23
CSMM 8 Implementation - Lesson Learned Standards ARIPPA 2010 Technical Symposium Harrisburg, PA August 25, 2010 Eric Swisher All4 Inc.

CSMM 8 Implementation - Lesson Learned Standards

Embed Size (px)

Citation preview

Page 1: CSMM 8 Implementation - Lesson Learned Standards

CSMM 8 Implementation - Lesson Learned

Standards

ARIPPA 2010 Technical Symposium Harrisburg,

PA

August 25, 2010

Eric SwisherAll4 Inc.

Page 2: CSMM 8 Implementation - Lesson Learned Standards

2

Overview Background Implementation Process Lesson Learned

Page 3: CSMM 8 Implementation - Lesson Learned Standards

3

Background Continuous Source Monitoring Manual

(CSMM) Revision 8 Data Validation Requirements Reporting Format QA Activities

Page 4: CSMM 8 Implementation - Lesson Learned Standards

4

Implementation Process CEMDPS Access Migration Error Check Certification Activities QA/QC Activities

Page 5: CSMM 8 Implementation - Lesson Learned Standards

5

CEMDPS Access Continuous Emission Monitoring

System Data Processing System (CEMDPS)• GreenPort• Web-based portal in which all CEMS

related information will be submitted. Phase I (Monitoring Plan) Phase II Testing Phase III Certification

Page 6: CSMM 8 Implementation - Lesson Learned Standards

6

Migration Error Check Standards

• Facility Emission Standards Tracking

• Analyzer Information

Page 7: CSMM 8 Implementation - Lesson Learned Standards

7

Standards Streamlining

• “This condition also assures compliance with….”

25 Pa. Code §123.22(c)(4) [SO2] 25 Pa. Code §123.41 [Opacity] 40 CFR Part 60, Subpart Da

Page 8: CSMM 8 Implementation - Lesson Learned Standards

8

Standards Values Averaging Periods

Page 9: CSMM 8 Implementation - Lesson Learned Standards

9

Tracking Tracking

• Analyzer Type• Measurement Basis (units, wet/dry)• Manufacturer• Model No.• Full Scale Range• LMESE

Page 10: CSMM 8 Implementation - Lesson Learned Standards

10

LMESE Lowest Monitored Emission Standard

Equivalent (LMESE )• Lowest emission standard (i.e., lb/hr,

lb/MMBtu, etc.) in terms of the analyzer output (i.e., ppm)

• Used to determine daily zero/upscale calibration drift

100 x /LMESE|A-R| =CE

Page 11: CSMM 8 Implementation - Lesson Learned Standards

11

LMESE LMESE [PADEP Default = (FS) ÷ 2] No LMESE for:

• Opacity (Abs. Difference)• CO2 (Abs. Difference)

• O2 (Abs. Difference)• VFR (most cases 2.5% range)• Dual Range Analyzers?

Page 12: CSMM 8 Implementation - Lesson Learned Standards

12

Alternative LMESE VFR (FS Range = 150,000 scfm)

• No flow standard• Maintenance Limit = ≤ 3,750 scfm

(2.5% * 150,000 scfm)• OOC = ≤ 7,500 scfm

(5.0% * 150,000 scfm)• Alternative LMESE = 62,500 scfm

(3,750 scfm ÷ 6.0%)

Page 13: CSMM 8 Implementation - Lesson Learned Standards

13

Example CEMDPS Information

As Received

Parameter Units MAN MN FS LMESE

Flow scfm Teledyne 150 150,000 75,000

Corrected

Parameter Units MAN MN FS LMESE

Flow scfm Teledyne 150 150,000 62,500

Page 14: CSMM 8 Implementation - Lesson Learned Standards

14

Streamlined Alternative LMESE

NOX (LMESE = 120 ppm)• Maintenance Limit = ≤ 6 ppm

(5.0% * 120 ppm)• OOC = ≤ 12 ppm

(10.0% * 120 ppm)

Page 15: CSMM 8 Implementation - Lesson Learned Standards

15

Streamlined Alternative LMESE

NOX (Part 75 Span = 260 ppm)• Maintenance Limit = ≤ 6.5 ppm

(2.5% * 260 ppm)• OOC = ≤ 13 ppm

(5.0% * 260 ppm)• Streamlined LMESE = 130 ppm

(6.5 ppm ÷ 5.0%)

Page 16: CSMM 8 Implementation - Lesson Learned Standards

16

Example CEMDPS Information

As Received

Parameter Units MAN MN FS LMESE

NOX ppm TECO 43C 300 150

Part 75 Petitioned

Parameter Units MAN MN FS LMESE

NOX ppm TECO 43C 300 130

Page 17: CSMM 8 Implementation - Lesson Learned Standards

17

Certification Activities 7-Day Drift DAHS Verification Sample Reports QA/QC Plan

Page 18: CSMM 8 Implementation - Lesson Learned Standards

18

7-Day Drift Evaluates the accuracy and stability

of CMS calibrations over an extended period of unit operation

Revision 6 CEMS Uses the LMESE drift tolerances

Page 19: CSMM 8 Implementation - Lesson Learned Standards

19

DAHS Verification Certifies that the DAHS is functioning

correctly• Normal Operating Hours• Process Down Hours• Partial Operating Hours• Invalid Data Hours• Missing Data Hours

Page 20: CSMM 8 Implementation - Lesson Learned Standards

20

Sample Reports Submittal of sample data via CEMDPS

to ensure proper data format

Page 21: CSMM 8 Implementation - Lesson Learned Standards

21

QA/QC Activities Daily Calibrations Calibration Error Tests vs. Linearity

Tests Maintenance Activities Flow Monitor Leak Checks

Page 22: CSMM 8 Implementation - Lesson Learned Standards

22

Other Lessons Learned Refresher Training

Page 23: CSMM 8 Implementation - Lesson Learned Standards

23

Questions?

[email protected](610) 933-5246, extension

17

All4 Inc.2393 Kimberton Road

P.O. Box 299Kimberton, PA 19442

610.933.5246 x17

www.all4inc.com