27
SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS CHAPTER 1 INTRODUCTION The mitigation of arcing fault hazards in medium voltage switchgear is an urgent concern that is being addressed in many ways by safe work practices, operator training, and innovative products and installations. One method of mitigating arc flash hazards associated with medium-voltage switchgear is the installation of active high-speed switch (HSS) systems[1]. These systems are designed to detect and quench a burning internal arc in less than one-third of one electrical cycle. The internal arc is extinguished by the HSS’s action of redirecting the fault current path from arcing through open air back to the intended current path of the switchgear bus. The new low-impedance current path provided by the HSS operation collapses the voltage at the point of the fault to near zero so that the arc is no longer sustainable. The system’s high speed of operation compared to arc quenching via circuit breaker tripping translates directly to lower arc flash incident energy and minimal equipment damage[1]. This paper explores application considerations of HSS systems relative to other available means of controlling and reducing the hazards of internal arcing faults in medium-voltage switchgear. HSS designs have not been in existence for very many years. As time passes, more success stories that confirm the robustness that manufacturers claim for the switch, light sensors, and electronics are expected. Dept.EEE 1 GCE Kannur

ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING

Embed Size (px)

Citation preview

Page 1: ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING

SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS

CHAPTER 1

INTRODUCTION

The mitigation of arcing fault hazards in medium voltage switchgear is an urgent

concern that is being addressed in many ways by safe work practices, operator training, and

innovative products and installations. One method of mitigating arc flash hazards associated

with medium-voltage switchgear is the installation of active high-speed switch (HSS)

systems[1]. These systems are designed to detect and quench a burning internal arc in less than

one-third of one electrical cycle. The internal arc is extinguished by the HSS’s action of

redirecting the fault current path from arcing through open air back to the intended current path

of the switchgear bus. The new low-impedance current path provided by the HSS operation

collapses the voltage at the point of the fault to near zero so that the arc is no longer

sustainable. The system’s high speed of operation compared to arc quenching via circuit

breaker tripping translates directly to lower arc flash incident energy and minimal equipment

damage[1]. This paper explores application considerations of HSS systems relative to other

available means of controlling and reducing the hazards of internal arcing faults in medium-

voltage switchgear.

HSS designs have not been in existence for very many years. As time passes, more

success stories that confirm the robustness that manufacturers claim for the switch, light

sensors, and electronics are expected.

HSS systems may be a viable solution to arc flash hazard mitigation in particular

situations such as the following:

1) where equipment is expected to be opened while energized;

2) where other means of AFIE reduction do not reach the target PPE category;

3) where selective coordination is most critical;

4) where extended switchgear downtime cannot be tolerated;

5) where the switchgear location cannot accommodate venting mechanisms for arc by-

products.

Dept.EEE 1 GCE Kannur

Page 2: ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING

SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS

CHAPTER 2

ARC FLASH AND HAZARDS

2.1 ARC HISTORY

In 1802, an English scientist Humphrey Davis demonstrated that electric current can

flow between two copper rods separated in air by short distance. Electric current will be in the

form of a band of ionised air that looks like an upward bow as in the figure. In fact electrical

science started with the study of electric arc. Soon, a number of inventions came forth such as

arc lamps, arc furnaces, spark plugs, arc welders and etc.

Fig 2.1 Electric arc

The electric arc is again a subject of great interest and study because of the hazards it

creates in electrical distribution systems due to its intense heat. It can destroy equipment and

cause severe or fatal injuries to unprotected personnel who are unfortunate to be in close

proximity to it.

An electric arc is an ongoing plasma discharge resulting from current flowing

through air, which is a normally nonconductive media. The effects of an electric arc depend on

the individual circumstances, but all are dangerous: extreme temperatures that can reach up to

30,000 °F, explosive pressure forces caused by the rapid expansion of gases and elements such

as vaporized copper, intense light, high noise levels and toxic fumes, as shown in Figure

below.

Dept.EEE 2 GCE Kannur

Page 3: ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING

SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS

Fig 2.2 Electrical arc.

2.2 DEFINITION OF ARC FLASH AND RELATED TERMS

Arc-flash hazard: a dangerous condition associated with the release of energy caused by an

electric arc.

Electric hazard: a dangerous condition in which inadvertent or unintentional contact or

equipment failure can result in shock, arc-flash burn, thermal burn, or blast.

Flash protection boundary: an approach limit at a distance from exposed live parts within

which a person could receive a second-degree burn if an electrical arc flash were to occur. The

incident heat energy from an arcing fault falling on the surface of the skin is 1.2 calories/cm2.

Incident energy: the amount of energy impressed on a surface, a certain distance from the

source, generated during an electrical arc event. One of the units used to measure incident

energy is calories per centimeter squared (cal/cm2).

Limited approach boundary: an approach limit at a distance from an exposed live part within

which a shock hazard exists.

Dept.EEE 3 GCE Kannur

Page 4: ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING

SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS

Fig. 2.3 Flash Protection Boundary

Qualified person: one who has skills and knowledge related to the construction and operation

of the electrical equipment and installations and has received safety training on the hazards

involved.

Restricted approach boundary: an approach limit at a distance from an exposed live part

within which there is an increased risk of shock, due to electrical arc over combined with

inadvertent movement, for personnel working in close proximity to the live part.

Prohibited approach boundary: an approach limit at a distance from an exposed live part

within which work is considered the same as making contact with the live part.

Working distance: the dimension between the possible arc point and the head and body of the

worker positioned in place to perform the assigned task. Thus, the Flash Protection Boundary

becomes an important approach distance from live equipment within which qualified personnel

must wear protective clothing and equipment and within which unqualified personnel are

prohibited. An exposure to 1.2 calories/cm2 would normally result in a curable second-degree

burn. Within this boundary, workers are required to wear protective clothing like fire resistant

(FR) shirts and pants and other equipment to cover various parts of the body. The flash

protection boundary distance varies with the type of equipment used. It is primarily a function

of the available voltage and fault current of the system at that point, and the tripping

characteristics of the upstream protective device.

Dept.EEE 4 GCE Kannur

Page 5: ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING

SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS

CATEGORIES OF PPE (PERSONAL PROTECTIVE EQUIPMENT) AS DESCRIBED IN

NFPA 70E

Category Cal/cm2 Clothing

0 1.2 Untreated Cotton

1 5 Flame retardant (FR) shirt and FR pants

2 8 Cotton underwear FR shirt and FR pants

3 25 Cotton underwear FR shirt, FR pants and FR coveralls

4 40 Cotton underwear FR shirt, FR pants and double layer switching coat

and pants

Table 2.1 Categories of PPE

2.3 ARC FLASH IN SWITCHGEAR

Internal free burning arcs in LV switchgear such as a motor control centre (MCC) arise

when a short circuit occurs and causes a current to flow through air inside the assembly. This

current can flow between phases, or between phases and the neutral or ground, or through a

combination of all these paths. The amount of energy released depends on the strength of the

current and the length of time that it flows. The results can be catastrophic—the internal

explosion, consisting of expansion of copper to 67,000 times its original volume, temperatures

at 19,000 °C, along with pressure and sound waves can threaten human life. Such arcs can

result from unfavourable environmental conditions leading to conductive deposits on isolating

support elements. Other causes can include vermin ingress or the growth of silver or tin

whiskers on exposed conductors. However, a far more likely cause is human error; from tools

or excess material left inside the system after inspection, maintenance, or testing. In fact, an

estimated 70% of arcs arise from human error. If an arc does occur, the most obvious threat is

to any maintenance or operating personnel in close proximity to the arc event site. In addition

to the human impact, there are business impacts. In an arc event, all affected switchgear is

likely to be permanently damaged. This takes any connected production equipment out of

service even if it is fully operational. Beyond loss of production, impacts can be felt in the

form of lawsuits, increased insurance costs and lowered common stock values.

Dept.EEE 5 GCE Kannur

Page 6: ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING

SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS

Fig 2. 4 Arc flash switchgear explosion

2.4 ARC FLASH HAZARDS

An electric arc, or arcing fault, is a flashover of electric current through the air from

one live conductor to another or to ground. An Arc Flash hazard is the danger that comes from

the heat energy generated in an Arc. Electric Arcs produce intense heat, sound blast and

pressure waves, and can ignite clothing, causing severe burns that are often fatal.

The demand for uninterrupted power has created the need for electrical workers to

operate and perform maintenance work on exposed live parts of electrical equipment. This

creates a hazard from potential electric shock. The electric shock hazard has been addressed in

electrical safety programs since electricity use began. However, only recently has the hazard

brought about by Arc Flash been prominently addressed.

The results of arc flash can be catastrophic—the internal explosion, consisting of

expansion of copper to 67,000 times its original volume, temperatures at 19,000 °C, along with

pressure and sound waves can threaten human life.

Dept.EEE 6 GCE Kannur

Page 7: ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING

SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS

The physical effects of an arc flash are:

• Pressure wave in the environment where the arc is generated;

• Heating of the materials coming into touch with the arc flash;

• Potentially harmful light and sound.

Personnel hazards due to the release of energy generated by an arc event may include:

• Burns;

• Injuries due to ejection of materials;

• Damage to hearing and to eye-sight

; • Inhalation of toxic gases

BURNS

The high temperature levels of the gases produced by the electrical arc and the

expulsion of incandescent metal particles may result in severe burns. Flames can cause all

types of burns, up to carbonization: the red-hot solid metal fragments can cause third degree

burns, superheated steam causes burns similar to hot liquids and the radiant heat generally

causes less severe burns.

INJURIES DUE TO EJECTED MATERIALS

The ejection of metal particles or other loose items caused by the electric arc can result

in severe injuries to the most sensitive parts of the human body, like the eyes. The materials

expelled due to the explosion produced by the arc may penetrate the cornea. The extent of the

lesions depends on the characteristics and kinetic energy of these objects. Also, the eye area

can sustain injuries to the mucosa, such as the cornea or retina, because of the gases released

by the arc and the emission of ultraviolet and infrared rays.

HEARING

As already mentioned, the electric arc is a true explosion, whose sound may cause

permanent hearing loss.

INHALATION OF TOXIC GASES

Dept.EEE 7 GCE Kannur

Page 8: ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING

SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS

The fumes produced by burnt insulating materials and molten or vaporized metals can

be toxic. These fumes are caused by incomplete burning and are formed by carbon particles

and by other solid substances suspended in the air.

2.5 MITIGATION

The mitigation of arcing fault hazards in medium voltage switch gear is an urgent

concern. It is being addressed in many ways by safe work practices, operator training and

innovative products and installations. Mitigation is defined as to make milder, less severe or

less violent. Arc flash mitigation involves taking steps to minimize the level of hazard or the

risk associated with an arc flash event.

The two ways of avoiding arc flash effects are

i) Reduce arc flash energy to a level where permitted tasks can be performed.

ii) Locate the workers so that he is not subject to harm.

2.6 CONVENTIONAL EQUIPMENT TO LIMIT THE EFFECT OF AN ARC

FLASH

Conventional electrical protection equipment does not sufficiently limit the effect

of an arc-flash:-

The duration of an Arc-Flash is mainly determined by the time it takes for overcurrent

or earth-fault protective devices to detect the fault, send a trip signal to the circuit breaker and

for the circuit breaker to subsequently disconnect the energy source. Fast acting fuses may

disconnect the circuit from the energy source in 8 ms or less when subjected to the high short-

circuit currents usually appearing in three-phase symmetrical bolted cases, while other devices

may take much longer to operate and remove the source of energy. But unbalanced, single-

phase and high-impedance fault currents are lower than three-phase bolted-fault currents, so

protection devices may not necessarily detect and limit arc-fault current and will require more

time to clear the fault.

Dept.EEE 8 GCE Kannur

Page 9: ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING

SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS

CHAPTER 3

HIGH SPEED SWITCHING (HSS) SYSTEM

3.1 FEATURES

• Method of mitigating arc flash hazards in which reduction of arc flash energy is

employed.

• It is conceptually very simple and effective.

• Used to detect and quench internal arc in less than one-third of one electrical cycle

Fig. 3.1 HSS typical schematic

3.2 HIGH SPEED SWITCHING

The high-speed switch (HSS) system is one method of mitigating arc flash hazards

associated with medium-voltage switchgear. It is conceptually very simple and effective but

often viewed skeptically as a radical approach that places too much stress on the power system

when it operates. In fact, it does transfer an internal arcing fault to the switchgear bus which

does create a bolted fault on the system. When the HSS control system detects illumination

with characteristics similar to that of an internal arc, confirmed by a corresponding rate of

change of current, an arc flash event is declared, and the normally open HSS very rapidly

closes to create a three-phase bolted fault, which thereby extinguishes the higher impedance

internal arc, such as that shown in Fig 3.1.

Dept.EEE 9 GCE Kannur

Page 10: ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING

SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS

Arc fault:-

Short circuit current resulting from conductors at different voltages making less than solid

contact. Results in a relatively high resistance connection compared to a bolted fault.

Bolted fault:-

Short circuit current resulting from conductors at different voltages becoming solidly

connected together.

Some HSS designs may operate based on other characteristics from internal arcing other than

light and current, such as temperature, pressure, sound, harmonics, etc.

The bolted fault remains on the system until cleared by the source overcurrent device.

The stress of a bolted fault is certainly a valid concern, but the HSS should not be dismissed

without carefully considering the benefits provided. The intrinsic benefits are as follows:

1) speed of operation:

a) effective incident energy (arc flash) reduction;

b) reduction of equipment damage and corresponding downtime due to an internal arcing

event;

c) Reduction of motor contribution to an internal arcing event.

2) effective protection even with exposed live parts;

3) independence from overcurrent coordination and arcing fault current variations;

4) No impact on switchgear room (no additional ventilation or ducting requirements).

These benefits translate to improved worker safety, procedural simplicity, power system

reliability, improved system availability, and, in some cases, reduced installed cost.

Dept.EEE 10 GCE Kannur

Page 11: ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING

SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS

CHAPTER 4

PERFORMANCE

This chapter mainly includes the main benefits of the high speed switching system

4.1 SPEED OF OPERATION

Commercially available HSS systems detect an arc and close in approximately 4–6ms

(0.2–0.3 cycle at 50 Hz). In contrast, modern vacuum circuit breakers can typically detect and

clear an arcing fault in not less than 50ms considering overcurrent or flash detection relay trip

contact closure time plus circuit breaker clearing time. In many cases, the operating time is

greater than 50ms, depending on the use of lockout relays, relay and circuit breaker vintage and

vendor type, and other variables. Lockout relays add one cycle. In retrofit scenarios, older

circuit breakers may be 5 or 8 cycle rated.

HSS is therefore about ten times faster than the fastest circuit breaker-based

arc detection and quenching schemes, which leads to the following benefits.

4.1.1 AFIE REDUCTION:

Arc flash incident energy (AFIE) is directly proportional to the time required to

extinguish the arc. Accumulated AFIE versus time is shown in Fig.4.1 for an arbitrary

example system: 13.8-kV system with 50-kA available fault current, solidly grounded using

standard 36-in (914 mm) working distance and 153-mm bus gap per IEEE 1584.

Dept.EEE 11 GCE Kannur

Page 12: ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING

SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS

Fig. 4.1 AFIE accumulation versus time example.

For the Fig 4.1 example system, AFIE calculations for switchgear with HSS result in

less than 1.2 cal/cm2 (the industry referenced second degree burn threshold). At this calculated

AFIE, non-melting or untreated natural fibre clothing may be worn along with hearing

protection, eye protection, and leather gloves as needed. For the best case circuit breaker

tripping times shown in Fig 4.1, heavier personal protective equipment (PPE) with flame

resistant clothing is required for higher energy exposures. PPE for higher energy exposures is

progressively more bulky, hot, and difficult to work in due to loss of visibility and dexterity.

Workers are relieved to get out of PPE in hot locations (although there are cooling systems

available to lessen the discomfort).

Personal protective equipment (PPE):- Safety devices worn by personnel to protect against

hazards. PPE includes helmets, hearing protection, face shields, gloves, safety boots,

respirators etc.

4.1.2 EQUIPMENT DAMAGE REDUCTION:

Arc blast effects can destroy equipment with the same phenomena that kill and injure

people. The IEEE Std. C37.20.7 guide for testing arc-resistant metal-enclosed switchgear does

not include internal equipment destruction as a failure criterion. Rework or replacement is

expected.

HSS manufacturer tests and actual field events, however, illustrate that the fast arc

quenching limits the damage to the point of the arc occurrence, with minimal additional

damage. As a result, troubleshooting, repair, testing, and return to service are simplified and

relatively quick. “As a general rule, removing the fault quickly will minimize the damage;

however, the overpressure event typically occurs in a time frame of less than 1 electrical

cycle”.

For medium-voltage switchgear, HSS systems are the only available devices to date that

can compete with the speed of overpressure and equipment destruction, as illustrated in Fig

4.1.

Dept.EEE 12 GCE Kannur

Page 13: ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING

SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS

4.1.3 REDUCTION OF MOTOR CONTRIBUTION TO AFIE:

Large induction and synchronous motors can contribute significantly to AFIE in some

industrial settings. The medium-voltage feeder breakers supplying motor loads will not trip for

motor contribution levels in many cases, so the full motor contribution can persist for several

cycles regardless of the main circuit breaker tripping time. In the case of bus differential relay

application, the motor contribution will persist until it decays to zero or the associated bus

lockout relay and feeder breaker trips, whichever comes first.

HSS addresses this issue in large measure due to the fast arc quenching time. Again, the

margin of improvement is approximately a factor of 10, based on the speed of quenching the

arc via HSS versus circuit breaker.

4.2 EFFECTIVE PROTECTION WITH EXPOSED LIVE PARTS

The IEEE Guide C37.20.7 guide for testing arc-resistant metal-enclosed

switchgear states that “The use of equipment qualified to this guide is intended to provide an

additional degree of protection to the personnel performing normal operating duties in close

proximity to the equipment while the equipment is operating under normal conditions.” The

standard excludes alteration of the equipment from normal operating condition and from

activities above or below the equipment, such as catwalks, installations on open grating, cable

vaults, and so forth. Any opening in the equipment invalidates the arc resistant category and

can expose personnel to the full effects of the arcing event. Arc-resistant switchgear is arc

resistant only when all covers are secured in place.

HSS systems, however, operate effectively regardless of exposed live parts or

the personnel performing work above or below the equipment. Working around exposed live

parts should normally be prohibited, but situations can and do arise where the risks associated

with equipment shutdown exceed the risks of working with the equipment opened.

4.3 INDEPENDENCE FROM OVERCURRENT COORDINATION

HSS systems rely on light sensors, current transformers, and possibly sensors for

other parameters to detect an arc and initiate HSS closing. The bolted fault current resulting

from HSS actuation has to be cleared by the source overcurrent device within the withstand

ratings of the switchgear and HSS system, but the protection of the worker is effective even if

Dept.EEE 13 GCE Kannur

Page 14: ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING

SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS

the relays in the system are improperly coordinated or if the arcing fault magnitude is not as

anticipated.

The selective coordination of overcurrent devices is often in direct conflict with

the need to trip the source circuit breaker(s) as fast as possible for arc flash hazard mitigation

purposes. For example, if the instantaneous trip level is above the lowest arcing fault current

magnitude, the relay may not trip instantaneously, resulting in high AFIE. On the other hand, if

the instantaneous trip level is set low enough to trip quickly for all possible values of arcing

current, selective coordination with downstream devices is frequently compromised.

Therefore, all values of arcing fault current magnitude must be considered from highest to

lowest. This requires careful judgment and frequent trade-offs between selective coordination

and AFIE mitigation. There are many reasons that arcing fault current levels can change,

including utility system upgrades or system switching, plant switching between main, tie, and

in-plant generator circuit breakers, varying quantities of running motors, and so forth.

Additionally, many times, the utility system changes without the customer being made aware.

Various means of addressing these issues have been implemented with success.

Bus differential relays are fast (approximately 80ms from overcurrent detection to

arcing fault elimination) yet inherently selective but cannot detect arcing faults outside the

protected zone current transformers, which, in most metal clad switchgear, do not encompass

the cable compartments. For example, the bus differential relays installed at the health care

facility cited in this paper did not detect the arcing fault condition because the bus differential

current transformers are inside the breaker cell while the fault occurred in the cable

compartment. Another example is that, while a worker may have an additional degree of

protection when racking a breaker from the front of the equipment, he may not be protected if

the cable compartment is opened.

Zone selective interlocking schemes (approximately 80 ms from overcurrent

detection to arcing fault elimination), also called fast trip schemes, achieve selective

coordination via restraint signals from the feeder circuit breakers going back to the main. If the

main detects a fault but receives a restraint signal from the feeder, the main breaker relay times

out normally per its time–current curve, allowing the feeder to selectively clear the

downstream fault. If the main detects a fault without a restraint signal, the main trips

instantaneously since the fault logically must be on the switchgear bus. The main circuit

breaker relay must, however, detect the fault at arcing current level, and it must still coordinate

with the feeder. Feeder breakers cannot be permitted to trip on motor contribution; otherwise,

Dept.EEE 14 GCE Kannur

Page 15: ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING

SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS

they will restrain the source breaker(s) and defeat the scheme entirely. Multisource line-ups

such as main–tie–main add still more complexity.

Alternative maintenance setting switches (approximately 80 ms from overcurrent

detection to arcing fault elimination) are used to lower relay pickup levels and sacrifice

coordination only when personnel are present or maintenance is being performed. Again, the

main circuit breaker relay must detect the fault at arcing current level, and careful procedural

rules must be implemented to ensure that personnel do not forget to turn on the maintenance

trip settings when beginning the work or forget to turn it off when done. Occupancy sensors

have been used to turn on inputs to electronic relays that automatically lower the relay

instantaneous settings and then restore them when personnel leave. While the reduced settings

are in effect, there is a possibility of nuisance nonselective tripping.

Arc flash detection relays (52–57 ms from arc detection to arcing fault elimination)

that combine light sensors, current sensing, and high speed relay outputs are immune to

overcurrent coordination and arcing fault current magnitude but rely on the relatively slow

circuit breaker tripping to quench the arc.

HSS systems (4–6 ms from arc detection to arcing fault elimination) are likewise

immune to the downstream coordination and arcing fault current magnitude considerations but

have the advantage of speed. The short-circuit withstand rating of the HSS itself is all that

needs to be considered in setting the source circuit breaker relays with regard to arc flash

protection. For circuit breaker-based arc quenching (other than arc flash detection relays), relay

settings are critical and must consider all possible arcing fault current magnitudes.

Power system short circuit, coordination, and arc flash studies must be kept up-to-

date and relay changes implemented as necessary. This statement is always true, but for HSS

installations, it is less critical because the arc flash hazard protection is unaffected. A related

benefit is that selective coordination for critical systems is made much simpler.

4.4 NO IMPACT ON SWITCHGEAR ROOM

Arc-resistant switchgear that relies on circuit breaker tripping must have a safe path to

vent the arc by-products. Ceiling and wall clearances, overhead equipment, doors, windows,

building capability to absorb pressure wave, fireproofing, weather, and vermin ingress are

among the considerations. Additionally, the arc-resistant switchgear may be larger and heavier

than the standard switchgear. These factors can grow the size, cost, and complexity of the

Dept.EEE 15 GCE Kannur

Page 16: ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING

SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS

switchgear room. Some HSS systems have been tested and comply with IEEE C37.20.7, and

they negate the need to purchase passive arc containment (heavily reinforced cubicles).

HSS system installations may require an additional section to accommodate the HSS;

otherwise, the installation is identical to that of the standard non-arc-resistant switchgear, as no

arc by products need to be accommodated.

4.5 DRAWBACKS OF HSS SYSTEM

• It places too much stress on the power system when it operates.

• Bolted fault remains on the system until cleared by the source overcurrent device.

Dept.EEE 16 GCE Kannur

Page 17: ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING

SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS

CHAPTER 5

CONCLUSION

The HSS system may be likened to an automobile airbag. Hopefully, it will never

have reason to operate for the entire life of the equipment, but if needed at any time, it must

operate instantly. Nuisance operation is unforgivable. The device cannot be tested in normal

operation. It has to be trusted.

HSS systems should be seriously considered for installation in medium-voltage

switchgear. Other means of enhanced equipment protection from arc flash hazards are

available. Switchgear size, importance, cost, complexity, growth needs, and architectural

considerations should be considered along with plant safe work practices, procedures, and

other available arc flash mitigating features.

A risk versus benefit analysis is recommended when installing HSS on the

secondary of older or less robust power transformers that, due to operating history or test

results, are considered near end of life.

Large medium-voltage motors should be evaluated for use on HSS-equipped systems

using actual machine and supply conductor impedances as well as manufacturer input. In many

cases, the additional stresses placed on the motor due to HSS closing will be minimal.

HSS systems can provide substantial rewards without exposing the power system to

undue risks beyond the unavoidable.

Dept.EEE 17 GCE Kannur

Page 18: ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING

SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS

REFERENCES

[1]Michael D. Divinnie, James K. Stacy, Antony C. Parsons. “Arc Flash Mitigation Using

Active High-Speed Switching,” IEEE Transactions on Industry Applications., Vol. 51, no.1,

Jan./Feb. 2015.

[2] Palak Parikh, Ray Luna, Michael Pilon, Roy Mao, “A Novel Approach for Arc-Flash

Detection and Mitigation: At the Speed of Light and Sound,”978-1-4799-0119-

7/13/$31.00©2013 IEEE.

[3] Johnny Simms, Gerald Johnson, “Protective Relaying Methods for Reducing Arc Flash

Energy,” 978-1-4244-6075-5/10/$26.00 ©2010 IEEE.

[4] Kanu R. Shah, Alan L. Cinsavich, Priyan De Silva, “Impact of Arc Flash Hazards on

Medium-Voltage Switchgear,” IEEE transactions on industry applications, vol. 44, no. 6,

November/December 2008.

[5] R. L. Doughty, T. E. Neal, T. Macalady, V. Saporita, and K. Borgwald, “The use of low

voltage current-limiting fuses to reduce arc-flash energy,” IEEE Transactions on Industry

Applications., vol. 36, no. 6, pp. 1741–1749, Nov./Dec. 2000.

Dept.EEE 18 GCE Kannur

Page 19: ARC FLASH MITIGATION USING ACTIVE HIGH-SPEED SWITCHING

SEMINAR REPORT 2016 ARC FLASH MITIGATION USING ACTIVE HSS

Dept.EEE 19 GCE Kannur