1. IMPORTANT NOTEThe present document reports the technical features of contractual work item and equipments. These technical features are used in the definition of price of works item as listed in the BoQ Work item list chapter. In particular the chapter 1.7. GENERAL AND PRELIMINARY of Particular Specifications (Drawing n3.4.3) page 14 state a general criterion that will allow the Contractor to chose any equipment or material present in the market that satisfy the contractual requests. It is important to notice that in the case of employment of specific products in the definition of the prices (so named PA items of Price Analysis list) the diction or equivalent was always used.
Particular Specifications for Electrical Works Rev. 01 2010Derby-E
Tender Documents Volume 3 Velipoje Sewerage Collection System and Waste Water Treatment Plant
PRETREATMENT UNIT
Technical specification
Derby-E
Particular Specifications Rev. 01 2010 Annexes
Sewage fine screeningThe equipment will be installed in channel with the following minimum technical features: - All made in stainless steel AISI 304; - Frame made in stainless steel and spiral in carbon steel - Spacing (circular hole) 3 mm; - Maximum inclination 45; - Channel width 600 mm; - Channel depth 1200 mm; - Discharge height from channel edge 1200 mm; - Axial total length 5600 mm; - Compaction rate 35% SS; - Maximum flowrate 317 m3/h (with ppm < 500 mg/l); - Screw conveyor diameter 200 mm; - Installed power 1.1 kW; international protection class IP55; insulation class F (Tmax=100C+ 15C); - Power supply 400V three-phase 50 Hz - Rubberized canvas side straps for holding the side walls of the channel; - Plates sliding screw conveyor in stainless steel Aisi 304; - Compaction zone consists of a cylinder, "Johnson profile with polyethylene pipe for the return of the liquid in the channel; - Dry pipe transport; - Dry pipe transport; - Dry compacted material; - bags in continued length 70 mt; - N 01 support foot telescopic; - Eyebolts for lifting.
Sand collector- Basin Diameter 2000 mm; - Diameter of dryers 100 DN; - Diameter turbine blades 1900 mm; - Rotational Speed 12 rpm; - Diameter Water connections 1" gas; - Diameter Water connections 1" gas; - Engine power 0,75 kW; - Utilization of carbon steel galvanized hot; - Bolting galvanized steel; - Gearmotor gear in oil bath; - Containment gear box - Plank thick; - Mixing paddles applied to the axis bearing; - Dryers tire "air lift" Aspiration sands decanted.
Sand selector- Stainless steel execution Aisi 304; - Helix carbon micro-alloyed steel; - Without central shaft propeller type; - Hopper capacity 0,7 mc; - Maximum Input Capacity 35 mc/h; - Screw length 4500 mm; - Tilting operating 25; - Nominal diameter auger 280 mm; - Thickness helix 20 mm; - Trough type Ad U; - Trough Diameter 325 mm; - Sliding Plates (n 04) 40 x 10 mm Stainless steel Aisi 304; - Overall length 4,7 m; - Overall Width max 1,85 m; - Cover lids bolted; - Inlet pipe DN 125 PN 10; - Water outlet pipe DN 200 PN 10; - Outfall N 01; - Outfall Vertical type; - Parallel shaft gearmotor type; - Gearmotor position side exhaust; - Gearmotor Model Nord Getreibe; - Installed power 0,25 kW - 400 V. - 50 Hz - IP55; - Screw rotation speed 5 rpm; - Coating wear plates bolted; - Rolling bolts A2; - Surface treatment with fiberglass; - Vent valve on the hopper; - n2 supporting foot carbon steel hot dip galvanized; - Lifting eyebolts; - Weirs internal profile thomson.
Tender Documents Volume 3 Velipoje Sewerage Collection System and Waste Water Treatment Plant
EQUALIZATION TANK EQUIPMENT
Technical specification
Derby-E
Particular Specifications Rev. 01 2010 Annexes
Multimicroprocessorcontrolunit Multimicroprocessorcontrolunitforthedeterminationoffreechlorine,pH,ORPpotentialand temperature,housedinasinglecontainer,IP55printedpolystyreneflameretardant,completewith4 digitaldisplaysfordisplayinginstantaneousmeasure;1displayalphanumeric(2x16)forprogramming. Withthefollowingmainfeatures: Switchboard: RS322serialoutput; Measuringcellwithflowregulator(60lt./h). Supplypressure+1bar(constant); Supply0220V50Hz.; MeasurementofChlorine(DPDphotometricmethod): Measurementrange0.002.00ppmofCl2; Resolution0.01ppmofCl2; Display3digitLED; nr.2setPOINTSconfigurableloadmax3A220V; Currentoutput0/420mAprogrammablebykeyboard; Frequencyanalysismin.3'max.60'programmablebykeyboard; Cumulativealarm,byrelay,repeatingondisplay,for:bulb,measuringcelldirty,exhaustedreagents,lackof water,exceedingthedelaytimeprogrammedforeachoftheSETPOINTS. MeasurementofpH(glasselectrodecombinedmonotube): MeasuringrangepH00.014.0; Resolution0.1pH; Display3digitLED; nr.2Setpointsconfiguredwithmax3A220V; Currentoutput0/420mAprogrammablebykeyboard; Frequencyanalysiscontinues; Cumulativealarm,byrelay,repeatingondisplay,lackofwater,exceedingthedelaytimeprogrammedfor eachoftheSetPoints. MeasurementofRedox(combinationelectrodemonotubeGold): Measurementrange999mV; Resolution1mV; Display3digitLED; Currentoutput0/420mAprogrammablebykeyboard; Frequencyanalysiscontinues; Temperature(NTC): Measuringrange050C; Resolution0.1C.; Display3digitLED; Currentoutput0/420mAprogrammablebykeyboard; Frequencyanalysiscontinues. Includingprobes,electrodes,mounting,electricalwiringandplumbingandeverythingelseneededtomake theworkcompleteandworkingtoperfectrulebook.
Conductivityanalyzermicroprocessor Conductivityanalyzermicroprocessorwiththefollowingcharacteristics: Rangeconfigurable:00:00to20:00mS,000to200mS,0000to2000mS,0020ms,000200ms; Accuracy+0.2%off.s.; NumericLCDDisplaywithinstantaneousmeasurement; AlphanumericBacklitLCDProgrammingDisplay; Automaticcalibration; Automaticormanualtemperaturecompensation(30...+130C); Planningbykeyboard:twosetpointswithhysteresis,cyclewashingoftheelectrode,Delaytime,limitsof theoutputcurrent,communicationparameters; Digitaloutputs:twooftheSETPOINTS,oneforactivationwashing,oneforalarm; Analogoutput,galvanicallyseparated,0/420mA(max750ohm); Powersupply0220V50Hz; ContainerAluminum; BoxFullcontainmentIP65transparentcover,fasteningpins,perforatedpanelandcoveredwithlexan gray; CellforconductivityThermocompensatedbodyPP1"andgraphiteelectrodes; ConstantK=1; CableS332(5meters)shielded4poles; Range050000mS; Temperature +140F (+60C). If the device is operated outdoors in strong sunlight, you should use a protective cover. -40 to +176F (-40C to +80C) to DIN EN 60068-2-14; Nb test : +80C/-40C, 1K/min, 100cycles
Storage temperature Resistance to alternating temperature cycles Climate class Ingress protection
DIN EN 60068-2-38 (Test Z/AD) DIN/IEC 68 T2-30Db With closed housing, tested according to IP 68, NEMA 6P (24h at 1.83m under water surface) IP 66, NEMA 4x With open housing: IP 20, NEMA 1 (also ingress protection of the display)
"Vibration resistance Electromagnetic compatibility (EMC)
Caution! Degree of protection IP 68 NEMA 6P applies for M12 PROFIBUS-PA plugs only when the PROFIBUS cable is plugged in. DIN EN 60068-2-64 / IEC 68-2-64: 20 to 2000 Hz, 1 (m/s2)2/Hz; 3 x 100 min Interference emission to EN 61326, Equipment Class B Interference immunity to EN 61326, Appendix A (Industrial) and NAMUR Recommendation NE 21 (EMC). A standard installation cable is sufficient if only the analogue signal is used. Use a shielded cable when working with a superimposed communication signal (HART).
Process conditionsProcess temperature -40 to +176F (-40C to +80C) A temperature sensor is integrated in the sensor for correction of the temperature-dependent time-of-flight. FMU 40/41: 10 to 44 psia (0.7 bar to 3bar abs.) FMU 42/43/44: 10 to 36 psia (0.7 bar to 2.5bar abs.)
Process pressure
19
Prosonic M
Mechanical constructionDesign; dimensions FMU40, FMU41
F12~3.4 (~86) 2.6 (65) 3.1 (78)
T122.7 (68) 3.7 (94)
2.6 (65) 1.3 (32)
3.1 (78)
ENDRESS+HAUSER Prosonic M
5.1 (129) 5.9 (150)
ENDRESS+HAUSER Prosonic M
5.1 (129) 6.4 (162)
3.3 (85)
3.3 (85)
FMU 40AF 60 1- NPT (G1) 0.9 (22) ~5.8 (148) ~3.4 (~87) AF 60 2 NPT G2
FMU 410.9 (22) ~5.8 (148)~3.3 (83)
1.5 (39)
1.9 (50)L00-FMU4xxxx-06-00-00-yy-006
Dimensions in inches (mm)
FMU42, FMU44 with slip-on flange
F12~3.4 (~86) 2.6 (65) 3.1 (78)
T122.7 (68) 3.7 (94)
2.6 (65) 1.3 (32)
3.1 (78)
ENDRESS+HAUSER Prosonic M
5.1 (129) 5.9 (150)
ENDRESS+HAUSER Prosonic M
5.1 (129) 6.4 (162)
3.3 (85)
3.3 (85)
FMU 42
FMU 44
3.3 (85)
~ 4.3 (110)
~ 4.2 (107)
~ 5.7 (145)
2.8 (70)
3.9 (98)L00-FMU4xxxx-06-00-00-yy-007
Dimensions in inches (mm)
20
Prosonic M
FMU42, FMU44 with mounting bracket
FMU 42
FMU 44
ENDRESS+HAUSER Prosonic M
ENDRESS+HAUSER Prosonic M
F12/ T12 M8
F12/ T12 M8
4.1 (105) 3.0 (75)
1.2 (30) 4.7 (119)
4.9 (125)
1.2 (30) 4.7 (119)L00-FMU4xxxx-06-00-00-yy-008
3.0 (75)
Dimensions in inches (mm)
FMU43
A~3.4 (86) 2.6 (65) 3.1 (78)
B
ENDRESS+HAUSER Prosonic M
5.1 (129) 5.9 (150)
HA ESS+ ENDR ic M Proson
USER
F12
2 x M8 3.3 (85)
~9.8 (248)
3.0 (75)
ANSI 4 (DN 100)
9.1 (230)
3.5 (89) 6.2 (158)L00-FMU4xxxx-06-00-00-yy-009
Dimensions in inches (mm); A: with slip-on flange; B: with mounting bracket
Mounting bracket for FMU42, FMU43 and FMU444.68" (119) 0.98" (25)
4.72" (120)
4.84" (123)
0.08" (2) 1.57" (40) 1.57" (40)
0.98" (25)
0.43" (11)L00-FMU4xxxx-06-00-00-yy-010
Dimensions in inches (mm)
21
Prosonic M
Flanges for FMU42 and FMU44E
A
B
D
0.79 (20)
G2 ISO228
CL00-FMU4xxxx-06-00-00-yy-011
suitable for 3" 150lbs / DN80 PN16 / 10K 80 4" 150 lbs / DN100 PN16 / 10K 100 6" 150 lbs / DN150 PN16 / 10 K 150 8" 150 lbs DN200 PN16 / 10 K 200
A 150 mm (5.91") 175 mm (6.90") 240 mm (9.45") 298.5 mm (11.75") 290 mm (11.42")
B 160 mm (6.30") 190.5 mm (7.50") 241.3 mm (9.50") 298.5 mm (11.75") 295 mm (11.61")
C 200 mm (7.87") 228.6 mm (9.00") 285 mm (11.22") 342.9 mm (13.50") 340 mm (13.39")
D 19 mm (0.75") 19 mm (0.75") 23 mm (0.91") 22.5 mm (0.89") 23 mm (0.91")
E 45 45 45 45 30
number of boreholes 8 8 8 8 12
Weight
Sensor FMU40 FMU41 FMU42 FMU43 FMU44
Weight approx. 5.5 lb (2.5 kg) approx. 6 lb (2.6 kg) approx. 6.6 lb (3 kg) approx. 8 lb (3.5 kg) approx. 9 lb (4 kg)
22
Prosonic M
Housing design
Types of housings F12 housing with sealed terminal compartment for standard or EEx ia (intrinsically safe) applications T12 housing with separate terminal compartment and explosion proof encapsulation Material Aluminum, seawater resistant, powder-coated Cover Aluminum, for version without local display Inspection glass for version with local display. This version cannot be supplied together with the ATEX II 1/ 2 D certificate.
Process connection, sealing material, sensor material
Sensor FMU40 FMU41 FMU42
Process connection Thread G 1 Thread NPT 1 - 11.5 Thread 2" Thread NPT 2" - 11.5 Universal flange DN 80 PN16 / ANSI 3" 150 lbs / JIS 10K 80 Universal flange DN 100 PN16 / ANSI 4" 150 lbs / JIS 10K 100 Mounting bracket Universal flange DN 100 / ANSI 4" / JIS16K100 Mounting bracket Universal flange DN 100 PN16 / ANSI 4" 150 lbs / JIS 10K 100 Universal flange DN 150 PN16 / ANSI 6" 150 lbs / JIS 10K 150 Universal flange DN200 PN16 / JIS 10K 200 Flange ANSI 8" 150 lbs Mounting bracket
Material in contact with process Sensor: PVDF Seal: EPDM Sensor: PVDF Seal: EPDM Sensor: PVDF Seal: VITON or EPDM Flange: PP, PVDF or SS 316L (1.4435 or 1.4404)1) Sensor: UP and SS 316Ti Seal: EPDM Flange: PP or SS 316Ti Sensor PVDF Seal: VITON or EPDM Flange: PP, PVDF or SS 316L (1.4435 or 1.4404)1
FMU43
FMU44
1)
Producer supplies DIN/EN flanges made of stainless steel AISI 316L with the material number 1.4435 or 1.4404. With regard to their temperature stability properties, the materials 1.4435 and 1.4404 are grouped under 13E0 in EN 1092-1 Tab. 18. The chemical composition of the two materials can be identical.
23
Prosonic M
Human interfaceDisplay and operating elements The LCD module VU 331 for display and operation is located beneath the housing cover. The measured value is legible through the glass in the cover. Open the cover to operate the device.LCD (liquid crystal display)
Order Code: Ser.-No.
IPTA >70C
65
: t >85C
Made in Germany
Maulburg
Messber Measurin eich g range U 16...36 max. 4...20 20 m mA V DC
ENDR MICR ESS+ OPILOHAUS : T II ER
Symbols
+
E
3 keys snap-fit
L00-FMxxxxxx-07-00-00-en-001
Symbol in display continuous Meaning Alarm flashing Warning Communication Security Locking
Function of the keysKey(s) Meaning
O or V S or W X or Z F O and F or S and F O and S and F
Navigate upwards in the selection list Edit numeric value within a function Navigate downwards in the selection list Edit numeric value within a function
Navigate to the left within a function group
Navigate to the right within a function group, confirmation.
Contrast settings of the LCD
Hardware lock / unlock After a hardware lock, an operation of the instrument via display or communication is not possible! The hardware can only be unlocked via the display. An unlock parameter must be entered to do so.
24
Prosonic M
Local operation
Operation with VU 331 The LC-Display VU 331 allows configuration via 3 keys directly at the instrument. All device functions can be set through a menu system. The menu consists of function groups and functions. Within a function, application parameters can be read or adjusted. The user is guided through a complete configuration procedure.Headline Position indicator
+
Symbol
Main value
Unit
E
Selection list
Function groups -> FunctionsHOME
XO SFG00 FG01 FG02 FG03 FG04 FG05 FG06 FG07 ...
F
F
X
FF000 F001 F002 F003 F004 ...
F
X
O S
XEnvelope curve
Help text
L00-FMU4xxxx-07-00-00-en-004
Operation with the handheld terminal DXR 375 On devices with HART communication, you can also access the menu using the handheld terminal DXR 375.
dsdmdm df das. asdas fa asas la.
dsdmdm df das. asdas fa asas la.
FMU42: LIC0001 ONLINE 1 GROUP SELECT 2 PV 8.7 m
FMU43: LIC0001 ONLINE 1 GROUP SELECTION 2 PV 8.7 m
Delete
HELP
SAVE
H
dsdmdm df das. asdas fa asas la.
9Bksp #%& Copy GHI
Page Up
6Delete
HELP
SAVE
FMU43: LIC0001 GROUP SELECTION 1 2 3 4 5 BASIC SETUP SAFETY SETTINGS TEMPERATURE LINEARIZATION EXTENDED CALIBR.
Delete
Page On
BkspDEF Hot Key MNO + Hot Key WXYZ
1 4 7 .
ABC Paste JKL Insert TUV
2 5 8 0
3 6 9 -
HSAVE HOME
dsdmdm df das. asdas fa asas la.
FMRU43: LIC0001 BASIC SETUP 1 2 3 4 5 MEASURED VALUE TANK SHAPE MEDIUM PROPERTY PROCESS COND. EMPTY CALIBR.
PQRS
Page Up Page On
,()
_
+*/
Bksp
FIELD COMMUNICATORSAVE HOME
375
L00-FMU4xxxx-07-00-00-de-005
25
Prosonic M
Remote operation
Operation with FieldCare FieldCare is producer's FDT based Plant Asset Management Tool. It can configure all intelligent field devices in your plant and supports you in managing them. By using status information, it also provides a simple but effective means of checking their health. Supports Ethernet, HART, PROFIBUS, FOUNDATION Fieldbus etc. Operates all Endress+Hauser devices Operates all third-party actuators, I/O systems and sensors supporting the FDT standard Ensures full functionality for all devices with DTMs Offers generic profile operation for any third-party fieldbus device that does not have a vendor DTM
Operation with Commuwin II (for communication variants HART or PROFIBUS-PA) Commuwin II is an operating software with graphical support (MS Windows) for intelligent transmitters with the communication protocols Rackbus, Rackbus RS-485, HART and PROFIBUS-PA. Commuwin II supports the following functions: Online configuration of transmitters Loading and saving of instrument data (Upload/Download) Orderly visualisation of measured values and limit values Display and recording of measured values with a line recorder It is not possible to display envelope curves with Commuwin II. To display them, please use the ToF Tool program supplied. Connections: HART with Commubox FXA 191 (available as accessory) PROFIBUS PA Operation with NI-FBUS Configurator (only Foundation Fieldbus) The NI-FBUS Configurator is an easy-to-use graphical environment for creating linkages, loops, and a schedule based on the fieldbus concepts. You can use the NI-FBUS Configurator to configure a fieldbus network as follows: Set block and device tags Set device addresses Create and edit function block control strategies (function block applications) Configure vendor-defined function and transducer blocks Create and edit schedules Read and write to function block control strategies (function block applications) Invoke Device Description (DD) methods Display DD menus Download a configuration Verify a configuration and compare it to a saved configuration Monitor a downloaded configuration Replace devices Save and print a configuration
Certificates and ApprovalsCE mark The measuring system meets the legal requirements of the EC-guidelines. Endress+Hauser confirms the instrument passing the required tests by attaching the CE-mark. The available certificates are listed in the ordering information. Note the associated safety instructions (XA) and control or installation drawings (ZD). EN 60529 Protection class of housing (IP-code) EN 61326 Electromagnetic compatibility (EMC requirements) NAMUR Standards committee for measurement and control in the chemical industry
Ex approval
External standards and guidelines
26
Prosonic M
Ordering informationProduct structure FMU 40Certificates A Variant for non-hazardous area E NEPSI Ex nA II T6 G ATEX II 3G EEx nA II T6 I NEPSI Ex ia IIC T6 J NEPSI Ex d(ia) IIC T6 K TIIS Ex ia II C T6 N CSA General Purpose Q NEPSI DIP S FM IS Cl. I,II,III Div. 1 Gr. A-G / NI Cl. I Div. 2 T FM XP Cl. I,II,III Div. 1 Gr. A-G U CSA IS Cl. I,II,III Div. 1 Gr. A-G / NI Cl. I Div. 2 V CSA XP Cl. I,II,III Div. 1 Gr. A-G 1 ATEX II 1/2 G or II 2 G; EEX ia IIC T6 2 ATEX II 1/2D, Alu blind cover 4 ATEX II 1/2 G or II 2 G; EEX d [ia] IIC T6 5 ATEX II 1/3D Y Special certificate Process connection R G 1 threadISO 228 N NPT 1 - 11,5 thread Y Special version Power supply/communication B 2 wire, 4...20mA-loop/HART H 4 wire, 10,5...32VDC / 4-20mA HART G 4 wire, 90...253VAC / 4-20mA HART D 2 wire, PROFIBUS PA F 2 wire, Foundation Fieldbus Y Special version Display / on-site operation 1 Without LC display 2 With LC display VU 331 incl. on-site operation 3 Prepared for remote display FHX 40 9 Special version Housing A Aluminum F12 housing coated to IP 68 C Aluminum T12 housing coated to IP 68; with separate terminal compartment D Aluminum T12 housing coated to IP 68; with separate terminal compartment; with overvoltage protection 9 Special version Screw union/entry 2 M20x1.5 screw union 3 G 1/2 entry 4 NPT 1/2 entry 5 M12 PROFIBUS-PA plug-in connector 6 7/8" FF plug 9 Special version FMU 40 Product designation
27
Prosonic M
Product structure FMU 41
Certificates A Variant for non-hazardous area E NEPSI Ex nA II T6 G ATEX II 3G EEx nA II T6 I NEPSI Ex ia IIC T6 J NEPSI Ex d(Ia) IIC T6 K TIIS Ex ia II C T6 N CSA General Purpose Q NEPSI DIP S FM IS Cl. I,II,III Div. 1 Gr. A-G / NI Cl. I Div. 2 T FM XP Cl. I,II,III Div. 1 Gr. A-G U CSA IS Cl. I,II,III Div. 1 Gr. A-G / NI Cl. I Div. 2 V CSA XP Cl. I,II,III Div. 1 Gr. A-G 1 ATEX II 1/2 G or II 2 G; EEX ia IIC T6 2 ATEX II 1/2D, Alu blind cover 4 ATEX II 1/2 G or II 2 G; EEX d [ia] IIC T6 5 ATEX II 1/3D Y Special certificate Process connection R G 2 threadISO 228 N NPT 2 - 11.5 thread Y Special version Power supply/communication B 2 wire, 4...20mA-loop/HART H 4 wire, 10.5...32VDC / 4-20mA HART G 4 wire, 90...253VAC / 4-20mA HART D 2 wire, PROFIBUS PA F 2 wire, Foundation Fieldbus Y Special version Display / on-site operation 1 Without LC display 2 With LC display VU 331 incl. on-site operation 3 Prepared for remote display FHX 40 9 Special version Housing A Aluminum F12 housing coated to IP 68 C Aluminum T12 housing coated to IP 68 with separate terminal compartment D Aluminum T12 housing coated to IP 68; with separate terminal compartment; with overvoltage protection 9 Special version Screw union/entry 2 M20x1.5 screw union 3 G 1/2 entry 4 NPT 1/2 entry 5 M12 PROFIBUS-PA plug-in connector 6 7/8" FF plug 9 Special version FMU 41 Product designation
28
Prosonic M
Product structure FMU 42
Certificates A Variant for non-hazardous area E NEPSI Ex nA II T6 G ATEX II 3G EEx nA II T6 I NEPSI Ex ia IIC T6 J NEPSI Ex d (Ia) IIC T6 K TIIS Ex ia II C T6 (in preparation) N CSA General Purpose Q NEPSI DIP S FM IS Cl. I,II,III Div. 1 Gr. A-G / NI Cl. I Div. 2 T FM XP Cl. I,II,III Div. 1 Gr. A-G U CSA IS Cl. I,II,III Div. 1 Gr. A-G / NI Cl. I Div. 2 V CSA XP Cl. I,II,III Div. 1 Gr. A-G 1 ATEX II 1/2 G EEX ia IIC T6 2 ATEX II 1/2 D, Alu bond cover 4 ATEX II 1/2 G EEX d [ia] IIC T6 5 ATEX II 1/3D Y Special certificate Process connection M Mounting bracket FAU20 P UNI flange 3"/DN80/80, PP, max. 2.5bar abs./ 36psia suitable for 3" 150lbs / DN80 PN16 / 10K 80 Q UNI flange 3"/DN80/80, PVDF, max. 2.5bar abs./ 36psia suitable for 3" 150lbs / DN80 PN16 / 10K 80 S UNI flange 3"/DN80/80, 316L, max. 2.5bar abs./ 36psia suitable for 3" 150lbs / DN80 PN16 / 10K 80 T UNI flange 4"/DN100/100, PP, max. 2.5bar abs./ 36psia suitable for 4" 150lbs / DN100 PN16 / 10K100 U UNI flange 4"/DN100/100, PVDF, max. 2.5bar abs./ 36psia suitable for 4" 150lbs / DN100 PN16 / 10K100 V UNI flange 4"/DN100/100, 316L, max. 2.5bar abs./ 36psia suitable for 4" 150lbs / DN100 PN16 / 10K100 Y Special version Power supply/communication B 2 wire, 4...20mA-loop/HART H 4 wire, 10.5...32VDC / 4-20mA HART G 4 wire, 90...253VAC / 4-20mA HART D 2 wire, PROFIBUS PA F 2 wire, Foundation Fieldbus Y Special version Display / on-site operation 1 Without LC display 2 With LC display VU 331 incl. on-site operation 3 Prepared for remote display FHX 40 9 Special version Housing A Aluminum F12 housing coated to IP 68 C Aluminum T12 housing coated to IP 68, with separate terminal compartment D Aluminum T 12 housing coated to IP 68, with separate terminal compartment; with overvoltage protection Y Special version Gland/Entry 2 M20x1.5 gland 3 G 1/2 entry 4 NPT 1/2 entry 5 M12 PROFIBUS-PA plug 6 7/8" FF plug 9 Special version Sealing Sensor/Flange 2 VITON flat sealing
29
Prosonic M
Sealing Sensor/Flange 3 EPDM flat sealing 9 special version Additional options A Additional options not selected FMU 42 Product designation
30
Prosonic M
Product structure FMU 43
Certificates A Variant for non-hazardous area M FM DIP Class II, III, Div. 1, Gr. E,F,G NI N CSA General Purpose P CSA DIP, Class II, III, Div. 1, Gr. E,F,G NI Q NEPSI DIP 2 ATEX II 1/2 D or II 2 D, Aluminium Deckel 5 ATEX II 1/3 D or II 3 D, Sichtdeckel Y Special version Process connection/material P Flange DN 100/ANSI 4"/JIS 16K100, PP (universal slip-on flange included) S Flange DN 100/ANSI 4"/JIS 16K100, SS 316TI (universal slip-on flange included) K Without slip-on flange/without mounting bracket (customer mounting equipment) M With mounting bracket Y Special version Power supply/communication H 4 wire, 10.5...32VDC / 4-20mA HART G 4 wire, 90...253VAC / 4-20mA HART D 2 wire, PROFIBUS PA F 2 wire, Foundation Fieldbus Y Special version Display / on-site operation 1 Without LC display 2 With LC display VU 331 incl. on-site operation 3 Prepared for remote display FHX 40 9 Special version Housing A Aluminium F12 housing coated to IP 68 9 Special version Screw union/entry 2 M20x1.5 screw union 3 G 1/2 entry 4 NPT 1/2 entry 5 M12 PROFIBUS-PA plug-in connector 6 7/8" FF plug 9 Special version FMU 43 Product designation
31
Prosonic M
Product structure FMU 44
Approval A Non-hazardous area 1 ATEX II 1/2G EEx ia IIC T6 (in preparation) 4 ATEX II 1/2G EEx d (ia) IIC T6 (in preparation) G ATEX II 3 G EEx nA II T6 (in preparation) 2 ATEX II 1/2 D, Alu blind cover (in preparation) 5 ATEX II 1/3 D S FM IS Cl.I,II,III Div.1 Gr.A-G, NI Cl.I Div.2 (in preparation) T FM XP Cl.I,II,III Div.1 Gr.A-G (in preparation) N CSA General Purpose U CSA IS Cl.I,II,III Div.1 Gr.A-G, NI Cl.I Div.2 V CSA XP Cl.I,II,III Div.1 Gr.A-G K TIIS EEx ia IIC T6 (in preparation) I NEPSI Ex ia IIC T6 (in preparation) J NEPSI Ex d(ia) IIC T6 (in preparation) E NEPSI Ex nA II T6 (in preparation) Q NEPSI DIP (in preparation) Y Special version, to be specified Process connection A 8" 150lbs FF, 316L, max 2.5bar abs./36psia E UNI flange 6"/DN150/150, PP, max 2.5bar abs./ 36psia, suitable for 6" 150lbs / DN150 PN16 / 10K 150 F UNI flange 6"/DN150/150, PVDF, max 2.5bar abs./36psia, suitable for 6" 150lbs /DN150 PN16 / 10K 150 G UNI flange 6"/DN150/150, 316L, max 2.5bar abs. 36psia, suitable for 6" 150lbs / DN150 PN16 / 10K 150 H UNI flange DN200/200, PP, max 2.5bar abs./ 36 psia, suitable for DN200 PN16 / 10K 200 J UNI flange DN200/200, PVDF, max 2.5bar abs./ 36psia, suitable for DN200 PN16 / 10K 200 K UNI flange DN200/200, 316L, max 2.5bar abs./ 36psia, suitable for DN200 PN16 / 10K 200 L 8" 150lbs FF, PP, max 2.5bar abs./ 36psia M Mounting bracket FAU20 N 8" 150lbs FF, PVDF, max 2.5bar abs./ 36psia T UNI flange 4"/DN100/100, PP, max 2.5bar abs./ 36psia, suitable for 4" 150lbs / DN100 PN16 / 10K 100 U UNI flange 4"/DN100/100, PVDF, max. 2.5bar abs./ 36 psia, suitable for 4" 150lbs / DN100 PN16 / 10K 100 V UNI flange 4"/DN100/100, 316L, max 2.5bar abs./ 36psia, suitable for 4" 150lbs / DN100 PN16 / 10K 100 Y Special version, to be specified Power supply; Output B 2-wire; 4-20mA HART D 2-wire; PROFIBUS PA F 2-wire; FOUNDATION Fieldbus G 4-wire 90-250VAC; 4-20mA HART H 4-wire 10.5-32VDC; 4-20mA HART Y Special version, to be specified Operation 1 w/o display, via communication 2 4-line display VU331, Envelope curve display on site 3 Prepared for FHX40, Remote display (accessory) 9 Special version, to be specified FMU 44 product designation, part 1
32
Prosonic M
Housing A F12 Alu, coated IP68 NEMA6P C T12 Alu, coated IP68 NEMA6P, Separate conn. compartment D T12 Alu, coated IP68 NEMA6P + OVP, Sep. conn. compartment, OVP = overvoltage protection 9 Special version, to be specified CAble entry 2 Gland M20 (EEx d > thread M20) 3 Thread G1/2 4 Thread NPT 1/2 5 Plug M12 6 Plug 7/8 9 Special version, to be specified Process Sealing Sensor/ Flange 2 Viton 3 EPDM 9 Special version, to be specified Additional option A Basic version Y Special version, to be specified FMU 44 complete product designation
Scope of delivery
Instrument according to the version ordered FieldCare software Operating manual according to the communication version for certified instrument versions: Safety Instructions, Control- or Installation drawings for FMU 40 *R**** and FMU 41 *R****: counter nut (PC) for FMU 40/41: sealing ring (EPDM) for gland M20x1.5: 1 cable gland for 2-wire instruments 2 cable glands for 4-wire instruments The cable glands are mounted on delivery.
33
Prosonic M
AccessoriesWeather protection cover A Weather protection cover made of stainless steel is recommended for outdoor mounting (order code: 543199-0001). The shipment includes the protective cover and tension clamp.
F12 / F23 / T12 housing
Orde MIC ES RO S+H Se r Code PIL AU r.-N o.: : Me Messbe asurireich ng ran ge U 16 ma x. 20 ...3 4...20 6 m mA V DC
EN DR
OT SE R II
IPTA >7
65
0C :
t >8 5C
Made in Germany
Maulburg
L00-FMR2xxxx-00-00-06-en-001
Installation bracket for FMU 40/41
15.7" (400)
4.72" (120) 0.63" (16) 4.72" (120)
9.84" (250)
0.12" (3)
1.18" (30)L00-FMU4x-00-00-00-de-001
for FMU 40, G1: Order No. 942669-0000 for FMU 41, G2: Order No. 942669-0001 suited for NPT 1" and 2" as well
34
Prosonic M
Adapter flange
sealing ring EPDM (supplied)
adapter flange
sensor
nozzleL00-FMUX3XXX-00-00-00-en-001
Version with metrical thread (FAU 70 E)Process Connection 12 DN 50 PN 16 A, flange EN1092-1 (DIN2527 B) 14 DN 80 PN 16 A, flange EN1092-1 (DIN2527 B) 15 DN 100 PN 16, A, flange EN1092-1 (DIN2527 B) Sensor Connection 3 Thread ISO228 G1-1/2 4 Thread ISO228 G2 Flange Material 2 316L 7 Polypropylene FAU 70 E Product designation
Version with conical thread(FAU 70 A)Process Connection 22 2" 150lbs FF, flange ANSI B16.5 24 3" 150lbs FF, flange ANSI B16.5 25 4" 150lbs FF, flange ANSI B16.5 Sensor Connection 5 Thread NPT1-1/2 6 Thread NPT2 Flange Material 2 316L 7 Polypropylene FAU 70 A Product designation
35
Prosonic M
Cantilever
C
A
0.79 (20)
0.79 (20)
1.38 (35)
0.98 1.97 3.94 (25) (50) (100)
D
M8
2.95 (75)
2.95 (75)
3.94 (100) C
B
1.38 (35)
4.13 (105)
1.97 / 2.44 (50 / 62)
0.87 (22)
0.26 (6.5)
0.59 (15)L00-FMU4xxxx-06-00-00-yy-005
A 23" 585 mm
B 9.83" 250 mm
C 0.08" 2 mm
D 7.87" 200 mm
for Sensor FMU 40
Material 316Ti/1.4571 galv. steel
Order Code 52014132 52014131 52014136 52014135 52014134 52014133 52014138 52014137
FMU 41
316Ti/1.4571 galv. steel
42.7" 1085 mm
29.5" 750 mm
0.12" 3 mm
11.8" 300 mm
FMU 40
316Ti/1.4571 galv. steel
FMU 41
316Ti/1.4571 galv. steel
The 1.97" (50 mm) or 2.44" (62 mm) orifices serve for the mounting of the FMU 40 or FMU 41 sensor, respecitvely. The 0.87" (22 mm) orifice may be used for an additional sensor.
36
Prosonic M
Mounting Frame0.51 (13) 3.94 (100)
2.17 (55)
0.98 (25)
1.33 (33.7) 0.79 (20)
0.13 (3.2)
2.36 (60) 0.16 (4)
28 / 55 (700 / 1400)
1.77 (45) 0.26 (6.5)
2.99 (76) 7.97 (200) 3.94 (100)
5.12 (130)
3.94 (100) 5.91 (150)L00-FMU4x-00-00-00-yy-005
Height 28" (700 mm) 28" (700 mm) 55" (1400 mm) 55" (1400 mm)
Material galv. steel 1.4301 (AISI 304) galv. steel 1.4301 (AISI 304)
Order Code 919791-0000 919791-0001 919791-0002 919791-0003
Wall Bracket0.20 (5) 0.26 (6.5) 4.33 0.98 (110) (25) 0.13 (3.2) 1.33 (33.7) ~ 8.39 (213) 0.51 (13) 5.91 (150)
7.09 (180)
~ 3.46 (88)
4.33 (110) 5.91 (150)L00-FMU4x-00-00-00-yy-006
Material galv. steel 316Ti/1.4571
Order Code 919792-0000 919792-0001
Commubox FXA191 HART
For intrinsically safe communication with FieldCare via the RS232C interface. For details refer to TI237F/00/ en. For intrinsically safe communication with FieldCare via the USB interface. For details refer to TI404F/00/en.
Commubox FXA195 HART
37
Prosonic M
Service Interface FXA193
The Service-Interface connects the Service plug of Proline and ToF instruments with the 9 pin RS 232C interface of a PC. (USB connectors must be equipped with a usual commercial USB/Serial adapter.) Product structureApprovalsA B C D 9 For use in non-hazardous areas ATEX II (1) GD CSA/FM Class I Div. 1 ATEX, CSA, FM other
Connection cableB E H X 9 Connection cable for ToF devices Connection cable for Proline and ToF devices Connection cable for Proline and ToF devices and Connection cable for Ex two-wire devices without connection cable others
FXA193-
Complete product designation
Associated documentation Technical Information: TI063D Safety Instructions for ATEX II (1) GD: XA077D Supplementary information for the cable adapters: SD092D Commubox FXA291 The Commubox FXA291 connects Endress+Hauser field instruments with CDI interface (= Endress+Hauser Common Data Interface) to the USB interface of a personal computer or a notebook. For details refer to TI405C/07/en.
!
Note! For the following producerinst
ruments you need the "ToF Adapter FXA291" as an additional accessory:
Cerabar S PMC71, PMP7x Deltabar S PMD7x, FMD7x Deltapilot S FMB70 Gammapilot M FMG60 Levelflex M FMP4x Micropilot FMR130/FMR131 Micropilot M FMR2xx Micropilot S FMR53x, FMR540 Prosonic FMU860/861/862 Prosonic M FMU4x Tank Side Monitor NRF590 (with additional adapter cable) Prosonic S FMU9x
ToF Adapter FXA291 The ToF Adapter FXA291 connects the Commubox FXA291 via the USB interface of a personal computer or a notebook to the following Endress+Hauser instruments: Cerabar S PMC71, PMP7x Deltabar S PMD7x, FMD7x Deltapilot S FMB70 Gammapilot M FMG60 Levelflex M FMP4x Micropilot FMR130/FMR131 Micropilot M FMR2xx Micropilot S FMR53x, FMR540 Prosonic FMU860/861/862 Prosonic M FMU4x Tank Side Monitor NRF590 (with additional adapter cable) Prosonic S FMU9x
For details refer to KA271F/00/a2.
38
Prosonic M
Remote display FHX40Wall-mounting (without mounting bracket) Pipe-mounting (mounting bracket and plate supplied optionally, see product structure) 0.33 (8.5)
Prosonic M Micropilot M Levelflex M
4.72 (120)
Separate housing FHX 40, NEMA 4 (IP 65)
ENOrde Se r Code r.-N o.: :
DR ES
IPTA >7
65C
Maulburg
Me Messbere asuri ich ng ran ge U 16 ma x. 20 ...3 4...20 6 m mA V DC
S+ HAU SE R
0C
: t >85
Made in Germany
4.80 (122)
7.09 (180) 6.30 (160)
3.15 (80) Cable
3.46 (88)4.72 (120) 3.23 (82) 4.65 (118) 3.78 (96)
0.25 (6.3)
4.80 (122) 4.17 (106)
max. 3.15 (80) min. 1.18 (30)
pipe
L00-FMxxxxxx-00-00-06-en-003
Technical data (cable and housing) and product structure:Max. cable length Temperature range Degree of protection Materials Dimensions 20 m (65 ft) -30 to +70C (-22 to 158F) IP65/67 (housing); IP68 (cable) acc. to IEC 60529 Housing: AlSi12; cable glands: nickle plated brass 122x150x80 mm (HxWxD) / 4.8" x 5.9" x 3.2"
Approval:A 1 S U N K Nn-hazardous area ATEX II 2 G EEx ia IIC T6, ATEX II 3D FM IS Cl.I Div.1 Gr.A-D CSA IS Cl.I Div.1 Gr.A-D CSA General Purpose TIIS ia IIC T6 (in preparation)
Cable:1 5 20m/65ft; for HART 20m/65ft; for PROFIBUS PA/FOUNDATION Fieldbus
Additional option:A B Basic version Mounting bracket, pipe 1"/ 2"
FHX40 -
Complete product designation
For connection of the remote display FHX40 use the cable which fits the communication version of the respective instrument.
39
Prosonic M
Supplementary documentationSystem Information SI 005F Ultrasonic level measurement Operating manual Depending on the communication variant ordered, the following operating manuals are supplied with the device:Communication 4 to 20mA, HART Profibus PA Foundation Fieldbus Operating manual BA 237F BA 238F BA 239F
These instructions describe the installation and first commissioning of the Prosonic M. From the operating menu, all functions are included, which are required for standard measurement tasks. Additional functions are not contained in the manual. Description of device functions BA 240F This contains a detailed description of all the functions of the Prosonic M and is valid for all communication variants. A pdf file of this document can be found in the supplied "ToF Tool - FieldTool Package" at "Help/ToF Tool Help/ Online Manual/ Operating Manual/Ultrasonic/Prosonic M FMU4x Functions"1). in the internet at "www.endress.com". Click "Download" and enter the product code "FMU4*" into the search form. KA 183F Can be found under the device housing cover. The most important menu functions are summarised on this sheet. It is intended primarily as a memory jogger for users who are familiar with the operating concept of Endress+Hauser time-of-flight instruments. Safety Instructions ATEX The following safety instructions are supplied with ATEX-certified device versions. If the devices are used in explosive areas, comply with all the specifications in these safety instructions.Certificate ATEX II 1/2 G or II 2 G EEx ia II C T6 ATEX II 1/2 G or II 2 G EEx ia II C T6 Communication HART (2-wire) Housing F12 Safety Instructions XA 174F
Short instructions
Instrument version FMU40 - 1*B*A* FMU41 - 1*B*A* FMU42 - 1*B*A*** FMU40 - 1*B*D* FMU41 - 1*B*D* FMU42 - 1*B*D*** FMU40 - 1*D*A* - 1*F*A* FMU41 - 1*D*A* - 1*F*A* FMU42 - 1*D*A*** - 1*F*A*** FMU40 - 1*D*D* - 1*F*D* FMU41 - 1*D*D* - 1*F*D* FMU42 - 1*D*D*** - 1*F*D***
HART (2-wire)
T12 with overvoltage protection
XA 224F
ATEX II 1/2 G or II 2 G EEx ia II C T6
Profibus-PA Foundation Fieldbus
F12
XA 175F
ATEX II 1/2 G or II 2 G EEx ia II C T6
Profibus-PA Foundation Fieldbus
T12 with overvoltage protection
XA 225F
1)
If the Operating Instructions have not been installed together with the "ToF Tool - FieldTool Package", they can be added to the installation subsequently.
40
Prosonic M
Instrument version FMU40 - 4*B*C* - 4*D*C* - 4*F*C* FMU41 - 4*B*C* - 4*D*C* - 4*F*C* FMU42 - 4*B*C*** - 4*D*C*** - 4*F*C*** FMU40 - G***** FMU41 - G***** FMU42 - G******* FMU40 - 2*B*A* - 2*D*A* - 2*F*A* - 5*B*A* - 5*D*A* - 5*F*A* FMU41 - 2*B*A* - 2*D*A* - 2*F*A* - 5*B*A* - 5*D*A* - 5*F*A* FMU42 - 2*B*A*** - 2*D*A*** - 2*F*A*** - 5*B*A*** - 5*D*A*** - 5*F*A*** FMU40 - 2*G*A* - 2*H*A* - 5*G*A* - 5*H*A* FMU41 - 2*G*A* - 2*H*A* - 5*G*A* - 5*H*A* FMU42 - 2*G*A*** - 2*H*A*** - 5*G*A*** - 5*H*A*** FMU43 - 2*G*A* - 2*H*A* - 5*G*A* - 5*H*A* FMU43 - 2*D*A* - 2*F*A* - 5*D*A* - 5*F*A*
Certificate
Communication
Housing
Safety Instructions
ATEX II 1/2 G or II 2 G EEx d [ia] II C T6
HART (2-wire) Profibus-PA Foundation Fieldbus
T12
XA 176F
ATEX II 3G EEx nA II T6
HART (2-wire) HART (4-wire, DC) HART (4-wire, AC) Profibus-PA Foundation Fieldbus
F12 T12 XA 179F T12 with overvoltage protection
ATEX II 1/2D ATEX II 1/3D
HART (2-wire) Profibus-PA Foundation Fieldbus
F12
XA 180F
ATEX II 1/2D ATEX II 1/3 D
HART (4-wire, DC) HART (4-wire, AC)
F12
XA 259
ATEX II 1/2 D or II 2 D ATEX II 1/3 D or II 3 D
HART (4-wire, DC) HART (4-wire, AC)
F12
XA 177F
ATEX II 1/2 D or II 2 D ATEX II 1/3 D or II 3 D
Profibus-PA Foundation Fieldbus
F12
XA 178F
41
Prosonic M
Safety Instructions NEPSI
The following safety instructions are supplied with NEPSI-certified device versions. If the devices are used in explosive areas, comply with all the specifications in these safety instructions.Certificate Ex ia II C T1 ... T6 NEPSI GYJ071468 Ex ia II C T1 ... T6 NEPSI GYJ071468 Communication HART (2-wire) Housing F12 Safety Instructions XA 436F
Instrument version FMU40 - I*B*A* FMU41 - I*B*A* FMU42 - I*B*A*** FMU40 - I*B*D* FMU41 - I*B*D* FMU42 - I*B*D*** FMU40 - I*D*A* - I*F*A* FMU41 - I*D*A* - I*F*A* FMU42 - I*D*A*** - I*F*A*** FMU40 - I*D*D* - I*F*D* FMU41 - I*D*D* - I*F*D* FMU42 - I*D*D*** - I*F*D*** FMU40 - J*B*C* - J*D*C* - J*F*C* FMU41 - J*B*C* - J*D*C* - J*F*C* FMU42 - J*B*C*** - J*D*C*** - J*F*C*** FMU40 - Q*B*A* - Q*D*A* - Q*F*A* FMU41 - Q*B*A* - Q*D*A* - Q*F*A* FMU42 - Q*B*A*** - Q*D*A*** - Q*F*A*** FMU40 - Q*G*A* - Q*H*A* FMU41 - Q*G*A* - Q*H*A* FMU42 - Q*G*A*** - Q*H*A*** FMU43 - Q*G*A* - Q*H*A* FMU43 - Q*D*A* - Q*F*A* FMU40 - E***** FMU41 - E***** FMU42 - E*******
HART (2-wire)
T12 with overvoltage protection
XA 442F
Ex ia II C T1 ... T6 NEPSI GYK071468
Profibus-PA Foundation Fieldbus
F12
XA 437F
Ex ia II C T1 ... T6 NEPSI GYJ071468
Profibus-PA Foundation Fieldbus
T12 with overvoltage protection
XA 443F
Ex d [ia] II C T1 ... T6 NEPSI GYJ071468
HART (2-wire) Profibus-PA Foundation Fieldbus
T12
XA 438F
DIP A21/A22 TA, T* NEPSI GYJ071468
HART (2-wire) Profibus-PA Foundation Fieldbus
F12
XA 441F
DIP A21/A22 TA, T* NEPSI GYJ071468
HART (4-wire, DC) HART (4-wire, AC)
F12
XA 444F
DIP A21/A22 TA, T* DIP A21/A22 TA, T*
HART (4-wire, DC) HART (4-wire, AC) Profibus-PA Foundation Fieldbus HART Profibus PA Foundation Fieldbus
F12 F12 F12 T12
XA 439F XA 440F
NEPSI Ex nA IIC T6
XA 403F
42
Prosonic M
Control drawings Installation drawingsInstrument version FMU40 - S*B*A* FMU41 - S*B*A* FMU42 - S*B*A*** FMU40 - S*D*A* - S*F*A* FMU41 - S*D*A* - S*F*A* FMU42 - S*D*A*** - S*F*A*** FMU40 - S*B*D* FMU41 - S*B*D* FMU42 - S*B*D*** FMU40 - S*D* D* - S*F*D* FMU41 - S*D* D* - S*F*D* FMU42 - S*D* D*** - S*F*D*** FMU40 - T*B*C* - T*D*C* - T*F*C* FMU41 - T*B*C* - T*D*C* - T*F*C* FMU42 - T*B*C*** - T*D*C*** - T*F*C*** FMU40 - U*B*A* FMU41 - U*B*A* FMU42 - U*B*A*** FMU44 - U*B*A***
The following control or installation drawings are supplied with the FM, CSA and TIIS-certified device versions:Communication Housing Control or Installation Drawing ZD 096F
Certificate
FM IS
HART (2-wire)
F12
FM IS
Profibus-PA Foundation Fieldbus
F12
ZD 097F
FM IS
HART (2-wire)
T12 with overvoltage protection ZD 139F
FM IS
Profibus-PA Foundation Fieldbus
T12 with overvoltage protection ZD 140F
FM XP
HART (2-wire) Profibus PA Foundation Fieldbus
T12
ZD 098F
CSA IS
HART (2-wire)
F12
ZD 088F
FMU40 - U*D*A* - U*F*A* FMU41 - U*D*A* - U*F*A* FMU42 - U*D*A*** - U*F*A*** FMU44 - U*D*A*** - U*F*A*** FMU40 - U*B* D* FMU41 - U*B* D* FMU42 - U*B* D*** FMU44 - U*B* D***
CSA IS
Profibus-PA Foundation Fieldbus
F12
ZD 099F
CSA IS
HART (2-wire)
T12 with overvoltage protection ZD 101F
FMU40 - U*D*D* - U*F*D* FMU41 - U*D*D* - U*F*D* FMU42 - U*D*D*** - U*F*D*** FMU44 - U*D*D*** - U*F*D***
CSA IS
Profibus-PA Foundation Fieldbus
T12 with overvoltage protection ZD 102F
43
Prosonic M
Instrument version FMU40 - V*B*C* - V*D*C* - V*F*C* FMU41 - V*B*C* - V*D*C* - V*F*C* FMU42 - V*B*C*** - V*D*C*** - V*F*C*** FMU44 - V*B*C*** - V*D*C*** - V*F*C*** FMU 40 - K***** FMU 41 - K*****
Certificate
Communication
Housing
Control or Installation Drawing
CSA XP
HART (2-wire) Profibus PA Foundation Fieldbus
T12
ZD 100F
TIIS Ex ia IIC T6
HART
F12
ZD 138F
Technical specificationPump N 3127, 60 Hz
Y/D startSUBCAB 7G2,5 mm2 7G2,5+2x1,5 mm2 7G4+2x1,5 mm2
VFD ApplicationScreened SUBCAB S3x2,5+3x2,5/3+4x1,5
Monitoring equipmentThermal contacts opening temp. 125 C
MaterialImpeller (.181) Impeller (185) Pump housing Stator housing Shaft O-rings Cast iron Hard Iron Cast iron Cast iron Stainless steel Nitrile rubber
N 3127ProductSubmersible pump for pumping clean water, surface water and waste water containing solids or long-fibred material.
Mechanical face sealsAlternative 1 Inner seal Corrosion resistant cemented carbide/ Aluminium oxide Corrosion resistant cemented carbide/ Corrosion resistant cemented carbide Corrosion resistant cemented carbide/ Corrosion resistant cemented carbide Outer seal Corrosion resistant cemented carbide/ Corrosion resistant cemented carbide Corrosion resistant cemented carbide/ Corrosion resistant cemented carbide Silicone carbide/ Silicone carbide
2
DenominationProduct code Installation Impeller characteristics1For
3 3127.181 (Hard Iron) 3127.185 P, S, T, Z, L1 LT, MT, HT, SH
Surface TreatmentAll cast parts are primed with a water-borne primer. The finishing coat is a high-solid two pack paint.
information about L-installation, see Technical Specification 894919
Process dataLiquid temperature-standard Depth of immersion The pH of the pumped liquid Liquid density max +40 C max 20 m pH 5,5-14 max. 1100 kg/m3
WeightSee dimensional drawing.
Option3127.090 3127.095 Warm liquid version on request Leakage sensor in stator housing Leakage sensor in oil housing Surface treatment Other cables Zinc anodes FLS CLS Epoxy treatment Ex. proof design (High chromium) Ex. proof design
Motor dataFrequency Insulation class Voltage variation - continuously running - intermittent running Voltage imbalance between phases No. of starts/hour max 5% max 10% max 2% max 30 60 Hz H (+180 C)
AccessoriesDischarge connections, adapters, hose connections and other mechanical accessories. Electrical accessories such as pump controller, control panels, starters, monitoring relays, cables.
CableDirect-on-line startSUBCAB 4G2,5 mm2 4G2,5+2x1,5 mm2 4G4 mm2 4G4+2x1,5 mm2 2
N 3127
LT-Motor rating and performance curveEx proof version available Installation
12 8 10 8 6 7 6 5
P2 [kW] / [hp]
Power factor cos
Starting current, A
Curve/Impeller No
Rated current, A
Rated power, hp
421
422
H [m] / [ft]P S T Z
60 50 40 30 20 10 0
18 16 14 12 10 8 6 4 2 0 0 0 20 40 60 80
LT
460 V, 60 Hz, 3 ~, 1740 r/min 422 422 421 422 422 7,3 7,5 10 7,5 7,5 9,8 9,9 13 30 30 75 62 75 67 67 0,83 0,85 0,87 0,95 0,95
230 V, 60 Hz, 1 ~, 1740 r/min
Y/D starting current is approximately 1/3 of D starting current.
422
421
MT-Motor rating and performance curveEx proof version available Installation
100
200 400 600 800 10001200140016001800 Q [l/s] / [usgpm]
Power factor cos
Starting current, A
Curve/Impeller No
P2 [kW] / [hp] 10 8 6P S T Z
Rated current, A
Rated power, hp
7438
6 5 4 H [m] / [ft]439
460 V, 60 Hz, 3 ~, 1740 r/min 439 439 439 438 439 7,3 7,5 10 10 7,5 9,8 9,9 13 13 75 62 75 75 0,83 0,85 0,87 0,87
70 60
MT20 16 12 8 4 0 0 0 10 200 20 30 40 600 50 60 70 80 400 800 1000 1200 1400 Q [l/s] / [usgpm]438
230 V, 60 Hz, 1 ~, 1740 r/min 32,0 66,0 0,97
50 40 30 20 10 0
Y/D starting current is approximately 1/3 of D starting current.
439
N 3127
3
HT-Motor rating and performance curveEx proof version available Installation
16 12 8 4 10 8 6 4
P2 [kW] / [hp]
487
488
Power factor cos
Starting current, A
Curve/Impeller No
Rated current, A
Rated power, hp
489
H [m] / [ft] 100
HT30 25 20 15
P 460 V, 60 Hz, 3 ~, 1740 r/min 489 489 487 488 489 489 7,3 7,5 10 10 10 7,5 9,8 9,9 13 13 13 75 62 75 75 75 0,83 0,85 0,87 0,87 0,87
S
T
Z
80 60 40
487
230 V, 60 Hz, 1 ~, 1740 r/min 32,0 66,0 0,97
10 20 0 5 0 0 0 10 200 20 400 30 40 600
488
Y/D starting current is approximately 1/3 of D starting current.
489
50
60
800 1000 Q [l/s] / [usgpm]
SH-Motor rating and performance curveEx proof version available Installation
P2 [kW] / [hp] 12 10 8 6 H [m] / [ft] 160 45 9 8 7 6 5248
Power factor cos
Starting current, A
Curve/Impeller No
Rated current, A
Rated power, hp
249
SH
P 460 V, 60 Hz, 3 ~, 3395 r/min 248 249 11 11 13 13 113 113 0,91 0,91
S
T
Z
140 40 120 100 80 60 40 20 0 35 30 25 20 15 10 5 0 0 0 5 100 10 200 15 20 300 25 30 400 500 Q [l/s] / [usgpm]248 249
Y/D starting current is approximately 1/3 of D starting current.
4
N 3127
Dimensional drawing
All dimensions are in mm.
LT, P-installation
LT, P-installation hydroejector
N 3127
5
LT, P-installation
LT, S-installation
LT, S-installation
LT, T-installation
6
N 3127
LT, Z-installation
LT, L-installation
MT, P-installation
MT, P-installation
b
N 3127
7
MT, P-installation
MT, P-installation JA 117
MT, S-installation
MT, S-installation
8
N 3127
MT, S-installation JA 117
MT, T-installation
MT, T-installation
MT, Z-installation
N 3127
9
MT, Z-installation
HT, P-installation
HT, S-installation
HT, T-installation
10
N 3127
HT, Z-installation
SH, P-installation
SH, P-installation
N 3127
11
SH, S-installation
12
N 3127
Technical specificationSubmersible mixers S 4650, 50 Hz
S 4650Monitoring equipmentThermal contacts opening temp. 125 C
MaterialStator housing Shaft Oil casing Part Jet ring Fixing plate Lifting deviceASTM 304: general purpose stainless steel ASTM 316 L: high grade stainless steel
Stainless steel Stainless steel Vinyl ester based SMC ASTM 304 ASTM 316 L
Propeller Angle ASTM 316 L Alloyed white iron
S 4650ProductDirect drive mixer with two or three blade propeller intended for mixing liquid and sludge containing fibres and solids. The mixer is designed to be operated completely immersed in the liquid.
Two blade propeller 5 9 Three blade propeller 5 7 9 10 11 4650.410 Guide bar system Flange mounted O-rings Alternative max +40 C max 20 m pH 1 - 12 max 5000 cp Mechanical face seals Alternative 50 Hz H (+180 C) max 5% max 10% max 2% max 30 3 2 1 Inner seal Corrosion resistant cemented carbide/ Corrosion resistant cemented carbide Corrosion resistant cemented carbide/ Corrosion resistant cemented carbide Outer seal Corrosion resistant cemented carbide/ Corrosion resistant cemented carbide Silicon carbide/ Silicon carbide 1 2 Material Nitrile rubber Fluorinated rubber
DenominationProduct code Installation
Alloyed white iron (extremely abrasion-resistant alloy)
Process dataLiquid temperature Depth of immersion The pH of the mixed liquid Liquid viscosity
Motor dataFrequency Insulation class Voltage variation - continuously running - intermittent running Voltage imbalance between phases No. of starts/hour
CableDirect-on-line startSUBCAB 4G2,5+2x1,5 mm2 4G4+2x1,5 mm2
Carbon/ Corrosion Corrosion resistant resistant cemented carbide cemented carbide/ Corrosion resistant cemented carbide
Surface TreatmentStainless steel parts are blasted to a dull grey surface.
4G6+2x1,5 mm2
3
S 4650WeightSee dimensional drawing.
AccessoriesStand and Single guide bar system, lifting equipment and other mechanical accessories. Electrical accessories such as starters, alarm units. See separate booklet or int.flygt.com, for further information Fthrust N 1040 1290 1530 Pin kW 4,4 5,4 6,5
Mixer data chartPropeller material ASTM 316 LPropeller code 125803SX 125805SX 125807SX 125809SX 125811SX Fthrust N 860 1100 1350 1620 1890 Pin kW 3,6 4,1 4,8 5,6 6,5 With jet ring (J) Without jet ring (F)
Propeller material Alloyed white iron (High-Chrome)Propeller code 125805HX 125807HX 125809HX 125811HX 125813HX Fthrust N 560 790 1010 1240 1450 Pin kW 3,00 3,40 3,95 4,65 5,55 Fthrust N 650 890 1120 1340 1540 Pin kW 3,20 3,75 4,45 5,30 6,20 With jet ring (J) Without jet ring (F)
Key to the 8-digit Propeller Code: 1:st and 2:nd digit - Motor pole No (16=16-pole) 3:rd and 4:th digit - Propeller diameter (77=766 mm) 5:th and 6:th digit - Propeller blade angle 7:th digit - Propeller material (S=ASTM 304, ASTM 316 L, H=High-Chrome) 8:th digit - Hydraulic end (J=with jet ring, F=without jet ring)
Motor ratingEx proof version available Ex. proof version FLS CLS Rated output power, kW
400 V, 50 Hz, 3 ~, 480 r/min 5,5 17 48 0,65
Option4650.490 Warm liquid version on request Leakage sensor in stator housing Leakage sensor in oil housing Seal flushing Seal protection Cutting rings Cable protection Two blade propeller
Power factor cos
Starting current, A
Rated current, A
4
S 4650Dimensional drawingAll drawings are available as Acrobat documents (.pdf) and AutoCad drawings (.dwg). Download the drawings from int.flygt.com or contact your ITT Flygt representative for more information. All dimensions are in mm.
With jet ring
Without jet ring
Flange mounted
5
S 4650
Vortex shield
6
Tender Documents Volume 3 Velipoje Sewerage Collection System and Waste Water Treatment Plant
SEQUENTIAL BATCH REACTOR
Technical specification
Derby-E
Particular Specifications Rev. 01 2010 Annexes
Technical Information
Oxymax W COS61Dissolved oxygen measurement Optical sensor according to the fluorescence quenching principle
Application The continuous measurement of the dissolved oxygen concentration is very important in many areas of water management: Sewage treatment plants: Oxygen measurement and regulation in the activated sludge basin for a highly efficient biological cleaning process Water monitoring: Oxygen measurement in rivers, lakes or seas as an indicator of the water quality Water treatment: Oxygen measurement for status monitoring of drinking water for example (oxygen enrichment, corrosion protection etc.) Fish farming: Oxygen measurement and regulation for optimum living and growth conditions Your benefits Optical technology: Minimum maintenance Maximum availability Compatible with tried-and-tested COS31 with COM2x3W: Easy measuring point changeover to optical technology Compatible with COS41 with COM2x3D with conversion kit Sensor with digital data transmission: Storage of calibration data in sensor Insensitive to electromagnetic interferences thanks to digital communication to the transmitter Maximum measurement accuracy: Longterm-stable measurement Long maintenance intervals Intelligent sensor self monitoring No flow needed - measurement possible in still water
TI387C/24/ae/07.07
Oxymax W COS61
Function and system designMeasuring principle Sensor design: Oxygen-sensitive molecules (markers) are integrated in an optically active layer (fluorescence layer). The surface of the fluorescence layer is in contact with the medium. The sensor optics are directed at the underside of the fluorescence layer. There is an equilibrium between the oxygen partial pressure in the medium and that in the fluorescence layer: If the sensor is immersed in the medium, the equilibrium is established very quickly. Measuring process: The sensor optics send green light pulses to the fluorescence layer. The markers "answer" (fluoresce) with red light pulses. The duration and intensity of the response signals is directly dependent on the oxygen contents and the partial pressure. If the medium is free from oxygen, the response signals are long and very intense. Oxygen molecules "quench" the marker molecules. As a result, the response signals are shorter and less intense. Measurement result: The sensor returns a signal that is in proportion to the oxygen concentration in the medium. The fluid temperature and air pressure are already calculated in the sensor. The optical signals are continuously monitored and analysed for plausibility. If inconsistencies occur, an error message is output via the transmitter. Aging of the sensor cap is detected. The transmitter first displays a warning for predictive maintenance and later generates an error message. In addition, the following fault conditions are detected in conjunction with the sensor check system of Liquisys M COM2x3: Implausibly high or low measured values Disturbed regulation due to incorrect measured values Measuring system The complete measuring system consists of the following at least: Oxygen sensor Transmitter, e.g. Liquisys M COM223/253 Special measuring cable if extension is necessary Assembly, e.g. COA250 flow assembly, CYA611 immersion assembly or COA451 retractable assembly Optional: CYH101 universal immersion assembly holder for immersion operation VS junction box (for cable extension) Chemoclean automatic spray cleaning system
Sensor monitoring
1
2
4Fig. 1: 1 2 3 4 Measuring system (example) CYA611 immersion assembly VS junction box (optional) Liquisys M COM253 transmitter COS61 oxygen sensor
3a0007362
2
Oxymax W COS61
InputMeasured variable Dissolved oxygen [mg/l, ppm, % SAT or hPa] Temperature [C, F) With Liquisys M COM 223/253: 0 to 20 mg/l (0 to 20 ppm) 0 to 200 % SAT 0 to 400 hPa
Measuring range
WiringElectrical connection Direct connection to the transmitter Connect the sensor directly to the transmitter (COM253-WX/WS) by using the special measuring cable with SXP plug.
a0004118
SXP plug
Direct connection to the transmitter (panel mounting device) Remove the SXP connector (transmitter side!) from the cable. Refer to the following table for the cable assignment and the assigned terminals for Liquisys M COM223-WX/WS. Please note that the cable assignment changes depending on the sensor version (fixed cable or TOP68 connection).Terminal COM223 Sensor with fixed cable (OMK) Core 87 0 96 97 88 YE GY PK BU BN Assignment +UB 0V Com. (digital) Com. (digital) UB Sensor with TOP68 connection (CYK71) Core YE WH GN BN Assignment +UB 0V Communication (digital) Communication (digital)
Koax innen UB
3
Oxymax W COS61
Connection with cable extension To lengthen the sensor connection beyond the length of the fixed cable, a junction box VS is required. Always connect the sensor cable with the SXP plug to the junction box. The cable extension to the transmitter then depends from the transmitter version, i.e. field device or panel mounted device.1 82 (3.23) 80 (3.15)YE GY PK BU BN 87 0 96 97 88 19 18a0004130 a0004129-en
4
2
2
3
GN WH
mm (inch)
Junction box VS to a panel mounted device 2 3 4 SXP plug from sensor Measuring cable (OMK) to the transmitter Connection department of the transmitter
Junction box VS to a field device 1 2 SXP plug to field device SXP plug from sensor
Performance characteristicsResponse time Reference operating conditions t90: 60 s Reference temperature: Reference pressure: Reference application: 2 % of measuring range end 0.5 % of measuring range end >2 years (under reference operating conditions, protect against direct sun light) 25C (77F) 1013 hPa (15 psi) Municipal wastewater treatment
Maximum measured error Repeatability Life time of the sensor cap
4
Oxymax W COS61
InstallationAngle of installation The sensor can be installed up to the horizontal in an assembly, support or a suitable process connection. Other angles and overhead installation are not recommended. Reason: possible sediment formation and resulting falsification of measured value.
!
Note! The optimum installation angle is 45 (e.g. with assembly CYA611-0E).
Aa0004087
Angle of installation A Permissible installation positions: 0 to 180
!
Note! Make sure you comply with the instructions for installing sensors. You will find them in the Operating Instructions for the assembly used.
EnvironmentAmbient temperature range Storage temperature 20 to +60C (-4 to 140F) 20 to +70C (-4 to 160F) at 95% relative humidity, non condensing Fixed cable versions: IP 68 (10 m / 33 ft) water column at 25C / 77F, for 30 days (similar to NEMA 6P) Top 68 plug-in head versions: IP 68 (1 m / 3.3 ft) water column at 50C / 122F for 7 days (similar to NEMA 6P)
Ingress protection
ProcessProcess temperature Process pressure 5 to 50C (23 to 120F) max. 10 bar (145 psi)
5
Oxymax W COS61
Mechanical constructionDesign, dimensions
220 (8.66)
186 (7.32)
220 (8.66) 186 (7.32)
40 (1.57)
mm (inch)
40 (1.57)a0004083-en
mm (inch)a0004084-en
Fixed cable version
TOP68 version
Weight
with cable length 7 m (23 ft): 0.7 kg (1.5 lbs.) with cable length 15 m (49 ft): 1.1 kg (2.4 lbs.) with TOP68 plug-in connection: 0.3 kg (0.66 lbs.) Sensor shaft: Cap with fluorescence layer: Fluorescence layer: G1 max. 100 m / 328 ft (including cable extension) internal stainless steel 1.4571 (AISI 316Ti) POM Silicone
Material
Process connection Maximum cable length Temperature compensation
6
Oxymax W COS61
Ordering informationProduct structureCertificate A Ex free version Cable length 0 Cable length: 1.5 m (4.9 ft) 1 Cable length: 7 m (23 ft) 2 Cable length: 15 m (49 ft) 8 Without cable (for TOP 68 version) 9 Special version acc. to customers specification Sensor head F G1, fixed cable with SXP plug S G1, TOP68 plug Accessories 0 without accessories COS61complete order code
Scope of delivery
The following items are included in the delivery: Oxygen sensor with transport protection cap for membrane protection Operating Instructions (on CD only) Brief Operating Instructions (paper version)
Certificates and approvalsElectromagnetic compatibilty Interference emission and interference immunity complies with EN 61326: 1997 / A1: 1998
!Assemblies (selection)
AccessoriesNote! In the following sections, you find the accessories available at the time of issue of this documentation. For information on accessories that are not listed here, please contact your responsible service. Retractable assembly Cleanfit COA451 Manually driven retractable assembly, stainless steel, with ball valve, for oxygen sensors; Ordering acc. to product structure (Technical Information TI368C/24/ae) Immersion assembly Dipfit W CYA611 For sensor immersion in basins, open channels and tanks, PVC Ordering acc. to product structure, see Technical Information TI166C/24/ae Flow assembly COA250 For sensor installation in pipe lines, PVC Ordering acc. to product structure (Technical Information TI111C/24/ae)
Zero solution
3 units to produce 3 x 1 liter oxygen-free solution order no. 50001041 COK31 special measuring cable For sensors COS31, COS61 and COS71 with TOP68 plug-in head Order numbers: Cable length 1.5 m (4.9 ft): 51506820 Cable length 7 m (23 ft): 51506821 Cable length 15 m (49 ft): 51506822
Measuring cable
7
Measuring cable OMK For use as extension cable between junction box VS and transmitter, not terminated Sold by the meter - order no. 50004124 CYK71 measuring cable Non-terminated cable for the connection of sensors (e.g. conductivity sensors) or the extension of sensor cables Sold by the meter, order numbers: non-Ex version, black: 50085333 Ex version, blue: 51506616 Junction box VS junction box With plug-in socket and 7-pole plug For cable extension from sensor (COS71, COS61, COS31, COS3 with SXP connector) to transmitter, IP 65 (similar to NEMA 4); Order no. 50001054 Liquisys M COM 223/253 Transmitter for oxygen measurement Field or panel-mounted housing HART or Profibus available Ordering acc. to product structure, see Technical Information (TI 199C/24/ae)
Transmitter
Technical Information
Turbimax W CUS65Turbidity and solids content sensor Installation and immersion sensor for low, medium and high concentrations using the four-beam pulsed light method
Application The Turbimax W CUS65 sensor is used for optical turbidity and solids content measurement. Due to various sensor heads the sensor is suitable for use from low to high concentration ranges. Wastewater clarification / sludge treatment Boiler feedwater monitoring Condensate monitoring Service water monitoring
Your benefits Four-beam pulsed light method for compensation of sensor soiling and wearing of optical components Sensor body made of stainless steel No mechanically moving parts, therefore no sensor blocking Measured value processing in sensor resulting in low signal transmission sensitivity Aeration systems do not affect measurement Plug system for quick commissioning
TI370C/07/en/01.08 71067562
Turbimax W CUS65
Function and system designMeasuring principle Turbidity measurement For turbidity measurement a light beam is sent through the medium and is diverted from its original direction by optically denser particles, e.g. solid matter particles. Four-beam pulsed light method The method is based on two light sources and two photo receivers. Long-life LEDs are used as monochromatic light sources. To eliminate interference from extraneous light sources, these LEDs are pulsed at a rate of several kHz. Two measuring signals are detected at the two photo receivers. The four measuring signals are processed in the sensor and are converted into proportional frequencies. The transmitter assigns the frequencies to the appropriate turbidity units and solids concentrations. The four-beam pulsed light method compensates the sensor soiling as well as the wearing of the optical components. S = Light source E = Light receiverS1 E1
S2
E2
a0008973
Four-beam pulsed light method
Measuring methods
Depending on the version, the sensor uses the absorption light method (CUS65-A, -B, -C) or the scattered light method (CUS65-D, -E). Absorption light method The measuring principle is based on the Lambert-Beer law. The turbidity of the medium is determined by the weakening of the light beam. The sensor LEDs send a directed light beam to the light receivers. The light beam intensity is weakened by the solid matter particles in the medium.I lg 0 = ECD IT
IT = I0 e
ECD
IA IT
I0 = Intensity of transmitted light IA = Intensity of absorbed light IT = Intensity of light transmitted IS = Intensity of scattered light E = Extinction coefficient C = Concentration D = Optical path length
I0
IS Da0008974
Absorption light method
90 NIR scattered light method The measurement uses the 90 scattered light method acc. to ISO 7027 / EN 27027. The turbidity of the medium is determined by the amount of scattered light. The transmitted light beam with a wavelength in the near-infrared range is scattered by the solid matter particles in the medium. The scattered beams are detected by scattered light receivers which are arranged at an angle of 90 to the infrared light sources.
2
Turbimax W CUS65
Is = I0 C A f(a) E1 IS IS P a I0 I0 a E2
I0 = Intensity of transmitted light IS = Intensity of scattered light A = Geometrical factor C = Concentration P = Particle f() = Angle correlation
S190 scattered light method
S2a0008975
Backscattered light method The measurement uses the backscattered light method. The turbidity of the medium is determined by the amount of backscattered light. The transmitted light beam is scattered by the solid matter particles in the medium. The backscattered beams are detected by scattered light receivers, which are arranged next to the light sources.Is = I0 C A f(a)
IS E1 I0 S1Backscattered light method
a
P
I0 = Intensity of transmitted light IS = Intensity of scattered light A = Geometrical factor C = Concentration P = Particle f() = Angle correlation
IS I0 aa0008976
I P
I = Intensity of transmitted light C = Concentration P = Reversal point Cal = Calibration range
0.8%
Cal
10%
Ca0008980
!
Note! CUS65-E has a reversal point at approx. 0.8% of solid matter (as dry substance) and can thus not be calibrated with water. Therefore only use the sensor starting from a concentration >10 g/l.
3
Turbimax W CUS65
Performance characteristicsMaximum measured error < 1% of measuring range end (system measured error related to the primary formazine standard / tracing according to ISO 5725 and ISO 7027 / EN 27027) 880 nm by four-beam pulsed light method CUS65-A, -B, -C, -E: CUS65-D: SiO2 Formazine acc. to ISO 7027 / EN 27027
Wave length Reference measurement Factory calibration
InstallationInstallation instructions Installation options: with retractable assembly CUA451 with immersion pipe CYY105 Note! Observe the required mounting clearance for the installation mode selected. Installing the sensor in pipes or close to a wall can lead to backscattering resulting in signal increase, mainly with measurements in low turbidity ranges (
Recommended