Download pdf - Imhoff Tank

Transcript

7/17/2019 Imhoff Tank

http://slidepdf.com/reader/full/imhoff-tank-568ce9d41d32b 1/17

Imhoff Tank 

The Imhoff tank was developed to correct the two main defects of the septic tank.

1. It prevents the solids once removed from the sewage from again being mixed with it, but

still provides for the decomposition of these solids in the same unit

2. It provides an effluent amenable to further treatment.

Contact between the waste stream and the anaerobic digesting sludge is practically eliminated

and the holding period in primary settling compartment at the tank is reduced. The Imhoff tank

may be either circular or rectangular and is divided into three compartments

1. the upper section or sedimentation compartment

2. the lower section known as the digestion compartment and

!. the gas vent and scum section

It is desirable to be able to reverse the direction of flow to prevent excessive deposition of solids

at one end of the sedimentation compartment. "eriodically reversing the flow will result in an

even accumulation of sludge across the bottom of the tank. In operation, all of the wastewater

flows through the upper compartment. #olids settle to the bottom of this sloped compartment,

slide down and pass through an opening or slot to the digestion compartment. $ne of the bottom

slopes extends at least six inches beyond the slot. This forms a trap to prevent gas or digesting

sludge particles in the lower section from entering the waste stream in the upper section. The

gas and any rising sludge particles are diverted to the gas vent and scum section.

Imhoff Tank Operation 

There are no mechanical parts in an Imhoff tank. %ttention should, however, be given to the

following

1

7/17/2019 Imhoff Tank

http://slidepdf.com/reader/full/imhoff-tank-568ce9d41d32b 2/17

a. &aily removal of grease, scum and floating solids from the sedimentation compartment.

 b. 'eekly scraping of the sides and sloping bottoms of the sedimentation compartment by a

rubber s(ueegee to remove adhering solids which may decompose.

c. 'eekly cleaning the slot at the bottom of the sedimentation compartment. This can be

done by use of a chain drag.

d. "eriodic reversal of flow where provided for in the design of the tank.

e. Control of the scum in the scum chamber, by breaking it up, hosing with water under

 pressure, keeping it wet with supernatant from the digestion compartment and removal if

the depth approaches two to three feet.

f. )emoval of sludge should be done before the sludge depth approaches within 1* inches

of the slot in the sedimentation compartment. It is better to remove small amounts

fre(uently than large amounts at long intervals. #ludge should be removed at a slow

regular rate to avoid coning +i.e. the formation of a channel through the sludge whichwould permit partially digested sludge and li(uid held in storage above the digested sludge

to be withdrawn from the tank. -efore winter temperatures are expected, most of the

digested sludge except that necessary for seeding +about 2 percent should be removed to

 provide space for winter accumulations when digestion is very slow. The height of the

sludge in the sludge compartment should be determined at inlet and outlet end of the tank

at least once a month.

g. %fter each time that sludge is removed, the sludge pipes should be flushed and drained to

 prevent sludge from hardening in and clogging the pipes.

h. "revention of /0oaming/. very effort should be made to prevent /foaming/ because

correction after the condition arises is sometimes difficult. /0oaming/ is usually

associated with an acid condition of the sludge and in such cases may be prevented or

corrected by treatment with lime or sodium bicarbonate to counteract the acidity of the

sludge. There are a few simple measures which may, under certain circumstances, remedy

or improve the condition.

1. The use of hydrated lime or sodium bicarbonate added to the gas

vents will usually aid in correction. The p value of the resulting sludge and lime

mixture in the digestion compartment should not exceed 3.4.

2. )emoving the tank from service where possible for a few days and

allowing it to rest will sometimes improve conditions.

!. %gitation of the gas vent area with a water hose or paddles will

sometimes help.

The Imhoff tank has no mechanical parts and is relatively easy and economical to operate. It

 provides sedimentation and sludge digestion in one unit and should produce a satisfactory

 primary effluent with a suspended solids removal of 5 to 4 percent and a -$& reduction of 16

to !6 percent. The two7story design re(uires a deep over7all tank. "rimary tanks with separate

digesters have largely replaced the Imhoff tank for large municipal installations. The Imhofftanks is best suited to small municipalities and large institutions where the tributary population is

6, or less, and a greater degree of treatment is not needed.

2

7/17/2019 Imhoff Tank

http://slidepdf.com/reader/full/imhoff-tank-568ce9d41d32b 3/17

3

7/17/2019 Imhoff Tank

http://slidepdf.com/reader/full/imhoff-tank-568ce9d41d32b 4/17

1. Imhoff tank  

0rom 'ikipedia, the free encyclopedia8ump to navigation, search 

Imhoff tank 

The Imhoff tank , named for German engineer  9arl Imhoff  +1*34:1;46, is a chamber suitablefor the reception and processing of sewage. It may be used for the clarification of sewage by

simple settling and sedimentation, along with anaerobic digestion of the extracted sludge. It

consists of an upper chamber in which sedimentation takes place, from which collected solids

slide down inclined bottom slopes to an entrance into a lower chamber in which the sludge is

collected and digested. The two chambers are otherwise unconnected, with sewage flowing only

through the upper sedimentation chamber and no flow of sewage in the lower digestion chamber.

The lower chamber re(uires separate biogas vents and pipes for the removal of  digested sludge,

typically after 47; months of digestion. The Imhoff tank is in effect a two7story septic tank  and

retains the septic tank<s simplicity while eliminating many of its drawbacks, which largely result

from the mixing of fresh sewage and septic sludge in the same chamber.

Imhoff tanks are being superseded in sewage treatment by plain sedimentation tanks using

mechanical methods for continuously collecting the sludge, which is moved to separate digestion

tanks. This arrangement permits both improved sedimentation results and better temperature

control in the digestion process, leading to a more rapid and complete digestion of the sludge.

% test for settleable solids in water, wastewater and stormwater uses an Imhoff cone, with or

without stopcock . The volume of solids is measured after a specified time period at the bottom

of a one7liter cone using graduated markings. =1>

Primary Treatment 

4

7/17/2019 Imhoff Tank

http://slidepdf.com/reader/full/imhoff-tank-568ce9d41d32b 5/17

"rimary treatment is designed to remove organic and inorganic solids by the physical processes

of sedimentation and flotation. "rimary treatment devices reduce the velocity and disperse the

flow of wastewater. In primary treatment the velocity of flow is reduced to 1 to 2 feet per

minute to maintain a (uiescent condition so that the material denser than water will settle out and

material less dense than water will float to the surface. %pproximately 5 to 4 percent of the

suspended solids are removed from the waste stream +26 7 !6? -$& reduction. The solids that

remain in suspension as well as dissolved solids will usually be biochemically treated insubse(uent processes for physical separation and removal in the final +secondary settling tanks.

The si@e and number of primary tanks is dependent on the estimated wastewater flow and the

design detention time. Aenerally, a detention time of 2 to ! hours will provide a sufficient time

 period for most particles to settle out. 0urther, the settling rate of a particle depends on the

strength and freshness of the wastewater being treated, the weight of the solid compared to the

specific gravity of water, the si@e and shape of the solid and the temperature of the water. 'ater

is more dense at lower temperaturesB therefore, the re(uired settling time increases. %s the

temperatures of the water increases, the re(uired settling time decreases. (ual distribution of

flow throughout the tank is critical. The greater the velocity in one area, the less the actual

detention time. #olids not having sufficient time to settle out will be discharged in the effluent.

"rinciple primary treatment devices are referred to as sedimentation tanks, primary tanks,

 primary clarifiers or primary settling tanks, some of which have the further function of providing

an additional compartment for the decomposition of settled organic solids which is known as

sludge digestion. There are several types of primary tanks in use.

Septic Tanks 

The septic tank was one of the earliest treatment devices developed. Currently, septic tanks

 provide wastewater treatment for small populations, such as individual residences, small

institutions, schools, etc.

They are designed to hold wastewater at low velocity, under anaerobic conditions for minimum

detention time of !4 hours. &uring this period, a high removal of settleable solids is achieved.

These solids decompose in the bottom of the tank with the formation of gas which, entrained in

the solids, causes them to rise through the wastewater to the surface and lie as a scum layer until

the gas has escaped, after which the solids settle again. This continual flotation and resettling of

solids carries some of them in a current toward the outlet to be discharged with the effluent. The

final effluent disposal occurs by subsurface methods. The effectiveness of this method isdependent on the leaching ability of the soil.

These primary type units re(uire a minimum of attention which involves an annual inspection

and the periodic +! 7 6 years removal of sludge and scum accumulations.

Imhoff Tank 

The Imhoff tank was developed to correct the two main defects of the septic tank.

1. It prevents the solids once removed from the sewage from again being mixed with it, but

still provides for the decomposition of these solids in the same unit

2. It provides an effluent amenable to further treatment.

5

7/17/2019 Imhoff Tank

http://slidepdf.com/reader/full/imhoff-tank-568ce9d41d32b 6/17

 

Contact between the waste stream and the anaerobic digesting sludge is practically eliminated

and the holding period in primary settling compartment at the tank is reduced. The Imhoff tank

may be either circular or rectangular and is divided into three compartments

1. the upper section or sedimentation compartment

2. the lower section known as the digestion compartment and

!. the gas vent and scum section

It is desirable to be able to reverse the direction of flow to prevent excessive deposition of solids

at one end of the sedimentation compartment. "eriodically reversing the flow will result in an

even accumulation of sludge across the bottom of the tank. In operation, all of the wastewater

flows through the upper compartment. #olids settle to the bottom of this sloped compartment,

slide down and pass through an opening or slot to the digestion compartment. $ne of the bottom

slopes extends at least six inches beyond the slot. This forms a trap to prevent gas or digestingsludge particles in the lower section from entering the waste stream in the upper section. The

gas and any rising sludge particles are diverted to the gas vent and scum section.

Imhoff Tank Operation 

There are no mechanical parts in an Imhoff tank. %ttention should, however, be given to the

following

a. &aily removal of grease, scum and floating solids from the sedimentation compartment.

 b. 'eekly scraping of the sides and sloping bottoms of the sedimentation compartment by a

rubber s(ueegee to remove adhering solids which may decompose.

6

7/17/2019 Imhoff Tank

http://slidepdf.com/reader/full/imhoff-tank-568ce9d41d32b 7/17

c. 'eekly cleaning the slot at the bottom of the sedimentation compartment. This can be

done by use of a chain drag.

d. "eriodic reversal of flow where provided for in the design of the tank.

e. Control of the scum in the scum chamber, by breaking it up, hosing with water under

 pressure, keeping it wet with supernatant from the digestion compartment and removal ifthe depth approaches two to three feet.

f. )emoval of sludge should be done before the sludge depth approaches within 1* inches

of the slot in the sedimentation compartment. It is better to remove small amounts

fre(uently than large amounts at long intervals. #ludge should be removed at a slow

regular rate to avoid coning +i.e. the formation of a channel through the sludge which

would permit partially digested sludge and li(uid held in storage above the digested sludge

to be withdrawn from the tank. -efore winter temperatures are expected, most of the

digested sludge except that necessary for seeding +about 2 percent should be removed to

 provide space for winter accumulations when digestion is very slow. The height of the

sludge in the sludge compartment should be determined at inlet and outlet end of the tankat least once a month.

g. %fter each time that sludge is removed, the sludge pipes should be flushed and drained to

 prevent sludge from hardening in and clogging the pipes.

h. "revention of /0oaming/. very effort should be made to prevent /foaming/ because

correction after the condition arises is sometimes difficult. /0oaming/ is usually

associated with an acid condition of the sludge and in such cases may be prevented or

corrected by treatment with lime or sodium bicarbonate to counteract the acidity of the

sludge. There are a few simple measures which may, under certain circumstances, remedy

or improve the condition.

1. The use of hydrated lime or sodium bicarbonate added to the gas

vents will usually aid in correction. The p value of the resulting sludge and lime

mixture in the digestion compartment should not exceed 3.4.

2. )emoving the tank from service where possible for a few days and

allowing it to rest will sometimes improve conditions.

!. %gitation of the gas vent area with a water hose or paddles will

sometimes help.

The Imhoff tank has no mechanical parts and is relatively easy and economical to operate. It

 provides sedimentation and sludge digestion in one unit and should produce a satisfactory

 primary effluent with a suspended solids removal of 5 to 4 percent and a -$& reduction of 16

to !6 percent. The two7story design re(uires a deep over7all tank. "rimary tanks with separate

digesters have largely replaced the Imhoff tank for large municipal installations. The Imhoff

tanks is best suited to small municipalities and large institutions where the tributary population is

6, or less, and a greater degree of treatment is not needed.

Mechanically-Cleaned Plain Sedimentation Tanks 

7

7/17/2019 Imhoff Tank

http://slidepdf.com/reader/full/imhoff-tank-568ce9d41d32b 8/17

"hoto Credit irginia &epartment of ealth 

These tanks may be rectangular, circular or s(uare, but all operate on the same principle of

collecting the settled solids by slow7moving scrapers to the point of removal.

In the rectangular tanks the wastewater enters at one end and flows hori@ontally to the other

end. The scrapers +flights are attached by their ends to two parallel chains which pass oversprockets. The flights move slowly along the tank floor, pushing the settled solids to a sludge

hopper at the end of the tank. %t the same time, the partially submerged flights, in their return

 path, push the floating solids, grease and oils +scum to a trough at the end of tank.

In the centerfeed circular tanks the wastewater enters at the center and flows radially and

generally hori@ontally to the periphery. The circular tanks have scraper arms attached to a

central motor7driven shaft. The bottom of the tanks are sloped toward the center and the

scrapers move the settled solids to a sludge hopper at the center. #kimmer arms, if present, are

attached tot he central shaft at the surface for the collection of floating solids, grease and oils

+scum.

In square tanks, the wastewater enters at the center and flows to the four sides. The scraper

mechanism is similar to that in the circular tanks. The maDor difference is that the rigid arms of

the scraper mechanism are e(uipped with pivoted corner blades which reach out into the four

corners of the tank and move the solids in these areas to the path of the circular mechanism.

Operation 

Collection and removal of sludge from the sedimentation tank, as well as correct maintenance

 procedures, are important factors in successful plant operation. The mechanical collectione(uipment can be run intermittently but is most often run on a continual basis. This prevents the

excess accumulation of solids on the tank bottom and reduces the load on the collector

mechanisms and thereby helps to prevent e(uipment damage. #olids left in the tank bottom too

long will gasify and rise to the surface, therefore, sludge should be removed from the tank as

often as necessary. This, in turn, is dependent on waste stream characteristics, volume of flow

and sludge (uality. The sludge removal schedule must be worked out for each plant by

observations and tests, keeping in mind that the obDective is to remove sludge at the proper rate,

at the proper rate, at the proper concentration and with the proper (uality for the receiving

 process unit. Concentrating the sludge reduces the volume of water being pumped and

contributes to pumping efficiency. There are, however, pump design limitations to consider.

#easonal revision of this schedule will probably be necessary. In addition, scum and grease

8

7/17/2019 Imhoff Tank

http://slidepdf.com/reader/full/imhoff-tank-568ce9d41d32b 9/17

should be removed daily from the tank surface.

% conscientious operator is aware that

mechanical e(uipment re(uires

attention and maintenance.

Inspection, cleaning, lubrication,

sampling, testing and record keeping

are important aspects of any

maintenance program.

"hoto Credit irginia &epartment of ealth 

The proper time schedules for preventive and corrective maintenance must be determined at

each wastewater facility. The best rule is to follow the instruction manual provided by the

e(uipment manufacturer.

Physical Oser!ations 

"hysical observations at the water surface of each clarifier can provide the operator with

valuable information regarding clarifier efficiency and related plant status. The observed data

can dictate the re(uired operational control necessary to achieve optimum unit efficiency and

subse(uent plant performance. These results should be confirmed through laboratory testing.

$bservations which should be made daily and the results recorded

1. 0loating solids accumulations should be noted, if present, whether existing as clumps or

as a dispersed accumulation

2. The formation of gas bubbles

!. The absence or presence of odors

5. &istribution of flow to multiple tanks

6. &istribution of flow over weirs

4. Eoss of solids in the effluent

$ther factors that should occasionally be checked are elevation and placement baffles.

"aoratory Control 

9

7/17/2019 Imhoff Tank

http://slidepdf.com/reader/full/imhoff-tank-568ce9d41d32b 10/17

valuation of primary treatment is dependent on laboratory analysis. The fre(uency of testing

and the /range/ of test results will vary from plant to plant. 'aste stream characteristics,

environmental conditions and in7plant operation will affect the test data at each facility.

Eaboratory tests commonly associated with primary tanks are shown below.

Parameter  Type of Sample  "ocation 

-$& CompositeInfluent

ffluent

#uspended #olids CompositeInfluent

ffluent

#ettleable #olids ArabInfluent

ffluent

 p ArabInfluent

ffluentTemperature Arab Influent

Comparison of influent versus effluent test results provides information re(uired to calculate and

evaluate clarifier efficiency.

Operational Prolems 

If visual observations, confirmed by lab analysis indicate poor clarifier operation, then the

 problem source must be identified so that corrective andFor preventive action can be taken.#ome common problems and discussed below.

%. #loating Sludge 

Cause:  #ludge decomposing in tank and floating to surface.

 Prevention and Cure:  )emove sludge more completely or more fre(uently by one or more of

the following methods.

1. $perate mechanical scrapers for longer periods or more often.

2. )eplace broken or warped wooden flightsB or adDust flights closer to the bottom.

!. )emove sludge from hoppers more completely by pumping or gravity withdrawal

for longer periods or at slower rates. 'here sludge clings to inclined surfaces, remove by

scraping or Detting.

 

-. Contents $lack and Odorous 

Cause:  #eptic wastewater or strong digester recycled supernatant. Prevention and Cure For septic wastewater:

10

7/17/2019 Imhoff Tank

http://slidepdf.com/reader/full/imhoff-tank-568ce9d41d32b 11/17

1. Correct flow obstructions in the collection systemB

2. Godify, pretreat, reduce, or eliminate organic wastes, such as cannery, milk

 processing, brewery, tannery, and organic textiles wastesB

!. "re7Chlorinate in the sewer systemB or ahead of sedimentation tank to reduce

decomposition of wastewaterB this is particularly effective when time of travel in sewer isunusually long or wastewater temperatures are high, or when certain industrial wastes are

 presentB

5. "reaerate wastes of types listed in Ho. 2 aboveB or  

6. Improve flow of wastewater system to reduce accumulations of solids.

0or strong recycled digester supernatant

1. Correct or improve sludge digestion to produce improved (uality supernatantB

2. )educe rate of withdrawal of supernatant to sedimentation tankB

!. #elect better (uality supernatant from another @one or delay withdrawal until (uality

improves, if that is possible.

5. ntil (uality improves, discharge part or all of supernatant to other points such as lagoon,

sludge drying bed, or aeration tank until (uality improves.

6. "resettle the supernatant.

C. %&cessi!e Sedimentation in Inlet Channels 

Cause:  elocity too low for cross7sectional area of channel at existing flow rates.

 Prevention and Cure:

1. )educe cross7sectional area.

2. %gitate with air, water, or other means to prevent deposits.

&. %&cessi!e #ouling of Surfaces and 'eirs (ith 'aste(ater Solids or )ro(ths 

Cause: %ccumulation of wastewater solids and resultant plant growth.

 Prevention and Cure:

1. Gore fre(uent and thorough scrubbing of all surfaces in contact with wastewater.

.  Intermittent Surging of #lo( 

Cause: igh intermittent pumping rates.

 Prevention and Cure:

1. %dDust controls for pump se(uence, pump combinations, andautomatic cut7in and cutoff water surface levels to maintain pumping rates close to rates of

inflow.

11

7/17/2019 Imhoff Tank

http://slidepdf.com/reader/full/imhoff-tank-568ce9d41d32b 12/17

0. $roken Scraper Chains and #requent Shear Pin #ailure 

Cause:  xcessive load on mechanical scraper.

 Prevention and Cure:

1. "eriodically empty tank and examine all metal parts for defects and wearB

2. )eplace defective and worn parts, particularly hinge pins, chain links, and wear shoes, and

 badly worn, broken, or warped scrapers +flightsB

!. Install grit chamber or otherwise reduce entrance of grit to the primary tanks if grit

accumulation is evidentB or 

5. $perate collector mechanism for longer period andFor pump sludge more often.

A. Sludge *ard to +emo!e from *opper 

Cause:

1. igh content of grit, clay, or other heavy compacted materialB or 

2. 'ithdrawal lines too small.

 Prevention and Cure:

1. )educe grit content by installing or modifying grit chamber, or locate and correct sources of 

grit entering the wastewater systemB

2. Eoosen compacted material manually or by pressure Detting with air or water hoseB

!. -ack7flush clogged pipelinesB

5. "ump sludge more fre(uentlyB or 

6. Godify sludge piping

Solids Accumulation

1. 0ollowing biological treatment +and, as an integral part of the secondary treatment process, is the secondary clarifier. The primary and secondary clarifier differ as to

 physical location and to the density of the solids handled, as well as in the (uality of the

tank effluent. #econdary solids are usually less dense and secondary effluents are

normally of a higher (uality than those of primary clarifiers.

2. In both the primary and secondary clarifiers, the sludge +settled solids is scraped or

drawn to a hopper or sump for removal, treatment and disposal. The sludge removal can

occur separately and independently in each unit, or the sludge from the secondary

clarifier can be pumped to the primary clarifier or to a separate thickener unit and mixed

with the primary sludge. This combination of primary clarifier sludge and secondary

clarifier sludge is collectively referred to as waste sludge and will usually undergo further treatment for ultimate disposal. 0re(uency of solids removal is dependent on sludge

(uality as well as the design of the related sludge wasting e(uipment devices.

12

7/17/2019 Imhoff Tank

http://slidepdf.com/reader/full/imhoff-tank-568ce9d41d32b 13/17

!. The actual sludge removal and disposal system +for the various types of clarifiers varies

from plant to plant. In addition, the floatable solids must be skimmed andFor pumped to

 be disposed of separately or with the settled solids.

 Clarifier %fficiency 

1. To calculate the efficiency of any treatment unit it is necessary to measure influent andeffluent parameters. 0re(uently, the determination of unit efficiency is appraised in terms

of -$& and suspended solids removal.

2. The operator should also be aware that recycled loadings from digesters, vacuum filters,

etc. can impose severe organic and suspended solids loadings on primary clarifiers. The

strength and volume of these recycled waste streams must be added to the influent

wastewater loadings in order to properly calculate unit process efficiencies.

Typical Clarifier fficiencies

1. Eisted below are some range values for primary clarifier efficiencies

+emo!al %fficiency

-iochemical $xygen &emand 26? 7 !6?

#ettleable #olids ;? 7 ;6?

#uspended #olids 5? 7 4?

Total #olids 1? 7 16?

2. Clarifier efficiencies vary depending on influent flow rate and wastewater characteristics

as well as in7plant conditions. The most important structural elements effecting clarifier

efficiency are inlet flow distribution and effluent weir placement. %lthough effluent weir

configurations are often beyond the control of the operator, there are some minor

alterations that can be made to improve the influent flow patterns so that the affect ofshort7circuiting is minimi@ed. These remedial alterations would include the installation

of target baffles or the installation or relocation of a maDor flow baffle.

!eir "#erflo$ %ate

1. $utlet weirs vary greatly in design. They provide for uniformed removal of clarifier

effluent from the surface of the tank.

13

7/17/2019 Imhoff Tank

http://slidepdf.com/reader/full/imhoff-tank-568ce9d41d32b 14/17

&'oto Credit( )ir*inia +epartment of ,ealt'

1. The term /weir overflow rate/ is used to express the number of gallons of wastewater that

flow over one linear foot of weir per day.

2. Gost designers recommend 1, to 2, gallons per day per linear foot of weir.

!. ven more important than overflow rate is the proper location of the weir launders so that

upflow velocities are minimi@ed.

+etention Time

1. This the time, expressed in hours, that wastewater is held in a tank based on wastewater

flow and tank volume. +This assumes total displacement and uniform flow through the

tank. &etention periods should be in the 2 7 ! hour range.

2. The /%ctual/ &etention Time in a clarifier is a better indicator of process capabilities,

since it is a direct measure of the short7circuiting flow patterns in that unit. xperience

has shown that the use of a fluorescein dye, introduced as an instantaneous slug at the

influent to the unit and then measured in the unit effluent over a period of several hours,

is the best measure of the actual detention time.

Surface Settlin* %ate

1. This is expressed as gallons per s(uare foot of tank area based on wastewater flow per

day. The range value for primary tanks varies from 6 7 36 gpdFs(.ft. This is an

important factor directly affecting the settleable solids and removal efficiency.

Chemical Treatment 

14

7/17/2019 Imhoff Tank

http://slidepdf.com/reader/full/imhoff-tank-568ce9d41d32b 15/17

Chemical treatment is included under primary treatment because it involves chemical and

 physical processes as distinct from the biological processes which are the basis of secondary

treatment. Chemical addition has application +1 in the treatment of industrial wastes which

are sometimes difficult to decompose by biological means, +2 where discharge to receiving

waters re(uire a higher degree of treatment than primary units can achieve, but secondary

treatment is not warrantedB +! after secondary treatment when a higher degree of treatment is

demanded +often referred to as tertiary treatment.

The exact point of chemical application is dependent on design considerations as well as permit

re(uirements. 'e are concerned, here, with chemical treatment and its application to primary

treatment.

Chemical treatment involves the addition of one or more chemicals to wastewater to produce

floc, which is an insoluble chemical compound that adsorbs colloidal matter, enmeshes non7

settleable suspended solids and settles more readily. The precipitating chemical also dissociates

or ioni@es in the wastewater and neutrali@es the electric charges held by colloidal particles

causing them to coagulate to form larger readily settleable solids. The chemicals most widely

used are aluminum sulfate +alum, ferric chloride, lime and polymers.

% chemical treatment plant usually has the following features

1. "reliminary &evices 7 screens, grit chambers, etc.

2. Chemical 0eeders

!. 0lash Gixing nits

5. 0locculation Tanks

6. #edimentation Tanks such as have already been described

4. Increased 0acilities for the Treatment and &isposal of #ludge

Chemical #eeders 

% large variety of units to feed chemicals, either dry or in solution, in controlled amounts, are

made by a number of manufacturers.

Mi&ing ,nits 

The chemicals, when added to sewage, must be thoroughly and (uickly mixed with it to provide

complete and uniform reactions. This is accomplished by violent agitation for a short period of

time either by mechanical or hydraulic methods. This agitation is carried on in special tanks, insections of other tanks, or in the piping system. #uch mixing devices are made by a number of

manufacturers.

15

7/17/2019 Imhoff Tank

http://slidepdf.com/reader/full/imhoff-tank-568ce9d41d32b 16/17

 

#locculators 

%fter the chemical is mixed with sewage it is gently agitated for 16 to ! minutes to foster the

coagulation of particles. If -$& reduction is desired, the agitation time may be increased to 56minutes. The colloidal and suspended solids meet and adhere together in large flocculant masses

which settle readily in the sedimentation tank. &ifferent types of e(uipment to accomplish this

 purpose are made by a number of manufacturers and must be designed to operate at varying

speeds as determined by the actual process characteristics.

Sludge 

The volume of sludge obtained by chemical treatment is greater than with standard primary

treatment, necessitating a comparable increase in the capacity of the sludge handling facilitiesand in the cost of sludge treatment and disposal.

%fficiency 

Chemical treatment can effect a reduction up to ; percent in suspended solids and up to 3

 percent in the -$&. It is well adapted to intermittent operation and has value in sewage

treatment to reduce pollution of streams during periods of low flow or to lessen pollution of

 bathing beaches and recreational waters during months when these facilities are in use. It is of

value also for the treatment of sewage containing high concentrations of industrial wastes which

will inhibit biological life and interfere with secondary treatment processes. $perational costs

are high due to increase in operator<s time, chemical usage and the (uantities of sludge to be

treated and disposed of.

"essons Inde&

 

0or lessons 4 : 2, answer the ven number &iscussion and )eview (uestions in your textbooks,

'astewater Treatment "lant $perations ols. I and II. "lease note that there are no &iscussionand )eview (uestions for Chapter 1; but your assignment for this chapter is to write a Gonthly

)eport. )efer to page 435 ol. II, as a reference. 'hen you have completed the assignment for

each chapter, email, mail or fax them assignment to your instructor.

"esson 1 'astewater Treatment 

"esson %ctivated #ludge "rocess J 0oodFGicroorganism )atio 

"esson / #lime Arowth "rocesses +Trickling 0ilter J )-C 

"esson 0  %erobic and %naerobic &igestion

"esson   'astewater Treatment "onds "esson 2  'astewater  

"esson 3  'astewater Treatment Gethods and &isposal 

16

7/17/2019 Imhoff Tank

http://slidepdf.com/reader/full/imhoff-tank-568ce9d41d32b 17/17

"esson 4 "reliminary Treatment 

"esson 5 "rimary Treatment 

"esson 16 #econdary Treatment 

"esson 11 &isinfection of 'astewater  

"esson 1 #olids andling and &isposal 

"esson 1/ %dvanced 'astewater Treatment 

"esson 10 #ampling and Testing "rocedures "esson 1 'astewater  

"esson 12 #ludge from a #ewage Treatment "lant as a 0easible #ource of nergy 

"esson 13 xtended %eration %ctivated #ludge "lant

"esson 14 #afety "rotocols for #ewer Cameras

KThis information was obtained from the New York Water Operations 

17


Recommended