12
PROMET SE Precision Ohm Meter

PROMET SE 2016

Embed Size (px)

Citation preview

Page 1: PROMET SE 2016

PROMET SEPrecision Ohm Meter

Page 2: PROMET SE 2016

Condition & Analysis of • Electrical contacts• Breaker Main Contacts

PROMET SE

Content

Problem

Effects on a connection

Solution

PROMET SE

Page 3: PROMET SE 2016

Electrical plant and equipment:Cross temperatures must not be exceeded

Resistance increase with operating time

Heating by power loss

Ageing connections

Which problem is to be solved?

Page 4: PROMET SE 2016

Switching devices are essential equipment in a substation.

The current must be interrupted save if a failure occurs.

To guarantee the operation the circuit breaker need maintenance.

Reasons:• Wear of the moving parts• Leak on valves and seals• Failures in control circuits• Deterioration of contact parts

Switching devices

Page 5: PROMET SE 2016

Reliable operation is endangered

Power supply companies want to avoid interruptions of energy transport

Inspection and maintenance of equipment

Lifetime and Functionality

Page 6: PROMET SE 2016

Contact: 2 surfaces

Contact surface: rough

Micro contacts

Small effective area Greater resistance

P = R I2

Contact resistance

Which affects the temperature of a connection?

Page 7: PROMET SE 2016

OxidationOxide layer reduce current bearing area

Contact wearMechanical effect movement, friction and arc effect

Contact forceForce can decrease: e.g. loose or misaligned contact

increase the contact temperature, leading to its destruction

Further effects for contact resistance

Page 8: PROMET SE 2016

New solution for connections and switching devices

PROMET SEPrecision Ohm Meter

Stand-alone unit and external control via ACTAS systems

Static- and dynamic resistance measurement

Page 9: PROMET SE 2016

Stand alone device

Up to 200 A

Small lightweight box

Independent from mains voltage

Static resistance measurement

Quality of contactse.g. busbar, earthing switches, …

Stand-alone

Page 10: PROMET SE 2016

Via ACTAS• Digital communication

Up to 200 A

2 breaks per phaseTotal: 3 x 2 chambers

Connection direct at the chamber• Short current and voltage cables• Less weight

Static and dynamic measurement• Synchronization betweenpoles and chambers

External control

PROMET SE

PROMET SE

Page 11: PROMET SE 2016

SpecificationsPROMET SE

Housing Hand case(200 x 178 x 100) mmWith strap for attachment to the breakerTransport case

Weight 1,5 kg (without accessories)Connection 4 mm safety plugs

9 mm high current plugsCurrent up to 200 ACurrent/Voltage channels

2

Terminal voltage

~ 2,5 VDC

Resistance up to 200mΩPower supply - Battery back-up (all day measurement)

- External power supply (AC-Adapter)

Page 12: PROMET SE 2016