Protection againstOvervoltages inPhotoVoltaic installations
According to the European Standards
Christian MacandaMember of : • French standard commitee for « SPD » UTE 37AB • Groupe GT37A Gimelec/Domergie• international standard commitee IEC WG3& WG4 /TC37A• Association Protection Foudre (APF)• Association Technique SEE – section « Foudre » (44.20)
PR130601- This document could not be transmitted or used, even partially, without the agreement of the CITEL company.
Reminder about lightning and surge risks in a PV installation
• Direct ligthning strike on the structure EN 62305-x series Standard
• Surge voltages Coming through the AC network : Due to the lightning activity and/orSwitching operations.
• Surge voltages Due to lightning strikes nearthe buildings or the PV installation, For on the lightning rods of the buildings.
• Surge voltages Generated by electromagneticCoupling of the electrical field Created by the ligthning activityon AC and DC networks.
Lightning activity
Impact onAerial lines
Electromagnetic couplingEarth potential rise
Direct impact
Damages on equipment
Reminder about lightning and surge risks in a PV installation
European Insurance Statistics
Surge protection for PV installation Grid-connectedEvolution of standards
To take care about the important issue of damages due to surge voltages, European standard organization (CENELEC) has published a complete set of technical documents.
European Standard Type of documents
HD 60364-7-712 PV installation guide
prEN 50539-11 PV Surge protector Tests
CLC/TS 50539-12 PV Surge protector installation
Surge Protectionof PV installations
Protection against Surge Voltages
Surge Protection Devices : SPDs
on DC side : - SPD Close by the inverter- Additional SPD close by the PV module,if distance > 10 m
on AC side :- SPD at the entrance of installation (Main electrical board)- Additional SPD close by the inverter (if distance > 10 m)
on signal line side :- SPD on the external line side of the inverter- SPD on the internal line side (towards sensors) of the inverter
General design for Lightning & Surge Protection of PV installations
The CENELEC Guide CLC/TS 50539-12 describes the general approach for Efficient surge protection of a Grid-connected PV installation
AC line
Signal line
SPD
SPD
SPD
kWh
1
2
5
5
4E
E
E
3
AC
DC
Type 2AC SPDcomplying IEC 61643-11
Type 2AC SPDcomplying IEC 61643-11
if distance <10 m,
Type 2 PV SPDcomplying prEN50539-11
no SPD
if distance > 10 m,
Type 2 PV SPDcomplying prEN50539-11
Type 2 PV SPDcomplying prEN50539-11
Signal line SPDcomplying IEC 61643-21
1
2
3
4
3
4
16 mm²
16 mm²
6 mm²
6 mm²
SPD
ACSwitchboard
Main earthing bar
Bonding bar
SPD
SPD
e.g windsensor
Building withPV install
Typical Surge protection solution for Domestic PV Installation
AC SPD at theMain electricalboard
AC SPD in Combiner boxClose to the inverter
Signal line SPDClose to the inverter
PV SPD in Combiner boxClose to the inverter
PV SPD close to PV modules
General design for Lightning & Surge Protection of PV installations
PV installation with Lightning Protection System (LPS)
AC line
SPD
SPD
SPD
ACSwitchboard
Main earthing bar
kWh
1
E
EBonding bar
AC DC
Type 1AC SPDcomplying IEC 61643-11
Type 2AC SPDcomplying IEC 61643-11
if distance <10 m,
Type 2 PV SPDcomplying prEN50539-11
no SPD
if distance > 10 m,
Type 1 PV SPDcomplying prEN50539-11
Type 1 PV SPDcomplying prEN50539-11
1
2
3
4
3
4
16 mm²
16 mm²
6 mm²
6 mm²
Bâtiment sans SPF
SPD
Non-Isolated LPSseparation distance "s" is notkept
4E
32
16 mm²
50 mm²
16 mm²ifType 1
Additionalearthingconductor
16 mm²ifType 1
General design for Lightning & Surge Protection of PV installations
Standard for PV SPD
New Testing guideprEN 50539-11
• Tests to be applied to SPDs connected to PV networks.
• Based on the IEC/EN61643-11 AC Test standard and on the french PV Test standard UTE C61740-51.
• Definition of new parameters
• End of life testing specific to PV
Standard for PV SPD
New parameters according to EN50539-11 standardUcpv : Maximum operating DC voltage of the SPD.
Ucpv ≥ 1,2 Uocstc
This declared voltage must be selected according to the maximum voltage of the PV generator in open circuit (Uocstc provided by PV panel manufacturers). Ucpv voltage must be greater or equal to 1,2 x UocSTC of the PV generator.
Iscwpv : Declared short circuit current of the SPDIscwpv ≥ 1,25 Iscstc
This admissible current by the SPD and its disconnector must be selected according to the current that can be delivered by the PV generator Iscstc. This current corresponds to the sum of currents that can be delivered by various PV strings in parallel or group of strings upstream the point of installation of the SPD. This Iscwpv current must be superior or equal to 1,25 x Iscstc of the PV generator.
Uocstc : Maximum voltage in open circuit of the PV generator
Iscstc : Short Circuit current of the PV generator
Standard for PV SPD
The mains difference between AC power SPDs and PV SPD is related to the behaviour in case of end of life. In order to define the relevant surge protector adapted to PV line, EN50539-11 standard specifies 2 dedicated tests :
• Overload Behaviour testing
• Ageing testing in humidity chamber
Specific “End of life” tests
New Standard for PV SPD
• Withstand of humid heat- Selection of MOVs adapted to a PV polarization- Specific process to withstand humid heat Result : tested leakage current < 10 µA (so << 100 µA)
• Overload testing- Appropriated selection of the type and voltage of MOVs- Optimized operation of the internal disconnector Result : disconnection in compliance with the overload test.
New ranges of SPD tested and in compliance with standards :
DS50PV/51 et DS50VGPV/51
DS60VGPV/51 (Type 1+2)
Evolution of CITEL SPD to be in compliance with EN50539-11
Selection of PV SPD following installation european guide CLC/TS50539-12
SPD Parameter Selection CITEL
Type of SPD - Type 2 for non-LPS or isolated-LPS installation- Type 1 for non-isolated-LPS and length E> 10 m
Type 1 DS60VGPV rangeType 2 DS50PV range
Standard compliance prEN 50539-11 comply
Max PV operating voltage(Ucpv)
1.2 x Uocstc (Max open circuit voltage) of the PV line Available for Uocstc = 500, 600, 800, 1000 and 1250 Vdc
Short-circuit withstand(Iscwpv)
1.25 x Iscsct (Max short circuit current) of the PV line.If Iscwpv of the SPD < 1.25 x Iscsct external fuse in the SPD branch is required.
Typical Iscwpv : 1000 A
Localization - Close to PV inverter input (< 10 m)- Additionnal SPD required close to remote PV modules
Discharge currents(In and Iimp)
- Type 1 : Iimp from 6,25 to 50 kA (10/350) depending of the LPS type and earthing conditions (see table)- Type 2 : In > 5kA
Iimp (Type 1) = 12. 5 kAIn (Type 2) = 20 or 15 kA
Protection level (Up)
< Uw (overvoltage withstand of PV equipment)(approximative calculation possible : Up < 5xUocstc)
i.e. for 1000 Vdc PV line, Up = 2.2 kV (DS50PV-1000G/51
Type 2 PV SPDCITEL DS50PV range
Type 1+2 PV SPDCITEL DS60VGPV range
SPD range of PV installation
-
PE
+
C
CITEL PV SPD DS50PV Range Description (Type 2)
15
Less wiringthrough standard
remote signaling for all poles
Fully assembled and ready-to-use SPD
Error-free changing of pluggable modules through a mechanical coding
Fault-resistant Y circuit
Safe distance between+ / - polarities and PE
Reverse polarity protected connection between the + and -
No leakage current = No interference from inverters
and grounding systems
Full-safe monitoring of all modules
Safe thermal disconnection from PV line without interruption and arcing
Easy replacing of protection pluggable modules
Multi-function terminals for conductors or busbars
Multi-diagram solution
EN50539-11 compliance
Disconnection indicators
Common and Differential mode protection
Double earthing connection possible
VG version available
CITEL PV SPD
SPDs Type 2Réf. DS50PV/51
In compliance with EN50539-11(Test reports by certified external lab)
• For Uocstc Voltage : 500, 600, 800 et 1000 Vdc
• « 3-Module » (Common/Diff mode) or « 2-Module » (Common mode) versions
• Iscwpv : 1000 A (without external disconnector)
• Nominal Discharge Current (In) : 15 kA 15 x pulse 8/20µs per pole
• Maximum Discharge Current (Imax) : 40 kA 1 x pulse 8/20µs per pole
• Monobloc base – Single remote signalling contact (option)
• Optimized grounding connection
• Gas tube to the ground (DS50PV-xxxG/51) leakage current suppression
+
Ft MI
to
-
C
V V
CITEL PV SPD
SPD Type 2Ref. DS50VGPV
• « VG » technology No current consumption, no leakage No ageing of varistors
• Uocstc voltage : 500 up to 1000 Vdc
• Uocstc voltage : 1250 Vdc
• Nominal Discharge current (In) : 15 kA 15 x pulse 8/20µs per pole
• Maximum Discharge Current (Imax) : 40 kA 1 x pulse 8/20µs per pole
• Monobloc base– Single remote signalling contact
• Optimized ground connection
• Remote signalling DS50VGPVS (option)
+
Ft MI
to
GDT
-
C
V
NEW
NEW +
Ft MI
to
-
C
V V
CITEL PV SPD
SPD Type 1Ref. DS60VGPV
• For PV installation with non-isolated lighting rod
• « VG » technology No current consumption, no leakage No ageing of varistors
• Uocstc voltage : 600 and 1000 Vdc
• Uocstc voltage : 1250 Vdc
• Nominal Discharge Current (In) : 20 kA15 x pulse 8/20µs per pole
• Maximum Lightning Current• Iimp : 12,5 kA onde 10/350µs • Iimp Total : 25 kA
• Remote Signalling contact in option : DS60VGPVS
NEW
DS60VGPV-1500G/51
Other SPDs for PV installationsAC and Signal line SPDs
AC SPDSingle-phaseType 2 compactDS240-230/G
AC SPD3-phase+neutralType 2 compactDS440-230/G
AC SPDType 1 compactDS130R
Data SPDRS485compactDLA-06D3
AC Surge Protectors for PV Inverters
Type 1DS130R
• Type 1 AC surge protectors (needed if LPS)• Pluggable modules• High efficiency (Up < 1.5 kV)• Remote signal for failure indication (option)• Iimp (10/350µs) : 12.5 kA/pole• Comply EN 61643-11/ test class I and II• UL 1449-ed3 recognized• Exclusive « MOV+GDT » Technology : DS130VG
CITEL « VG » technology
3-phase+N SPD DS134R-300/G
AC Surge Protectors for PV Inverters
Type 2DS40 and DS10 range
• Type 2 AC surge protectors• MOV Technology• Pluggable modules• Remote signal for failure indication
(option DS40S ou DS10S)• In / Imax : 20/40 kA (DS40) et 5/10 kA (DS10)• Comply EN 61643-11/ test class I and II• Version VG technology available : DS40VG • UL 1449-ed3 recognized
3-phase AC SPDDS44S-230/G
AC Surge Protectors for PV Inverters
Type 2 CompactDS240 and DS215
• Type 2 AC single-phase surge protectors• Reduced dimensions• MOV Technology• Pluggable modules• Remote signal for failure indication
(option DS240S or DS215S)• In / Imax : 20/40 kA (DS240) et 5/15 kA (DS215)• Comply EN 61643-11/ test class I and II• UL 1449-ed3 recognized
Single-phase AC SPDDS240S-400
Single-phase AC SPDDS215-400
Dataline Surge Protectors for PV Inverters
Dataline Surge ProtectionDLA range
PV Inverters could be equipped with supervision features, connected through dataline, as RS422, RS485 for reliability, Surge protection is required
• 1-pair dataline surge protector• Reduced dimensions• High discharge current , low clamping voltage• Pluggable module• Available for all types of data transmission• Comply EN 61643-21
SPD for signal lineDLA-24D3
PV Installation Typical Combiner boxes for domestic application
Typical Surge protection solution for Industrial PV Installation
3-phase AC SPD at theMain electrical board
3-phase AC SPD in Combiner boxClose to the inverter
PV SPD in Combiner boxClose to the inverter
Surge Protection for PV installation
Typical Surge protection solution for PV Power Plant
Signal line SPD close to inverters
Type 1 3-phase AC SPD in Combiner boxclose to the inverter
Type 1 PV SPD in Combiner box
close to the modules
Type 1 PV SPDsclose to the
inverters
Surge Protection for PV installation
PV InstallationExample
DC panels for 6 inverters
AC panels for 6 single-phase panels 3-phase AC network connection
Surge Protection for Off-grid PV installations
Surge protection Approach
• DC surge protectors (DS2x0-xxDC) on the input of the PV lines coming from the outside.• AC surge protectors (DS40, DS240..) on the input of the possible additionnal exernal AC
power supplies (wind turbine, power generator, AC grid)• AC surge protectors (type DS40, DS240..) on the AC lines for outdoor loads (pumps,
lighting…)• Additionnal surge protector on outdoor systems are recommended if they are remote
from the main building (> 10 m).
Régula teur
Batterie
AC
DC
to
PARAFOUDRE DC
PARAFOUDRESAC
to
Equipementsextérieurs distants
Pompes-Eclairage...
Générateur extérieur (optionnel)Groupe-Eolien-Réseau BT
Modules PV
DC
DC
Chargesinternes AC
Chargesinternes DC
toto
to
*
to*
*
Surge Protection for Off-grid PV installations
DS2x0-DC range : SPD for Off-grid PV installations
• Type 2 pluggable Surge protectors• Compact size (l18 mm width) • DIN rail mounting• Imax from 20 to 40 kA• Nominal voltages : from 12 to 350 Vdc• Remote signalling for disconnection (option)
Part Number DS220-12DC
DS220-24DC
DS230-48DC
DS240-75DC
DS240-95DC
DS240-110DC
DS240-130DC
DS240-220DC
DS240-280DC
DS240-350DC
Nominal DC voltage
Un 12 Vdc 24 Vdc 48Vdc 75 Vdc 95 Vdc 110 Vdc 130 Vdc 220 Vdc 280 Vdc 350 Vdc
Max operating DC voltage
Uc 24 Vdc 38 Vdc 65 Vdc 100 Vdc 125 Vdc 150 Vdc 180 Vdc 275 Vdc 350 Vdc 460 Vdc
Nominal discharge current
In 10kA 10 kA 15 kA 20 kA 20kA 20 kA 20 kA 20 kA 20 kA 20 kA
Maximum discharge current
Imax 20 kA 20 kA 30 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA
Protection Level @ In
Up 250 V 250 V 300 V 390 V 450 V 500 V 620 V 900 V 1200 V 1400 V
Protection Level @ 3kA
195 V 195 V 230 V 280 V 310 V 370 V 510 V 690 V 920 V 1000 V
Dimmension(width)
18 mm 18 mm 18 mm 18 mm 18 mm 18 mm 18 mm 18 mm 18 mm 18 mm
Surge Protection for Off-grid PV installations