83
Variable Refrigerant Flow - VRF The Comfort Conditioning Solution Features and Benefits

Variable Refrigerant Flow - VRF

Embed Size (px)

DESCRIPTION

The Comfort Conditioning Solution Features and Benefits

Citation preview

Page 1: Variable Refrigerant Flow - VRF

Variable Refrigerant Flow - VRFThe Comfort Conditioning Solution

Features and Benefits

Page 2: Variable Refrigerant Flow - VRF

1

• The compressor is the highest power-consuming component in the air-conditioning system

• Component optimization increases performance.

Air Conditioning System

• Expansion valves, fans, bypass solenoid valves also affect system performance

• Expansion valves, fans, bypass solenoid valves also affect system performance

Page 3: Variable Refrigerant Flow - VRF

2

What is a VRF System?

• A system that provides

▪ Climate control & zoning comfort

▪ Effective energy consumption by means of optimized inverter driven scroll compressor & temperature controls, producing highly responsive cooling and/or heating

VRF

Page 4: Variable Refrigerant Flow - VRF

3

What makes a VRF?

• Outdoor units with single or multiple variable speed DC compressors

• Single or multiple indoor units equipped with temperature sensing devices

• A factory suppliedzone temperature supervisory control, GUI and networking capabilities

VRF

Page 5: Variable Refrigerant Flow - VRF

4

VRF System & Inverter• The inverter reacts to indoor and outdoor

temperature fluctuation by varying the power consumption and adjusting the compressor speed to its optimum energy usage.

• The refrigerant is compressed to the required high pressure level

• Inverter provides superior energy efficiency performance

VRF

Page 6: Variable Refrigerant Flow - VRF

5

VRF Outdoor Fan Motor Control• Multi stage fan speed operation provides:

• Input power savings, lower steps have lower power consumption compared to higher steps.

• Optimizes condenser pressure control to achieve desired discharge pressure and ensure optimum mass flow through the system.

• Cycle stabilization provides optimum efficiency as compared to fix fan speed.

Page 7: Variable Refrigerant Flow - VRF

6

VRF Piping

• Improves refrigerant cycle efficiency by connecting multiple indoor units to a common liquid and suction line through the use of STA Separation Tube Assemblies and/or Headers and EEV Electronic Expansion Valves

VRF

Page 8: Variable Refrigerant Flow - VRF

7

Reduces piping cost and work• STA and or header diverts the common flow of

refrigerant to an individual evaporator. The flow of refrigerant is further metered by an EEV or Electronic Expansion Valve.

VRF

Page 9: Variable Refrigerant Flow - VRF

8

VRFVideo

Page 10: Variable Refrigerant Flow - VRF

9

VRF Benefits• Less copper versus multi-split • Eliminates most ductwork • Quicker installation• OEM software simplifies layout• Long piping lengths • Compact ductless system

VRF

Page 11: Variable Refrigerant Flow - VRF

10

Flexible piping design

Actual piping length

Height difference

377 – 540 Ft.*230 – 330 Ft.*

100 – 165 Ft.*

Suitable for apartment & office buildings too

100 to

165 ft.max.

Total piping length

VRF

* VARIES BY MANUFACTURER

Page 12: Variable Refrigerant Flow - VRF

11

Outdoor unit

Rectangular type L type Square type

Refrigerant piping

This extra-long piping system can also cope with buildings of various shapes.

Design freedom

Actual max. piping length 230 ft, Total max. piping length 377 ft*

*Varies by manufacturer

VRF

Indoor units

Page 13: Variable Refrigerant Flow - VRF

12

Design Software

Piping Layout Remote ControlSelection

JobCosting

VRF

Page 14: Variable Refrigerant Flow - VRF

13

Advanced Computer Controlled• Low energy consumption

• Inverter regulates compressor to its optimum energy usage

• Higher refrigerant performance with less power

VRF

Page 15: Variable Refrigerant Flow - VRF

14

Central Air Inefficiency

• VRF systems allows you to minimize inefficient ductwork.

– Save money

– Improve comfort

– Protect health

– Save Space

– Reduce Noise

Central

Page 16: Variable Refrigerant Flow - VRF

15

According to D.O.E.

• “Typical duct systems lose 25 to 40 percent of the heating or cooling energy put out by the central furnace, heat pump, or air conditioner.”

• “Homes with ducts in a protected area such as a basement may lose somewhat less than this, while some other types of systems (such asattic ducts in hot, humid climates) often lose more.”

Central

Page 17: Variable Refrigerant Flow - VRF

16

Central Air Inefficiency

• VRF systems minimize inefficient ductwork.

• VRF systems minimize inefficient ductwork.

Central

Page 18: Variable Refrigerant Flow - VRF

17

Multi-Split vs. VRF System• VRF systems allows you to minimize the refrigerant

path compared to a multi-zone mini-split.

Multi-Split VRF

Page 19: Variable Refrigerant Flow - VRF

18

The heart of a VRF system• Inverter driven DC scroll compressor(s) provides

highly responsive cooling and/or heating by quickly varying in speed from 1,000 up to 6,000 rpm.

Outdoor unit

Scroll Compressor

DC Inverter Control Signal line

Senses the temperature of each room and optimizes operation.

Temperature Sensor

Temperature sensor

Indoor unit Indoor unit

VRF

Page 20: Variable Refrigerant Flow - VRF

19

What Zoning does for Efficiency• Why cool spaces you do not occupy? • Individual zoning control of a VRF system

minimizes electrical usage.

VRF

0%10%20%30%40%50%60%70%80%90%

100%

Kitchen Living Bed-1 Bed-2 Dining

CentralVRF

Page 21: Variable Refrigerant Flow - VRF

20

Effective comfort at lower cost• Reacts to indoor and outdoor temperature

fluctuation by varying power consumption and adjusting compressor speed to its optimum energy usage to achieve desired set point quickly and maintain it more closely.

VRFR

oom

tem

pera

ture

(deg

.) Set temperature

40 min. Time

Roo

m te

mpe

ratu

re (d

eg.) Set temperature

20 min. Time

Conventional Model Inverter

Revolution of COMPRESSOR Revolution of COMPRESSOR

Page 22: Variable Refrigerant Flow - VRF

21

• Conventional: Room temperature drops rapidly when compressor turns OFF which result in an unstable room temperature

• Inverter: Range of room temperature change is small. Because after set temp is reached, compressor will not shut off to control temp but will maintain temp by decreasing or increasing revolution.

ON

Roo

m te

mpe

ratu

re (d

eg.)

Set temperature

TimeR

oom

tem

pera

ture

(deg

.)

Set temperature

Time

3 deg. 1 deg.

Conventional Model Inverter

ONRevolution of COMPRESSOR

OFF OFFON

Revolution of COMPRESSOR

Variable Refrigerant FlowVRF

Page 23: Variable Refrigerant Flow - VRF

22

Connectable Capacity• Central Air 100%

Connectable Capacity

VRF

• VRF 50% to 150% Connectable Capacity

48,000 BTU

Central

48,000 BTU48,000 BTU

48,000 BTU 24,000 BTU

72,000 BTU

Page 24: Variable Refrigerant Flow - VRF

23

Connectable Capacity• Ability to connect up to

150% of name plate rated indoor units*

* Varies by manufacturer• If all indoor units are

operated simultaneously system will not produce more than 110% of system capacity

• Example A:– 2-Story Building

Mixed Use. VRF stretches square footage covered by a single system when not all areas are occupied simultaneously

48,000 BTU Small Office used only during the day

24,000 BTUApartmentused only atnight

VRF

150%150%ConnectableConnectable

Page 25: Variable Refrigerant Flow - VRF

24

Lack of Connectable CapacityMulti-Split

18K 9K 9K

18K9K 9K

Load Calculation 48,000 BTU Field Application 72,000 BTU

5K 5K

7K 5K4K

12K

10K

• 6 tons applied where load only calls for 4 tons• Higher equipment cost by installing two systems in

order to provide most rooms with individual control.

Page 26: Variable Refrigerant Flow - VRF

25

Example of Connectable Capacity VRF

Field application 69,000 BTU connectable capacity

Load calculation 48,000 BTUwithout party quests

5K 5K

7K 5K4K

12K

10K

Actual 51,750 BTU withall indoor units calling

6.75K 6.75K 5.25K 5.25K

10.5K 6.75K 5.25K 5.25K

Actual 48,000 BTU availablefor party with bedroom units off

9K 9K

14K9K 7K

9K 9K 7K 7K

14K9K 7K 7K

Page 27: Variable Refrigerant Flow - VRF

26

Benefits of Connectable Capacity

• Reduced equipment cost by not installing additional equipment when a system can be shared instead.

• The ability to flexible size for different loads.• Stretch square footage covered by over-sizing and

reducing capacity at each indoor unit by design

Multi-Split VRF

6-Tons when only 4-Tons required Indoor unit for every room yet 4-Tons

18K 9K 9K

18K9K 9K

9K 9K 7K 7K

14K9K 7K 7K

Page 28: Variable Refrigerant Flow - VRF

27

VRF Benefits

Lower equipmentcosts, more efficient

Up to 150% connectible

100% connectible100% connectible

ConnectibleCapacity

Flexible zoning. Cool the spaces you occupy not the spaces you don’t

Up to 16 zones. Wireless, wired, & group remotesInverter provides more stable room temp.

Up to 4 zones Wireless or wired remote

1 or 2 zones without expensive zoning controls

Zoning

Least energy consumption with greatest comfort

Variable speedcompressor at optimum speed and maximizesrefrigerant flow

Variable speedcompressor but refrigerant flow efficiency loss

Compressor runs at its maximum speed

EnergyConsumption

Quicker cooling, greater comfort, more stable room temperature

Shorter piping run with better refrigerant distribution

Long piping but efficient air flow with evaporator in A/C space

Short piping run but great efficiency loss in ductwork

RefrigerantCycle / AirDistribution

Greatest comfortLess temperature fluctuation

Quickest, Highly responsive piping and compressor combination ½ the time of a conventional unit

Quicker, Moderately responsive piping and compressorcombination

SlowlyUnresponsivecompressor

Cools off hot room

BenefitVRF SystemMulti-SplitCentral AirConceptVRF

Page 29: Variable Refrigerant Flow - VRF

28

Flexible Remote ControlGroup RemoteController

Wireless Remote

Full FeaturedWired RemoteControl

SimpleWiredRemote

Page 30: Variable Refrigerant Flow - VRF

29

Power line + ground /signal line + ground = 6 wires

Power line/signal line+ ground = 4 wires

Wiring A

Wiring B

Power line + ground /signal line + ground = 6 wires

Group Remote Controller

Page 31: Variable Refrigerant Flow - VRF

30

Wiring systemWiring is simplified by using a daisy chain approach. In this case wiring provides power as well as communication signal in a three wire harness.

Page 32: Variable Refrigerant Flow - VRF

31

Simplified Wiring

• NEC compliant• Disconnect switch may be required• Outdoor units requires 208/230V 40A single

phase or 3-phase, depends on BTU’s• Indoor units powered from the outdoor unit using

3 wires and ground. Usually 14AWG.• Indoor required two lines for power, typically

208/230 V single phase 15A.• 3rd line used for networking and data

communication

Page 33: Variable Refrigerant Flow - VRF

32

3/8 Liquid3/4 Gas

1/4 Liquid5/8 Gas

1/4 Liquid3/8 Gas

1/4 Liquid5/8 Gas

1/4 Liquid1/2 Gas

3/8 Liquid, 3/4 Gas

3/8 Liquid3/4 Gas

Mix and Match Flexibility Large and Small Ceiling CassettesFrom 7-42K BTU

Condensing UnitCombinations from2Tons to 31.5 Tons

Wall Mount Coils from 7K to 36K BTU

Compact Duct Coilsfrom 7K to 18K BTU

Duct Type Coilsfrom 18K to 45K BTU

Page 34: Variable Refrigerant Flow - VRF

33

Piping system

Refrigerant flow is accumulated by using STA separation tube assemblies in reverse and then dividing refrigerant flow to as many as 48 indoor units

Page 35: Variable Refrigerant Flow - VRF

34

1. Short Term Stop Gap Method• All manufacturers test up to five evaporators under an agreed

upon test method to prove minimum EER efficiency (We estimate 1 year in development)

2. Interim Test Method• Develop test method for new ductless multi and VRF test

standard based on 210/240.(Tentatively draft ARI1230) (We estimate 2 years in development)

3. Long Term Method• Computer simulation through OEM software approved by ARI to

demonstrate efficiency regardless of combination (We estimate 3 years in development)

VRF

Page 36: Variable Refrigerant Flow - VRF

35

Equipment1 - Outdoor unit 1 - Indoor unit2 – Dampers2 – Thermostats

HALL

THERMOSTAT 2

THERMOSTAT 1

Two Temperature Controlled ZonesOne Air Flow Settings per ZoneTwo Temperature Controlled ZonesOne Air Flow Settings per Zone

Because room temperature sensor is housed in thermostat, the temp of only two rooms can be controlled.

Central

Page 37: Variable Refrigerant Flow - VRF

36

Each indoor units has an

individual remote control

and a room temperature

sensor

Each indoor units has an

individual remote control

and a room temperature

sensor

Individual Temperature Control Individual Air Flow SettingsIndividual Temperature Control Individual Air Flow Settings

Equipment:1- Outdoor unit8 - Indoor units 8 - Remote controls

Equipment:1- Outdoor unit8 - Indoor units 8 - Remote controls

HALLWAY

VRF

Page 38: Variable Refrigerant Flow - VRF

37

No Individual temperature/air flow settingsNo Individual temperature/air flow settingsCentral

Because set temperature is matched to living room, the ideal temperature cannot be selected for other rooms.

Because set temperature is matched to living room, the ideal temperature cannot be selected for other rooms.

Page 39: Variable Refrigerant Flow - VRF

38

Individual units with temperature sensors in each room provide comfortable separate room temperatures matched to the room’s use.

Individual units with temperature sensors in each room provide comfortable separate room temperatures matched to the room’s use.

HALL

Individual temperature/air flow settingIndividual temperature/air flow settingVRF

Page 40: Variable Refrigerant Flow - VRF

39

No Individual temperature/air flow settingNo Individual temperature/air flow setting

Heat-sensitive adults present in living room

Cold-sensitive infantPresent in the bedroom

When temperature and air flow are set to accommodate infant in bedroom, people in other rooms are too hot because setting are same in all rooms.When temperature and air flow are set to accommodate infant in bedroom, people in other rooms are too hot because setting are same in all rooms.

Individual air flow cannot be selected because there is one set air flow for all rooms.

Loud fan sound, rooms nearest indoor unit especially noisy, because large fan creates large air flow.

Central

Page 41: Variable Refrigerant Flow - VRF

40

Temperature and air flow can be individually set according to the room usage conditions.

Quiet operation as low as 23db

VRF

Page 42: Variable Refrigerant Flow - VRF

41

When direct sunlight or other disturbances change room load, system response for individual rooms is impossible because set temperature matched to living room.

Central

A.M. P.M.

Changing Sun Load

Page 43: Variable Refrigerant Flow - VRF

42

When the heat load changes by direct sunlight or other disturbance, settings can be changed for each room. All the rooms can be kept comfortable.

Changing Sun LoadVRF

A.M. P.M.

Page 44: Variable Refrigerant Flow - VRF

43

Cool air also flows to unoccupied rooms so it takes time to reach set temperature.

The farther the room is from the indoor unit, the poorer the cooling. Large amounts of cool air flow to the outlets nearest indoor unit.

Ex: When returning home in the summerCentralTime to Reach Set Point

VRF

Full capacity concentrated at operating indoor units located in the rooms in which people returning home congregate, other units turned off.

Each room cooled quickly and evenly.

Page 45: Variable Refrigerant Flow - VRF

44

After cooling stoppedMold is easily produced with the condensed water as the nutrientSince the area of the duct is large; a large amount of mold is produced.

When cooling begins

Mold spores sticking to dust are blown into room

Inaccessible ducts are difficult to clean or remove mold.

Duct MaintenanceCentral

Page 46: Variable Refrigerant Flow - VRF

45

When cooling beginsIndoor units installed in each room with small duct area. Mold production and dust are suppressed.

Accessible ducts make periodic cleaning easy preventing mold production

VRFDuct Maintenance

After cooling stoppedSmall amount of condensation form on each indoor unit (duct)Since the area of the duct is small; mold production is minimized.

Page 47: Variable Refrigerant Flow - VRF

46

Variable Refrigerant Flow (VRF) technology provides effective comfort with low energy consumption.

The operational savings come from the zoning because only occupied spaces are conditioned.

The work of the refrigerant is adjusted with an inverter & and the flow further gauged with the EEV

VRF - Precise Modulation

Page 48: Variable Refrigerant Flow - VRF

47

Thermal Expansion Valve TXV• Susceptible to valve hunting: overfeeding and

starving of refrigerant flow to the evaporator.• Hunting can be reduced by relocating the

sensing bulb to a better location

TXV Operation is Totally Independent of Compressor Operation

TXV Operation is Totally Independent of Compressor Operation

Page 49: Variable Refrigerant Flow - VRF

48

Lack of TXV Integration• What standard TXVs do not do:

– Control evaporator pressure– Cycle the compressor– Control running time– Control room temperature

• Three main working forces on the TXV are:– Remote bulb or sensing bulb pressure (opening

force)– Spring pressure (closing force)– Evaporator pressure (closing force)

Page 50: Variable Refrigerant Flow - VRF

49

Thermal Expansion Valve TXV

• As evaporator load increases, available refrigerant will boil off more rapidly. If it is completely evaporated prior to exiting the vapor will continue to absorb heat (superheat).

Con

dens

er

Evap

orat

or

Compressor

TXV

Page 51: Variable Refrigerant Flow - VRF

50

TXV & Superheat• Super heat is heat added to a

substance above its saturation temperature. The amount of super heat in a system is a concern.

• To little: liquid refrigerant entering compressor washes out the oil causing premature failure

• To much: valuable evaporator space is wasted and possibly causing compressor overheating problems.

STOP

Page 52: Variable Refrigerant Flow - VRF

51

EEV – Positioning System• EEV function is to maintain the pressure

differential and also to distribute the right amount of refrigerant to each indoor unit.

• Fine control on the refrigerant flow provides a superior level of room temperature control & ensures no wastage of energy

EEV is responding directly to room temperature and room load

Page 53: Variable Refrigerant Flow - VRF

52

EEV – Positioning System• EEV = Stepper Motor + Expansion Valve• Stepper motor is a brushless, synchronous

electric motor that can divide a full rotation into a large number of steps, 500 steps/rev

• Primary characteristic is its ability to rotate a prescribed small angle (step) in response to each control pulseapplied to its windings

Page 54: Variable Refrigerant Flow - VRF

53

EEV – Positioning System• Expansion valve is the component that controls

the rate at which liquid refrigerant can flow into an evaporator coil

• Control algorithm is continuously providing signals to the EEV to open or close by small amounts to vary the amount of refrigerant being delivered to the evaporator meetingtargeted superheat.

Page 55: Variable Refrigerant Flow - VRF

54

Thermistors• A type of resistor used to measure temperature

changes, relying on the change in its resistance with changing temperature.

Page 56: Variable Refrigerant Flow - VRF

55

• Measurement By a sensor (thermistor) connected to the refrigerant cycle or the “space"

• DecisionMade in Advanced Computer Controller

• ActionTaken through an output device ("actuator") such as the stepper motor in the EEV or Variable speed inverter compressor

Control Loop Components

Page 57: Variable Refrigerant Flow - VRF

56

Control Loop at Local Evaporator

• The controller takes a measured value from the space (by means of a thermistor) and compares it with a reference SETPOINT value.

• The difference (or "error" signal) is then used to adjust a system component in order to bring the spaces' measured value back to its desired SETPOINT.

ΣSetpoint + error

- Room temperature

Page 58: Variable Refrigerant Flow - VRF

57

Control loop at local evaporator• The digital controller can adjust space outputs

based on the HISTORY and RATE OF CHANGE of the error signal, which gives more accurate and stable control.

Page 59: Variable Refrigerant Flow - VRF

58

Controller uses 3 correcting calculations”• Proportional control to improve the rise time • Integral control to eliminate the steady-state error • Derivative control to improve the overshoot

based on the rate of change of the error

Controller’s algorithm

Page 60: Variable Refrigerant Flow - VRF

59

PID CalculationsP: Handles immediate error, the error is multiplied by a

Proportional constant P, and added to controlled variable.

I: Controller output is proportional to the amount of time the error is present. Integral action eliminates offset. It looks atthe history of the error signal

D: Controller output is proportional to the rate of change of themeasurement or error. Controller output is calculated by the rate of change of the measurement with time.

Page 61: Variable Refrigerant Flow - VRF

60

So what’s an Inverter?• An inverter controls the operating speed of

a DC motor by controlling the frequencyand voltage of the power supplied to the motor.

• An inverter provides the controlled power. In most cases, the inverter includes a rectifier so that DC power for the inverter can be provided from mains AC power.

Page 62: Variable Refrigerant Flow - VRF

61

Inverter Principle

• Bridge Rectifier

Provides the same polarity of output voltage for any polarity of the input voltage. In other words, converts alternating current (AC) input into direct current (DC) output.

Diodes are used to rectify AC by blocking the negative or positive portion of the waveform

Page 63: Variable Refrigerant Flow - VRF

62

Diode Bridge• Alternating current

(AC) whose magnitude and direction vary cyclically (60Hz)

• Basic Operation:current flows to the right along the upper colored path to the output, and returns to the supply via the lower one.

• If supplied current direction changes output current direction remains the same, DC

• Result: Negative part of the waveform has been eliminated

Load

Page 64: Variable Refrigerant Flow - VRF

63

Inverter Principle• Smoothing Condenser

used to smooth the ripple voltage present in a pulsating DC voltage output of a power supply rectifier.

• Most modern electronic devices require a steady DC supply

Page 65: Variable Refrigerant Flow - VRF

64

Inverter Block Diagram

Page 66: Variable Refrigerant Flow - VRF

65

Inverter Control Video VRF

Page 67: Variable Refrigerant Flow - VRF

66

Inverter Principle• IPM (Inverter Power Module)

It is composed of 6 transistors and drives the motor by high speed signal switching.

• The drive voltage signal is transferred to the drive circuit from a microcomputer, and varies the supply frequency to the motor (PWM system) to rotate the motor.

• Currently, insulated gate bipolar transistors IGBT’s are used in most inverter circuits

Page 68: Variable Refrigerant Flow - VRF

67

PWM Pulse Width Modulation• Signal involves the modulation of its duty cycle, to

control the amount of power sent to a load.

• Many digital circuits can generate PWM signals outputs to control an electrical motor.

• Usually use a counter that increments periodically and is reset at the end of every period of PWM.

• If counter value is more than the reference value, the PWM output changes state from high to low.

Page 69: Variable Refrigerant Flow - VRF

68

PWM

Page 70: Variable Refrigerant Flow - VRF

69

DC Inverter Control Function Basic Circuit of 3-Phase Inverter

Page 71: Variable Refrigerant Flow - VRF

70

Why do I want an Inverter?• Benefits of an Inverter Air Conditioner:

– Compared to the common On-Off controlled compressor; the inverter controlled compressor is able to run at the proper revolution to provide the best efficiency and reduce losses.

– When the maximum capacity is not required, the compressor revolution is decreased. This means the input power decreases too, which results in increased system efficiency.

Page 72: Variable Refrigerant Flow - VRF

71

Power balance control technology achieves high operational efficiencies by detecting low pressure and high pressure and precisely controls the optimum refrigerant condition via refrigerant flow rate.

Efficient DC inverter scroll compressor varies capacity according to the load

Low Electric Consumption

Page 73: Variable Refrigerant Flow - VRF

72

Power Oil Return• Oil return is important to

ensure that there is adequate lubrication for the compressor, especially during part load operation.

• Reducing oil logging in the system improves heat exchange efficiency in the condenser and evaporators saving energy.

Page 74: Variable Refrigerant Flow - VRF

73

Effective use of heat exchanger

The outdoor unit can achieve the most efficient operation by matching the heat exchanger of the outdoor unit to the systems requirements and the required load capacity of the conditioned space.

Example

31.5 Tons31.5 Tons of availableheat exchangers

9 HP9 HP of compressors by using 3 outdoor units together

Max. 10.5 HP Max. 10.5 HP Max. 10.5 HP

Page 75: Variable Refrigerant Flow - VRF

74

• Quiet operation (varies by manufacturer)Normal operation mode: 57dB(A)Night operation mode 54 dB(A)

• Inverter compressor makes system even quieter when it is operating at slower RPMs

Operation / Comfort

Page 76: Variable Refrigerant Flow - VRF

75

Central remote controller

Up to 400 indoor units or 64 groups can be controlled. Central remote controller can control the system by selecting All Groups, User Defined Groups or Individual Remote Controller Groups

Page 77: Variable Refrigerant Flow - VRF

76

Central control by tenant

Individual control

Central remote controller

Central remote controller

Central remote controller

Page 78: Variable Refrigerant Flow - VRF

77

PC Control

Operating recordSchedule controlOperation control

List table displayFloor layout displayRotating 3-D display

Calculating electricity charges

PC controllerUp to 400 indoor

units or 400 groups can be controlled

Page 79: Variable Refrigerant Flow - VRF

78

PC controller (Calculating electricity charges)

Each tenant bill can be made by calculating function of PC controller

Electricity company

Total Electricity bill

PC controller Tenant-A

Tenant-B

Tenant-C

Tenant-D

Tenant-EMeter

Power supply

Apportioned charges

Tenant bill

Tenant bill

Tenant bill

Tenant bill

Tenant bill

The accumulated refrigerant time and indoor unit capacity.

Page 80: Variable Refrigerant Flow - VRF

79

BMS compatibility

BMS: Building Management System

Page 81: Variable Refrigerant Flow - VRF

80

Extensive monitoring and analyzing functions for maintenance

Simple connection by transmission adaptor and RS-232C cable (RS-232C cable field supplied).

Service tool (Software)

Page 82: Variable Refrigerant Flow - VRF

81

VRF - Summary

• Climate control & zoning comfort• Effective energy consumption • Inverter driven scroll compressor &

digital temperature controls, • Produces a highly responsive cooling

and/or heating.• Cooling/Heating only on demand

Page 83: Variable Refrigerant Flow - VRF

82

Thank Youfor your time and

attention.

We hope you will consider VRF technology for

your next project