81
SCHOOL OF ARCHITECTURE, BUILDING & DESIGN BACHELOR OF SCIENCE (HONOURS) IN ARCHITECTURE BUILDING SERVICES (BLD 60903 / ARC 2423) PROJECT 2: BUILDING SERVICES IN PUBLIC BUILDINGS GROUP MEMBERS: ANDY HENG WEE XIANG 0327152 CHIA CHENG WEI 0322091 KOOI YONG KAI 0323152 LEE XIANG LOON 0322090 LOUIS DE ROZARIO 0327136 ONG EU XUAN 0319050 TUTOR: MR AZIM SULAIMAN

Building Services: Elderly care center services

Embed Size (px)

Citation preview

SCHOOL OF ARCHITECTURE, BUILDING & DESIGN

BACHELOR OF SCIENCE (HONOURS) IN ARCHITECTURE

BUILDING SERVICES (BLD 60903 / ARC 2423)

PROJECT 2:

BUILDING SERVICES IN PUBLIC BUILDINGS

GROUP MEMBERS:

ANDY HENG WEE XIANG 0327152

CHIA CHENG WEI 0322091

KOOI YONG KAI 0323152

LEE XIANG LOON 0322090

LOUIS DE ROZARIO 0327136

ONG EU XUAN 0319050

TUTOR: MR AZIM SULAIMAN

2

TABLE OF CONTENTS

Pages

Table of Contents 2 – 3

1.0 Abstract 4

2.0 Introduction 5

3.0 Findings & Analysis

3.1 Fire Protection System

3.1.1 Introduction 6 – 7

3.1.2 Literature Review 8 – 9

3.1.2.1 Active Fire Protection System

3.1.2.2 Passive Fire Protection System

3.1.3 Research Findings 10 – 42

3.1.3.1 Active Fire Protection System

3.1.3.1.1 Zone Configuration

3.1.3.1.2 Fire Detection

3.1.3.1.3 Portable Fire Extinguishers

3.1.3.1.4 External Fire Hydrant System

3.1.3.1.5 Hose Reel System

3.1.3.2 Passive Fire Protection System

3.1.3.2.1 Separation of Risk Area

3.1.3.2.2 Beam, Column and Separating Wall

3.1.3.2.3 Fire Doors

3.1.3.2.4 Measurement of Travel Distance to Exits

3.1.3.2.5 Exits

3

3.2 Air Conditioning System 43 – 56

3.2.1 Introduction

3.2.2 Literature Review

3.2.3 Research Findings

3.2.3.1 Air Conditioning Outdoor Unit

3.2.3.2 Air Conditioning Indoor Unit

3.3 Mechanical Ventilation System 57 – 67

3.3.1 Introduction

3.3.2 Literature Review

3.3.2.1 Extract System

3.3.2.2 Supply System

3.3.3 Research Findings

3.3.3.1 Return Air Grille

3.3.3.2 Fire Exhaust Fan

3.3.3.3 Supply Air Diffusers

3.4 Mechanical Transportation System 68 – 76

3.4.1 Introduction

3.4.2 Literature Review

3.4.3 Research Findings

3.4.3.1 Method of operation (Direct Acting)

3.4.3.2 Hydraulic Elevator Component

3.4.3.3 Safety System

4.0 Conclusion 77 – 78

5.0 References 79 – 80

6.0 Appendix 81

4

1.0 ABSTRACT

This report is to analyse and find out the requirement of different building systems required

either based on By-Laws or human requirements onto the proposed building of an Elderly Care

Centre. It helps to understand to provide a better design and environment for the occupants of

the building.

The report is carried out to find out the importance of a fire protective system and its safety for

the users. Air conditioning system and mechanical ventilation system both provide extra

comfort through cool and movement of air, respectively. A mechanical transportation system

is crucial for the elderly to access to upper floors due to certain disabilities.

These four systems include fire protective system, air conditioning system, mechanical

ventilation system and mechanical transportation system will be further discussed and

elaborated further in the report.

5

2.0 INTRODUCTION

The site of the Elderly Care Community Centre in Taman Kanagapuram, Old Klang Road in

Petaling Jaya is a flat rectangular plot of 22 metres wide and 44 metres long in between two

residential bungalows. The idea was to create functional spaces embracing a central courtyard

and freeing the building through multiple open views along the long stretch of corridors. The

centre is built for the seniors in the community to create a dynamic social interaction and foster

good relationship among the staff members of the centre, family, friends, relatives and

neighbouring residents. The centre aims to bring out the positivity to counteract the dull and

slow-paced life seen in the existing nursing homes within a few kilometres radius through

interaction and functional spaces.

The centre provides a medium and platform for the common public to engage and participate

in a wide range of leisure and education programmes, an initiative that is not present in the

other nursing homes. It helps to provide a significant value to the neighbourhood context due

to rapid urbanization surrounding the area.

The Elderly Care Centre requires different building systems to become one whole functional

unit. Each system will play different roles for the safety, comfort and basic requirement for the

building occupants in order to properly function by fulling the requirement of By-Laws and the

elderly themselves.

6

3.0 FINDINGS & ANALYSIS

3.1 Fire Protection System

3.1.1 Introduction

Fire can be defined as fast oxidation of a material in the exothermic compound procedure of

ignition, discharging warmth, light, and different response items. Blazes comprise principally

of carbon dioxide, water vapour, oxygen and nitrogen. Fire in its most normal frame can bring

about fire, which can possibly bring about physical harm through smouldering. A fire can

spread 4.6 meters per second. Fire occurs when there is presence of air and some sort of fuel.

With a specific end goal to permit burning to happen, the fuel must be warmed to its start

temperature. This substance response will keep on processing the length of there is sufficient

warmth, fuel and oxygen.

Figure 1: Fire tetrahedron

FUEL – Any combustible material in any state, solid, liquid

or gas.

OXYGEN – The air around us consists of 21% of oxygen.

At least 16% is needed for combustion to occur.

OXYGEN – Energy required to increase temperature of the

fuel to the ignition temperature in order to have combustion

process.

7

These four elements must be present at the same time for a fire to be produced:

Combustible material or fuel

Exothermic reaction of the fire

Sufficient heat to maintain ignition temperature

Sufficient oxygen to maintain the process of combustion

FUEL + OXYGEN (from the air) = COMBUSTION PRODUCT (CO2 + H2O) + HEAT ENERGY

Cost effective active and passive fire protection system should be intended to join proficient in

new offices and redesign ventures. Aloof and dynamic fire protection systems are compelling

in recognizing, containing, controlling and quenching a fire occasion in the early stage. In each

building, the fire architects are required to guarantee a sensible level of assurance of human

life from flame and the item ignition and additionally to lessen the potential misfortune from

flame.

8

3.1.2 Literature Review

3.1.2.1 Active Fire Protection System

Both the active and passive fire protection systems are basic in guaranteeing the well-being

and security of the users in the building. Active fire protection system is about a procedure or

an approach to caution the tenants or clients, furthermore, the endeavours to control or quench

the fire by utilizing the strategies of applying programmed or physically worked fire

mechanical framework. The techniques that are incorporated into this systems are the fire

discoveries which incorporate smoke/warm discovery, triggers, alerts, pump room and others.

These systems, particularly the fire alert systems, are critical to advise the clients in the building

that departure is vital subsequent to recognizing the smoke or warmth amid the fire. Sprinkle

frameworks which are incorporated into the dynamic fire insurance framework are vital to back

off the rate of flame as the glass of the sprinkles will blast to discharge water when there is

intemperate warmth from the fire. Active fire protection systems are especially helpful in

bigger structures where it is harder to ventilate the focal spaces through common openings, for

example, the windows, so smoke and warmth extraction frameworks are frequently utilized.

3.1.2.2 Passive Fire Protection System

Another system being utilized is the passive fire protection system which is presented in parts

of the building or structure as an obstruction to the fire and back off the rate of fire and smoke

from spreading to different territories or parts of the building. A standout amongst the most

critical elements in detached fire insurance framework is the assurance of escape courses from

the fire and smoke to drag out the escape time by outlining and bringing heatproof trademark

9

into the components of the building. There are two key critical segments in uninvolved fire

assurance framework. The first is the compartmentalization of the spaces with fire-evaluated

assembling parts, for example, the fire-appraised dividers and entryways are mulled over to

counteract the fire spreading from space to space. This is critical in making an oxygen

hindrance and compartmentalize the spaces amid a fire. The fire-evaluated divider not just

speak to an immediate shield which the fire would need to physically blaze through to pass,

additionally, a stifle point for air amid the fire. The second part that is extremely critical is the

way to get out that decides the system and proficiency of escape to outside of the working amid

the occasion of flame and crisis. This includes the use of leave signs, crisis staircase plan and

others.

10

3.1.3 Research Findings

3.1.3.1 Active Fire Protection System

The following research explains the type of active fire protection system proposed to be used

in the Elderly Care Centre building. The main role of active fire protection systems are to

extinguish fire outbreaks during fire emergencies by using both mechanical and manually

methods, whichever is convenient at the time of emergency. The systems will be discussed and

elaborated deeper and further in the paper.

3.1.3.1.1 Zone Configuration

Figure 2: Zone configuration

11

Guide to Fire Protection in Malaysia 13.1.2 (iii)(a): Maximum floor area should not

exceed 200m2.

The total floor area each floor is 400m2. The maximum fire detection floor area should not

exceed 200m2, thus the building is divided into four zones to ensure effective smoke detection.

3.1.3.1.2 Fire Detection

Smoke Detectors

Figure 3: A smoke detector located in the building

Smoke detectors integrated into open areas under flat horizontal ceilings, the horizontal

distance from any point in the area to the detector nearest to that point should not exceed 7.5

meters. Requirements are as being in a corridor less than 5 meters wide, the horizontal distance

given in and above may be increased by half the difference between 5 meters and the width of

the corridor. For corridor wider than 5 meters, it should be treated as an open area. Smoke

detector should be sited so that their sensitive elements are not less than 25mm or more than

600mm below the ceiling or roof.

12

The smoke detectors that have been introduced on specific locations of the roofs of every floors

are photoelectric smoke locators which are the most appropriate and suggested smoke

indicators among all. Photoelectric smoke finders are locators that contain a light source in a

light-touchy electric sensor. The light source will be situated 90-degree that the light from the

light source will shoot straight crosswise over and misses the sensor, which will then be

exasperated and hit the sensor. It will then trigger the alert when the smoke enters the chamber

and dissipates the light.

Figure 4: Photoelectric smoke detector diagram

Photoelectric smoke detectors ordinarily react speedier to a fire in its initial, seething stage

which is some time recently the wellspring of the fire blasts into blazes. These detectors are

more sensitive to the huge ignition particles that exude amid moderate, seething flames, which

more often than not happen during the evening.

13

Figure 5: Location of smoke detectors

Uniform Building By-Laws 1984 Clause 225: Detecting and extinguishing fire

(1) Every building shall be provided with means of detecting and extinguishing fire and with

fire alarms together with illuminated exit signs in accordance with the requirements as specified

in the Tenth Schedule to these By-laws.

A smoke detector is placed in each zone. On the ground floor, detectors are installed on the

corridor ceilings, one of which is located in front of the lift lobby. They are sited so that their

sensitive elements are not less than 25mm below ceiling. On the first floor, detectors are

installed on the walls of the building. They are installed on the exterior walls that face the inside

(central courtyard) of the building.

14

Audio Alarm Sounder

Figure 6: Location of Alarm Sounders

Uniform Building By-Laws 1984 Clause 237: Fire alarms

(1) Fire alarms shall be provided in accordance with the Tenth Schedule to these By-laws.

When the smoke detector is triggered, the audio fire alarm system will be activated to arouse

and attract the attention of the occupants so that the evacuation can be carried out without

causing harm to the occupants. Four alarms are installed on each floor, with two alarm sounders

placed in each zone of the building.

15

3.1.3.1.3 Portable Fire Extinguishers

Figure 7: Portable fire extinguisher

The installation of portable fire extinguishers should be located in positions where they can be

easily spotted by person following an escape route. Extinguishers should be located preferably

within recessed closets if they would be sited along protected corridors to avoid obstruction

during evacuation. They should be sited not more than 20 meters from a potential fire hazard.

Figure 8: Cutaway of a portable fire extinguisher

16

The portable extinguishers can be classified to specific classes with different purposes to fight

different kinds of fires (5.2.2). The classes are as follows:

Uniform Building By-Laws 1984 Clause 227: Portable extinguishers

Portable extinguisher shall be provided in accordance with the relevant codes of practice and

shall be sited in prominent positions on exit routes to be visible from all directions and similar

extinguishers in a building shall be of the same method of operation.

17

Figure 9: Location of portable extinguishers following escape routes

Portable fire extinguishers are always located within reach, in conspicuous locations that can

be easily spotted following an escape route. Following the evacuation flow, portable

extinguishers are places along the corridors, by emergency exits, and by the fire staircase.

18

Figure 10: Location of portable extinguishers

Portable extinguishers are also located by the exit of every room, on corridors, stairways,

lobbies and fire escape landings to allow easier access.

19

3.1.3.1.4 External Fire Hydrant System

Figure 11: A fire hydrant

A fire hydrant is an association point by which fire fighters can take advantage of a water

supply. All the external fire protection systems comprise of hydrants associated with a similar

pipeline. The ends of the pipeline is attached to the pumps and water supply tank of the fire-

fighting rooms. It is an effective method for stifling vast fire; the fire hydrant framework

empowers the fire contender to assault the seal of the fire from a separation. A fire hydrant is

a vertical steel pipe with an outlet, near which two fire hoses are put away. Amid a crisis which

more water is required to beat the fire mischance circumstance, fire contenders will go to the

outlet, tear open the hoses, append one to the outlet, and physically open it with the goal that

water surges out of the spout of the hose. When the fire warrior opens the hydrant, water will

spout out, and sensors will recognize a drop in weight in the framework. This drop in weight

will trigger the fire pumps to turn on and begin pumping water at an enormous flow rate

20

According to the ‘Guide to Fire Protection in Malaysia’, under Chapter 6: External Fire

Hydrant System, 6.2.2 Hydrant Outlets, pillar hydrants should be located at not more than 30

meters away from the breaching inlet for the building. The hydrant should not be less than 6

meters from the building so as to allow firemen to operate the hydrant safely, away from the

burning building and falling debris. The hydrant mains are usually laid underground. The

piping is usually of cement lined steel pipe.

In 6.2.3 Hydrant Pumps, it is stated that the hydrant pumps draw water from the fire water

storage tank and two sets of pump, one on duty and the other on standby, are provided. The

standby hydrant pump set should be supplied with power from the emergency generator if this

is available. Electrical cabling to supply power to the hydrant pumps should be of fire related

type of cable. The hydrant pump set should be protected from the weather and away from

locations likely to be flooded.

Under 6.2.4 Hydrant Tanks, it is implied that the fire water storage tank should be sized for a

minimum effective capacity of 135,000 litres and should be refilled automatically from a water

supply pipe capable of providing a minimum flow rate of 1,200 l/min. The tank may be of

pressed steel, fiberglass reinforced polyester or concrete. The tank should be compartmented

unless they are of reinforced concrete and water level indicator should be provided to show the

amount of water available.

And lastly, on 6.4.5 Pump Starter Panels and Controls, it stated that the pump starter panel

should be complete with indicator lights. Ventilation slots should be provided with insect

screen to prevent entry of vermin. Hydrant pumps shall start automatically upon actuation of

21

the pressure switches but should only be stopped manually. The pressure switches are normally

installed in the test and drain line on the pump discharge side.

Figure 12: Main parts of a typical fire hydrant

Figure 13: Indication of external fire hydrant (not exact) and hydrant cabinet (ground floor

plan)

22

Uniform Building By-Laws 1984 Clause 225: Detecting and extinguishing fire

(2) Every building shall be served by at least one fire hydrant located not more than 91.5 meters

from the nearest point of fire brigade access.

(3) Depending on the size and location of the building and the provision of access for fire

appliances, additional fire hydrant shall be provided as may be required by the Fire Authority.

In residential lots, external fire hydrant is located by the side of the street, they retrieve water

supply from the public water main. On our site, the fire hydrant was already supplied for in the

neighbourhood.

A hydrant cabinet that stores equipment and accessories such as water hoses and nozzles is

located by the main entrance of the building to allow easier access during outbreaks.

23

3.1.3.1.5 Hose Reel System

Figure 14: Hose reel systems situated in buildings

The hose reel system is proposed for the occupants to use amid the early phases of a fire. Fire

hose reels are situated at vital places in structures to give a sensibly available and controlled

supply of water for flame smothering. Fire hose reel systems comprise of pumps, channels,

water supply and hose reels found deliberately in a building, guaranteeing appropriate scope of

water to battle a fire.

24

Figure 15: Diagram of hose reel system

According to the ‘Guide to Fire Protection in Malaysia’, under Chapter 7: Hose Reel System,

7.2.2 Hose Reels, it is implied that hose reels should be placed such that all areas are within 30

meter hose coverage of each hose reel. Hose reels are usually located in prominent positions at

each floor level along escape routes or beside exit doors or staircases, preferably within

recessed closets. The rubber hoses should be 30 meters in length and 25mm in diameter.

Nozzles should be of the jet and spray adjustable type of different diameters but 8mm is a

recommended size.

Furthermore, in 7.2.7 Hose Reel Systems fed from other Sources, it is stated that the hose reel

system may be tapped off from pressurized hydrant provided pressure reducing valves are

incorporated to reduce the pressure to the appropriate level.

25

Figure 16: Location of hose reel (in hydrant cabinet) and installation of water tank (ground

floor plan)

In our building, the hydrant cabinet that stores the hoses, nozzles and accessories are located

at the main entrance of the building for easy access. The water tank that stores the water to put

out the fire would be located in the mechanical and electrical room at the back of the building.

26

3.1.3.2 Passive Fire Protection System

The following research explains the types of passive fire system proposed to be used in the

building. The main role of passive fire system is to resist or slow down the spread of fire

outbreaks during fire emergencies by using building or structural systems in the building. The

system will be discussed and elaborated deeper and further in the paper.

3.1.3.2.1 Separation of Risk Area

Figure 17: Fire risk area (Ground floor plan)

27

Uniform Building By-Laws 1984 Clause 139: Separation of Fire Risk Area

The following areas or uses shall be separated from the areas of the occupancy in which they

are located by fire resisting construction of elements of structure of a FRP to be determined by

the local authority based on the degree of fire hazard:

(a) boiler rooms and associated fuel storage areas

(b) laundries

(c) repair shops involving hazardous processes and materials

(d) storage areas of materials in quantities deemed hazardous

(e) liquefied petroleum gas storage area

(f) linen rooms

(g) transformer rooms and substations

(h) flammable liquid stores

Fire risk area should be isolated from other more public area. Therefore, the M&E room and

the kitchen area for the design proposal are placed behind the plot, separating them from the

main area of higher human concentration. In an event of an emergency, the number of people

getting injured will be less or nil.

28

3.1.3.2.2 Beam, Column and Separating Wall

Figure 18a: Ground floor plan Figure 18b: First floor plan

Uniform Building By-Laws 1984 Clause 147: Construction of Separating Wall

(1) Any separating wall apart from wall separating buildings not divided into compartments

within the limit of size with letter “X” indicated in Part 1 of Ninth Schedule, should be

constructed with fully non-combustible materials, excluding any surface finishing to the wall

which complies with the requirement of the by-laws. These required FRP for the wall should

be obtained without the assistance from the non-combustible materials of such surface

finishing.

29

(2) Any beams or column, any structure carrying the load, or separating wall is also required

to be constructed of non-combustible materials which comply the requirement of the paragraph

above (1) in terms of combustibility.

Referring to the Fifth Schedule of Uniform Building By-Laws 1984, our building belongs to

the ‘INSTITUTIONAL’ group as our building, an Elderly Care Centre, is being used as living

accommodation for person suffering from disabilities due to old age or illness. Therefore, in

the Ninth Schedule of Uniform Building By-Laws 1984, the minimum period of fire resistance

under this group for the elements of structure of the ground and upper storey should be at least

one hour.

Therefore, the walls for our building proposal will fulfil the criteria of having FRP of an hour

or more. This is to allow the elderly and other occupants to leave the building during an event

of a fire especially in a room since the building is more to an open clustered design. These

walls will protect the occupants from fire during the period of escape.

Uniform Building By-Laws 1984 Clause 143: Beam or Column

Any beam or column forming part of, and any structure carrying, and external wall which is

required to be constructed of non-combustible materials shall comply with the provisions of

paragraph (3) of by-law 142 as to non-combustibility.

30

Figure 19: Steel beam with cementitious fire proofing

In some parts of our building, there will be exposed steel structure. In the event of fire, the

temperature from the fire is not sufficient to melt the steel structures but overtime, it will

decrease the strength of the steel causing it to lose its stability as well as bearing capacity,

resulting in collapse. In order to protect the occupants, cementitious fire proofing or

Vermiplaster (fire proofing gypsum plater) will be sprayed throughout the steel structure such

as beam and column providing fire protection up to two hours.

31

3.1.3.2.3 Fire Doors

Figure 20: Fire rating doors

Uniform Building By-Laws 1984 Clause 162: Fire Doors in Compartment Walls and

Separating Walls

(1) Fire doors of the appropriate FRP shall be provided.

(2) Openings in compartment walls and separating walls shall be protected by a fire door having

FRP in accordance with the requirement for that wall specified in the Ninth Schedule to these

By-Laws.

32

The minimum Fire Rating Period (FRP) of the fire doors in the proposed building will be at

least half an hour. The function of the space determine the fire rating period of the fire doors.

Uniform Building By-Laws 1984 Clause 163: Half Hour and One Hour Doors

Fire doors conforming to the method of construction as stipulated below shall be deemed to

meet the requirement of the specified FRP:

(a) (i) Fire doors having FRP of half hour - a single door of 900mm x 2100m high or

double doors 1800mm x 2100mm high should be constructed of solid hardwood core of not

less than 37mm laminated with adhesives conforming to either BS 745 “Animal Glues”, or

BS1204, “Synthetic resin adhesives (phenolic and aminoplastic) for wood” Part 1, “Gap filling

adhesives”, or BS1444, “Cold setting casein glue for wood”, faced both sides with plywood to

a total thickness of more than 43mm with all edges finished with a solid edge strip full width

of the door. The meeting stiles of double doors shall be rabbeted 12mm deep or may be butted

provided the clearance is kept to a minimum.

(b) (i) Fire doors having FRP of one hour – single door not exceeding 900mm x 2100m

high or double doors not exceeding 1800mm x 2100mm high constructed as for (a) for half

hour fire door but incorporating both faces either externally or beneath the plywood faces a

layer of asbestos insulating board to BS3536 (not asbestos cement) not less than 3mm thick.

33

Figure 21: Single leaf and double leaf fire doors

These doors are usually thicker compared to the normal doors and usually more durable during

a fire according to their FRPs. They act as a barrier to separate the fire from the emergency

exits, keeping the occupants safe during evacuation.

Uniform Building By-Laws 1984 Clause 164: Doors Closer for Fire Doors

(1) All fire doors should be fitted with automatic door closer of hydraulic spring operated type

in the case of swing doors and of wire rope and weight type in the case of sliding doors.

34

Figure 22: Automatic door closer

The reason of installing an automatic door closer is to allow the fire doors to close without any

man’s operation in case of any fire. This is important to avoid the spread of fire into the

emergency route.

3.1.3.2.4 Measurement of Travel Distance to Exits

Uniform Building By-Laws 1984 Clause 165: Measurement of Travel Distance to Exits

(4) The maximum travel distances to exits and dead end limits shall be as specified in the

Seventh Schedule of these By-Laws.

Based on our building type as an institutional, the maximum travel distance:

Dead end limit – 9.0m

Unsprinkled area – 30.0m

Sprinkled area – 45.0m

35

Figure 23: Distance to the nearest exits

This requirement should be fulfilled in order to make sure the occupants can reach the exits

within the limits, and leave the building safely and immediately when there is fire or any

emergency.

3.1.3.2.5 Exits

Uniform Building By-Laws 1984 Clause 166: Exits to be Accessible All Times

(1) Except as permitted by By-Laws 167 not less than two separate exits shall be provided from

each storey together with such additional exits as may be necessary

36

(2) This exits shall be sited and the exit access shall be so arranged that the exits are within the

limits of travel distance as specified in the Seventh Schedule to these By-Laws and are readily

accessible at all times.

Uniform Building By-Laws 1984 Clause 167: Storey Exits

(1) Except as provided for in By-Laws 194 every compartment shall be provided with at least

two storey exits located as far as practical from other and in no case closer than 4.5m and in

such position that the travel distance specified in the Seventh Schedule to these By-Laws are

not exceeded.

(2) The width of storey exits shall be in accordance with the provisions in the Seventh Schedule

to these By-Laws.

Uniform Building By-Laws 1984 Clause 168: Staircases

(1) Except as provided for in By-Laws 194, every upper floor shall have means of egress via

at least two separate staircase.

(2) Staircases shall be of such width that in the event of any one staircase not being available

for escape purposes the remaining staircases shall accommodate the highest occupancy load of

any one floor discharging into it calculated in accordance with provisions in the Seventh

Schedule to the By-Laws.

(3) The required width of staircase shall be maintained throughout its length including at

landings.

(4) Doors giving access to staircases shall be so positioned that their swing shall at no point

encroach on the required width of the staircase or landing.

37

Uniform Building By-Laws 1984 Clause 169: Exit Route

(1) No exit route may reduce in width along its path of travel from the storey exit to the final

exit.

Figure 24: Storey exits

Figure 25: Staircases

38

Separate exits are very important in our building proposal as an elderly care centre. It allows

the elderly to evacuate from the building as soon as possible without the need of travelling long

distances to reach the only available exit. Therefore, two staircases are proposed to ensure the

flow during emergency.

Uniform Building By-Laws 1984 Clause 172: Emergency Exit Signs

(1) Storey exits and access to such exits shall be marked by readily visible signs and shall not

be obscured by any decorations, furnishings or other equipment.

(2) A sign reading “KELUAR” with an arrow indicating the direction shall be placed in every

location where the direction of travel to reach the nearest exits is not immediately apparent.

(3) Every exit sign shall have the word “KELUAR” in plainly legible letters not less than

150mm high with the principal strokes of the letters not less than 18mm wide. The lettering

shall be in red against a black background.

(4) All exit signs shall be illuminated continuously during periods of occupancy.

(5) Illuminated signs shall be provided with two electric lamps not less than 15 watts each.

Figure 26a: “KELUAR” signage

39

Figure 26b: Position of “KELUAR” signage

Storey exits and access to the exits should be mentioned clearly with a “KELUAR” sign with

an arrow indicating the direction of travel, indicating the direction to nearest exits. They are

required in a building because they lead the people to the nearest exits especially during an

emergency. People tend to get nervous when there’s an emergency. As a result, the local

authority mentioned that a signage is required in order to assist the occupants to the nearest

exits available. Therefore, the “KELUAR” sign will be placed at the doors of every public

rooms as well as the corridors, guiding the occupants to the nearest exits available at the

proposed building.

40

Uniform Building By-Laws 1984 Clause 173: Exit Doors

(1) All exit doors shall be openable from the inside without the use of a key or any special

knowledge or effort.

(2) Exit doors shall close automatically when released and all door devices including magnetic

door holders, shall release the doors upon power failure or actuation of the fire alarm.

Figure 27: Exit Doors and Escape Staircase

According to Clause 173 (1), the door swing is to be the direction of escape. The reason behind

this law is that in any case of emergency, when the door is partially blocked, the fire or escape

door will still be able to open to the escape route due to its swing direction, allowing the

evacuation of the occupants from the building.

41

Uniform Building By-Laws 1984 Clause 174: Arrangement of Storey Exits

(1) Where two or more storey exits are required, they shall be spaced at not less than 5m apart

measured between the nearest edges of the openings.

(2) Each exits shall give direct access to:

(a) a final exit

(b) a protected staircase leading to a final exit; or

(c) an external route leading to a final exit.

Figure 28a: Final exit Figure 28b: Storey exit and final exit

42

Figure 28c: Exits and final exits of proposed building

In any case of emergency, the occupants are to be move from the “blue” (exits) to the nearest

“red” (final exits).

43

3.2 Air Conditioning System

3.2.1 Introduction

Air conditioning systems are a necessity in Malaysia due to its tropical climate. Commonly

known as air-cond or A/C, air conditioning systems are devices used to provide an acceptable

level of occupancy comfort by controlling temperature, humidity, air distribution and indoor

air quality (IAQ) in order to maintain thermal comfort. Air conditioning systems are a group

of components working together to remove heat from a particular space, such as compressors,

condensers, ductworks and others.

3.2.2 Literature Review

Figure 29: Compressive refrigerant cycle

Refrigerant cycle serves the purpose of discharging unwanted heat from the inside of a building

space to the outside. The type of refrigerant cycle proposed in the Elderly Care Centre’s air

44

conditioning system is a compressive refrigerant cycle, which is a fully enclosed system

consisting four stages: expansion, evaporation, compression and condensation. Within this

enclosed system there is a chemical compound named a refrigerant. The refrigerant will be

liquefied and evaporated repeatedly during the process of it releases, and absorbs heat in the

cycle to help remove heat from the supply air and discharge it to the outside air. Thus, the

refrigerant can be used over and over again.

For the chosen building for this assignment, the system chosen is the split unit air conditioning

system. Being one of the most popular types of air conditioning systems nowadays, it is widely

used in residential housings and small scale buildings due to its silent, simple operation as well

as its elegant look. The system consists of two units, the outdoor unit and also the indoor unit,

both interconnected using copper tubing. Photos of the general components and diagrams for

the system are shown in Figures 29 and 30.

Figure 30: General components of split unit air conditioning system: outdoor unit, indoor

unit, control switch and copper tubing

45

Figure 31: Diagram of a split unit air conditioning system

The name ‘split system’ comes from the way this system actually works, split system air

conditioners are cooling systems that have ‘split’ functions; there is an external system outside

which is called the condensing unit. Located inside this unit is a compressor/pump, which

produces cold or hot gas that is fed through piping to the internal unit mounted on a wall. Split

systems do not actually add cool air to an area but instead remove heat from the existing air,

leaving the remaining air cooler. The cooling is accomplished by refrigerant, a compressor and

an evaporator. The refrigerant acts like a sponge (“squeeze”), compress it and the heat is

expelled; let it expand and it will absorb heat. If you squeeze it outside, the heat is expelled

into the air; bring it back inside and let it expand and it will soak up more heat from within.

Therefore, this gives the feeling of the system transferring hot or cold air across the room at an

even flow to create a balanced temperature.

46

3.2.3 Research Findings

The air conditioning system chosen to be used in the elderly care centre is the split unit system.

This is due to the small scale of the residential building as well as their small spaces inside the

vicinity. Besides that, the wall type indoor unit is chosen instead of a ceiling unit in order to

avoid disruption to the ceiling fans in such a small space.

Split unit air conditioning system consists of two parts, indoor and outdoor units, both having

to be less than 15 meters apart. The outdoor unit is hung or placed on the exterior of the room

of the indoor unit, where there is sufficient air flow around it to remove heat from its

compressor and condenser. The indoor unit is usually hung on the wall of the interior that is to

be cooled.

The outdoor unit removes heat from the refrigerant and also draws in surrounding air, blowing

it over the compressor and condenser, and thus cooling them. Besides that, the condenser is

also covered in aluminium fins so that the heat from the refrigerant can be removed at a much

faster rate. Meanwhile, the indoor unit works by drawing warm room air and passing it over

the filter and evaporator, which leads to the cooling of the air. Connecting these two units are

two copper tubes covered in a layer of insulation, one to supply the refrigerant to the cooling

coil and the other to return it to the compressor.

47

Figure 32: Split unit air conditioning flow chart

3.2.3.1 Air Conditioning Outdoor Unit

An outdoor unit of a split unit system acts as a small sized chiller, compromising the most

important components such as compressors and condensers. The unit runs at a minimum level

of noise to provide acoustic comfort to the environment. There are several components inside

of the outdoor unit as shown in Figure 33.

48

Figure 33: Split unit system outdoor unit components

1. Compressor

Figure 34: Compressor

49

External power is supplied to the compressor, which is utilized for compressing refrigerant and

increases its pressure before sending it to the condenser. The size of the compressor varies

depending on the desired air conditioning load. In most domestic split air conditioners,

hermetically sealed type compressor is used. In such compressors, the motor used for driving

the shaft is located inside the sealed unit and it is not visible externally.

2. Condenser Coil

Figure 35: Condenser Coil

It is a coiled copper tubing with one or more rows depending on the size of the air conditioning

unit and compressor. The condenser is also covered with aluminium fins so that the heat from

the refrigerant can be removed at a faster rate.

50

3. Condenser Cooling Fan

Figure 36: Condenser cooling fan

The condenser cooling fan is an ordinary fan with three or four blades and is driven by a motor.

The cooling fan is located in front of the compressor and the condenser coil. As the blades of

the fan rotate, it absorbs the surrounding air from the open space and blows it over the

compressor and the condenser with the aluminium fins and thus cooling them.

4. Expansion Valve

Figure 37: Expansion valve

51

The expansion valve is usually a copper capillary tubing with several rounds of coils. The high

pressure and medium temperature refrigerant leaves the condenser and enters the expansion

valve, where its temperature and pressure drops suddenly.

MS 1525:2007 Code of Practice on Energy Efficiency and Use of Renewable Energy for

Non-residential Buildings Section 8: Air-Conditioning and Mechanical Ventilation

(ACMV) System

8.4.4.2 Outdoor air supply and exhaust systems should be provided with motorised or gravity

dampers or other means of automatic volume shut-off or reduction during period of non-use or

alternate use of the spaces served by the systems.

In the Elderly Care Centre, outdoor units are installed around the side facades, hidden from the

views from the front while blending with the form of building without spoiling the aesthetic

value of the centre. The area where the outdoor unit is located also ensures sufficient air flow

to remove the heat produced. Work of maintenance can be easily done as the outdoor unit can

be easily accessed. In some areas, vegetation are used to hide outdoor units.

52

Figure 38: Location of air conditioning outdoor units

53

3.2.3.2 Air Conditioning Indoor Unit

Indoor units serve similar purposes as air handling unit (AHU). However, the air is not

distributed to different spaces. The cooled air is directly transferred to the spaces where the

indoor unit is located and the flow of air is controlled by the horizontal louvers. Split unit

indoor units run at an extremely low level of noise. Hence, people have considered it as white

noise which could enhance the sleeping quality or working performance. The type of indoor

unit chosen for this assignment is the wall mounted type. The several components of an indoor

wall mounted unit as shown in Figure 39.

Figure 39: Split unit system indoor unit components

54

1. Evaporator Coil

Figure 40: Evaporative coil

Acts as a cooling coil is a copper coil made of turns of copper tubing with one or more rows

depending on the capacity of the air conditioning system. The cooling coil is covered with the

aluminium fins so that the maximum amount of heat can be transferred from the coil to the air

inside the room.

2. Air Filter

Figure 41: Air filters

55

An air filter removes all dirt particles from the room air and helps supplying clean air to the

room. The air filter in the wall mounted type of the indoor unit is placed just before the cooling

coil.

3. Cooling Fan/Blower

Figure 42: Cooling fan/blower

The blower sucks the hot and unclean air from the room and resupplies clean and cool air back.

The shaft of the blower rotates inside the bushes and it is connected to a small multiple speed

motor, thus the speed of the blower can be changed. When the fan speed is changed with the

remote, the speed of the blower changes.

4. Louvers/ Fins

The cool air supplied by the blower is passed into the room through louvers. The louvers help

change the angle or direction in which the air needs to be supplied into the room as per

requirements. There are two types of louvers, horizontal and vertical. The horizontal louvers

are connected to a small motor and their position can be set by the remote control, and the

56

vertical louvers are operated manually and one can easily change their position as per the

requirements.

In the Elderly Care Centre, indoor wall mounted units are placed in areas which require air

conditioning on a rigid concrete wall that can properly withstand its weight. Units are placed

2.4 meters above ground level as specified and also to ensure easy accessibility. Locations are

also carefully considered where air can be distributed as evenly as possible into the interior

spaces.

57

3.3 Mechanical Ventilation System

3.3.1 Introduction

Ventilation is the process of changing air from outside or circulating air within a space.

Ventilation is mainly used to control indoor air quality by removing carbon dioxide, unpleasant

smells, excessive moisture and contaminants to replenish the indoor space with oxygen. It can

also be used to improve the thermal comfort when the introduction of outside air helps to

achieve desired indoor psychometric conditions. Ventilation can be divided into natural

ventilation and mechanical ventilation.

Mechanical ventilation is the system which encourages during the process of changing air

condition and quality in an enclosed space when natural ventilation is not appropriate.

Mechanical ventilation circulates fresh air with the aid of fan and makeup air supply.

Mechanical ventilation incorporates heating, cooling and humidity control. This can be alluded

to as warming ventilation and aerating and cooling (HVAC). Mechanical ventilation is differed

from natural ventilation as it needs electricity to support its system.

Mechanical ventilation is commonly used in Malaysia’s buildings in order to ventilate the

spaces and to provide good indoor air quality condition. Mechanical ventilation system is

considered to be reliable in delivering the designed flow rate, regardless of the impacts of

variable wind and ambient temperature. Filtration system can be installed in the mechanical

ventilation system so that the harmful substances can be filtered before entering the building.

Besides that, natural ventilation has no control on the amount of airflow where mechanical

ventilation is more controllable compared to natural ventilation. The services can be planned

58

on the sources of airflow and the air is filtered before entering the house, which could prevent

the air leaking in to the house from undesirable area like crawl space and causing the increase

the level of air pollution.

3.3.2 Literature Review

When natural ventilation is not effective enough, mechanical ventilation system is responsible

to remove stale air inside the building with fresh air and draw in outside air when the

environment is polluted and high humidity. Exhaust fan is the basic component among the

several components which removes stale air from the building’s interior. There are two types

of mechanical ventilation system which are spot ventilation and energy recovery ventilation

system. Spot ventilation can be categorized into supply system, extract system and combination

system. Combination system is the system which consists of supply and extract system. All

these systems are having similar components which include fans, filters, ductworks, fire

dampers and diffusers.

3.3.2.1 Extract System

Figure 43: Exhaust ventilation air flow diagram

59

Exhaust ventilation system is known as fans. It works by depressurizing the interior, creating

negative pressure on its inlet and the system exhausts the air from the interior while make-up

air infiltrates through leaks in the building shell and passive vent. Mechanical extract fans are

installed in the duct connected to the central exhaust point in the building and discharge away

the air from occupying the space owing to its combination with heats, fumes, smoke water

vapour or odour.

3.3.2.2 Supply System

Figure 44: Supply ventilation air flow diagram

The supply ventilation system has a fan and duct system that introduces fresh air into the

interior. This system pressurizes the interior by supplying from outside in order to maintain

positive pressure. This system can be used in a polluted and noisy environment and it can filter

the incoming air. The air supply is located in high place and it should not be located near the

outlet location to prevent air from escaping that is being circulated inside the building. A fan

and a set of ductwork are used to distribute the fresh air from outside or it can be connected

with the returning air duct, allowing the fan and ducts to process the outdoor air before being

distributed.

60

3.3.3 Research Findings

MS 1525 code 8.4.5 Mechanical Ventilation Control

“Each mechanical ventilation system (supply/exhaust) should be equipped with a readily

accessible switch or other means for shut down or volume reduction when ventilation is not

required. Example of such devices would include timer switch control, thermostat control, duty

cycle programming and CO/CO2 sensor control.”

3.3.3.1 Return Air Grille

Figure 45: Diagrams of return air grille

The return air grille is placed at the toilet and kitchen to ensure the building is well-ventilated

and foul air expelling out from the building. Each of the toilet will be provided with a 495mm

x 495mm return air grille which is enough to cover the whole area in the toilet. For the kitchen,

a return air grille is proposed at the stove and another 595mm x 1195mm return air grille on

the ceiling of the dining area as shown in Figure 46. To avoid big objects from entering and

damaging the duct, they usually use grillwork to cover the duct behind. Filters are also installed

to trap pollutants and allow better air flow.

61

Figure 46: The placement of the return air grille

3.3.3.1.1 Components involved in extract ventilation system

Fan

Figure 47: Propeller fan

62

Fan is to bring in outdoor air and remove hot, humid and polluted air. There are several types

of fan which include the propeller fan, axial fan and centrifugal fan. In this project, the propeller

fan is proposed because it’s low cost of installation and quiet. The propeller fan can also remove

large volume of air.

Filter

Figure 48: Air filter

An air filter will typically play two roles in a HVAC system. It acts as an indoor quality

mitigation component to trap and prevent dust, smoke, bacteria from entering the room and

also protects the HVAC equipment (such as fans and coils) from the environment dirt.

Ductwork

Figure 49: Ductwork

63

Ductwork is used to channel outside air towards the room or the air from the room towards the

outside. It may be steel, rigid glass fibre, flexible, or cloth. The first three materials are by far

the most common.

Fire Damper

Figure 50: Fire damper

Fire damper is usually placed at the compartment wall. It penetrates fire-rated assemblies and

will need to be outfitted with fire dampers. Its main purpose is to prevent the spreading of fire

from one room to another.

Grille and Diffuser

Figure 51: Air Grille

64

A “diffuser” is defined (ASHRAE, 2013) as a circular, square, rectangular, or linear air

distribution outlet. A “register” is defined (ASHRAE, 2013) as a combination grille and damper

assembly over an air opening. A “grille” (ASHRAE, 2013) is a louvered or perforated covering

for an opening in an air passage which can be located in a wall. It is normally located at the

edge of the ductwork where is released into the room.

3.3.3.2 Fire Exhaust Fan

Figure 52: Proposed fire damper

Figure 53: Typical fire damper installation details

Fire damper is a passive fire protection product used in heating ventilation and air conditioning

(HVAC) ducts to prevent the spread of fire inside the ductwork through fire resistance rated

65

walls and floors. A 500mm x 500mm fire damper is proposed at near to the kitchen where it

has the high possibility on catching fire as shown in Figure 54. Whenever there is fire

happening inside the Elderly Care Centre, the fire damper will help to extract the smoke. The

fire damper system is always on its standby mode and it will function when the concentration

of smoke hits the system.

Figure 54: Placement of the fire dampers

66

3.3.3.3 Supply Air Diffusers

A 495mm x 495mm air supply diffusers are located at the pharmacy, therapy room and some

of the enclosed rooms of the Elderly Care Centre as shown in Figure 56. It supplies air into the

room and it is preferred when passive ventilation fails or is incapable of regulating airflow

inside out of the Elderly Care Centre.

Figure 55: Supply air diffusers

67

Figure 56: Placement of supply air diffusers

68

3.4 Mechanical Transportation System

3.4.1 Introduction

The mechanical transportation is an energy-using services which becomes an integral part of

modern buildings to move people and goods. The need of this such system arises with the

expectations of quality by the final user and with the provision of access for elderly and

disabled people. Others services, fire protection, means of escape and proper maintenance are

of the highest importance when designing this system. The energy consumption may be low,

but a significant amount of electrical power is required for short periods.

3.4.2 Literature Review

Hydraulic Elevator

Figure 57: Hydraulic elevator Figure 58: Hydraulic elevator diagram

69

Hydraulic elevators are typically used for low-rise buildings of two to eight stories, suitable for

lifting goods, in hospitals and old folks’ homes. They are supported by a piston at the bottom

of the elevators that pushes the elevator up as an electric motor forces oil into the piston. As it

descends, a valve releases the fluid from the piston. Travelling at a maximum speed of 61m

per minute, hydraulically operated lifts have the advantage of very quiet operation and lower

maintenance costs compared to other types of elevators. These elevators also have low

structural cost due to lower imposed load in comparison to electric and traction elevators. A

major drawback of this this type of elevator is that it is a high-heat producing system. Pollution

in ground water may occur if the oil leaks into the ground at the base of the elevator.

70

3.4.3 Research Findings

Uniform Building By-Laws 1984 Clause 124: Lifts

For all non-residential buildings exceeding 4 storeys above or below the main access level at

least one lift shall be provided.

A hydraulic elevator is proposed in this two-storey Elderly Care Centre to provide ease of

convenience to the users of the buildings. The staircase is situated closely to the elevator for

emergency purposes. The placement of elevator is within 45m walking distance to the elevator

lobby from any point in the building.

Figure 59: Location of lift on ground floor and first floor plan

71

According to ‘MS 1184:2002 Code of Practice on Access for Disabled Persons to Public

Building’s’, an unobstructed depth clearance of minimum 1800mm is provided in front of the

lift door. A handrail in the lift car is 600mm long at 1000mm above the finished floor level,

fixed adjacent to the control panel. To allow wheelchair users to access the elevators, a clear

opening of 1000mm is provided and sensing devices are implemented to ensure that lift car and

landing doors remain unclosed while the opening is obstructed as shown in Figure 60.

Figure 60: Lift car requirement according to MS 1184:2002 Code of Practice On Access For

Disabled Persons To Public Buildings

72

3.4.3.1 Method of operation (Direct Acting)

Figure 61: Method of operation for hydraulic elevators

The pump forces fluid from the tank into a pipe leading to the cylinder. When the valve is

opened, the pressurized fluid will take the path of least resistance and return to the fluid

reservoir. But when the valve is closed, the pressurized fluid has nowhere to go except into the

cylinder. As the fluid collects in the cylinder, it pushes the piston up, lifting the elevator car.

When the car approaches the correct floor, the control system sends a signal to the electric

motor to gradually shut off the pump. With the pump off, there is no more fluid flowing into

the cylinder, but the fluid that is already in the cylinder cannot escape (it can't flow backward

through the pump, and the valve is still closed). The piston rests on the fluid, and the car stays

where it is.

73

To lower the car, the elevator control system sends a signal to the valve. The valve is operated

electrically by a basic solenoid switch (Actuator). When the solenoid opens the valve, the fluid

that has collected in the cylinder can flow out into the fluid reservoir. The weight of the car and

the cargo pushes down on the piston, which drives the fluid into the reservoir. The car gradually

descends. To stop the car at a lower floor, the control system closes the valve again.

3.4.3.2 Hydraulic Elevator Component

Hydraulic elevators differ from other types of elevators in the components of machine / drive

system and safety system. The lift car is driven by direct acting where the piston pushes up the

car directly as shown in Figure 63.

Figure 62: Hydraulic elevator component

74

Figure 63: Hydraulic lift drive

Piston

The cylinder piston is constructed using steel pipe of sufficient thickness and suitable safety

margin. The cylinder top is equipped with a cylinder head with an internal guide ring and self-

adjusting packing.

Hydraulic Power Unit

Figure 64: Hydraulic power unit

75

The power unit as shown in Figure 64 is operated with minimum noise and vibration to avoid

distraction to the users in the building. As such, vibration insulators are mounted above the

machine room floor and a silencer unit is fitted in the hydraulic system to reduce the

transmission of pulsations from the pump to the car and the elimination of airborne noise.

3.4.3.3 Safety System

Uniform Building By-Laws 1984

Clause 153: Smoke detectors for lift lobbies –

(1) All lift lobbies shall be provided with smoke detectors.

Clause 154: Emergency mode of operation in the event of mains power failure –

(1) On failure of mains power of lifts shall return in sequence directly to the designated floor,

commencing with the fire lifts, without answering any car or landing calls and park with doors

open.

Clause 155: Fire mode of operation –

(2) If mains power is available all lifts shall return in sequence directly to the designated floor,

commencing with the fire lifts, without answering any car or landing calls, overriding the

emergency stop button inside the car, but not any other emergency or safety devices, and park

with doors open.

(3) The fire lifts shall then be available for use by the fire brigade on operation of the fireman's

switch.

(4) Under this mode of operation, the fire lifts shall only operate in response to car calls but not

to landing calls in a mode of operation in accordance with by-law 154.

76

Hydraulic elevators have seismic valves located in the pit close to the jack that is designed to

withstand pressure in the case where the hydraulic line is broken due to seismic activity. A

buffer-striking member on the underside of the car helps to stop the elevator before the piston

reaches its down limit of travel.

77

4.0 CONCLUSION

Fire must not be taken lightly. In fact, fire is dangerous and hazardous when is not controlled

in the right environment. The active systems are meant to control fires and prevent further

damage caused by it. Active systems are meant to be used in emergencies or when threats of

fire outbreak occurs. These systems are designed to put out fires effectively and in an orderly

manner in most situations. Most importantly situations where there are more than one public

involve. Hence, the importance of active systems should not be taken lightly and to be

understood by the public.

Passive fire system refers to the elements of the buildings that provide fire protection, ensuring

occupants’ safety in the building. This system block or slow down the spread of fire through

the help of fire resistant wall and fire doors, just to name some. Fire doors help to

compartmentalize the building while giving its occupants means of escape. Fire walls as well

as the floors help to separate the building into compartments to stop the spread of fire and

smoke from one to another. The importance of these elements is to provide sufficient time for

people in the building to escape. Not only that, staircases play an important role to provide the

upper floor occupants to leave the building via the nearest staircase to the exit or final exit. Exit

signage is also significant to provide guidance to the occupants on the right way to the final

exit in a limited period of time. In short, passive fire system should always be considered during

the design of the building, minimizing the impact of the fire on the occupants inside the

building at the same time allowing them to leave the building safely in the limited period of

time.

78

A split unit air conditioning system is the most suitable for the Elderly Care Centre as it is a

small residential building. Besides, it also allows flexibility in control, only turning on when it

is to be used, saving electricity and energy. At the same time, the wall mounted type is more

suitable in small interior spaces which have a ceiling fan equipped, so that the A/C unit is not

disrupted by the ceiling fan or lighting.

This Elderly Care Centre has a lot of enclosed spaces causing poor natural airflow. Hence,

mechanical ventilation must be introduced to enhance the efficiency of the ventilation of the

building. Different spaces require ventilation at different hours, so separated accessible

switches to control different air distribution systems are required. Thus, the mechanical

ventilation allows polluted air to be extracted out and cleans air drawn in the spaces efficiently.

A hydraulically operated elevator is proposed in this Elderly Care Centre as it is suitable for

lifting goods and easily operable with lower maintenance cost. The acceleration and travel

experience is also very smooth due to the lack of brake, ropes, pulleys or winding gears.

79

5.0 REFERENCES

Fire Protection System

1. D. (Ed.). (2011). Guide to Fire Protection in Malaysia. Kuala Lumpur, Selangor: The

Institute of Fire Engineers (UK) Malaysia Branch.

2. Fire causes. (n.d.). Retrieved November 23, 2016, from http://www.nfpa.org/news-

and-research/fire-statistics-and-reports/fire-statistics/fire-causes

3. Ionization vs photoelectric. (n.d.). Retrieved November 23, 2016, from

http://www.nfpa.org/public-education/by-topic/smoke-alarms/ionization-vs-

photoelectric

4. The Combustion Process. (n.d.). Retrieved November 23, 2016, from

http://www.auburn.edu/academic/forestry_wildlife/fire/combustion.htm

5. Uniform Building By-Laws 1984. (2013). Petaling Jaya, Selangor: International Law

Book Service.

6. What is a hydrant and why are they so important? (n.d.). Retrieved November 23,

2016, from https://www.fire.nsw.gov.au/home-fire-safety/hydrant-why.html

Air Conditioning System

1. Climate Design. (n.d.) Common Air Conditioning Terms You Should Know | Climate

Design. Retrieved November 13, 2016, from http://www.climatedesign.com/common-

air-conditioning-terms-know/

2. Haresh, K (2009). Parts of Split Air Conditioners: Outdoor Unit. Retrieved November

19, 2016, from http://www.brighthubengineering.com/hvac/45044-parts-of-the-split-

air-condioners-outdoor-unit/

80

3. Malaysian Standard. (2007) Code of practice on energy efficiency and use of

renewable energy for non-residential buildings (1st ed.). Putrajaya.

4. Mitsubishi Electric Cooling and Heating. (n.d.). 5 Advantages of Ductless Cooling

and Heating Systems. Retrieved 10 November 2016, from

http://www.mitsubishicomfort.com/articles/ductless/5-advantages-of-ductless-

cooling-and-heating-systems

5. Zero, B. & Zero, B. (2016). Air Conditioning | Heating & Cooling Experts in Ottawa

ON. Belowzerohvac.ca. Retrieved November 22, 2016, from

http://belowzerohvac.ca/air-conditioners-ottawa/

Mechanical Ventilation System

1. Haines, R. & Wilson, C. (2003). HVAC systems design handbook (1st ed.). New

York: McGraw-Hill.

2. MacIntyre, N. & Branson, R. (2009). Mechanical ventilation (1st ed.). St. Louis, MO:

Saunders Elsevier.

3. Swenson, S. D. (1995). HVAC: Heating, ventilating, and air conditioning.

Homewood, IL: American Technical.

4. Young, A. N. (2000). Building services. London: U.C.L. Bartlett School of

Architecture and Planning.

Mechanical Transportation System

1. Ching, F., & Adams, C. (2001). Building construction illustrated. New York: Wiley.

2. Hall, F., & Greeno, R. (2005). Building services handbook. Oxford: Elsevier

Butterworth-Heinemann.

3. Uniform Building By-Laws 1984. (2013). Petaling Jaya, Selangor: International Law

Book Service.