Universal Measuring Device
UMG 96LOperating InstructionsBrief instructions see last page
D
Minimum value
Programming modeSum measurementPhase to phase
PasswordVoltage transformerCurrent transformer
Key 1 Key 2
Mean valueSupply
Peak value
ww
w.jan
itza.
de
Dok N
r.
1.03
1.01
4.8
Art.
Nr.
33.03
.05
3
Janitza electronics GmbHVor dem Polstck 1D-35633 LahnauSupport Tel. (0 64 41) 9642-22Fax (0 64 41) 9642-30e-mail: info@janitza.deInternet: http://www.janitza.de
w
Page 2
All rights reserved. No part of this manual maybe reproduced or duplicated without the writtenpermission of the author. Any contraventionsare punishable and will be prosecuted with alllegal means.No liability can be taken for the faultless condi-tion of the manual or damage caused by theuse of it. As failures cannot be avoided com-pletely, we shall be very grateful for any advice.We are anxious to remove all failures as soonas possible. The mentioned software and hard-ware descriptions are registered trademarks inthe most cases and are subject to the regula-tions by law. All registered trademarks are prop-erty of the corresponding companies and arefully recognized by us.
Issue Note13.01.04 First Edition.15.04.04 Measurement uncertainly.27.03.06 Page 10/12 marking voltage
measurement.11.01.07 Page 9, Abb.5, 6 and 8 been
cancelled.12.04.07 Storage temperature -25C.
Table of contentsThe meaning of symbols 3Hints for the user 3Receipt control 3
Contents of delivery 3Hints for maintenance 4
Service 4Product description 5
Intended use 5Functional description 5
Installation 6Mounting place 6Measuring and operating voltage 6Current measurement 7Sum current measurement 7Connecting options 8
Putting into service 10Installation 10Attach measuring and operating voltage 10Connect measuring current 11Check phase assignment 11Check current direction 11Check measurement 11Check phase power 11Check sum power 11
Elimination of errors 12Error messages 13
Usage and indication 14Indication mode 14Programming mode 14Key functions 15Table, measured value indication 16Current transformer 18Voltage transformer 19Averaging times 20Measured value indication 21
Measured value rotation time 21Measured value selection 22Delete minimum and maximum values 23Delete energy 23Working hours counter 24LCD contrast 24Software Release 25User password 25
Uncertainty of measurement 26Configuration data 28Declaration of conformity 29
Safety guidelines 29Test voltage 29EMC requirements 29
Technical data 30Ambient conditions 30Measurement 30Connectable cables 30Dimensions 31Connection example 31
Brief instructions 32Change current transformer ratio 32Call up measured values 32
Page 3
m
Beware of dangerous electrical voltage.
This symbol shall warn you about possi-ble danger, which can occur during instal-lation, putting into service and usage.
The meaning of symbolsThe symbols, which are used in this manual,have the following meaning:
c
Hints for the userThis device may be inserted and used by quali-fied personnel only according to the safetyregulations. Please follow the legal and safetyregulations for the corresponding applicationwhile using the device.Qualified personnel are persons, who are famil-iar with installation, mounting, putting into serv-ice and operation of the product and have quali-fications according to their occupation, for ex-ample:- Education or instruction resp. the right toswitch on or off, ground or characterize currentcircuits or devices according to the standardsof safety techniques.- Education or instruction in care and use ofsafety equipment according to the standardsafety techniques.
m Attention!If the device is not used according to thismanual, a safe use cannot be granted,and the instrument might cause danger.
c Attention!If a UMG 96L is installed in panels ofmetal, the panel must be earthed.
Receipt controlIn order to ensure a perfect and safe use of thedevice, a proper transport, expert storage, erec-tion and mounting and careful usage and main-tenance is required. In case that a safe opera-tion can no longer be granted, the device hasto be put out of service and has to be protectedagainst unintentional putting into service.A safe operation can no longer be assumed, ifthe device shows visible damage, does not work in spite of intact net supply, has been exposed to disadvantageous condi-tions for a longer time (e.g. storage beyond al-lowed climate without adaption to the room cli-mate, dew etc.) or transport use (e.g. fallingfrom great height, even without visible dam-age).
Please test the contents of delivery for comple-tion, before starting the installation of the de-vice.
Contents of delivery1 pc. UMG96L,2 pcs. fixing brackets,1 pc. manual.As an option, a seal with part no. 29.01.907 canbe delivered.
All delivered options and versions are listed onthe delivery papers.
This manual also describes options,which have not been delivered and donot belong to the contents of delivery.
m
Page 4
ServiceIf there are questions, which are not describedin this manual, please contact us directly.For an efficient handling we need the followinginformation:
- Description of device (see type plate),- Serial digit (see type plate),- Software Release,- Measuring and operating voltage and- detailed description of error.
You can reach us:Monday until Thursday
between 07:00 and 15:00and Friday
between 07:00 and 12:00
Janitza electronics GmbHVor dem Polstck 1D-35633 LahnauSupport: Tel. (0 64 41) 9642-22Fax (0 64 41) 9642-30e-mail: info@janitza.deInternet: http://www.janitza.de
Hints for maintenanceBefore delivery the device is tested in varioussafety checks and marked with a seal. If thedevice is opened, these checks must be re-peated.For instruments, which are opened outside themanufacturing works, no warranty is grantedwhatsoever.
Repairing and calibrationRepairing and calibration work can be carriedout in the manufacturing works only.Front foilThe cleaning of the front foil has to be effectedwith a soft cloth using a common cleansingagent. Acid or acidic agents are not allowed forcleaning.
Waste managementThe UMG96L can be disposed and recycled aselectronical waste according to the legal regu-lations.
Page 5
Functional descriptionThe electronical three phase measurementsystem determines and digitalizes the effectivevalues of voltages and currents in 50/60 Hz net-works.The operating voltage for operation of UMG96Lis generated by the measuring voltage L1-N. Arandom test measurement is carried out eachsecond at all current and voltage inputs. Meas-uring signal interruptions, which last longer thanone second are safely recognized.For each random test one period is scanned.From those sampled values the microproces-sor calculates the electric quantities. Thesemeasured values are indicated within the pro-grammable display. The energy as well as theminimum and maximum values are storedevery 15 minutes whereas the programmeddata are stored immedately is a none volatilememory (EEPROM).The scanning frequency for all measuring in-puts is calculated from the net frequency ofphase 1. At a net frequency of 50Hz the scan-ning frequency is 2,5kHz and for 60Hz it is3,0kHz.
Diagr. Generation of the operating voltage frommeasurement voltage.
Product descriptionIntended useThe UMG96L is suitable for fix mounting andthe measurement of voltage, current, poweretc. in low voltage switchgear. The measure-ment is designed for 3 phase systems with neu-tral conductor (TN and TT-mains).The UMG96L is suitable for mounting in fix andweather protected panels. Conducting panelsmust be earthed.Due to the high resistance against interference,the UMG 96L is suitable for continous and un-supervised operation.
As the UMG96L receives its power from phaseL1 of the measuring voltage, at least phase L1and the neutral conductor N must be con-nected.The attached voltage must be within the rangeof the measuring and operation voltage shownon type plate.Either ../5A or ../1A current transformers can beconnected to the current measuring inputs.The connection of the measuring and operat-ing voltage is carried out on the back side ofthe UMG96L via all-insulated spring powerclamps.
The measuring and operating voltages must beconnected to the UMG 96L via a separation(switch or power switch) and an overcurrentprotection fuse (2-10A) in the building installa-tion. The separation (switch or power switch)must be near the UMG 96L and easily accessi-ble.
UMG96L
Generation of oper-ating voltage
L2
L3
N
L1
PE
Voltage measurement
3M 3M 3M
Page 6
InstallationMounting placeThe UMG96L is suitable for a fix insertion intolow and medium voltage switchgear. Anymounting position is possible.Measuring and operating voltageThe operating voltage of the UMG96L is gener-ated by the measuring voltage. The measure-ment is designed for three phase systems withneutral conductor (TN and TT mains). Themeasuring and operating voltages must be con-nected to the UMG 96L via a separation (switchor power switch) and an overcurrent protection(2-10A) within the building installation.The con-nection of the measuring and operatingvoltages is carried out at the back side of theUMG 96L via shock protected spring clamps.
230V/400V Standard versionPhase L1 and the neutral conductor N must beconnected, and the attached voltage must bewithin the range of the measuring and operat-ing voltage.
120V/220V Special versionPhase L1 and the neutral conductor N must beconnected, and the attached voltage must bewithin the range of the measuring and operat-ing voltage.
60V/110V Special versionPhase L1 and the neutral conductor N must beconnected, and the attached voltage must bewithin the range of the measuring and operat-ing voltage.
Attention!Before the device is connected to volta-ge for the first time, it should be depos-ited the installation room for at least 2hours, to create a temperature assimila-tion and avoid condensation and dew.
Attention!The limits indicated in the technical datamay not be exceeded, not even whilechecking and putting into service of theUMG 96L.
- The connection wires for the operating volta-ge leading to the UMG96L must be suitable forvoltages up to 300V against ground.
- The measuring and operating voltage has tobe protected by a fuse, which must be in therange of 2A to 10A.
- A switch or power switch for the operating vol-tage must be provided within the building instal-lation.
- The switch has to be near the instrument andeasily accessible.
- The switch must be marked as separation forthis instrument.
cc
Page 7
Sum current measurementIf the current measurement is carried out viatwo current transformers, the total transformerratio must be set to the UMG96L.
Example: Sum current transformerA current measurement is carried out via onecurrent transformer with a ratio of 1000/5A andanother one with a ratio of 200/5A. The summeasurement is carried out with a sum trans-former 5+5/5A.The UMG96L has to be programmed as fol-lows:
Primary current: 1000A + 200A = 1200ASecondary current: 5A
Current measurementThe current measurement is carried out via ../5A or ../1A current transformers. In case thatthe current has to be measured by an Ampere-meter in addition to the UMG96L, the Ampere-meter has to be connected in series to theUMG96L.In mains with voltage up to 300VAC againstground, currents up to 5A can be connectedand measured directly to the UMG 96L.
Attention!Current transformers may not be han-dled in open condition of the secondary,as the secondary clamps can lead livevoltage.
Attention!Prior to connecting or exchanging theUMG 96L, the secondary clamps of theexternal current transformers have to beshort circuited.
Diagr. Connection example: UMG96L withAmperemeter in series.
c
c
Attention!The program allows current and voltagetransformer ratio setting only, if the maxi-mum phase power can reach up to50.0MW and the sum power can reach amaximum value of 150.0MW.
L l
K kA
l
k
UMG96L
VerbraucherConsumer
EinspeisungSupply Verbraucher 1
Consumer 1Verbraucher 1 Consumer 1
Einspeisung 1 Supply 1
Einspeisung 1 Supply 1
UMG96L
L l
K k
L l
K kAK AL
K l
k l
BK BlInaccuracyThe inaccuracy of the current measuring inputis +- 1% of the measuring range (5A). There-fore, the inaccuracy of the current measure-ment is +-50mA.Example: InaccuracyWith a current transformer 200/5A, the meas-uring range is 200A. The inaccuracy is +-1% of200A = +-2A.
ResolutionThe maximum resolution of the current meas-uring inputs is 10mA. The indication changesin 0.01A steps.Example: Resolution current transformer 200/5AWith a current transformer ratio of 200/5A, aresolution of 10mA*40 = 400mA is effected.The display changes in 0.4A steps.
Small currentsThe minimum working current is 20mA. At shortcircuited or open current measurement input,the UMG 96L can indicate a small current. Thiscurrent is within the range of the allowed meas-urement inaccuracy.
m
Page 8
Diagr.: Connection example 4Measurement with three voltage transformersand two current transformers.
Connecting options
Diagr.: Connection example 1Four wire measurement with three currenttransformers
Diagr: Connection example 2. Four wire meas-urement with two current transformers.
Diagr.: Connection example 3Measurement with three voltage transformersand three current transformers.
UMG96LVoltage Measure-
mentsee type plate
Currentmeasurement
0,02 .. 5A
L1 L2 L3 N
Verb
rau
che
rCo
nsu
mer
k l
k l../5(1)A
../5(1)A
L1L2L3PEN
1k 1l 2k 2l 3k 3l
1 2 3 4 5 6 7 8 9 10
UMG96LVoltage Measure-
mentsee type plate
Currentmeasurement
0,02 .. 5A
L1 L2 L3 N
Verb
rau
che
rCo
nsu
mer
k lk l
k l../5(1)A
../5(1)A../5(1)A
L1L2L3PEN
1k 1l 2k 2l 3k 3l
1 2 3 4 5 6 7 8 9 10
x x
UMG96LVoltage Measure-
mentsee type plate
Currentmeasurement
0,02 .. 5A
L1 L2 L3 N
u u u
U U U
x
X X X
Verb
rau
che
rCo
nsu
mer
k lk l
k l../5(1)A
../5(1)A../5(1)A
L1L2L3PEN
1k 1l 2k 2l 3k 3l
1 2 3 4 5 6 7 8 9 10
xx
UMG96LVoltage Measure-
mentsee type plate
Currentmeasurement
0,02 .. 5A
L1 L2 L3 N
u u u
U U U
x
X X X
Verb
rau
che
rCo
nsu
mer
k l
k l../5(1)A
../5(1)A
L1L2L3PEN
1k 1l 2k 2l 3k 3l
1 2 3 4 5 6 7 8 9 10
Page 9
Diagr.: Connection example 7Measurement in IT networks via three currenttransformers.
Verb
rau
che
rCo
nsu
mer
k lk l
k l../5(1)A
../5(1)A../5(1)A
L1L2L3N
UMG96LVoltage Measure-
mentsee type plate
Currentmeasurement
0,02 .. 5A
L1 L2 L3 N 1k 1l 2k 2l 3k 3l
1 2 3 4 5 6 7 8 9 10
PE
Page 10
Putting into serviceThe putting into service of the UMG 96L shouldbe carried out as follows:
InstallationThe UMG96L is designed for mounting in lowvoltage distributions, which contain overvoltagein measurement category III. The UMG96L issuitable for installation in fixed and weatherproof panels. Conducting panels must beearthed. Any mounting position is possible. Formounting on front panels or doors, the deliv-ered fixing brackets have to be used.
Program current and voltage transformersWhen the device leaves the manufacturer, acurrent transformer of 5/5A is set.The set voltage transformer ratio has to bechanged only, if a voltage transformer is con-nected.When connecting voltage transformers, pleaseobserve the allowed measuring and operatingvoltage stated on type plate!
Attach measuring and operating voltageThe allowed measuring and operating voltageof UMG 96L is indicated on the type plate.
c
The connection wires for measuring voltageleading to the UMG96L must be suitable forvoltages up to 300V against ground and 520Vphase to phase.After connecting the stated measuring and op-erating voltage to the UMG 96L, all segmentsof the display appear. After approx. two sec-onds, the UMG 96L switches to the first meas-ured value indication.In case that no indication appears, pleasecheck, if the attached operating voltage iswithin the rated voltage range.
Attention!Mesuring and operating voltage, whichdo not correspond to the indication onthe type plate, can lead to malfunctionand damage of the instrument.
Strommessung/Current Measurement
k lL2 L3L1
k lk l
5 7 108 96
SpannungsmessungVoltage Measurement
2 1
L1
4
N
3
L3 L2
UMG
96L
45-65
Hz
IP
202,
5VA
Made
in
G
erm
any
S V
J
M
A
D
E
P
m
2-10A
Diagr. Side view42 6
90 96
Fixing brack-ets
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
Panel max. 6
Page 11
Check measurementProvided that all voltage and current inputs areconnected correctly, the phase and sum poweris calculated and displayed correctly.
Check phase powerIn case that a current transformer is assignedto the wrong outer conductor, the correspond-ing power is measured and indicated incor-rectly.The assignment of the outer conductor and cur-rent transformer is correct, if no voltage ismeasured between the outer conductor and theprimary of the corresponding current trans-former.To ensure that the outer conductor at the volta-ge input is assigned to the right current trans-former, please short circuit the secondary of thecorresponding current transformer. The appar-ent power of this phase at UMG 96L must beindicated by zero.
If the apparent power is indicated correctly, butthe real power has a - sign, the current trans-former clamps are interchanged, or power issupplied to the energy supplier.
Check sum powerProvided that all voltage, current and power inthe corresponding phase is indicated correctly,the sum power must be displayed correctly byUMG 96L either.For verification, the sum power measured byUMG96L should be compared to the energystated by the real and reactive energy countersof the supplier.
Connect measuring currentThe UMG96L is designed for the connection of../1A and ../5A current transformers. With thecurrent inputs, only alternating current but nodirect current can be measured.
Check current directionShort circuit two current transformers on thesecondary. The real power in the connectedphase has to be:Positive (+) for consumption of real power andnegative (-) for supply of real power (power sta-tion service).In case that no real power is indicated, the as-signment of voltages and currents may bewrong.
Check phase assignmentThe assignment of the outer conductors to thecurrent transformer is correct, if a current trans-former is short circuited on the secondary, andthe indicated current in the correspondingphase decreases to a value at the UMG96L,which corresponds to the secondary currentplus tolerance.
Attention!Current transformers may not be han-dled in open condition, as there might belive voltage at the secondaries.
Please connect the current inputs one after theother, and compare the indicated current of thedisplay with the actual current. Please note,that the current transformer ratio is set to 5/5Aand has to be adapted to the existing currenttransformers.In case that the current transformer is shortcircuited on the secondary, the indicated cur-rent at the corresponding conductor at UMG96L has to decrease to a value, that corre-sponds to the secondary current plus tolerance.The current indicated by UMG 96L, has to con-form to the input current, under considerationof the current transformer and tolerance.
c
Strommessung/Current Measurement
k lL2 L3L1
k lk l
5 7 108 96
SpannungsmessungVoltage Measurement
2 1
L1
4
N
3
L3 L2
UMG
96L
45-65
Hz
IP
202,
5VA
Made
in
G
erm
any
S V
J
M
A
D
E
P
m
2-10A
Page 12
Elimination of errors
Error
Display dark.
Measured value can-not be called up.
No current indication.
Current too small.
Current incorrect.
Voltage L-N incor-rect.
Voltage L-L too small/ too high.
Reason
Prefuse released.Device defective.
The indication has been de-leted from measured value se-lection.
Corresponding voltage is notconnected.
Current measurement in wrongphase
Current measurement in wrongphaseCurrent transformer pro-grammed incorrectly.Measuring range exceeded.
The current peak at measuringinput was exceeded caused byharmonic waves.
The current at measuring inputwas below measuring range.
Measurement in wrong phase.
Voltage transformer ratio pro-grammed incorrectly.
Phase conductors inter-changed.
N not connected.
Voltage transformer ratio pro-grammed incorrectly.
Elimination
Insert fuse.Send the device to the producer for repair.
Add the required measured value indica-tion to the measured value selection.
Connect corresponding voltage.
Check and correct connection.
Check and correct connection.
Read ratio of current transformer and pro-gram accordingly.Insert a current transformer with a higherratio.
Insert a current transformer with a higherratio.Attention! Please ensure, that the meas-uring inputs are not overloaded.Insert a current transformer with a smallerratio.Check and correct connection.
Check and correct connection.
Read the voltage transformer ratio at thevoltage transformer and program accord-ingly.
Check and correct connection.
Check and correct connection.
Read voltage transformer ratio at the vol-tage transformer and program accord-ingly.
Page 13
Error
Phase shift ind/cap.
Programmed dataget lost.
Real power too small/ too high.
Real power supply /consumption inter-changed.
Err in display.
The device does notoperate in spite ofthe above.
Reason
Current path is assigned to thewrong voltage path.
The device was exposed toelectro magnetical distur-bance, which was higher thanthose mentioned in the techni-cal data.
Current transformer ratio isprogrammed incorrectly.Current path is assigned to thewrong voltage path.
At least one current trans-former connection is inter-changed.Current path is assigned to thewrong voltage path.
See error messages
Device defective.
Elimination
Check and correct connection.
Improve external protection measuressuch as protection, filtering, earthing andlocal separation.
Read current transformer ratio and pro-gram accordingly.Check and correct connection.
Check and correct connection.
Check and correct connection.
Please send the device back to the pro-ducer with a detailed description of theerror.
Error messagesWhile exceeding an allowed measured valuerange, the UMG 96L indicates the error mes-sage Err.An exceeding of a measured value rangearises, if at least one of the three existing cur-rent or voltage inputs or the frequency is out ofthe specified measuring range.The symbols "V", "A" and Hz indicate, whichmeasured value is out of range.The phase is marked by the arrows upwards inwhich the exceeding occured.
m Attention!Voltage and current beyond the specifi-cations may destroy the device.
Exceeding of measuringrange in phase L1/L2/L3
A = Current pathV = Voltage pathHz = Frequency
L1
L2
L3
Hz
VA
Page 14
Usage and indicationThe usage of the UMG96L is carried out via thekeys one and two. Measured values and pro-gramming data are indicated on the liquid crys-tal display. You must distinguish between
Indication mode andProgramming mode.
By entering a password, you can avoid uninten-tional change of programming data.
Indication modeIn indication mode please scroll through theprogrammed measured value indications byusing the keys 1 and 2. When the device is de-livered, you can call up all measured valuesshown in table 1. For each measured value in-dication, up to three measured values are indi-cated. The measured value rotation allows toindicate all selected measured values on an al-ternate basis with a selectable changing time.
Programming modeIn programming mode the settings, which arenecessary for the operation of the UMG96L,can be indicated and changed. Pressing thekeys 1 and 2 simultaneously for about 1 sec-ond, you reach programming mode via thepassword indication. If no user password is pro-grammed, you reach the first programmingmenu directly. The programming mode ismarked with the text PRG in the display.With key 2 you can shift between the program-ming menues.
If you are in the programming mode and nokeys are pressed for 60 seconds, or you pressthe keys 1 or 2 simultaneously for approx. 1second, you return to the indication mode.
Programming mode
Key 2Key1
1 2
capcosind
capcosind
capcosind
L1
L2
L3
Hz S
CT VT K1 K2
L-L
PRGMkWhMkVArh
Programming menus:- Current transformer,- Voltage transformer,- Averaging times, Measured value indications
- Changing time,- Measured value selection,- Measured value rotation,
- Delete minimum and peak values,- Delete energy,- LCD contrast,- Software Release,- User pasword.
Page 15
Key functions
21
2
21
simultaneous
long short1
simultaneous
long
shor
t
Measuredvalues
Program-ming menu
Measuredvalues
Measuredvalues
Measuredvalues
Program-ming menu
2
1 Confirm selection
short digit +1long digit -1
Program-ming menu
2 short value *10(decimal point to theright)
long value /10(decimal point to the left)
Indication mode Password Programming modeSc
roll
Progr
am
min
gCh
ange
m
ode
2
long
shor
t
Program-ming menu
2flashing
Page 16
Measured valuesL1 Apparent powerL2 Apparent powerL3 Apparent power
Mean valuesL1 Apparent powerL2 Apparent powerL3 Apparent power
Measured value sum
real power
Mean value sum
real power
Measured value sum
apparent power
Mean valuesum
apparent power
Maximum value(Consumption)
sumreal power, mean
Maximum value(Consumption)
sumreal power meas.
Maximum valuesL1 Apparent powerL2 Apparent powerL3 Apparent power
Maximum valuesum meas. valueapparent power
Maximum values L1-N Voltage L2-N Voltage L3-N Voltage
Minimum values L1-N Voltage L2-N Voltage L3-N Voltage
Maximum values L1 Real power L2 Real power L3 Real power
Minimum values L1 Real power L2 Real power L3 Real power
Measured values L1-L2 Voltage L2-L3 Voltage L3-L1 Voltage
Table, measured value indication
Mean valuesL1 CurrentL2 CurrentL3 Current
Maximum values L1 Current L2 Current L3 Current
Max. valuesL1 Curr. mean val.L2 Curr. mean val.L3 Curr. mean val.
Measured values L1-N Voltage L2-N Voltage L3-N Voltage
Measured valuesL1 CurrentL2 CurrentL3 Current
Measured value Current in N
Measured values L1 Real power L2 Real power L3 Real power
Mean values L1 Real power L2 Real power L3 Real power
Maximum valuesL1 Real powerL2 Real powerL3 Real power
Mean value Current in N
Maximum value Measured value
current in N
Maximum values Mean value
current in N
Page 17
Mean valuesL1 Reactive powerL2 Reactive powerL3 Reactive power
Measured values L1 Reactive power L2 Reactive power L3 Reactive power
Max. values (ind)L1 Reac. powerL2 Reac. powerL3 Reac. power
Measured valueSum
reactive power
Mean value Sum
reactive power
Max. value (ind)Sum
reactive power
Measured value L1 cos(phi) L2 cos(phi) L3 cos(phi)
Measured valueSum
cos(phi)
Measured value L1 Frequency
Measured value(Consumption)
Sumreal energy
Measured valueSum
reactive energy(ind)
Working hourscounter
Page 18
Current transformerCurrent transformers with either 1A or 5A sec-ondary can be connected to the UMG96L.A transformer ratio of 5A/5A is preset by themanufacturer. In programming mode the cur-rent transformer setting is marked by the sym-bol CT.
ProgrammingIn programming mode please scroll to the cur-rent transformer ratio by pressing key 2. Con-firm the selection by pressing key 1.The first digit of the primary current flashes andcan be changed by pressing key 2.If key 1 pressed again the next digit will be se-lected and flashes now.If the entire digit flashes, the decimal point canbe moved.Press key 2 shortly - The decimal point movesto the right.Press key 2 longer - The decimal point movesto the left.If no digit flashes anymore, you can shift to theindication of the voltage transformer.
Primary (5.00kA = 5000A)
Secondary Currenttransformersymbol
PRG
k AL1
L2
L3 CT
Example: Sum current transformerA current measurement is carried out via twocurrent transformers, one with a ratio of 1000/5A and another transformer with a ratio of 200/5A. The sum measurement is carried out witha sum current transformer 5+5/5A.The UMG96L has to be programmed with thefollowing values:
Primary current: 1000A + 200A = 1200ASecondary current: 5A
m Attention!The program allows current and voltagetransformer ratio setting only, if the maxi-mum phase power can reach up to50.0MW and the sum power can reach amaximum value of 150.0MW.
Page 19
Voltage transformerThe phase to phase voltage (L-L) is indicatedon display of the UMG 96L as secondary andprimary voltage. The transformer ratio is calcu-lated from the programmed primary and sec-ondary voltage. In programming mode, the vol-tage transformer settings are marked by thesymbol VT.The standard version is preset by the manufac-turer with a ratio of 400V/400V.
The secondary voltage is always indicated inV. The corresponding symbol V is not dis-played.The primary voltage is indicated in V or kV.The corresponding symbol is displayed in Vor kV.
Primary voltage
Secondary voltagePhase to phaseVoltage transformer ratio
PRG
VL1
L2
L3 VT
L-L
m
UMG96L Setting range voltage transformerVersion Type plate L-L secondary L-L primary
Standard version 196 .. 255V 400V 100V .. 60kV (400V)Special version 90 .. 160V 200V, 220V 100V .. 60kV (200V)Special version 45 .. 80V 100V, 110V 100V .. 60kV (100V)
Secondary voltage is 100V
Primary voltage is 10,0kVProgrammingIn programming mode, please scroll to the vol-tage transformer setting by pressing key 2.Confirm selection with key 1.
The first digit of the primary voltage flashes andcan be changed by pressing key 2.If key 1 is pressed again the next digit will beselected and flashes.If the entire digit flashes, you can move thedecimal point.If no digit flashes anymore, you may shift to in-dication and programming of the outputs bypressing key 2.
Example: Voltage transformer ratio 100V/10kV
PRG
kVL1
L2
L3 VT
L-L
Attention!The program allows current and voltagetransformer ratio setting only, if the maxi-mum phase power can reach up to50.0MW and the sum power can reach amaximum value of 150.0MW.
Page 20
Averaging timesA mean value is calculated for the most at thecurrent and power values. A common averag-ing time for the current measured values L1,L2, L3 and N , as well as one for power meas-ured values, real power, apparent power and re-active power is programmable.
Presettings:Averaging time of currents = 900 secondsAveraging time of power = 900 seconds
The following averaging times are selectable: 5, 10, 30, 60, 300, 480, 900 seconds
Programming of averaging time
Averaging time for real powerIn programming mode please scroll to the av-eraging time for power with key 2. Confirm se-lection by pressing key 1.
The averaging time flashes and can bechanged by pressing key 2. Confirm changedaveraging time with key 1.The averaging time stops flashing. The averag-ing time for power has been programmed.By using key 2 you can now shift to program-ming menu Averaging time for current.
Averaging time for CurrentsIn programming menu please scroll to the av-eraging time for currents. Confirm selection bypressing key 1.
The averaging time flashes and can bechanged by pressing key 2. Confirm changedaveraging time with key 1. The averaging timestops flashing. The averaging time for currentshas been programmed. By using key 2 you cannow shift to programming menu Rotation time.
Example for the averaging time of current meanvalue, here 30 seconds.
Example for the averaging time of real powermean value, here 900 seconds.
Method of taking the meanThe used exponential method reaches at least95% of the measured value after the set aver-aging time.
MEn = MEn-1 + (MA-MEn-1) / NMEn = indicated mean valueMA = measured valuen = consecutive digitN = digit of measured values, of witch
mean values shall be built.
L1
L2
L3
S
PRG W
PRGMkWhMkVArh
L1
L2
L3
S
PRG
A
Page 21
Measured value indicationOnce in a second all measured values are cal-culated and can be indicated on the display.Two methods are available for calling up themeasured value indications (see table 1).- The selection of measured value indicationsvia the keys 1 and 2, herein called measuredvalue selection.- The automatically rotating indications of se-lected measured value indications, hereincalled measured value rotation.
A measured value rotation time has be pro-grammed additionally for the measured valuerotation.
All mesured values for the measured value se-lection are preset by the manufactures. For theautomatic rotation nothing is preset by themanufacturer. The rotation time is preset with 0seconds.
ProgrammingIn programming mode please scroll to themenu measured value rotation, by using key 2.Confirm selection with key 1.
The first digit of the rotation time flashes andcan be changed by pressing key 2. By pressingkey 1 again the next digit will be selected andflashes.If no digit flashes anymore, you can shift to pro-gramming menu Measured value selection bypressing key 2.
PRGL1
L2
L3
S
Rotation time in seconds indicated
Measured value rotation timeBoth methods are available simultaneously.The measured value rotation is programmed, ifat least one measured value indication and onemeasured value rotation time bigger than 0seconds is programmed. If no key is pressedfor about 60 seconds, an automatical changeto rotation mode will be carried out, and all pro-grammed measured values will be indicatedone after the other.
Setting range of measured value rotation time:0 .. 250 seconds
If 0 seconds are programmed, no rotation willbe carried out. Nevertheless, measured valueindications which are not programmed in themeasured value selection, can be used formeasured value rotation.
Abb.
Page 22
PRGL1
L2
L3
ProgrammingIn programming mode please scroll to program-ming menu mesured value indication bypressing key 2.Confirm selection by pressing key 1.The first measured value indicated stated in ta-ble 1 (see page 16 and 17) occurs.A selection of the measured value indication iscarried out by pressing the keys quickly.Key 1 - Scroll to the right within the measured
value indications.Key 2 - Scroll downwards within the measured
value indications.
For the selected measured value indication, itcan now be determined whether it will be avail-able for measured value selection and for auto-matic rotation.The selection is carried out by an extendedpush on keys 1 or 2.Key 1 - Measured value selection.Key 2 - Automatic rotation.
Once the programming is finished, you returnto indication mode by pressing keys 1 and 2 si-multaneously.
Measured value selectionAll measured values stated in table 1 (see page16 and 17) can either be displayed via keep 1and 2 measured value selection or automati-cally measured value rotation.All measured values for the measured valueselection are preset by the manufakturer. Forthe automatical measured value rotationnothing is preset by the manufakturer.The condition of the selection is indicated bythe output symbols. These symbols have thefollowing meaning:
PRG
AL1
L2
L3 K1 K2
Measured value selectionMeasured value rotation
Measured value indication ofthe current values
Measured value selectionK1 The indication can be reached via thekeys.K1 The indication cannot be reached via keys.
Measured value rotationK2 The indication changes automatically.K2 The indication does not change automati-cally.
Page 23
Delete energyThe real and reactive energy can only be de-leted together via the keys.
PRG WhL1
L2
L3
DeleteIn programming mode please scroll to themenu delete energy by using key 2.By pressing key 1 you can shift between digits0 and 1. These digits have the following mean-ing:0 = Real and reactive energy not to be deleted.1 = Real and reactive energy to be deleted.
Leave menu Delete energy by pressing key 2.In case that digit 1 was displayed real andreaktive energy were deleted.
Delete minimum and maximumvaluesIn programming mode, Deletion of minimumand maximum values is marked by arrows up-wards and downwards. All minimum and maxi-mum values will be deleted simultaneously inmenu Deletion of minimum and maximum val-ues.An exception is the maximum value of the cur-rent mean value. The maximum value of thecurrent mean value can also be deleted directlyin indication menu by an extended pressing ofkey 2.
DeleteIn programming mode please scroll to Deletionof minimum and maximum values by pressingkey 2.With key 1 you can shift between the indicateddigits 0 and 1. These digits have the followingmeaning:0 = Minimum and maximum values not to
be deleted.1 = Minimum and maximum values to be
deleted.
Leave menu Deletion of minimum and maxi-mum values by pressing key 2. In case thatdigit 1 was displayed, all minimum and maxi-mum values were deleted.
PRGL1
L2
L3
PRGL1
L2
L3
PRG WhL1
L2
L3
Page 24
Working hours counterThe working hours counter detects the time, inwhich the UMG96L measures and indicatesdata. The time is measured with a resolution of15 minutes and is indicated in hours. The work-ing hours counter cannot be deleted.
L1
L2
L3
h
Display example: The UMG96L indicates40201 working hours.
LCD contrastThe favoured view for the LCD display is frombelow. The LCD contrast of the LCD displaycan be adapted by the user. The contrast set-ting is possible in the range from 0 to 7.
0 = very light7 = very dark
ProgrammingIn programming mode please scroll to LCDcontrast by pressing key 2. Confirm selectionwith key 1.
The first digit of the contrast setting is flashing.Move to the right digit with key 1.Now you can change the digit with key 2.Afterwards you can shift to programming menuuser password by pressing key 2.
PRGL1
L2
L3
PRGL1
L2
L3
Page 25
User passwordA user password can be programmed in orderto avoid an unintentional change of program-ming data. Only after entering the correct pass-word, a shifting into the following programmingmenues possible.No user password by the manufacturer is pre-set (000). In this case, the password menu willbe skipped and you reach the current trans-former menu directly.
In case that a user password was programmed,a 000 appears in the display of the passwordmenu.The first digit of the password menu flashesand can be changed with key 2. By pressingkey 1, the next digit will be selected andflashes.Only after the correct password was entered,you reach the programming menu for the cur-rent transformer.In case that a changed password is not knownanymore, the device must be sent back to themanufacturer.
Software ReleaseThe internal software of the UMG96L will beimproved and extended continuously. The soft-ware update is registered in the device by aspecific number the so called software release.The software release cannot be changed by theuser.
User password
Example: In UMG96L, the software release1.23 is installed.
PRGL1
L2
L3
PRGL1
L2
L3
Page 26
m
Uncertainty of measurementQuantity Indicating range Measuring range1) Measurement
uncertainly2)
Auxiliary voltage5) 196..255VVoltage L-N 0 .. 34kV 50 .. 255V +-1,5% rngVoltage L-L 0 .. 60kV 87 .. 442V +-2,0% rngCurrent 0,00 .. 9,99kA 0,02 .. 6,00A +-1,0% rngCurrent in N 0,00 .. 9,99kA 0,06 .. 18,00A +-3,0% rngReal power, consumption, sum 0,00W .. 150MW 3,9W .. 3,825kW +-1,5% rngReal power, supply, sum -0,00W .. -150MW -3,9W .. -3,825kW +-1,5% rngApparent power, sum 0,00VA .. 150MVA 3,9VA .. 3,825kVA +-1,5% rngReactive power (Q0), sum 0,00var .. 150Mvar 3,9var .. 3,825kvar +-1,5% rng
Auxiliary voltage5) 90 .. 160VVoltage L-N 0 .. 34kV 25 .. 160V +-1,5% rngVoltage L-L 0 .. 60kV 45 .. 277V +-2,0% rngCurrent 0,00 .. 9,99kA 0,02 .. 6,00A +-1,0% rngCurrent in N 0,00 .. 9,99kA 0,06 .. 18,00A +-3,0% rngReal power, consumption, sum 0,00W .. 150MW 1,8W .. 2,4kW +-1,5% rngReal power, supply, sum -0,00W .. -150MW -1,8W .. -2,4kW +-1,5% rngApparent power, sum 0,00VA .. 150MVA 1,8VA .. 2,4kVA +-1,5% rngReactive power (Q0), sum 0,00var .. 150Mvar 1,8var .. 2,4kvar +-1,5% rng
Auxiliary voltage5) 45 .. 80VVoltage L-N 0 .. 34kV 16 .. 80V +-1,5% rngVoltage L-L 0 .. 60kV 28 .. 139V +-2,0% rngCurrent 0,00 .. 9,99kA 0,02 .. 6,00A +-1,0% rngCurrent in N 0,00 .. 9,99kA 0,06 .. 18,00A +-3,0% rngReal power, consumption, sum 0,00W .. 150MW 0,9W .. 1,2kW +-1,5% rngReal power, supply, sum -0,00W .. -150MW -0,9W .. -1,2kW +-1,5% rngApparent power, sum 0,00VA .. 150MVA 0,9VA .. 1,2kVA +-1,5% rngReactive power (Q0), sum 0,00var .. 150Mvar 0,9var .. 1,2kvar +-1,5% rng
cos(phi) 0,00i .. 1.00 .. 0,00c 3)Frequency (of voltage) 45,0 .. 65,0Hz +-1,5% rdgReactive energy, inductive v6) < 10 0..999 999 9.99kvarh class 24) v6) < 100 0..999 999 99.9kvarh class 24) v6) >= 100 0..999 999 999kvarh class 24)Real energy, consumption v6) < 10 0..999 999 9.99kWh class 24) v6) < 100 0..999 999 99.9kWh class 24) v6) >= 100 0..999 999 999kWh class 24)Working hours counter 0..999 999 999h +-2Min./Day
Attention!The program allows current and voltage transformer ratio setting only, if the maximum phasepower can reach up to 50.0MW and the sum power can reach a maximum value of150.0MW.
Page 27
These specifications presuppose a yearly calibration and a warm up time of 10 minutes.Used abbreviations:
rng = of measuring rangerdg = of measured value
1) Measuring range with scale factor = 1, (Current tranformer = 5/5A, 1/1A)
2) In the range of -10..18C and 28..55C, an additional error of +-0,5 of measured value has tobe considered per K.3) If the measured apparent power is in the range of 1% .. 100% of the measuring range, cos(phi)is indicated with an accuracy of +-3%.4)
Accuracy class according to DIN EN61036:2001-01, VDE0418part 7, IEC61036:1996 + A1:20005)
The auxiliary voltage is taken from the measuring voltage.6)
The maximum indication range and the resolution of real and reactive energy depends on Transformer ratio v = vi * vu.
vi = Transformer ratio of current transformer.vu = Transformer ratio of voltage transformer.
Example: 200/5A -> vi = 401000/100V -> vu = 10v = vi * vuv = 40 *10v = 400
1 10 100 400 v
999.999.999
210.000.000
21.000.000,0
2.100.000,00
Energy/kvarh /kWh
Transformer ratio v
Indication range and resolution forreal and reactive energy
Page 28
Configuration dataDescription Display Setting range Presettings
Current transf., primary CT 1A .. 10,0kA 5ACurrent transf., secondary CT 1A, 5A 5AVoltage transf., primary Type plate, 196 .. 255V VT 100V .. 60.0kV 400V Type plate, 90 .. 160V VT 100V .. 60.0kV 200V Type plate, 45 .. 80V VT 100V .. 60.0kV 100VVoltage transformer, sec. Type plate, 196.. 255V VT 400V (not changeable) 400V Type plate, 90 .. 160V VT 200V, 220V 200V Type plate, 45 .. 80V VT 100V, 110V 100VAveraging time, current 5, 10, .. 900Sec. 900Sec.Averaging time, power 5, 10, .. 900Sec. 900Sec.Measured value rotation 0 .. 250seconds 0 = no rotationMeasured value selection All indications all indicationsLCD contrast 0 .. 7 3Software Release not changeable x.xxUser passwort 000 .. 999 000 = no passwordWorking hours counter not changeable 0h
Page 29
Declaration of conformityThe UMG96L fulfills the protection guidelines of:Guideline 89/336/EWG in combination with DIN EN61326 (2002-03) as well asGuideline 73/23/EWG and 93/68/EWG in combination with EN 61010-1 (2002-08)
Safety guidelinesSafety requirements for electrical equipment for measurement, control, and laboratory usePart1: General requirements : EN61010-1:2001, IEC 61010-1:2001
Test voltageEnclosure against measuring inputs : 2kV ACBetween the inputs for measuring and auxiliary voltage and the current inputs exists a functionalseparation of 2000V AC.
EMC requirementsElectromagnetic emission : DIN EN61326:2002-03, table 4, class BElectromagnetic immunity : DIN EN61326:2002-03, table A.1 Enclosure : ESD test, IEC61000-4-2:2001 (4kV/8kV)
: Electromagnetic RF-field, IEC61000-4-3:2002 (10V/m): Netfrequent magnetic field, IEC61000-4-8:2000 (120A/m)
AC-power line : AC-Power variation and dropout, IEC61000-4-11:2000: Fast transients (Burst), IEC61000-4-4:2001 (2kV): Powerful pulse (Surge), IEC61000-4-5:2000 (1kV L- N): RF induced on lines, IEC61000-4-6:2000 (3V)
Current transformer inputs : Fast transients (Burst), IEC61000-4-4:2001 (2kV): Powerful pulse (Surge), IEC61000-4-5:2000 (1kV): RF induced on lines, IEC61000-4-6:2000 (3V)
Page 30
Weight : 250gCalorific value : 2,2MJ (610Wh)Ambient conditionsMeasurement category : III (Measurement within building installation)Pollution degree : 2Protection class : II = with protective earthAmbient temperature : -10C .. +55CStorage temperature : -25C .. +70CHumidity : 15% up to 95% without dewProtection class
Front : IP50 according to IEC60529Front with seal (Option) : IP65 according to IEC60529Back side : IP20 according to IEC60529
Mounting position : randomOperating height : 0 .. 2000m over sea level
MeasurementMeasuring inputs
Measuring rate : 1 measurement per secondRated pulse voltage : 4kVSignal frequency : 45Hz .. 1000HzScanning frequency : 2,5kHz/3,0kHz (Net frequency 50Hz/60Hz)
Measuring and operating voltage : see type plateFuse : 2A .. 10A (medium time lag type)Frequency of fundamental : 45Hz .. 65HzPower consumption Phase (L-N) : ca. 0,1VA per phase.230V/400V Standard version
operating voltage : 196 .. 255V ACRange : L-N 50V .. 255V, L-L 86V .. 442V
120V/220V Special versionoperating voltage : 90 .. 160V ACRange : L-N 25V .. 160V, L-L 45V .. 277V
60V/120V Special versionoperating voltage : 45 .. 80V ACRange : L-N 16V .. 80V, L-L 28V .. 139V
Current measurementPower consumption : approx. 0,2VARated current at ../5A (../1A) : 5A (1A)
Minimum working current : 20mACurrent limit at ../1A : 1,2A (sinus shape)Current limit at ../5A : 6A (sinus shape)
Overload : 150A for 2 Sec.Accuracy class of energy measurement : class 2
Connectable cablesOne wire, multiple-wire, fine wire : 0,08 - 2,5mm2Pin contacts : 1,5mm2, only one conductor may be connected
per terminal!
Technical data
Page 31
All dimensions in mm
DimensionsCut out: 92+0,8 x 92+0,8 mm
Diagr. Back view
Strommessung/Current Measurement
kl
L2 L3L1kl
kl
5 7 108 96
SpannungsmessungVoltage Measurement
2 1
L1
4
N
3
L3 L2
UMG
96L
45-65
Hz
IP
202,
5VA
Made
in
G
erm
any
S V
J
M
A
D
E
P
m
2-10A
Diagr. Side view42 6
90 96
Fixing angles
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
Panel max. 6
Diagr.: Connection example 1Four wire measurement with three current trans-formers.
Connection example
Type
pl
ate
UMG96LVoltage Measure-
mentsee type plate
Currentmeasurement
0,02 .. 5A
L1 L2 L3 N
Verb
rau
che
rCo
nsu
mer
k lk l
k l../5(1)A
../5(1)A../5(1)A
L1L2L3PEN
1k 1l 2k 2l 3k 3l
1 2 3 4 5 6 7 8 9 10
Page 32
Brief instructions
Change current transformer ratioShift to programming modeIf you are in the indication mode please press the keys 1 and2 simultaneously for approx. 1 second. Now you reach pro-gramming mode.The symbols for programming mode PRG and for the currenttransformer CT appear.Confirm selection with key 1.The first digit of the primary flashes.
Call up measured valuesShift to indication modeIf you are in programming mode please press the keys 1 and2 simultaneously for approx. 1 second. Now you reach the in-dication mode.The symbol PRG for programming mode does not appear inthe display and the first measured value indication, e.g. forthe voltage appears.
Key 2With key 2 you scroll between the different measured valueindications for current, voltage, power etc.
Key 1With key 1 you scroll between the mean values, maximumvalues etc., related to the corresponding measured value.
Change primary current:Change the flashing digit with key 2.Select the next digit to be changed by pressing key 1.The selected digit flashes.If the entire number flashes, the decimal point can bemoved.
Change secondary current:Only 1A or 5A can be set as secondary current.Select secondary current with key 1.Change flashing digit with key 2.
Leave programming mode:Press both keys simultaneously for approx. 1 second.The current transformer setting will be stored and you returnto indication mode.
VL1
L2
L3
1 2
Primary current
Secondary current 1 2
Current transformer symbol 1 2
Programming mode
PRG
k AL1
L2
L3 CT
PRG
k AL1
L2
L3 CT
Recommended