Hazardous (Classified) Locations 1910.307

Hazardous classified locations

Embed Size (px)

DESCRIPTION

Hazardous classified locations

Citation preview

Page 1: Hazardous classified locations

Hazardous (Classified) Locations1910.307

Page 2: Hazardous classified locations

INTRODUCTION

• A hazardous location is any location where a potential hazard, either a fire or an explosion can exist due to the presence of flammable, combustible, or ignitable materials.

• These materials can consist of gases, vapors, liquids, dusts, fibers, etc.

Page 3: Hazardous classified locations

HAZARDOUS LOCATION TYPES

• Class I Locations:

An area where flammable gases or vapors are or can be present in the air in quantities sufficient to produce explosive or ignitable mixtures. For Example

* Petroleum Refineries, Gasoline storage and dispensing areas, Dry cleaning plants, Spray Finishing areas, utility gas plants.

Page 4: Hazardous classified locations

Continued

• Class II Locations:

An area where presence of combustible dust present a fire or explosion hazard. For example:

Grain elevators, flour and feed mills, Use or store of magnesium or aluminum powders, producers of plastics, fireworks.

Page 5: Hazardous classified locations

Continued

• Class III LocationsClass III Locations::

An area made hazardous due to the An area made hazardous due to the presence of easily ignitable fibers or presence of easily ignitable fibers or flyings. For example:flyings. For example:

Textile mills, cotton gins, cotton seed Textile mills, cotton gins, cotton seed mills, plants that shape or cut wood and mills, plants that shape or cut wood and create sawdust or flyings.create sawdust or flyings.

Page 6: Hazardous classified locations

Hazardous Location Conditions

• In addition to the types of hazardous locations, the kind of conditions under which these hazards are present are very important : Normal Conditions, Abnormal Conditions.

• Division 1: Normal Conditions

• Division 2 : Abnormal Conditions

Page 7: Hazardous classified locations

Continued• Class I, Class II, and Class III hazardous

locations can be either Division 1 or Division 2

• Good examples of Class I, Division 1 locations: areas near open dome loading facilities or adjacent to relief valves in a petroleum refinery, because the hazardous material would be present during normal plant operations.

Page 8: Hazardous classified locations

Continued

• Closed storage drums containing flammable liquids in an inside storage room would not normally allow hazardous vapors to escape into the atmosphere but, what happens if one of the containers is leaking? You have got a Division 2 – Abnormal – condition … A Class I, Division 2 hazardous location.

Page 9: Hazardous classified locations

Class I, Division 1• Where ignitable concentration of flammable gases,

vapors or liquids can exist all of the time or some of the time under normal operating conditions.

• Where ignitable concentrations of such gases or vapors may exist frequently because of repair or maintenance operations or because of leakage.

• Faulty operations of equipment or processes might release ignitable concentrations of flammable gases or vapors and might cause simultaneous failure of electrical equipment in such a way as to directly cause the electrical equipment to become a source of ignition.

Page 10: Hazardous classified locations

Class I, Division 2

• Is a location in which volatile flammable liquids or flammable gases are handled, processed, or used, but in which the liquids, vapors, or gases will normally be confined within closed containers or closed systems from which they can escape only in case of accidental rupture or breakdown of such containers or systems or in case of abnormal operation of equipment.

Page 11: Hazardous classified locations

Class I, Division 1 & Class I, Division 2

Page 12: Hazardous classified locations

Class II, Division 1 & Class II, Division 2

Page 13: Hazardous classified locations

Class III, Division 1 & Class III Division 2

Page 14: Hazardous classified locations

Nature of Hazardous Substances

• The gases and vapors of class I locations are broken into four groups : A, B, C, and D. These materials are grouped according to the ignition temperature of the substance, its explosion pressure, and other flammable characteristics.

Page 15: Hazardous classified locations

Group A

• Group A is an atmosphere containing acetylene.

• Equipment with rating up to 536º F (280ºC) can be utilized.

Page 16: Hazardous classified locations

Group B

• Group B is an atmosphere containing hydrogen, or gases or vapors with a hazard equal to hydrogen. Butadiene, and ethylene and propylene oxide are included in this group.

Page 17: Hazardous classified locations

Group C

• Group C is an atmosphere containing cyclo-propane, ethyl ether, or gases or vapors with hazard equal to these gases.

Page 18: Hazardous classified locations

Group D

• Group D is an atmosphere containing acetone, alcohol, benzene, butane, gasoline, propane, natural gases or gases with vapors with a hazard equal to these gases.

Page 19: Hazardous classified locations

Nature of Hazardous Substances

• In Class II - dust locations – we find the hazardous materials in Groups: E, F, G. These groups are classified according to the ignition temperature and the conductivity of the hazardous substance.

• Conductivity is an important consideration in Class II locations, especially with metal dusts.

Page 20: Hazardous classified locations

Group E

• Group E is an atmosphere containing metallic dusts or other dusts with a similar hazard that is equivalent, such as Aluminum and Magnesium dusts.

Page 21: Hazardous classified locations

Group F

• Group F is an atmosphere containing Carbon Black, Charcoal Coal, or Coke dusts with 8% or less total volatile material.

Page 22: Hazardous classified locations

Group G

• Group G is an atmosphere containing grain dusts, flour , starch, cocoa, and similar types of materials.

Page 23: Hazardous classified locations

Continue

• Class III locations are not broken into groups.

Page 24: Hazardous classified locations

North America Optional Area Classification

Class I, Zone 0, 1, and 2

Page 25: Hazardous classified locations

Class I, Zone 0 is a Locations in which:

• Ignitable concentration of flammable gases or vapors are present continuously; or

• Ignitable concentrations of flammable gases or vapors are present for long periods of time.

Page 26: Hazardous classified locations

Class I, Zone 1 is a location:• In which ignitable concentrations of flammable gases

or vapors are likely to exist under normal operating conditions; or

• May exist frequently because of repair or maintenance operations or because of leakage;

• In which equipment is operated or processes are carried on, of such a nature that equipment breaking down or faulty operations could result in the release of ignitable concentrations of flammable gases or vapors and also cause simultaneous failure of electrical equipment in a mode to cause the electrical equipment to become a source of ignition.

Page 27: Hazardous classified locations

Class I, Zone 2 is a location

• In which ignitable concentrations of flammable gases or vapors are not likely to occur in normal operation and, if they do occur, will exist only for a short period.

• Ignitable gases and liquids are confined within closed containers from which they can escape, only as a result of accidental rupture or breaking of the containers or system, or as a result of abnormal operation of the equipment.

Page 28: Hazardous classified locations
Page 29: Hazardous classified locations

Elements of Hazardous Area Classification

• Sparks can occur by electrical or mechanical activity.

• Electrically the sparks are usually made by:

• Switching contacts

• Loose contacts in circuit carrying current

• Poorly mating metallic faces that are carrying current

• Static discharge.

Page 30: Hazardous classified locations
Page 31: Hazardous classified locations

Mixtures of Gases, Vapors and Air

• Ignition can only lead to a fire or explosion if three necessary components occur simultaneously, these are:

1. Flammable gas or vapor is present in sufficient quantities. (leakage)

2. Sufficient air (oxygen)3. Source of ignition (this could be spark having

sufficient energy or hot surface that will cause spontaneous or auto-ignition.

Page 32: Hazardous classified locations
Page 33: Hazardous classified locations

Gases and Vapors

• Imagine a flammable gas or vapor slowly leaking into confined volume of air that is not replenished.

• The concentration of gas or vapor in the mixture will be too low to support combustion

• As concentration increases until we reach LEL.• More increase we reach UEL.• LEL is very important in case of hazardous areas

to dilute it by air to low and safe levels

Page 34: Hazardous classified locations

Temperature Class

• It is important to know how hot equipment gets, so that hot surfaces cannot be ignition sources.

• Six temperature classes are used T1 – T6• The lower the number the higher the maximum

allowable surface temperature• Temperature classification is based on fault

conditions.• T-class must be below Auto-ignition Temperature

of the gas.

Page 35: Hazardous classified locations
Page 36: Hazardous classified locations

Example of AIT

• Material AIT (°C)• Carbon Disulfate 102• Diethyl Ether 170• Kerosene 210• Ethylene 450• Propane 466• Methane 538• Hydrogen 560

Page 37: Hazardous classified locations

Apparatus Group

• All flammable gases are sub-grouped into IIA, IIB or IIC on the bases of:

1. How easily the burning gas will burn through a narrow gap (measured as the maximum experimental safe gap (MESG)

2. The maximum spark ignition energy (MIE)

Page 38: Hazardous classified locations

Apparatus Group

• A group IIA gas or vapor is the hardest of these sub-groups to ignite by a spark.

• Conversely a group IIC gas or vapor is the easiest to ignite.

Page 39: Hazardous classified locations

Explosion Groups• The maximum experimental safe gap is determined

using a test apparatus.• Each gas or vapor/air mixture in its most volatile form,

under normal temp. and pressure is filled into the interior and exterior chambers of the test apparatus.

• The circumferential gap between the two chambers is accurately adjusted to the desired value.

• The explosive mixture in the interior chamber is ignited and the flame propagation, if any is observed through the windows in the exterior chamber.

• To find the maximum value of gap which prevents ignition of the explosive mixture in the exterior chamber.

Page 40: Hazardous classified locations

MESG (Maximum Experimental Safe Gap)

• The maximum clearance between two parallel metal surfaces that has been found, under specified test conditions, to prevent an explosion in a test chamber from being propagated to a secondary chamber containing the same gas or vapor at the same concentration.

Page 41: Hazardous classified locations

MIC (Minimum Igniting Current) Ratio

• The ratio of the minimum current required from an inductive spark discharge to ignite the most easily ignitable mixture of a gas or vapor, divided by the minimum current required from an inductive spark discharged to ignite methane under the same test conditions.

Page 42: Hazardous classified locations

Explosion ClassesApparatus group for flameproof enclosure “d” Limiting Gap

Width

Minimum Ignition Current for Intrinsically

Safe Circuits “i”

Ratio in relation to Methane

A > 0.9 mm > 0.8

B > Or = 0.5 to 0.9 mm

> Or = 0.45 to 0.8

C < 0.5 mm < 0.45

Page 43: Hazardous classified locations

Example of MIE

• Material Ignition Energy µJ

• Hydrogen 40

• Ethylene 120

• Propane 320

• Methane 525

Page 44: Hazardous classified locations
Page 45: Hazardous classified locations

Explosion Groups & Temp. ClassesExp.

Groups

T1 T2 T3 T4 T5 T6

I Methane

IIA Acetone

Ethane

Propane

Ammonia

Ethane

Ethyl Alcohol

N-Butane

N-Hexane

Petrol

Diesel Fuel

Heating oil

Acetaldehyde

Ethyl-ether

IIB Town Gas Ethylene

Diethyl ether

CO

IIC Hydrogen Carbon Disulfide

Page 46: Hazardous classified locations

Equipment for Hazardous Locations

• Equipment for Class I locations:The equipment used in Class I locations are housed in enclosures designed to contain any explosion that might occur if hazardous vapors were to enter the enclosure and ignite.Also it is designed to cool and vent the products of this explosion.

Page 47: Hazardous classified locations
Page 48: Hazardous classified locations
Page 49: Hazardous classified locations
Page 50: Hazardous classified locations
Page 51: Hazardous classified locations

Equipment for Class II Locations

• Class II locations make use of equipment designed to seal out dust. The enclosures are not intended to contain an internal explosion, but rather to eliminate the source of ignition so no explosion can occur within the enclosure.

Page 52: Hazardous classified locations

Equipment for Class III Locations

• Equipment used in class III locations need to be designed to prevent fibers and flyings from entering the housing. It also needs to be constructed in such a way as to prevent the escape of sparks or burning materials.

• It must also operate below the point of combustion.

Page 53: Hazardous classified locations

Types of Protection

1. Flameproof Enclosures “d”2. Intrinsic Safety “i”3. Increased Safety “e”4. Powder/Sand Filled “q”5. Pressurized Apparatus “p”6. Oil Immersion “o”7. Special Protection “s”8. Encapsulation “m”9. Type of protection N “N”

Page 54: Hazardous classified locations

Flameproof Enclosures “d”

Type of protection, for which the parts which can ignite an explosive atmosphere are inside an enclosure which willWithstand the pressure of theExplosion within the enclosure.

Prevent the transmission of theExplosion to an explosiveAtmosphere surrounding theEnclosure.

Page 55: Hazardous classified locations
Page 56: Hazardous classified locations
Page 57: Hazardous classified locations

Intrinsic Safety “i”

• Type of protection, for which the energy in the electrical circuit is held so low that sparks, arcs or temperatures capable of causing ignition cannot occur.

• Includes sub-division into the categories ia & ib

• Ia must not produce any ignition when any combination of two faults is present.

• Ib must not produce any ignition, in normal operation, when one fault is present.

Page 58: Hazardous classified locations

Increased Safety “e”

• Type of protection, for which measures are taken to prevent the possibility of non-permissible high temperatures and the formation of sparks or arcs on inner or outer parts of electrical apparatus, on which these do not occur in normal operation, with an increased level of safety.

Page 59: Hazardous classified locations

Powder/Sand Filled “q”

• The electrical apparatus enclosure is filled with powder or sand.

• An arc occurring in the enclosure does not ignite an explosive atmospheres surrounding the enclosure.

Page 60: Hazardous classified locations

Pressurized Apparatus “p”

• Preventing the entry of surrounding atmosphere into the enclosure by holding an ignition-protection gas (air, inert gas) under over-pressure in relation to the surrounding atmosphere

Page 61: Hazardous classified locations

Oil Immersion “o”

• Electrical apparatus or parts thereof are made safe by immersion in oil such that potentially explosive atmosphere above the surface of the oil or outside the enclosure will not be ignited.

Page 62: Hazardous classified locations
Page 63: Hazardous classified locations
Page 64: Hazardous classified locations
Page 65: Hazardous classified locations
Page 66: Hazardous classified locations

European System

Page 67: Hazardous classified locations

Hazardous Zones

• Zone 0

• Zone 1

• Zone 2

• Non-Hazardous area

• Area that was deemed to be completely free of potential hazards.

Page 68: Hazardous classified locations

Area (Zone) Classification

• In order to evaluate and stipulate the necessary protective measures, hazardous areas have been classified into different zones in respect to the probable occurrence of an explosive atmosphere.

• Hazardous area is defined as three-dimensional space in which a flammable atmosphere may be expected to be present at such frequencies as to require special precautions for the construction and use of electrical apparatus.

• The European classification: Hazardous areas are divided into three zones:

• Zone 0 , Zone 1, and Zone 2

Page 69: Hazardous classified locations

Zone 0

• Is a zone in which an explosive gas/air mixture is continually present for long periods of time.

Page 70: Hazardous classified locations

Zone 1

• Is a zone in which an explosive gas/air mixture is likely to occur under normal operating conditions.

Page 71: Hazardous classified locations

Zone 2

• Is a zone in which an explosive gas/air mixture is unlikely to occur under normal operating conditions, and if it does it will exist only for a short period of time.

Page 72: Hazardous classified locations

Extend of zone

• The distance in any direction, vertical and horizontal, from the source of release to the point where the flammable atmosphere has been diluted by air to a sufficiently low level

• For a given release the extend will vary with the vaporizing potential of the fluid release, the ventilation state and the bouyancy factor of the vapor.

Page 73: Hazardous classified locations
Page 74: Hazardous classified locations
Page 75: Hazardous classified locations

Area Classification

Oil Water Separator

Page 76: Hazardous classified locations

Floating-Roof Tank

Page 77: Hazardous classified locations

Fixed Roof Tank

Page 78: Hazardous classified locations
Page 79: Hazardous classified locations

Selection of apparatusZone Type of Protection

0 Intrinsically safe Ex ia

Special protection Ex s

1 Any type of protection suitable for zone 0

Flameproof Ex d

Intrinsically safe Ex ib

Pressurized Ex p

Increased safety Ex e

Special protection Ex s

2 Any type of protection suitable for Zone 0 or Zone 1

Ex N or Ex n

Oil immersion Ex o

Quartz Filled Ex q

Page 80: Hazardous classified locations

Types of Protection for Ingress of Water and Solid Particles

European Practice

Page 81: Hazardous classified locations

Enclosure (IP) Protection

• The measures required to be applied to the enclosure to provide a chosen degree of protection to:

1. Persons against contact with internal live or rotating parts inside the enclosure, and to the apparatus against ingress of solid objects, dusts, etc.

2. The apparatus against the ingress of water, spray, jets, heavy seas and even total immersion.

Page 82: Hazardous classified locations
Page 83: Hazardous classified locations

Ingress Protection against Particles3rd Digit Degree of Protection

0 No mechanical protection

1 Protection against large-sized foreign bodies (hands)

2 Protection against 12.5 mm diameter foreign bodies (finger)

3 Protection against the ingress of foreign bodies greater than 2.5 mm thick.

4 Protection against the ingress of foreign bodies greater than 1 mm thick

5 Protection against the ingress of dust, whereby dust shall not enter the enclosure in sufficient quantities to cause equipment malfunction.

6 Complete protection from ingress of dust.

Page 84: Hazardous classified locations

Ingress Protection against Liquids

3rd Digit Degree of Protection

0 No protection

1 Protection against drops of condensed water

2 Protection against drops of liquid with the equipment tilted at any angle up to 15 degree from the vertical

3 Protection against rain falling at an angle of 60 degree or less from vertical

4 Protection against water splashed from any direction

5 Protection against jets of water

6 Protection against water from heavy seas

Page 85: Hazardous classified locations

Continue

7 Protection against immersion in water under stated conditions of pressure and time

8 Protection against immersion in water under specified pressure, for an indefinite period of time.

Page 86: Hazardous classified locations

Ingress Protection

• The degree of protection depend upon whether the equipment will be installed outdoors and exposed to the extremes of the weather, or indoors and exposed (or not) to dust or liquid ingress.

• If the location is outdoors, then the IP code will typically vary between IP54 and IP66

• For indoor equipment in a hazardous area not exposed to particles or water, the minimum IP code would be typically IP44

Page 87: Hazardous classified locations

Commonly Used IP Codes

0 1 2 3 4 5 6 7 8

0

1 IP11 IP12

2 IP21 IP22 IP23

3 IP31 IP32 IP33 IP34

4 IP41 IP42 IP43 IP44

5 IP54 IP55

6 IP65 IP66 IP67 IP68

Page 88: Hazardous classified locations

Marking

• Applicable national or international standard (BS5501 Part 5, IEC60079 Part 2

• Name or abbreviation of the testing lab (BASEEFA)

• Approved symbol for the certifying authority EEX hexagonal symbol

• Type of protection EEX “d” EEX “e”• Gas Group IIA IIB IIC• Temperature Class T6• Serial or certificate number

Page 89: Hazardous classified locations

Example

•EEx de IIC T6

Page 90: Hazardous classified locations

EEx ib IIB T4• E: European Standards• Ex ib: Intrinsically safe to category ib• II: Certification for use in apparatus group II

(in other industries) (I is for mines)

• B: Explosion classes

• T4: The ignition temperature of any gas or vapor with which this device will be used is not less than 135 degree C