions:

P15 > Pthreshold

with P15 : actual 15min demand ( P15 = P * t / tp) Pthreshold : overload threshold tp : demand period (15min) t: actual time of the 15min demand period

d) example nominal voltage: 3x230/400V current: 6A Overload threshold: 0.5kW

t = (Pthreshold / P) * 15min = 0.5/(3*230*6)*15min = 01:49 (mm:ss)

00:00 15:00 30:00 01:49 16:49

Page 33: AS220_PR_E_Manual UK.pdf

13 Security functions Page 33 of 67

Product manual 1.9 AS220

13 Security functions

13.1 Error messages The AS220 meter regularly executes self-test routines running in the background. These are used to test all important parts for proper functioning. If there is a malfunction or an operator error, the error messages and/or diagnostic alarms on the display will output a detailed error Identifier, which can be evaluated via the optical or electrical interfaces. It can contain one or more error messages.

There is also an option for displaying the error message in conformity with the OBIS Identifier Number system and the VDEW Specification (Identifier "F.F"). Note that the VDEW Specification subdivides errors into 4 groups. The significance of the individual bits in each group can be selected on a manufacturer-specific base. In the alpha Meter, the following specifications for fatal errors apply, beginning from the left: If any error condition (F.F, F.F.1, F.F.2) will occur, an alarm indicator on the LCD will be activated (see chapter 6).

13.1.1 Certification relevant alarms

Error identification with ODIS Identifier F.F If an error of this kind occurs, the meter's certification will be cancelled, and the display will be frozen ("F.F * * * * * * * * "). The error identifier can also be read out through the electrical or optical interface.

0 0 0 0 0 0 0 0 | | | | | | | | | | | | | | x x reserved or not used | | | | | 1 checksum error of parameterization class | | | | | 2 checksum error of billing data | | | | | 4 checksum of ELSTER parameterization class | | | | x reserved or not used | | | 1 I²C-Bus-error | | | 2 load profile storage error x x x reserved or not used

13.1.2 Non Certification relevant alarms

Error identification with OBIS Identifier F.F.1 If an alarm of this kind occurs, the display will be frozen ("F.F.1 * * * * * * * * "). An alarm of this kind can likewise be read out through the electrical or optical interface.

0 0 0 0 0 0 0 0 | | | | | | | | | | | | | | | 2 loss of time and date | | | | | | 1 power quality profile initialization error | | | | | x reserved or not used | | | | 1 non fatal checksum error of setting class | | | 1 terminal cover removal detection | | | 2 main cover removal detection | | 1 magnetic field detection | 1 battery empty 1 loss of time and date (not shown on display)

Page 34: AS220_PR_E_Manual UK.pdf

13 Security functions Page 34 of 67

Product manual 1.9 AS220

13.1.3 Diagnostic messages

Error identification with OBIS Identifier F.F.2 If a diagnostic message of this type occurs, it is output on the display in a rolling depiction with "F.F.2 * * * * * * * * ". A diagnostic message of this kind can likewise be read out through the electrical or optical interface.

0 0 0 0 0 0 0 0 | | | | | | | | | | | | | | | 4 configurable event 1 active | | | | | | | 8 configurable event 2 active | | | | | | 1 one time communication error between meter uP and meter chip | | | | | 1 reverse run detection | | | | x reserved or not used | | | 1 load profile / log book stopped | | 1 overload 1 exceed | | 2 overload 2 exceed | | 4 load Limit threshold exceed x x reserved or not used

Error identification with OBIS Identifier F.F.3 If a diagnostic message of this type occurs, it is output with "F.F.3 * * * * * * * * ". A diagnostic message of this kind can likewise be read out through the electrical or optical interface.

0 0 0 0 0 0 0 0 | | | | | | | 1 power quality monitoring value 1 - underflow | | | | | | | 2 power quality monitoring value 1 - overflow | | | | | | 1 power quality monitoring value 2 - underflow | | | | | | 2 power quality monitoring value 2 - overflow | | | | | 1 power quality monitoring value 3 - underflow | | | | | 2 power quality monitoring value 3 - overflow | | | | 1 power quality monitoring value 4 - underflow | | | | 2 power quality monitoring value 4 - overflow | | | 1 power quality monitoring value 5 - underflow | | | 2 power quality monitoring value 5 - overflow | | 1 power quality monitoring value 6 - underflow | | 2 power quality monitoring value 6 - overflow | 1 power quality monitoring value 7 - underflow | 2 power quality monitoring value 7 - overflow 1 power quality monitoring value 8 - underflow 2 power quality monitoring value 8 - overflow

Page 35: AS220_PR_E_Manual UK.pdf

13 Security functions Page 35 of 67

Product manual 1.9 AS220

13.2 Terminal cover removal detection The terminal cover opening will be detected if the event stays longer than a programmable time of 0-120s. The following actions are done:

• Error message on the LCD (F.F.1 00010000)

• Display of error symbol

• Detection of the last 10 with start and end time&date. This event list can be readout by the standard data readout list.

• After the detection of 10 events the latest event will be overwritten

The error message will be reset by use of the “Reset of event logs” or “register reset”.

13.3 Main cover removal detection The main cover opening will be detected if the event stays longer than a programmable time of 0-120s. The following actions are done:

• Error message on the LCD (F.F.1 00010000)

• Display of error symbol

• Detection of the last 10 events with start and end time&date. This event list can be readout by the standard data readout list.

• After the detection of 10 events the latest event will be overwritten

The error message will be reset by use of the “Reset of event logs” or “register reset”.

13.4 Magnetic tamper detection The magnetic tamper detection will be active if the event stays longer than a programmable time of 0-120s. The following actions are done:

• Error message on the LCD (F.F.1 00100000)

• Display of error symbol

• Detection of the last 10 events with start and end time&date. This event list can be readout by the standard data readout list.

• After the detection of 10 events the latest event will be overwritten

The error message will be reset by use of the “Reset of event logs” or “register reset”.

13.5 Reverse run detection The reverse run detection will be active if the event stays longer than a programmable time of 0-120s. The following actions are done:

• Error message on the LCD (F.F.2 00000100)

• Display of error symbol

• Detection of the last 10 events with start and end time&date. This event list can be readout by the standard data readout list.

• After the detection of 10 events the latest event will be overwritten

The error message will be reset by use of the “Reset of event logs” or “register reset”.

Page 36: AS220_PR_E_Manual UK.pdf

13 Security functions Page 36 of 67

Product manual 1.9 AS220

13.6 Basic log file 13.6.1 Characteristic of the log file By using the log file of the meter the following events can be recorded with the current time & date stamp:

• Power outage • Change of time & date • Malfunction of the meter • Demand reset • Reset of load profile/logfile • Energy or demand tariff change • Loss of time & date • Change of meter configuration • Detection of terminal &main cover removal • Magnetic tamper detection • Reverse run detection • With every power outage the total active energy register T0 can be stored in

the log file

13.6.2 Certified log file The log file of the meter can be used as a „certified log file“. It is not possible to delete the log file without breaking the certification seal. Therefore it is allowed to change the meter LED and pulse output constants under the following conditions:

• The indication of the pulse constant have to be displayed on the LCD • The change of the pulse constant is done by formatted command • Every change of the pulse constants will be registered in the log file with

Time & date stamp: identifier, previous constant, new constant • The log file can only be erased by breaking the certification seal • The load profile storage has the same size as the load profile storage

13.6.3 Log file format The meter's operating logbook entries can be read out in accordance with the procedure selected for outputting the load profile: • The operating log file is treated like a load profile. The Identifier "P.98" designates the

operating logbook of the VDEW Specification meter • The operating log file is read out using the "R5" formatted commands, which are specified

as follows to supplement DIN EN 62056-21: The "R5" command causes a load profile formatted with OBIS to be output. The answer generated by the meter in response is given as a self-sufficient telegram.

• Erasure of the operating log file is performed using the "W5" command defined to supple-ment DIN EN 62056-21.

Erasing the log file automatically causes the load profile memory to be erased • If a time range is requested in the order, but there are no entries for it, the meter will

respond with "P.98 (ERROR)”. • The status word describes the event or the status change which has led to the event in the

logbook. In the status bit, however, it is perfectly possible for more than one status bit to be set to "1". Which event entails which element information is defined below:

Page 37: AS220_PR_E_Manual UK.pdf

13 Security functions Page 37 of 67

Product manual 1.9 AS220

13.6.4 Readout modes of the log file by using R5 / R6 - commands The orders listed below can be sent to the meter:

Order OBIS Identifier Template: GG.AA

Parameters required (the brackets are separators in conformity with DIN EN 62056-21

Remarks

Readout of operating logbook

P.98 Readout of the operating logbook completely available in the meter (;)

1) The semicolon must Also be transferred, as a special separator

P.98 Readout of an interval:

(ZSTs11 ; ZSTs11) 2) The time stamp before

the semicolon de- signates the begin of the readout interval

P.98 Readout from the beginning of the logbook record in the meter up to an end time (;ZSTs11)

3) The time stamp behind the semicolon desig- nates the end of the interval for readout

P.98 Readout from a starting time up to the end of the record in the meter: (ZSTs11;)

4) Both time stamps are inside the interval limits 1) If a time stamp is omitted, then the be- ginning or the end of the logbook record in the meter will be used as the interval limit

13.7 Second log file – storing meter configuratio ns A second log file can be activated in the meter. In that case it is possible to store the last 30 events of a meter configuration change with time and date stamp. This feature can be used to detect unknown manipulation of the meter programming. The following data can be stored:

• Change of meter configuration • Reset of register (billing) data • Reset of billing load profile • Reset of power quality monitoring profile

Page 38: AS220_PR_E_Manual UK.pdf

13 Security functions Page 38 of 67

Product manual 1.9 AS220

13.8 Standard register data list In addition to the log file, the following events, errors or operating malfunctions can be outputted in the AS220 in the normal readout mode, using the appropriate OBIS Identifier. All the parameters can be assigned to one of the 2 data readout list (see chapter 7.1 and 7.2).

• Number of total duration of all power failures • Number of power failures • Beginning and end of the last interruption in power supply • Number of communication processes • Number of maximum resets • Date and time of the last demand reset • Date of last parameterization • Error messages • Status information (power outage, etc., see chapter 9.7)

Additionally the following last 10 events can be displayed in the register data list:

• Counter + Start and end of power outage with time and date stamp (OBIS ID: 96.77. - counter) (OBIS ID: 96.77.xx - last 10 time & date stamps) • Counter + Start and end of reverse energy flow with time and date stamp (OBIS ID: 96.72. - counter) (OBIS ID: 96.72.xx - last 10 time & date stamps) • Counter + Start and end of main cover removal with time and date stamp (OBIS ID: 96.70 - counter) (OBIS ID: 96.70.xx - last 10 time & date stamps) • Counter + Start and end of main cover removal with time and date stamp (OBIS ID: 96.71 - counter) (OBIS ID: 96.71.xx - last 10 time & date stamps) • Counter + Start and end of magnetic field detection with time and date stamp (OBIS ID: 96.78 - counter) (OBIS ID: 96.78.xx - last 10 time & date stamps)

13.9 Data integrity In designing the AS220, special attention has been paid to measuring stability and the integrity of the billing data acquired. The extensive integrity concept is based on several different components. Crucial parts of the hardware are in redundant design. Billing data are, for example, stored in an EEPROM and also held in a buffered RAM. This means the integrity of these data can be cross-checked. In the software, checksums are regularly formed for the crucial billing and parameterization data. Any malfunction is immediately indicated on the display with an informative error message. There is also an option for closing a forwarding contact, if a malfunction occurs. Data are saved automatically in the EEPROM:

• during a power failure • after a tariff or maximum switchover • or at the latest every 24 h

Page 39: AS220_PR_E_Manual UK.pdf

13 Security functions Page 39 of 67

Product manual 1.9 AS220

13.10 Security protection against reprogramming The alpha Meter possesses different security levels.

• Password for all parameter changes

• Selectable IEC address for electrical and optical communication (only by sending the IEC address a successful communication can be achieved)

• Hardware protection by terminal cover removal

• Hardware protection b internal Jumper (under certification seal)

The security protection can be programmed as described in table 2. For optical and electrical interface the following parameters can be secured by different passwords, terminal cover opening separately.

Password Password Password Terminal Hradware 1 2 3 cover Jumper removal A) meter parameters identification X tariff source X switch point clock X demand reset X demand overload X baudrate X Synchronisation X power quality X display settings X display parameters X pulse constants X load profile/log file X energy/demand data X password configuration X X B) formatted commands set time & date X demand reset X reset PQ profile X reset power loss counters X reset terminal cover opening X reset of register data X X reset of log file & load profile X X C) reading commands register data list(billing) service data list log file x load profile x profile of network parameters x

Table 2: Example of security protection of AS220

Page 40: AS220_PR_E_Manual UK.pdf

13 Security functions Page 40 of 67

Product manual 1.9 AS220

13.11 Display of meter status information’s Detailed status information for the meter regarding the state of its inputs and outputs can be read out using appropriate status words, and shown on the display. Status of the inputs/outputs (Status Word 1)

Interpretation of the status word with the OBIS-Identifier C.3:

0 0 0 0 0 0 0 0 | | | | | | | | | | | | | | x x: gen.: status of the control inputs | | | x x x: reserved or not used | | 0 contactor relay closed | | 1 contactor relay open | | 2 contactor relay released for manual switch on (Armed) | 1 contactor relay switch-off by communication | 2 contactor relay switch-off by load limiting function x reserved or not used

Status of internal control signals (Status Word 2)

Interpretation of the status word with OBIS Identifier C.4:

0 0 0 0 0 0 0 0 | | | | | | | | | | | | | | | 1 Maximum tariff M1 active | | | | | | | 2 Maximum tariff M2 active | | | | | | | 4 Maximum tariff M4 active | | | | | | | 8 Maximum tariff M8 active | | | | | | 1 Energy tariff T1 active | | | | | | 2 Energy tariff T2 active | | | | | | 4 Energy tariff T3 active | | | | | | 8 Energy tariff T4 active | | | x x x Reserved or not used | | 8 Directional signal, active + | | 4 Directional signal, reactive + x x Reserved or not used

Status of internal operating states (Status Word 3)

Interpretation of the status word with OBIS Identifier C.5: 0 0 0 0 0 0 0 0 | | | | | | | | | | | | | | x x reserved or not used | | | | | 8 reverse run | | | | 4 measurement in reactive + or - direction (+/-Q) | | | | 8 measurement in active + or - direction (+/-P) | | | 1 terminal cover currently removed | | | 2 main cover currently removed | | 2 tariff source – internal clock | | 4 setting mode active | | 8 parameterization mode active | 1 contactor relay - switch-off by communication | 2 contactor relay - switch-off by load limiting function

2 demand reset disabled, electrical interface (not shown on display) 4 demand reset disabled, optical interface (not shown on display) 8 demand reset disabled, manual push button (not shown on display)

Page 41: AS220_PR_E_Manual UK.pdf

13 Security functions Page 41 of 67

Product manual 1.9 AS220

13.12 Summarize of Anti Tampering features

13.12.1 Terminal cover opening detection To manipulate the meter in most cases the terminal cover has to be opened. The last 10 events can be stored with time and date stamp. Details, see chapter 13.3

13.12.2 Main cover opening detection To manipulate the meter in most cases the main cover has to be opened. The last 10 events can be stored with time and date stamp. Details, see chapter 13.4

13.12.3 Magnetic field detection For manipulating meter big magnetic are used. Even the AS220 can’t be manipulated by magnets it can detect the last 10 events with time and date stamp. Details, see chapter 13.5

13.12.4 Reverse run detection The reverse energy measurement can be used for detect tampering. In that case the exact “tampered energy value” is available. The last 10 events can be stored with time and date stamp. Details, see chapter 13.4

13.12.5 Always run positive measurement The meter can be configured in that way that it always the total energy is measured, even in the case of reverse energy flow. Details, see chapter 5.2.3

13.12.6 Detection of anti creep conditions The duration of anti creep conditions can be measured by the meter. This can be used as an indication of meter manipulation.

13.12.7 Security concept The tampering of the meter configuration is secured by different password levels and additional by opening the terminal cover, which is normally sealed by the utility seal. Details, see chapter 13.9

13.12.8 Logfile All tampering issues, power outages, etc. can be stored with time and date stamp in the logfile of the meter. Details, see chapter 13.5 and 13.6.

Page 42: AS220_PR_E_Manual UK.pdf

14 Instrumentation measurement Page 42 of 67

Product manual 1.9 AS220

14 Instrumentation measurement

14.1 Instantaneous power quality parameters The AS220 meter supports the measurement of the following instantaneous parameters like:

• Voltage and current

• Power factor

• Active-, reactive- and apparent power

• Frequency All parameters can be displayed on the LCD or read out by the optical or electrical interface.

All instantaneous parameter can be assigned to the standard data readout list or in a separate service list.

The updating of the calculation and measuring of the instantaneous data will be done every 1s.

14.2 Instantaneous power quality counters Furthermore the AS220 offers additional features to observe the network regarding power quality issues. Therefore up to 16 different counters with up to 16 thresholds can be configured to detect the occurrence, if a power quality value is above or below a predefined threshold during a user programmable period (1, 2, 3, 4, 5, 6, 10,12, 15,20, 30, 60 minutes).

Furthermore 2 log file events and 2 relay contacts can be activated if 1 or more events will be above or below the predefined threshold.

PQ quantity Threshold Counter Log file Event 1

Log file Event 2

Relay 1

Relay 2

See chapter 14.1 > threshold 1a

< threshold 1b

Counter 1a

Counter 1b

See chapter 14.1 > threshold 2a

< threshold 2b

Counter 1a

Counter 1b

See chapter 14.1 > threshold 3a

< threshold 3b

Counter 1a

Counter 1b

See chapter 14.1 > threshold 4a

< threshold 4b

Counter 1a

Counter 1b

See chapter 14.1 > threshold 5a

< threshold 5b

Counter 1a

Counter 1b

See chapter 14.1 > threshold 6a

< threshold 6b

Counter 1a

Counter 1b

See chapter 14.1 > threshold 7a

< threshold 7b

Counter 1a

Counter 1b

See chapter 14.1 > threshold 8a

< threshold 8b

Counter 1a

Counter 1b

Page 43: AS220_PR_E_Manual UK.pdf

14 Instrumentation measurement Page 43 of 67

Product manual 1.9 AS220

14.3 Load profiling of power quality parameters The load profiling of the network parameters supports the following characteristic:

• Use of EN62056-21 protocol, identical to the readout of the load profile of the billing data

• Readout by optical and electrical interface

• Separate load profile interval (1 .. 60min)

• All parameters can be changed without breaking the certification seal

• Up to 8 load profile channels

• Recording of the following parameters

• Voltage and current per phase

• Power factor per phase

• Active-, reactive- and apparent power

• Frequency

• Recording type per channel

• Average value per interval

• Minimum value per interval

• Maximum value per interval

• Data storage depends on the size of the load profile of the billing data The status bits of the network parameter profile are designed as :

MG: Measurement disturbed The bit is set at the end of the interval, if after an initialization or after a power up not all values are calculated.

UV: Change of time & date With every time&date change the actual interval will be aborted

SA: Power outage

With every power outage the actual interval will be aborted SW: Power up

After every power up the bit will be set at the end of the interval

Page 44: AS220_PR_E_Manual UK.pdf

15 Integrated connect / disconnect relay Page 44 of 67

Product manual 1.9 AS220

15 Integrated connect / disconnect relay With the integrated connect / disconnect relay the possibility exists to connect or disconnect the end consumer remotely. The integrated relay can be used for switching up to 100A.

15.1 Remote connect / disconnect The integrated disconnect relay offers the attached feature set, which can be controlled remotely using the GSM/GPRS communication module.

• A formatted command to switch the relay ON/OFF is supported

• The disconnect relay status will be updated every 1min

• After the relay is switched OFF the LCD of the meter indicates “rel. OFF” 7 digit fileld “Ctr” 3 identifier digits field

• If the relay was switched OFF, an “ARM” command has to be send to the meter to allow the customer to switch ON.

• After sending the “ARM” command to the meter, on the LCD the following message appears:

“PRESS.ON” 7 digits field “Ctr” 3 identifier digits field

• When the “PRESS.ON” message appears on the display the customer has to press the push button >4s.

• Pressing the push button shortly (<2s) the meter displays its standard display menu

• After leaving the standard display menu “PRESS.ON” will be displayed again

15.2 Load limiting function • The relay can be controlled by a load limiting threshold ( all PQ values can be used:

voltage, current, demand, frequency, ...). The relay switches OFF, if the actual PQ value is above a limit for longer than a predefined time (1..255s).

• The load limiting threshold can be changed by a formatted command

• The disconnect relay status will be updated every 1min

• After the relay was switched OFF the LCD indicates “rel. OFF” 7 digits “LLi” 3 identifier digits

• After a programmable time (1…255min, actually this time is set equal “0”) the LCD will indicate the message

“PRESS.ON” 7 digits “LLi” 3 identifier digits

• When the “PRESS.ON” message appears on the display the customer has to press the push button >4s.

• Pressing the pushbutton shortly (<2s) the meter displays its standard display menu

• After leaving the standard display menu “Rel.OFF” or PRESS.ON” will be displayed

Page 45: AS220_PR_E_Manual UK.pdf

16 Communication module Page 45 of 67

Product manual 1.9 AS220

16 Communication module For Smart Metering application a modular communication module can be fit in the AS220 meter, see fig 9. Different communication modules are available

Fig. 9: AS220 with integrated communication module In general the interface between meter and communication module provides the following feature set:

• A connection to 230V for a separate power supply of the module

• Isolated communication interface to read the AS220 meter data (Rx, Tx). The used protocol is based on EN62056-21

• 2 wire connection to the terminals for additional wired communication, placed on the terminal block of the meter

• 3 wire connection to the terminal block as a customer interface, placed on the terminal block of the meter

16.1 AM100 module – GSM/GPRS The AM100 module offers the following features:

• NTA 8130 compatible solution, DSMR V2.2

• customer interface (RJ11 connector on the AM100 module) free accessible

• WAN-communication between module and AMI server using GSM/GPRS technology

• WAN protocols based on DLMS/COSEM

• Wireless M-Bus communication (868MHz) to read gas and water meters according the EN 13757-4 standard

• Wired M-Bus communication to read gas and water meters according the EN 13757-3 standard

• Up to 4 wireless or wired M-Bus meters can be connected to the module

• Up to 8 status indication LED’s

For more details of the communication module, see AM100_pr_E.pdf

+

=

Page 46: AS220_PR_E_Manual UK.pdf

16 Communication module Page 46 of 67

Product manual 1.9 AS220

16.2 AM700 module – RS485 + DLMS protocol support The AM700 module offers the following features:

• RS485 interface for connection up to 32 meters to a bus

• EN62056-21 to DLMS protocol converter

Electrical characteristics: terminals brought out: RT+ (Data+), RT- (Data-) Protocol: as per EN 62056-21 Baud rate: max. 9600 baud Terminating resistor: The bus has to be terminated with 100 ohm. By using the RS485 interface up to 32 meters can be connected with a line length of 1000m. The used protocol corresponds to EN 62056-21. In that case the IEC meter address should be used for reading the meters. In the following figure describes the way to use the RS485 interface in combination with different meter types. 2-wire connection (terminals)

28 RS485, RT- (Data-) 27 RS485, RT+ (Data+) remark: The RS485 bus has to be terminated (active) at modem side. At all

ELSTER modems this this realized already internaly.

Fig. 10 Connection of AS220 with AM700 module using the RS485 interface

Data- Data- Data- Data+ Data+ Data+

Data+

100 Ohm Data-

HHU or PC or Modem

100 Ohm

390 Ohm

390 Ohm

-

+

Page 47: AS220_PR_E_Manual UK.pdf

17 Calibration and test Page 47 of 67

Product manual 1.9 AS220

17 Calibration and test

17.1 Calibration The alpha meter AS220 has been adjusted in the factory, with the calibration constants matched to the software concerned. Subsequent calibration by the customer is not required.

17.2 Accuracy test using a test bench For testing the AS220 meter with a test bench the user should be aware that the AS220 has no voltage and current bridges.

17.3 Manufacturer specific test mode By sending a formatted command through the optical interface, the meter can be put into a special test mode, for reducing the test duration’s involved. In this test mode, the following parameters can be selected:

• Automatic increase in the decimal places for energy values to 3, 4 • Increase in the LED's flashing frequency (Imp/kWh)

• Increase the flashing frequency (Imp/kWh) of the pulse outputs

• Assignment of measured variables (+P, -P, Q1 .. Q4) to the LED

Remark: this feature is necessary for testing the reactive energy measurement • Selection of desired energy (T1-T4) or demand tariff (M1-M4)

If you switch over to call mode during the test mode, the Identifier selected and the corresponding measured value will remain on the display until a new call is made or the power supply is interrupted. The measured-value display is continually updated. The test mode can be quit via the following events:

• Formatted command

• 24 hours after activation

• pressing the [A]-button >5s

Page 48: AS220_PR_E_Manual UK.pdf

17 Calibration and test Page 48 of 67

Product manual 1.9 AS220

17.4 Simplified test mode For a simple function test routine not requiring any special software tools, you can use the following function: if you select a power or energy value in the display, the LED will flash either in accordance with (+P/-P) or in accordance with the reactive power (Q1 .. Q4). This makes it relatively easy to detect which value is being measured. The maximum retention time of the display value can be set by the customer. If you press the parameterization key before this test, then the display values selected will be retained in the display.

17.5 Simple creep and anti-creep test The shortened creep and anti-creep test can be shown on the LC display or the shared LED.

• Display Arrow in display "ON": meter starts measuring

Arrow in display "OFF": no energy is being measured. This applies for all 4 possible energy types (+P, -P, +Q, -Q)

• LED

"Standstill" is signaled by a steady-light at the LED. In any other case the LED indicates energy-proportional pulses.

17.6 Checksum display By configuration it is possible to display a checksum over all setting- and parametrization classes of the meter. With that 8 digit number is very easy for the customer to proof, if the meters have an identical parameterization.

Page 49: AS220_PR_E_Manual UK.pdf

18 User program Page 49 of 67

Product manual 1.9 AS220

18 User program

18.1 Reading and configuration tool alphaset The alpha Meter can be read out, set and parameterized via the optical or electrical interface, in accordance with the EN 62056-21 protocol. For this purpose, you need the alphaSET readout and setting tool, which can be used to alter and read out the meter's register contents, load profile and logfile data and all setting parameters. The program is a 32-Bit application and runs under Windows 95/98, Windows 2000, Windows XP and Windows NT. AlphaSET supports the following functionality:

Readout parameters • standard data list • Service list (second data readout list) • Log file • Load profile of billing data • Profile of instrumentation parameters • Complete meter configuration

Change of meter parameters

• Identification and passwords • Switch time clock parameters • Demand reset parameters • Baud rates • Pulse constants • Load profile parameters of billing data • Instrumentation parameters • Parameters of instrumentation profile

Formatted commands

• Set time and date • Set pulse constant • Reset all counters • Reset profile of instrumentation parameters • Reset load profile of billing data • Reset register data

All parameters can be readout or changed remotely by using transparent GSM or PSTN modems

Page 50: AS220_PR_E_Manual UK.pdf

19 Installation and start-up Page 50 of 67

Product manual 1.9 AS220

19 Installation and start-up

19.1 Installation and general function control The meter is mechanically secured in place by first suspending it in the upper eye, and screwing it into position through the two bottom mounting points to the left and right of the terminal block. The suspension eye enables the meter to be installed in either an open or concealed configuration as desired. Using these 3 mounting points, the meter is installed on a meter panel. If the meter has started up, this will be indicated directly by an arrow in the display, and by the energy pulse LED, which will flash in accordance with the preset pulse constant (Fig. 10).

Fig 10 Front view of the AS220

1 LC Display 2 Alternate button 3 Name plate 4 Optical interface

5 Utility seal 6 Energy pulse diode 7 Main cover 8 Terminal cover 9 Communication module 10 Certification seal

9

1

3

4

6 2

10

7

8

5

Page 51: AS220_PR_E_Manual UK.pdf

19 Installation and start-up Page 51 of 67

Product manual 1.9 AS220

19.2 Installation check using the meter display After the meter has been properly connected, its function can be tested as follows: Scroll mode As long as the alternate button is not pressed, the scroll mode will

appear. Depending on the version involved, this may consist of one value or of several values, shown in a rolling display mode.

Display check When the alternate button is pressed, the first thing to appear is the

display check. All segments of the display must be present. Pressing the alternate

button will switch the display to its next value. Error message If the display check is followed by an error message, it can be

interpreted as explained in Section 9. Fast run-through If the alternate button is repeatedly pressed at intervals of 2s < t <5s ,

all the main values provided will appear. Creep check If the meter starts measuring, the energy pulse diode will blink

according the measured energy. The relevant arrows (+P, -P, +Q, -Q) on the display are switched ON after 2-3s. Anti creep check If the meter is in idling mode, the energy pulse diode will be

continuously lit up. The relevant arrows (+P, -P, +Q, -Q) on the display are also switched off.

Page 52: AS220_PR_E_Manual UK.pdf

19 Installation and start-up Page 52 of 67

Product manual 1.9 AS220

19.3 Installation recommendations During the installation the following issues should be considered

WARNING

Installation must be always carried out by appropriately trained and qualified personnel in accordance with normal metering custom and practice.

The installer is responsible for the choice of connecting cables that must be appropriate for the voltage and current rating of the meter and for ensuring that the supply is properly fused. It is recommended that meters are protected by fuses equal to the meter rating. i.e. fuse for a meter.

Isolate all circuits before carrying out the installation.

Refer to the nameplate to ensure that the correct meter is being installed.

Refer to the connection diagram inside the terminal cover. Failure to comply with these instructions may result in damage and/or electric shock

Page 53: AS220_PR_E_Manual UK.pdf

20 Type key Page 53 of 67

Product manual 1.9 AS220

20 Type key

AS220 - _ _ _ _ - _ _ _ - _ _ _ - _ _ _ _ _ - _ _ _ _ _

Direct connection D Direct connection (BS) B

220V H 230V 7

5 (80) A 1 5 (60) A 5 5 (100) A 6 10 (60) A 7 10 (80) A 8 10 (100) A 9 20 (100) A D

class 1 1 class 2 2

class A A class B B quantity +P 1 quantity +P,-P 2 quantity +P,+Q 3 quantity +P,Q1,Q4 4 quantity +P,-P,+Q,-Q 5 quantity +P,-P,Q2,Q3 6 quantity +P,-P,Q1..Q4 7 quantity +P,Q1 8 quantity +P,+Q,-Q 9

quantity +P,-P,+Q,-Q,Q1,Q3 A quantity +P,+Q,Q4 F

1 energy tariff 1 2 energy tariffs 2 3 energy tariffs 3 4 energy tariffs 4

1 demand tariff 1

2 demand tariffs 2 3 demand tariffs 3 4 demand tariffs 4

0 no demand tariff 0

No ripple receiver O

real time clock with calendar S

Page 54: AS220_PR_E_Manual UK.pdf

20 Type key Page 54 of 67

Product manual 1.9 AS220

AS220 - _ _ _ _ - _ _ _ - _ _ _ - _ _ _ _ _ - _ _ _ _ _

exchangeable battery option E

no external control input 0 no mech. output relay 0 1 S0 output relay (pulse or control output) 1

no electronic output relay 0

Load profile, 8 channels, (1 channel, 30 days, 15min) A Load profile, 8 channels, (1 channel, 260 days, 15min) B

No load profile storage 0

electrical interface for comms module with aux. terminals M electrical interface for comms module without aux. terminals N

Backlightened Display B

Detection of terminal & main cover opening D no detection 0

Standard value measurement, 0 Absolute value measurement, (P = /+P/ ) B

With integrated disconnect relay (up to 100A) S Without integrated disconnect relay (up to 100A) 0 nominal frequency, 50Hz 0 nominal frequency, 60Hz 1

Page 55: AS220_PR_E_Manual UK.pdf

21 Name plate Page 55 of 67

Product manual 1.9 AS220

21 Name plate The alpha Meter's rating plate contains the following mandatory information: - Property Number - Accuracy Class - Serial Number - Output and test pulse constants - Manufacturer - Meter and consumption type - Model designation - Symbol for degree of protection - Year of manufacture - identifier system - Conformity symbol - Rated voltage - Rated/Limit current intensity ratio - Rated frequency

Fig. 15 Example for the alpha Meter's rating plate design

Page 56: AS220_PR_E_Manual UK.pdf

22 Technical data of the AS220 Page 56 of 67

Product manual 1.9 AS220

22 Technical data of the AS220 Nominal voltage 2-wire, 1-system

220V .. 240V -20% .. +15%

Nominal frequency 50/60Hz +/-5%

Nominal/maximum current

Continuous current Short duration

DC: 5(60)A, 5(80)A, 20(100)A, 5(100)A DC: 7000A for 3 cycles

Starting current < 16mA

Accuracy EN 62053-21 EN 50470-1 and EN 50470-3

Class 1 or 2 Class A or B acc. MID

Power supply

Nominal voltage Capacitive power supply, working range –20% .. +15% Un >400V for longer than 4h

1 electronic outputs Acc. S0 standard Acc. EN62053-3

interfaces Optical interface Electrical interface to E-meter WAN communication LAN communication

As per EN 62056-21, up to 9600 Baud GSM/GPRS using different modes transparent mode, EN62056-21 DLMS/COSEM protocol Wireless M-Bus acc. EN 13757-4

Internal tariff source 4 tariffs 4 seasons weekday dependent tariff scheme

Acc. EN 62054-21

Time backup for RTC Battery Accuracy

> 10 years continuous operation at 25o C, shelf life of 5 years < 5ppm or <0,5s/day

Time backup for readout without main power

Supercap Internal battery Additional exchangeable battery

0,5 days 4 years, depending on number of readouts 7 years, depending on number of readouts

Integrated disconnect relay

Current rate Number of switchings

up to 100A 10.000

Temperature conditions

Operating temperature Storage temperature Humidity Temperature coefficient

-40°C ... +70°C -40°C ... +80°C 0 ..100% rel. humidity, non-condensing <0,01% per oC (PF=1 and PF=0,5)

EMC compatibility

Surge withstand (1,2/50us) Dielectric test

6kV, Rsource = 2 Ohm 4kV, 1 min, 50Hz MID E2

Power consumption Basic meter Basic meter + comms module

1W, 7VA per phase

Connections Main terminals Auxiliary terminals

Ø = 9,0mm Ø = 4,0mm

Housing DIN dimensions BS version Degree of protection: Material

DIN 43857 Part 2 BS 7856 Housing: IP54, terminal block IP31 Polycarbonite, flame-retardant, Self-extinguishing plastic, recyclable, MID M1

weight < 0,4 kg (without module)

Page 57: AS220_PR_E_Manual UK.pdf

23 OBIS identifiers of AS220 Page 57 of 67

Product manual 1.9 AS220

23 OBIS identifiers of AS220 In the following chapter all the OBIS-identifiers are listed, that are supported by the meter AS220. All data can be readout on the LCD or optical/electrical interface. The amount of OBIS identifiers can be roughly subdivided into two large groups:

1. Identifiers for measuring values; these are starting with a number between 1 and 89. 2. Identifiers for general purpose objects ; these are starting either with a “0”, a “C” or a

“96”

23.1 Identifiers for measuring values As mentioned above, these are starting with a number between 1 and 89 (after the optional “medium/channel”-sequence); these are called “value group C” in EN 62056-61. The number represents the type of measuring, e.g. 1 = “active power +” or 31 = current L1”.

The second number (“value group D”) stands for the measuring type, e.g. x.5 = “last average” or 8 = “time integral 1”.

The third number represents the actual tariff; if 0 ⇒ no rate.

Below you will find a list of all possible combinations, delivered by the meter. In order to shorten the list, the tariff, if delivered, is represented by the placeholder “t”, this can be a cipher 0..4.

23.1.1 Power Measuring

OBIS Plain Text Links

1.2.t +P, cumulative maximum, tariff „t“ 2.2.t -P, cumulative maximum, tariff „t“ 3.2.t +Q, cumulative maximum, tariff „t“ 4.2.t -Q, cumulative maximum, tariff „t“ 5.2.t Q1, cumulative maximum, tariff „t“ 6.2.t Q2, cumulative maximum, tariff „t“ 7.2.t Q3, cumulative maximum, tariff „t“ 8.2.t Q4, cumulative maximum, tariff „t“ 9.2.t +S, cumulative maximum, tariff „t“ 10.2.t -S, cumulative maximum, tariff „t“

1.4.0 +P, minutes and average of actual period 2.4.0 -P, minutes and average of actual period 3.4.0 +Q, minutes and average of actual period 4.4.0 -Q, minutes and average of actual period 5.4.0 Q1, minutes and average of actual period 6.4.0 Q2, minutes and average of actual period 7.4.0 Q3, minutes and average of actual period 8.4.0 Q4, minutes and average of actual period 9.4.0 +S, minutes and average of actual period 10.4.0 -S, minutes and average of actual period

Page 58: AS220_PR_E_Manual UK.pdf

23 OBIS identifiers of AS220 Page 58 of 67

Product manual 1.9 AS220

OBIS Plain Text Links

1.5.0 +P, average of last measuring period 2.5.0 -P, average of last measuring period 3.5.0 +Q, average of last measuring period 4.5.0 -Q, average of last measuring period 5.5.0 Q1, average of last measuring period 6.5.0 Q2, average of last measuring period 7.5.0 Q3, average of last measuring period 8.5.0 Q4, average of last measuring period 9.5.0 +S, average of last measuring period 10.5.0 -S, average of last measuring period

1.6.t +P, demand, tariff “t” 2.6.t -P, demand, tariff “t” 3.6.t +Q, demand, tariff “t” 4.6.t -Q, demand, tariff “t” 5.6.t Q1, demand, tariff “t” 6.6.t Q2, demand, tariff “t” 7.6.t Q3, demand, tariff “t” 8.6.t Q4, demand, tariff “t” 9.6.t +S, demand, tariff “t” 10.6.t -S, demand, tariff “t”

1.6.t*vv +P, demand, tariff “t”, historical value 2.6.t*vv -P, demand, tariff “t”, historical value 3.6.t*vv +Q, demand, tariff “t”, historical value 4.6.t*vv -Q, demand, tariff “t”, historical value 5.6.t*vv Q1, demand, tariff “t”, historical value 6.6.t*vv Q2, demand, tariff “t”, historical value 7.6.t*vv Q3, demand, tariff “t”, historical value 8.6.t*vv Q4, demand, tariff “t”, historical value 9.6.t*vv +S, demand, tariff “t”, historical value 10.6.t*vv -S, demand, tariff “t”, historical value

Page 59: AS220_PR_E_Manual UK.pdf

23 OBIS identifiers of AS220 Page 59 of 67

Product manual 1.9 AS220

23.1.2 Energy Measuring

OBIS Plain Text Links

1.8.t +A, active energy, tariff „t“ 2.8.t -A, active energy, tariff „t“ 3.8.t +R, reactive energy, tariff „t“ 4.8.t -R, reactive energy, tariff „t“ 5.8.t R1, reactive energy, tariff „t“ 6.8.t R2, reactive energy, tariff „t“ 7.8.t R3, reactive energy, tariff „t“ 8.8.t R4, reactive energy, tariff „t“ 9.8.t +S, apparent energy, tariff „t“ 10.8.t -S, apparent energy, tariff „t“

1.8.t*vv +A, active energy, tariff „t“, historical value 2.8.t*vv -A, active energy, tariff „t“, historical value 3.8.t*vv +R, reactive energy, tariff „t“, historical value 4.8.t*vv -R, reactive energy, tariff „t“, historical value 5.8.t*vv R1, reactive energy, tariff „t“, historical value 6.8.t*vv R2, reactive energy, tariff „t“, historical value 7.8.t*vv R3, reactive energy, tariff „t“, historical value 8.8.t*vv R4, reactive energy, tariff „t“, historical value 9.8.t*vv +S, apparent energy, tariff „t“, historical value 10.8.t*vv -S, apparent energy, tariff „t“, historical value

1.9.t +A, active „delta“ energy, tariff „t“ 2.9.t -A, active „delta“ energy, tariff „t“ 3.9.t +R, reactive „delta“ energy, tariff „t“ 4.9.t -R, reactive „delta“ energy, tariff „t“ 5.9.t R1, reactive „delta“ energy, tariff „t“ 6.9.t R2, reactive „delta“ energy, tariff „t“ 7.9.t R3, reactive „delta“ energy, tariff „t“ 8.9.t R4, reactive „delta“ energy, tariff „t“ 9.9.t +S, apparent „delta“ energy, tariff „t“ 10.9.t -S, apparent „delta“ energy, tariff „t“

1.9.t*vv +A, active „delta“ energy, tariff „t“, historical value 2.9.t*vv -A, active „delta“ energy, tariff „t“, historical value 3.9.t*vv +R, reactive „delta“ energy, tariff „t“, historical value 4.9.t*vv -R, reactive „delta“ energy, tariff „t“, historical value 5.9.t*vv R1, reactive „delta“ energy, tariff „t“ , historical value 6.9.t*vv R2, reactive „delta“ energy, tariff „t“, historical value 7.9.t*vv R3, reactive „delta“ energy, tariff „t“, historical value 8.9.t*vv R4, reactive „delta“ energy, tariff „t“, historical value 9.9.t*vv +S, apparent „delta“ energy, tariff „t“, historical value 10.9.t*vv -S, apparent „delta“ energy, tariff „t“, historical value

Page 60: AS220_PR_E_Manual UK.pdf

23 OBIS identifiers of AS220 Page 60 of 67

Product manual 1.9 AS220

23.1.3 Instantaneous Values

OBIS Plain Text Links

21.7.0 +P, L1, instantaneous value, total 22.7.0 -P, L1, instantaneous value, total 23.7.0 +Q, L1, instantaneous value, total 24.7.0 -Q, L1, instantaneous value, total 29.7.0 +S, L1, instantaneous value, total 30.7.0 -S, L1 instantaneous value, total 31.7.0 I, L1, instantaneous value, total 32.7.0 U, L1, instantaneous value, total 33.7.0 LF, L1, instantaneous value, total 34.7 f, L1, instantaneous value, total

23.1.4 Supervision Data

OBIS Plain Text Links

21.32.0 +P, L1, power quality supervision, lower limit 22.32.0 -P, L1, power quality supervision, lower limit 23.32.0 +Q, L1, power quality supervision, lower limit 24.32.0 -Q, L1, power quality supervision, lower limit 29.32.0 +S, L1, power quality supervision, lower limit 30.32.0 -S, L1, power quality supervision, lower limit 31.32.0 I, L1, , power quality supervision, lower limit 32.32.0 U, L1, power quality supervision, lower limit 33.32.0 LF, L1, power quality supervision, lower limit 34.32.0 F, L1, power quality supervision, lower limit

21.36.0 +P, L1, power quality supervision, upper limit 22.36.0 -P, L1, power quality supervision, upper limit 23.36.0 +Q, L1, power quality supervision, upper limit 24.36.0 -Q, L1, power quality supervision, upper limit 29.36.0 +S, L1, power quality supervision, upper limit 30.36.0 -S, L1, power quality supervision, upper limit 31.36.0 I, L1, , power quality supervision, upper limit 36.36.0 U, L1, power quality supervision, upper limit 33.36.0 LF, L1, power quality supervision, upper limit 34.36.0 F, L1, power quality supervision, upper limit

Page 61: AS220_PR_E_Manual UK.pdf

23 OBIS identifiers of AS220 Page 61 of 67

Product manual 1.9 AS220

23.2 General Purpose Objects 23.2.1 Objects, that OBIS-identifier starts with “0 ”

OBIS Plain Text Formatting

0.0.0 Utility identification #1 0.0.1 Utility identification #2 0.0.2 Utility identification #3 0.0.3 Utility identification #4 0.0.4 Utility identification #5 0.0.5 Utility identification #6

0.1.0 demand reset counter 0.1.0(nn)<CR><LF> | | | +----- 2 ciphers 00..99 +----------- OBIS identifier

0.1.2 Date of demand reset 0.1.3 Time of demand reset

0.2.0 program revision No. 0.2.0(iiii)<CR><LF> | | | +----- length 4 ASCII-chars +----------- OBIS identifier

0.2.1 parameter set identification 0.2.2 time switch program no.

0.2.x(iiiiiiii)<CR><LF> | | | +----- length 8 ASCII-chars +----------- OBIS identifier

0.3.0 LED pulse constant active energy 0.3.1 LED pulse constant reactive energy 0.3.3 Output pulse constant active energy 0.3.4 Output pulse constant reactive energy

0.3.x(123456.12)<CR><LF> | | || | | |+---- 2 decimals | | +----- decimal dot | +----------- 1 to 6 pre-dot ciphers +----------------- OBIS identifier

0.5.1.1 Demand overload No. 1 0.5.1.2 Demand overload No. 2

0.51 Current meter season 0.51(n)<CR><LF> | | | +----- 1 cipher 1..4 +---------- OBIS identifier

0.8.0 Measurement period (the length of .. in minutes)

0.8.0(nn)<CR><LF> | | | +----- 2 ciphers 01..60 +----------- OBIS identifier

0.9.0 Number of days since last reset 0.9.0(nn)<CR><LF> | | | +----- 2 ciphers 00..99 +----------- OBIS identifier

0.9.1 Current meter time 0.9.2 Current meter date

0.9.5 Current day of week 0.9.5(n)<CR><LF> | | | +----- 1 cipher 1..7 +----------- OBIS identifier

Page 62: AS220_PR_E_Manual UK.pdf

23 OBIS identifiers of AS220 Page 62 of 67

Product manual 1.9 AS220

23.2.2 Objects, that OBIS-identifier starts with “C ”

OBIS Plain Text Formatting

C.1.0 Meter serial number C.1.0(iiiiiiii)<CR><LF> | | | +---- length 8 ASCII-chars +---------- OBIS identifier

C.1.3 Date of production C.2.0 Number of parameterisations C.2.0(nn)<CR><LF>

| | | +----- 2 ciphers 00..99 +----------- OBIS identifier

C.2.1 Date of last parameterisation change C.2.5 Date of calibration C.3.0 State of inputs / outputs C.4.0 State of internal signals C.5.0 Internal states

C.6.0 battery usage timer C.7.0 Sum of total power failures of all 3 lines

0.x.0(123456)<CR><LF> | | | +----- length 6 ciphers +----------- OBIS identifier

C.50 Tariff hours weekdays C.51 Tariff hours saturday C.52 Tariff hours sunday C.52 Start date of last total power failure C.53 Start time of last total power failure C.54 End date of last total power failure C.55 End time of last total power failure C.56 total time of ALL power fails / battery

use time counter C.56(123456)<CR><LF> | | | +------ length 6 ciphers +----------- OBIS identifier

C.60 Date of last communication C.61 Date of last demand reset C.63 Remaining time in interval C.63(mm:ss)<CR><LF>

| | | +----- minutes:seconds +---------- OBIS identifier

C.65 Parameter checksum C.65(hhhhhhhh)<CR><LF> | | | +----- checksum 8 Hex-chars +---------- OBIS identifier

C.70 Source of tariffs/demand reset C.70(nn)<CR><LF>

| | | +------ 2 hex chars 00..FF +----------- OBIS identifier

C.60 Tariff periods weekdays C.61 Tariff periods saturday C.62 Tariff periods sunday C.64 Demand period weekday C.65 Demand period saturday C.66 Demand period sunday

Page 63: AS220_PR_E_Manual UK.pdf

23 OBIS identifiers of AS220 Page 63 of 67

Product manual 1.9 AS220

OBIS Plain Text Formatting

C.77.1 Start and end of power outage with time & date stamp, phase 1

C.77.5 Start and end of reverse run detection with time & date stamp

C.77.6 Start and end of magnetic detection with time & date stamp

23.2.3 Objects, that OBIS-identifier starts with “9 6”

These objects are absolutely identical to those, which are starting with “C“. So, you can just replace the “C“ with “96“ – and vice versa.

23.2.4 Objects, that OBIS-identifier starts with “P ”

OBIS Plain Text Formatting

P.98 Log file P.01 Load profile of billing data P.02 Profile of power quality data

23.2.5 Objects, that OBIS-identifier starts with “F ”

OBIS Plain Text Formatting

F.F Fatal errors F.F.1 Non fatal errors F.F.2 warnings F.F.3 warnings F.F.4 warnings

Page 64: AS220_PR_E_Manual UK.pdf

24 Dimensions of AS220 Page 64 of 67

Product manual 1.9 AS220

24 Dimensions of AS220 24.1 Outside dimension of AS220 (BS standard)

Fig 16: Outside dimensions of the AS220 housing (BS standard)

Page 65: AS220_PR_E_Manual UK.pdf

24 Dimensions of AS220 Page 65 of 67

Product manual 1.9 AS220

24.2 Terminal block of AS220 meter (BS standard)

Fig 19 terminal block of direct connected AS220 (BS version)

Page 66: AS220_PR_E_Manual UK.pdf

24 Dimensions of AS220 Page 66 of 67

Product manual 1.9 AS220

24.3 Outside dimension of AS220 (DIN standard)

Fig 20: Outside dimensions of the AS220 housing (DIN standard)

Page 67: AS220_PR_E_Manual UK.pdf

24 Dimensions of AS220 Page 67 of 67

Product manual 1.9 AS220

24.4 Terminal block of AS220 meter (DIN standard)

Fig 21 terminal block of direct connected AS220 (DIN version)