BRS2216 Outdoor Power System
1
Telecom Power RBS2216
Outdoor System
NTBU
BRS2216 Outdoor Power System
21
Telecom Power System
Telecom Power SystemTelecom Power System
AC
Distribution U
nit
Rectifier # 1
Control Supervisory Unit (CSU)
LOA
D (Sw
itch ,AD
SL…E.T.C
.)
Output D
C D
istribution Unit
LVDS
Rectifier # 3
Rectifier # 2
Rectifier # N
Battery
AC Input
Generator
U.P.S
BRS2216 Outdoor Power System
3
ContentsSystem Overview
Main Feature/Configuration
Outdoor Cabinet Type (1.8M)
Power Distribution configuration (AC,Surge , DC Load , Battery.
Rectifier Power shelf configuration
Rectifier module specification (DP2700)
New Smart CSU controller with LCD Display
System Function Introduction
Delta Remote/Monitor function
-- NRMS monitor software (Mini USB port)
-- Web Server/ SNMP function (Optional)
Q&A
BRS2216 Outdoor Power System
4
Delta DPS 2700 Series Power System
Main Features:AC Input: Optional for three conditions
220Vac, Single phase (Already) 380Vac, Three phases / Five Wire ( Y Connection)
System Capacity: -54Vdc / 150A Max. IP Protect:Power system Bay: IP54, Equipment Bay: IP55DC Distribution: Load Breaker Configurations: Breaker (DIN rail ), Battery Breaker: ~125A Breaker, 2 Positions Max.LVDB *1 (Standard): 150A on Battery Side
LVDL *1: 150A on Load SideRectifier: -54Vdc/50A (DPR2700) *3Controller: New Smart CSU with LCD Relay Output: Total 8 Positions, Customer DefinableLocal/Remote Monitoring and Control – NRMS software
Local Access: By NRMS via RS232 InterfaceInternet Web Server Function: By Web Server Software/SNMP via RJ45 Interface (Optional)
System Dimension (W*D*H): 55.1” x 33.5” x 71.3” inch / 1400 x 850 x 1810mmOperating Temperature: 0℃~+55℃(32℉~131℉)
BRS2216 Outdoor Power System
5PDU ( four Configurations)
Rectifier ESR-48/56A
Battery & Base
New Smart CSU (Main Board))
New Smart CSU (Relay Board))
19” Rectifier Shelf (SB-05N/HG A )
160W Heat-exchanger
CCU (Climate Control Unit )
BRS2216 Outdoor Power System
6
RBS2216 Outdoor System Drawing
BRS2216 Outdoor Power System
7
Delta Power System Drawing
BRS2216 Outdoor Power System
8
CCU
Tem
p S
enso
r
Hea
t Exc
hang
er
Airs
ysH
X160
-B1
CSU FL
Tem
p S
enso
r
Fan Tray
Fan ON/OFF ControlHi Temp Alarm
Hi Temp AlarmHEX status Monitoring
Fan
Spee
d C
ontro
l
(Full speed operation)
Architecture of Cooling Control
Delta Power System Drawing - CoolingBHEX
BRS2216 Outdoor Power System
9
RBS2216 Equipment Bay Configurations
RBS2216
160 W/K Heat Exchanger
Plinth
7pcs of 3-hole Cable Gland reserved(Details show on later page)
10U(H) Max. Space for Transmission Equipment
4pcs of M10 insert nuts pre-installed in Bracket For RBS2216 Installation, Pitch: 572mm * 307mmLoad capacity(Tray): 300Kg
Micro Switch (Front Door)
Estimated Weight: 140 Kg (With HEX)(Transmission equipment excluded)
Add markings on base frame for for RBS2216 installation.
AP29
10mm
BRS2216 Outdoor Power System
10
RBS2216 Power System Bays Configurations
Air Filter Frame mountedon Front Door
Power systemClimate Control Unit
Bottom cable entries
Fan tray mounted on inside of roof
4U Space for DDF-OVP
2nd Battery Shelf
1st Battery Shelf
AC termination
Changeover Switch
Cable gland for DC cables to equipment bay
Metal duct to AC termination
External Alarm Terminal
(Battery excluded in cabinet)
(Battery excluded in cabinet)
Estimated Weight: 127 Kg (With Power system)(Battery strings, DF-OVP excluded)
BRS2216 Outdoor Power System
11
Add AC Socket
RBS2216 AC Panel Configurations
Changeover Switch
Phase 1 (with Genset Socket & Changeover Switch):
Implementation: from first batch
Genset Socket
Phase 2 (without Genset Socket & Changeover Switch):
Implementation: TBD (Inventory Concern)
AP36
BRS2216 Outdoor Power System
12
DC LightSmoke Sensor
Humidity Sensor
RBS2216 Lights & Sensors
BRS2216 Outdoor Power System
13
AC main input Terminal BlockFor 3 phases and neutral connections
AC Grounding Bus Bar 4pcs of M6 insert nuts
RBS2216 AC Input Terminations
AC cabling from outside wallslot (L150mm * W60mm)through cable glands and metal wiring ducts to main AC terminations
3pcs of MG32A 3-hole Cable Gland
For cable range (OD): 5~10mm
BRS2216 Outdoor Power System
14
AC MAINS INPUT1 PHASE 220V 50/60Hz
S T
AC BREAKER 3P
N
R PE
SURGE ARRESTER
AC-T&SURGE-TAC-S&SURGE-S
R
TS
AC-R&SURGE-R
AC-N
N
SURGE-SSURGE-T
SURGE-R
L N
3P 380Vac Start Type
Main Power AC input Type
1P 220Vac Type
AC MAINS INPUT3 PHASE 380V + N 50/60Hz
S T
AC BREAKER 3P
N
R PE
SURGE ARRESTER
AC-T&SURGE-TAC-S&SURGE-S
R
TS
AC-R&SURGE-R
AC-N
N
SURGE-SSURGE-T
SURGE-R
R S T N
BRS2216 Outdoor Power System
15
Plate (1pcs):Pre-install on right sideDesign to block unused side
RBS2216 AC Cable Entry on Both Sides
AC cables pass through left side of plinth.
New requirement:AC cables can pass through right side of plinth.
AP32
BRS2216 Outdoor Power System
16
Rear Cover
Keep clearance between roof and rear cover to prevent interference
Roof
RBS2216 Roof Installation Improvement
Modify rear cover for roof installation without removing rear covers
(Section View from Right Side)
AP24
BRS2216 Outdoor Power System
17
RBS2216 Cable Entries
4pcs of bottom cable entries reserved
7pcs of side cable entries reserved
3pcs MG32A 3-hole Cable Gland For cable range (OD): 5~10mmFor AC Terminations
2pcs of 3-hole Cable GlandsFor jumper cable 1/2” (OD 12.5mm)
9pcs of compartment cable entries reserved
Genset Socket, 32A 3N~(R, S, T, N, PE)
2pcs of 3-hole Cable GlandsFor jumper cable 1/4” (OD 6.35mm)
1pce of MG25A 3-hole Cable GlandFor cable range (OD): 2.6~3.6mm
(Delta internal cable)
3pcs MG32A 3-hole Cable Glands
For cable range from (OD 5~10mm)
1pcs MG25A 1-hole Cable Gland For cable range (OD): 12~16mmFor DC grounding cable
4pcs of MG32A 1-hole CableFor cable range (OD): 15~22mm(2E1, Alarm cable, 1 power cable for MW)
4pcs of MG32A 3-hole Cable GlandsFor cable range (OD):5~10mm(Ericsson’s cables )
BRS2216 Outdoor Power System
18
RBS2216 Battery Configurations
2nd Battery ShelfMax. Space suitable forCSB TPX122200 * 4pcs
1st Battery ShelfMax. Space suitable forCSB TPX122200 * 4pcs
Reserved cabling space forJumper Cables
BRS2216 Outdoor Power System
19
Recommended Spare Parts & Part Numbers
RBS 2216, 1.8MESOA150-ABA01
Remark
CU-18A A-SClimate Control Unit V
3790335100-SController(NCSU)-LCD Display V
5505602118-SController(NCSU)-Main Board V
ESR-48/56A A-SRectifier 2700W (DPR2700) V
3790335000Temperature Sensor Cable 3M V
EX-F01 B-SFan Tray V
EX-H01 A-SHeat Exchanger 22W/K
(Delta HEX)NA
Air Filter G33243139500 V
Heat Exchanger160W/K
50400000196V
Model NameSpare parts(Delta P/N)
BRS2216 Outdoor Power System
20
SMR Shelf 19” H type
SB-05N/HG A DPS 2700 shelf 54V/150A
W x H x D=19 x 1.7 x 11.7 inch =483 x 44 x 297.8 mm
BRS2216 Outdoor Power System
21
Features and Benefits-48V/41.7A, Output; Max. Power 2000W
Wide Input Voltage Range (90V~300V)
Power Factor Correction (>0.99)
Hot-pluggable, All Connectors are at the rear
Compact Size
≅ 24W/in3 (48V) Power Density
Dimension:42mm/1U(H)*125.5mm/2.8U(W)*268mm(D)
Light weight:1.64 Kg (4.4lb)
Horizontal(1U)/Vertical(2.8U) Models Available
High Efficiency: >91% (48V)
Fan cooling and Easy replaceable fan design
Operation temp.:-5oC~+65oC
UL/CUL,TUV/CE Certificated
DP 2000 Series Rectifier
BRS2216 Outdoor Power System
22
Rectifier - Interface
I/O ConnectorOutputSignalInput
Load Sharing Bus IBUSD2
ID digitalIDDD1
ID analogIDAC2
Short pin for well connectionINHC1
Communication groundCGNDB1
RS 485 + communicationRS485+A2
RS 485 – communicationRS485-B2
Signal ground SGNDOA1
DC Output “+”VO+P8-P10
DC Output “-”VO-P5-P7
Precharge VOPP4
DescriptionSignal Pin Number
AC main, frame groundFGP3
AC main, N terminalAC_NP2
AC main, L terminal AC_LP1
DescriptionSignal Pin Number
BRS2216 Outdoor Power System
23
RS-485
New Smart CSU: DPS 2700 Series
Configuration,Supervision Terminal Interface
Web/SNMP Card
Ethernet
Configuration,Supervision
(web browser)
54Vdc/50A With SMR
AnalogSignal Detection
LCD Display
RS-485 X 3 With SMR
RS-485 With SMR
AnalogI.D address
BRS2216 Outdoor Power System
24
Easy integration with most Delta power systemsModular system controllerUser friendly operating interface
Large 128 x 64 pixel LCD Display Entry of alarm and system parameters from keypad
High reliable RS-485 communication with RectifierEasy system expansion
Easy extendable custom-design I/O boardComplete function support
More then 100 system events logTemperature & Voltage compensation chargingSmart Battery managementGreen Function
Different possibilities for remote monitoring1 outside communication port (Mini USB) DB9Local Access monitoring & ControlWeb Server Function (RJ-45)
Power System Controller – New Smart CSU
User Interface
BRS2216 Outdoor Power System
25
Delta Power System Monitoring & Control
Build in HTTP Web Server
AC Distribution Rectifiers
DC Distribution Battery Management
Environment Data
Acquisition
Control &Supervisory
Unit
Client User Client User
Internet
Telecom Power Manage Program
Local
Client User
Mini USB
BRS2216 Outdoor Power System
26
Local Access
Mini USB
NRMS Monitor software
BRS2216 Outdoor Power System
27
Web Server Function and Feature (Optional)Features:
Applied in TCP/IP Internet/Intranet Environment
Complete Supervising to Power System
User-friendly Graphic Interface
Dynamic information presentation
Password function
Multi Language Support
Microsoft Explorer and Netscape SupportMain Screen
StatusParameter Setting
Alarm Configuration
BRS2216 Outdoor Power System
28
Q & A