Upload
amit-chakraborty
View
146
Download
0
Embed Size (px)
Citation preview
SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS
CHAPTER 1
INTRODUCTION
The mitigation of arcing fault hazards in medium voltage switchgear is an urgent
concern that is being addressed in many ways by safe work practices, operator training, and
innovative products and installations. One method of mitigating arc flash hazards associated
with medium-voltage switchgear is the installation of active high-speed switch (HSS)
systems[1]. These systems are designed to detect and quench a burning internal arc in less than
one-third of one electrical cycle. The internal arc is extinguished by the HSS’s action of
redirecting the fault current path from arcing through open air back to the intended current path
of the switchgear bus. The new low-impedance current path provided by the HSS operation
collapses the voltage at the point of the fault to near zero so that the arc is no longer
sustainable. The system’s high speed of operation compared to arc quenching via circuit
breaker tripping translates directly to lower arc flash incident energy and minimal equipment
damage[1]. This paper explores application considerations of HSS systems relative to other
available means of controlling and reducing the hazards of internal arcing faults in medium-
voltage switchgear.
HSS designs have not been in existence for very many years. As time passes, more
success stories that confirm the robustness that manufacturers claim for the switch, light
sensors, and electronics are expected.
HSS systems may be a viable solution to arc flash hazard mitigation in particular
situations such as the following:
1) where equipment is expected to be opened while energized;
2) where other means of AFIE reduction do not reach the target PPE category;
3) where selective coordination is most critical;
4) where extended switchgear downtime cannot be tolerated;
5) where the switchgear location cannot accommodate venting mechanisms for arc by-
products.
Dept.EEE 1 GCE Kannur
SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS
CHAPTER 2
ARC FLASH AND HAZARDS
2.1 ARC HISTORY
In 1802, an English scientist Humphrey Davis demonstrated that electric current can
flow between two copper rods separated in air by short distance. Electric current will be in the
form of a band of ionised air that looks like an upward bow as in the figure. In fact electrical
science started with the study of electric arc. Soon, a number of inventions came forth such as
arc lamps, arc furnaces, spark plugs, arc welders and etc.
Fig 2.1 Electric arc
The electric arc is again a subject of great interest and study because of the hazards it
creates in electrical distribution systems due to its intense heat. It can destroy equipment and
cause severe or fatal injuries to unprotected personnel who are unfortunate to be in close
proximity to it.
An electric arc is an ongoing plasma discharge resulting from current flowing
through air, which is a normally nonconductive media. The effects of an electric arc depend on
the individual circumstances, but all are dangerous: extreme temperatures that can reach up to
30,000 °F, explosive pressure forces caused by the rapid expansion of gases and elements such
as vaporized copper, intense light, high noise levels and toxic fumes, as shown in Figure
below.
Dept.EEE 2 GCE Kannur
SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS
Fig 2.2 Electrical arc.
2.2 DEFINITION OF ARC FLASH AND RELATED TERMS
Arc-flash hazard: a dangerous condition associated with the release of energy caused by an
electric arc.
Electric hazard: a dangerous condition in which inadvertent or unintentional contact or
equipment failure can result in shock, arc-flash burn, thermal burn, or blast.
Flash protection boundary: an approach limit at a distance from exposed live parts within
which a person could receive a second-degree burn if an electrical arc flash were to occur. The
incident heat energy from an arcing fault falling on the surface of the skin is 1.2 calories/cm2.
Incident energy: the amount of energy impressed on a surface, a certain distance from the
source, generated during an electrical arc event. One of the units used to measure incident
energy is calories per centimeter squared (cal/cm2).
Limited approach boundary: an approach limit at a distance from an exposed live part within
which a shock hazard exists.
Dept.EEE 3 GCE Kannur
SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS
Fig. 2.3 Flash Protection Boundary
Qualified person: one who has skills and knowledge related to the construction and operation
of the electrical equipment and installations and has received safety training on the hazards
involved.
Restricted approach boundary: an approach limit at a distance from an exposed live part
within which there is an increased risk of shock, due to electrical arc over combined with
inadvertent movement, for personnel working in close proximity to the live part.
Prohibited approach boundary: an approach limit at a distance from an exposed live part
within which work is considered the same as making contact with the live part.
Working distance: the dimension between the possible arc point and the head and body of the
worker positioned in place to perform the assigned task. Thus, the Flash Protection Boundary
becomes an important approach distance from live equipment within which qualified personnel
must wear protective clothing and equipment and within which unqualified personnel are
prohibited. An exposure to 1.2 calories/cm2 would normally result in a curable second-degree
burn. Within this boundary, workers are required to wear protective clothing like fire resistant
(FR) shirts and pants and other equipment to cover various parts of the body. The flash
protection boundary distance varies with the type of equipment used. It is primarily a function
of the available voltage and fault current of the system at that point, and the tripping
characteristics of the upstream protective device.
Dept.EEE 4 GCE Kannur
SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS
CATEGORIES OF PPE (PERSONAL PROTECTIVE EQUIPMENT) AS DESCRIBED IN
NFPA 70E
Category Cal/cm2 Clothing
0 1.2 Untreated Cotton
1 5 Flame retardant (FR) shirt and FR pants
2 8 Cotton underwear FR shirt and FR pants
3 25 Cotton underwear FR shirt, FR pants and FR coveralls
4 40 Cotton underwear FR shirt, FR pants and double layer switching coat
and pants
Table 2.1 Categories of PPE
2.3 ARC FLASH IN SWITCHGEAR
Internal free burning arcs in LV switchgear such as a motor control centre (MCC) arise
when a short circuit occurs and causes a current to flow through air inside the assembly. This
current can flow between phases, or between phases and the neutral or ground, or through a
combination of all these paths. The amount of energy released depends on the strength of the
current and the length of time that it flows. The results can be catastrophic—the internal
explosion, consisting of expansion of copper to 67,000 times its original volume, temperatures
at 19,000 °C, along with pressure and sound waves can threaten human life. Such arcs can
result from unfavourable environmental conditions leading to conductive deposits on isolating
support elements. Other causes can include vermin ingress or the growth of silver or tin
whiskers on exposed conductors. However, a far more likely cause is human error; from tools
or excess material left inside the system after inspection, maintenance, or testing. In fact, an
estimated 70% of arcs arise from human error. If an arc does occur, the most obvious threat is
to any maintenance or operating personnel in close proximity to the arc event site. In addition
to the human impact, there are business impacts. In an arc event, all affected switchgear is
likely to be permanently damaged. This takes any connected production equipment out of
service even if it is fully operational. Beyond loss of production, impacts can be felt in the
form of lawsuits, increased insurance costs and lowered common stock values.
Dept.EEE 5 GCE Kannur
SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS
Fig 2. 4 Arc flash switchgear explosion
2.4 ARC FLASH HAZARDS
An electric arc, or arcing fault, is a flashover of electric current through the air from
one live conductor to another or to ground. An Arc Flash hazard is the danger that comes from
the heat energy generated in an Arc. Electric Arcs produce intense heat, sound blast and
pressure waves, and can ignite clothing, causing severe burns that are often fatal.
The demand for uninterrupted power has created the need for electrical workers to
operate and perform maintenance work on exposed live parts of electrical equipment. This
creates a hazard from potential electric shock. The electric shock hazard has been addressed in
electrical safety programs since electricity use began. However, only recently has the hazard
brought about by Arc Flash been prominently addressed.
The results of arc flash can be catastrophic—the internal explosion, consisting of
expansion of copper to 67,000 times its original volume, temperatures at 19,000 °C, along with
pressure and sound waves can threaten human life.
Dept.EEE 6 GCE Kannur
SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS
The physical effects of an arc flash are:
• Pressure wave in the environment where the arc is generated;
• Heating of the materials coming into touch with the arc flash;
• Potentially harmful light and sound.
Personnel hazards due to the release of energy generated by an arc event may include:
• Burns;
• Injuries due to ejection of materials;
• Damage to hearing and to eye-sight
; • Inhalation of toxic gases
BURNS
The high temperature levels of the gases produced by the electrical arc and the
expulsion of incandescent metal particles may result in severe burns. Flames can cause all
types of burns, up to carbonization: the red-hot solid metal fragments can cause third degree
burns, superheated steam causes burns similar to hot liquids and the radiant heat generally
causes less severe burns.
INJURIES DUE TO EJECTED MATERIALS
The ejection of metal particles or other loose items caused by the electric arc can result
in severe injuries to the most sensitive parts of the human body, like the eyes. The materials
expelled due to the explosion produced by the arc may penetrate the cornea. The extent of the
lesions depends on the characteristics and kinetic energy of these objects. Also, the eye area
can sustain injuries to the mucosa, such as the cornea or retina, because of the gases released
by the arc and the emission of ultraviolet and infrared rays.
HEARING
As already mentioned, the electric arc is a true explosion, whose sound may cause
permanent hearing loss.
INHALATION OF TOXIC GASES
Dept.EEE 7 GCE Kannur
SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS
The fumes produced by burnt insulating materials and molten or vaporized metals can
be toxic. These fumes are caused by incomplete burning and are formed by carbon particles
and by other solid substances suspended in the air.
2.5 MITIGATION
The mitigation of arcing fault hazards in medium voltage switch gear is an urgent
concern. It is being addressed in many ways by safe work practices, operator training and
innovative products and installations. Mitigation is defined as to make milder, less severe or
less violent. Arc flash mitigation involves taking steps to minimize the level of hazard or the
risk associated with an arc flash event.
The two ways of avoiding arc flash effects are
i) Reduce arc flash energy to a level where permitted tasks can be performed.
ii) Locate the workers so that he is not subject to harm.
2.6 CONVENTIONAL EQUIPMENT TO LIMIT THE EFFECT OF AN ARC
FLASH
Conventional electrical protection equipment does not sufficiently limit the effect
of an arc-flash:-
The duration of an Arc-Flash is mainly determined by the time it takes for overcurrent
or earth-fault protective devices to detect the fault, send a trip signal to the circuit breaker and
for the circuit breaker to subsequently disconnect the energy source. Fast acting fuses may
disconnect the circuit from the energy source in 8 ms or less when subjected to the high short-
circuit currents usually appearing in three-phase symmetrical bolted cases, while other devices
may take much longer to operate and remove the source of energy. But unbalanced, single-
phase and high-impedance fault currents are lower than three-phase bolted-fault currents, so
protection devices may not necessarily detect and limit arc-fault current and will require more
time to clear the fault.
Dept.EEE 8 GCE Kannur
SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS
CHAPTER 3
HIGH SPEED SWITCHING (HSS) SYSTEM
3.1 FEATURES
• Method of mitigating arc flash hazards in which reduction of arc flash energy is
employed.
• It is conceptually very simple and effective.
• Used to detect and quench internal arc in less than one-third of one electrical cycle
Fig. 3.1 HSS typical schematic
3.2 HIGH SPEED SWITCHING
The high-speed switch (HSS) system is one method of mitigating arc flash hazards
associated with medium-voltage switchgear. It is conceptually very simple and effective but
often viewed skeptically as a radical approach that places too much stress on the power system
when it operates. In fact, it does transfer an internal arcing fault to the switchgear bus which
does create a bolted fault on the system. When the HSS control system detects illumination
with characteristics similar to that of an internal arc, confirmed by a corresponding rate of
change of current, an arc flash event is declared, and the normally open HSS very rapidly
closes to create a three-phase bolted fault, which thereby extinguishes the higher impedance
internal arc, such as that shown in Fig 3.1.
Dept.EEE 9 GCE Kannur
SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS
Arc fault:-
Short circuit current resulting from conductors at different voltages making less than solid
contact. Results in a relatively high resistance connection compared to a bolted fault.
Bolted fault:-
Short circuit current resulting from conductors at different voltages becoming solidly
connected together.
Some HSS designs may operate based on other characteristics from internal arcing other than
light and current, such as temperature, pressure, sound, harmonics, etc.
The bolted fault remains on the system until cleared by the source overcurrent device.
The stress of a bolted fault is certainly a valid concern, but the HSS should not be dismissed
without carefully considering the benefits provided. The intrinsic benefits are as follows:
1) speed of operation:
a) effective incident energy (arc flash) reduction;
b) reduction of equipment damage and corresponding downtime due to an internal arcing
event;
c) Reduction of motor contribution to an internal arcing event.
2) effective protection even with exposed live parts;
3) independence from overcurrent coordination and arcing fault current variations;
4) No impact on switchgear room (no additional ventilation or ducting requirements).
These benefits translate to improved worker safety, procedural simplicity, power system
reliability, improved system availability, and, in some cases, reduced installed cost.
Dept.EEE 10 GCE Kannur
SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS
CHAPTER 4
PERFORMANCE
This chapter mainly includes the main benefits of the high speed switching system
4.1 SPEED OF OPERATION
Commercially available HSS systems detect an arc and close in approximately 4–6ms
(0.2–0.3 cycle at 50 Hz). In contrast, modern vacuum circuit breakers can typically detect and
clear an arcing fault in not less than 50ms considering overcurrent or flash detection relay trip
contact closure time plus circuit breaker clearing time. In many cases, the operating time is
greater than 50ms, depending on the use of lockout relays, relay and circuit breaker vintage and
vendor type, and other variables. Lockout relays add one cycle. In retrofit scenarios, older
circuit breakers may be 5 or 8 cycle rated.
HSS is therefore about ten times faster than the fastest circuit breaker-based
arc detection and quenching schemes, which leads to the following benefits.
4.1.1 AFIE REDUCTION:
Arc flash incident energy (AFIE) is directly proportional to the time required to
extinguish the arc. Accumulated AFIE versus time is shown in Fig.4.1 for an arbitrary
example system: 13.8-kV system with 50-kA available fault current, solidly grounded using
standard 36-in (914 mm) working distance and 153-mm bus gap per IEEE 1584.
Dept.EEE 11 GCE Kannur
SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS
Fig. 4.1 AFIE accumulation versus time example.
For the Fig 4.1 example system, AFIE calculations for switchgear with HSS result in
less than 1.2 cal/cm2 (the industry referenced second degree burn threshold). At this calculated
AFIE, non-melting or untreated natural fibre clothing may be worn along with hearing
protection, eye protection, and leather gloves as needed. For the best case circuit breaker
tripping times shown in Fig 4.1, heavier personal protective equipment (PPE) with flame
resistant clothing is required for higher energy exposures. PPE for higher energy exposures is
progressively more bulky, hot, and difficult to work in due to loss of visibility and dexterity.
Workers are relieved to get out of PPE in hot locations (although there are cooling systems
available to lessen the discomfort).
Personal protective equipment (PPE):- Safety devices worn by personnel to protect against
hazards. PPE includes helmets, hearing protection, face shields, gloves, safety boots,
respirators etc.
4.1.2 EQUIPMENT DAMAGE REDUCTION:
Arc blast effects can destroy equipment with the same phenomena that kill and injure
people. The IEEE Std. C37.20.7 guide for testing arc-resistant metal-enclosed switchgear does
not include internal equipment destruction as a failure criterion. Rework or replacement is
expected.
HSS manufacturer tests and actual field events, however, illustrate that the fast arc
quenching limits the damage to the point of the arc occurrence, with minimal additional
damage. As a result, troubleshooting, repair, testing, and return to service are simplified and
relatively quick. “As a general rule, removing the fault quickly will minimize the damage;
however, the overpressure event typically occurs in a time frame of less than 1 electrical
cycle”.
For medium-voltage switchgear, HSS systems are the only available devices to date that
can compete with the speed of overpressure and equipment destruction, as illustrated in Fig
4.1.
Dept.EEE 12 GCE Kannur
SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS
4.1.3 REDUCTION OF MOTOR CONTRIBUTION TO AFIE:
Large induction and synchronous motors can contribute significantly to AFIE in some
industrial settings. The medium-voltage feeder breakers supplying motor loads will not trip for
motor contribution levels in many cases, so the full motor contribution can persist for several
cycles regardless of the main circuit breaker tripping time. In the case of bus differential relay
application, the motor contribution will persist until it decays to zero or the associated bus
lockout relay and feeder breaker trips, whichever comes first.
HSS addresses this issue in large measure due to the fast arc quenching time. Again, the
margin of improvement is approximately a factor of 10, based on the speed of quenching the
arc via HSS versus circuit breaker.
4.2 EFFECTIVE PROTECTION WITH EXPOSED LIVE PARTS
The IEEE Guide C37.20.7 guide for testing arc-resistant metal-enclosed
switchgear states that “The use of equipment qualified to this guide is intended to provide an
additional degree of protection to the personnel performing normal operating duties in close
proximity to the equipment while the equipment is operating under normal conditions.” The
standard excludes alteration of the equipment from normal operating condition and from
activities above or below the equipment, such as catwalks, installations on open grating, cable
vaults, and so forth. Any opening in the equipment invalidates the arc resistant category and
can expose personnel to the full effects of the arcing event. Arc-resistant switchgear is arc
resistant only when all covers are secured in place.
HSS systems, however, operate effectively regardless of exposed live parts or
the personnel performing work above or below the equipment. Working around exposed live
parts should normally be prohibited, but situations can and do arise where the risks associated
with equipment shutdown exceed the risks of working with the equipment opened.
4.3 INDEPENDENCE FROM OVERCURRENT COORDINATION
HSS systems rely on light sensors, current transformers, and possibly sensors for
other parameters to detect an arc and initiate HSS closing. The bolted fault current resulting
from HSS actuation has to be cleared by the source overcurrent device within the withstand
ratings of the switchgear and HSS system, but the protection of the worker is effective even if
Dept.EEE 13 GCE Kannur
SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS
the relays in the system are improperly coordinated or if the arcing fault magnitude is not as
anticipated.
The selective coordination of overcurrent devices is often in direct conflict with
the need to trip the source circuit breaker(s) as fast as possible for arc flash hazard mitigation
purposes. For example, if the instantaneous trip level is above the lowest arcing fault current
magnitude, the relay may not trip instantaneously, resulting in high AFIE. On the other hand, if
the instantaneous trip level is set low enough to trip quickly for all possible values of arcing
current, selective coordination with downstream devices is frequently compromised.
Therefore, all values of arcing fault current magnitude must be considered from highest to
lowest. This requires careful judgment and frequent trade-offs between selective coordination
and AFIE mitigation. There are many reasons that arcing fault current levels can change,
including utility system upgrades or system switching, plant switching between main, tie, and
in-plant generator circuit breakers, varying quantities of running motors, and so forth.
Additionally, many times, the utility system changes without the customer being made aware.
Various means of addressing these issues have been implemented with success.
Bus differential relays are fast (approximately 80ms from overcurrent detection to
arcing fault elimination) yet inherently selective but cannot detect arcing faults outside the
protected zone current transformers, which, in most metal clad switchgear, do not encompass
the cable compartments. For example, the bus differential relays installed at the health care
facility cited in this paper did not detect the arcing fault condition because the bus differential
current transformers are inside the breaker cell while the fault occurred in the cable
compartment. Another example is that, while a worker may have an additional degree of
protection when racking a breaker from the front of the equipment, he may not be protected if
the cable compartment is opened.
Zone selective interlocking schemes (approximately 80 ms from overcurrent
detection to arcing fault elimination), also called fast trip schemes, achieve selective
coordination via restraint signals from the feeder circuit breakers going back to the main. If the
main detects a fault but receives a restraint signal from the feeder, the main breaker relay times
out normally per its time–current curve, allowing the feeder to selectively clear the
downstream fault. If the main detects a fault without a restraint signal, the main trips
instantaneously since the fault logically must be on the switchgear bus. The main circuit
breaker relay must, however, detect the fault at arcing current level, and it must still coordinate
with the feeder. Feeder breakers cannot be permitted to trip on motor contribution; otherwise,
Dept.EEE 14 GCE Kannur
SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS
they will restrain the source breaker(s) and defeat the scheme entirely. Multisource line-ups
such as main–tie–main add still more complexity.
Alternative maintenance setting switches (approximately 80 ms from overcurrent
detection to arcing fault elimination) are used to lower relay pickup levels and sacrifice
coordination only when personnel are present or maintenance is being performed. Again, the
main circuit breaker relay must detect the fault at arcing current level, and careful procedural
rules must be implemented to ensure that personnel do not forget to turn on the maintenance
trip settings when beginning the work or forget to turn it off when done. Occupancy sensors
have been used to turn on inputs to electronic relays that automatically lower the relay
instantaneous settings and then restore them when personnel leave. While the reduced settings
are in effect, there is a possibility of nuisance nonselective tripping.
Arc flash detection relays (52–57 ms from arc detection to arcing fault elimination)
that combine light sensors, current sensing, and high speed relay outputs are immune to
overcurrent coordination and arcing fault current magnitude but rely on the relatively slow
circuit breaker tripping to quench the arc.
HSS systems (4–6 ms from arc detection to arcing fault elimination) are likewise
immune to the downstream coordination and arcing fault current magnitude considerations but
have the advantage of speed. The short-circuit withstand rating of the HSS itself is all that
needs to be considered in setting the source circuit breaker relays with regard to arc flash
protection. For circuit breaker-based arc quenching (other than arc flash detection relays), relay
settings are critical and must consider all possible arcing fault current magnitudes.
Power system short circuit, coordination, and arc flash studies must be kept up-to-
date and relay changes implemented as necessary. This statement is always true, but for HSS
installations, it is less critical because the arc flash hazard protection is unaffected. A related
benefit is that selective coordination for critical systems is made much simpler.
4.4 NO IMPACT ON SWITCHGEAR ROOM
Arc-resistant switchgear that relies on circuit breaker tripping must have a safe path to
vent the arc by-products. Ceiling and wall clearances, overhead equipment, doors, windows,
building capability to absorb pressure wave, fireproofing, weather, and vermin ingress are
among the considerations. Additionally, the arc-resistant switchgear may be larger and heavier
than the standard switchgear. These factors can grow the size, cost, and complexity of the
Dept.EEE 15 GCE Kannur
SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS
switchgear room. Some HSS systems have been tested and comply with IEEE C37.20.7, and
they negate the need to purchase passive arc containment (heavily reinforced cubicles).
HSS system installations may require an additional section to accommodate the HSS;
otherwise, the installation is identical to that of the standard non-arc-resistant switchgear, as no
arc by products need to be accommodated.
4.5 DRAWBACKS OF HSS SYSTEM
• It places too much stress on the power system when it operates.
• Bolted fault remains on the system until cleared by the source overcurrent device.
Dept.EEE 16 GCE Kannur
SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS
CHAPTER 5
CONCLUSION
The HSS system may be likened to an automobile airbag. Hopefully, it will never
have reason to operate for the entire life of the equipment, but if needed at any time, it must
operate instantly. Nuisance operation is unforgivable. The device cannot be tested in normal
operation. It has to be trusted.
HSS systems should be seriously considered for installation in medium-voltage
switchgear. Other means of enhanced equipment protection from arc flash hazards are
available. Switchgear size, importance, cost, complexity, growth needs, and architectural
considerations should be considered along with plant safe work practices, procedures, and
other available arc flash mitigating features.
A risk versus benefit analysis is recommended when installing HSS on the
secondary of older or less robust power transformers that, due to operating history or test
results, are considered near end of life.
Large medium-voltage motors should be evaluated for use on HSS-equipped systems
using actual machine and supply conductor impedances as well as manufacturer input. In many
cases, the additional stresses placed on the motor due to HSS closing will be minimal.
HSS systems can provide substantial rewards without exposing the power system to
undue risks beyond the unavoidable.
Dept.EEE 17 GCE Kannur
SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS
REFERENCES
[1]Michael D. Divinnie, James K. Stacy, Antony C. Parsons. “Arc Flash Mitigation Using
Active High-Speed Switching,” IEEE Transactions on Industry Applications., Vol. 51, no.1,
Jan./Feb. 2015.
[2] Palak Parikh, Ray Luna, Michael Pilon, Roy Mao, “A Novel Approach for Arc-Flash
Detection and Mitigation: At the Speed of Light and Sound,”978-1-4799-0119-
7/13/$31.00©2013 IEEE.
[3] Johnny Simms, Gerald Johnson, “Protective Relaying Methods for Reducing Arc Flash
Energy,” 978-1-4244-6075-5/10/$26.00 ©2010 IEEE.
[4] Kanu R. Shah, Alan L. Cinsavich, Priyan De Silva, “Impact of Arc Flash Hazards on
Medium-Voltage Switchgear,” IEEE transactions on industry applications, vol. 44, no. 6,
November/December 2008.
[5] R. L. Doughty, T. E. Neal, T. Macalady, V. Saporita, and K. Borgwald, “The use of low
voltage current-limiting fuses to reduce arc-flash energy,” IEEE Transactions on Industry
Applications., vol. 36, no. 6, pp. 1741–1749, Nov./Dec. 2000.
Dept.EEE 18 GCE Kannur
SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS
Dept.EEE 19 GCE Kannur