TR-MARINE / CARGO WATCH II v.02
OPERATION AND MAINTENANCE MANUAL
PROJECT REF NO : TRM-CWII/G48 SHIYARD : GISAN HULL NO : NB48
CARGO PUMP CONTROL & MONITORING SYSTEM
Page 2 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
TABLE�OF�CONTENTS�
1.� GENERAL�DESCRIPTION�........................................................................................................................�6�
2.� INSTALLATION�INSTRUCTIONS�..............................................................................................................�6�
3.� ADJUSTMENT�.......................................................................................................................................�6�
4.� COMMISSIONING�.................................................................................................................................�6�
5.� OPERATION�BASICS�..............................................................................................................................�7�
5.1.� GENERAL�..............................................................................................................................................�7�
5.2.� CONTROL�PANELS�.................................................................................................................................�8�
5.2.1.�REMOTE�PANEL�....................................................................................................................................�8�
5.2.1.1.� MAIN�WINDOW�...........................................................................................................................�8�
5.2.1.2.� HYDRAULIC�OPERATION�WINDOW.............................................................................................�10�
5.2.1.3.� CARGO�PUMPS�WINDOW�..........................................................................................................�20�
5.2.1.4.� ALARM�WINDOW�......................................................................................................................�21�
5.2.1.5.� SETTINGS�WINDOW�...................................................................................................................�22�
5.2.1.6.� TREND�WINDOW�.......................................................................................................................�23�
5.2.1.7.� AUXILIARY�PUMPS�WINDOW�.....................................................................................................�24�
5.2.2.�LOCAL�PANEL�......................................................................................................................................�26�
5.2.2.1.� MAIN�WINDOW�.........................................................................................................................�26�
5.2.2.2.� OPERATION�WINDOW�...............................................................................................................�28�
5.2.2.2.1.� OPERATION�WINDOW�1�........................................................................................................�30�
5.2.2.2.2.� OPERATION�WINDOW�2�........................................................................................................�33�
5.2.2.2.3.� OPERATION�WINDOW�3�........................................................................................................�35�
5.2.2.2.4.� OPERATION�WINDOW�4�........................................................................................................�37�
5.2.2.3.� CARGO�PUMPS�WINDOW�..........................................................................................................�38�
5.2.2.3.1.� CARGO�PUMP�1�WINDOW�.....................................................................................................�39�
5.2.2.3.2.� CARGO�PUMP�2�WINDOW�.....................................................................................................�40�
5.2.2.3.3.� STRIPPING�PUMP�WINDOW�..................................................................................................�40�
5.2.2.4.� ALARM�WINDOW�......................................................................................................................�41�
5.2.2.5.� SETTINGS�WINDOW�...................................................................................................................�42�
5.2.2.5.1.� CARGO�PUMP�1�SETTINGS�WINDOW�.....................................................................................�44�
5.2.2.5.2.� CARGO�PUMP�2�SETTINGS�WINDOW�.....................................................................................�44�
5.2.2.5.3.� CARGO�PUMP�3�SETTINGS�WINDOW�.....................................................................................�45�
5.2.2.5.4.� SYSTEM�SETTINGS�WINDOW�.................................................................................................�45�
5.2.2.6.� TREND�WINDOW�.......................................................................................................................�46�
6.� OPERATION�MODES�...........................................................................................................................�46�
6.1.� LOCAL�(MANUAL)�CONTROL�OPERATION�............................................................................................�46�
Page 3 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
6.2.� LOCAL�CONTROL�PANEL�OPERATION�...................................................................................................�46�
6.3.� REMOTE�CONTROL�PANEL�OPERATION�...............................................................................................�47�
7.� ALARM�LIST�........................................................................................................................................�47�
8.� MAINTANENCE�...................................................................................................................................�51�
9.� TROUBLE�SHOOTING�..........................................................................................................................�51�
10.� PLC�MANUAL�......................................................................................................................................�52�
���������� � �
Page 4 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
TABLE OF FIGURES FIGURE�1�REMOTE�PANEL�MAIN�WINDOW�............................................................................................................�8�FIGURE�2�SYSTEM�INFO�POPUP�WINDOW�..............................................................................................................�9�FIGURE�3�REMOTE�PANEL�HYDRAULIC�OPERATION�WINDOW�.............................................................................�10�FIGURE�4�CARGO�PUMPS�TOUCH�PLACES�ON�WINDOW�......................................................................................�10�FIGURE�5�CARGO�PUMP�1�POPUP�WINDOW�........................................................................................................�11�FIGURE�6�CARGO�PUMP�2�POPUP�WINDOW�........................................................................................................�12�FIGURE�7�STRIPPING�PUMP�POPUP�WINDOW�......................................................................................................�12�FIGURE�8�PROPORTIONAL�VALVES�POSITIONS�.....................................................................................................�13�FIGURE�9�CARGO�PUMPS�SPEED�FEEDBACK�.........................................................................................................�13�FIGURE�10�FILTER�SITUATIONS�..............................................................................................................................�13�FIGURE�11�HYDRAULIC�SYSTEM�PRESSURE�...........................................................................................................�13�FIGURE�12�SOLENOIDS�VALVES�TOUCH�PLACES�ON�WINDOW�.............................................................................�14�FIGURE�13�DRAIN�VALVES�POPUP�WINDOW�........................................................................................................�14�FIGURE�14�HYDRAULIC�MAIN�PUMPS�TOUCH�PLACES�ON�WINDOW�...................................................................�15�FIGURE�15�HYDRAULIC�MAIN�PUMPS�READY�CONDITIONS�POPUP�WINDOW�.....................................................�15�FIGURE�16�HYDRAULIC�MAIN�PUMPS�POPUP�WINDOW�......................................................................................�15�FIGURE�17�SUCTION�VALVES�ON�WINDOW�..........................................................................................................�16�FIGURE�18�HYDRAULIC�OIL�HEATER�TOUCH�PLACE�ON�WINDOW�........................................................................�16�FIGURE�19�HYDRAULIC�OIL�HEATER�POPUP�WINDOW�.........................................................................................�16�FIGURE�20�HYDRAULIC�OIL�TANK�TEMPERATURE�INDICATOR�..............................................................................�16�FIGURE�21�VALVES�FEEDBACK�...............................................................................................................................�17�FIGURE�22�AUXILIARY�PUMPS�POPUP�TOUCH�PLACES�.........................................................................................�17�FIGURE�23�HFC�PUMP�POPUP�WINDOW�..............................................................................................................�18�FIGURE�24�HCC�PUMP�POPUP�WINDOW�..............................................................................................................�18�FIGURE�25�MENU�AND�BACK�BUTTONS�................................................................................................................�19�FIGURE�26�SETTINGS�PASSWORD�POPUP�WINDOW�.............................................................................................�19�FIGURE�27�REMOTE�PANEL�MENU�WINDOW�.......................................................................................................�19�FIGURE�28�REMOTE�PANEL�CARGO�PUMPS�WINDOW�.........................................................................................�20�FIGURE�29�ALARM�STATE�ANIMATED�VALUE�........................................................................................................�20�FIGURE�30�SPEED�ADJUST�BUTTONS�.....................................................................................................................�20�FIGURE�31�REMOTE�PANEL�ALARM�WINDOW�......................................................................................................�21�FIGURE�32�REMOTE�PANEL�SETTINGS�WINDOW�..................................................................................................�22�FIGURE�33�POPUP�KEYBOARD�FOR�VALUE�INPUT�.................................................................................................�22�FIGURE�34�REMOTE�PANEL�TREND�WINDOW�.......................................................................................................�23�FIGURE�35�REMOTE�PANEL�AUXILIARY�PUMP�WINDOW�......................................................................................�24�FIGURE�36�SEA�WATER�COOLING�PUMP�1�POPUP�WINDOW�...............................................................................�25�FIGURE�37��SEA�WATER�COOLING�PUMP�2�POPUP�WINDOW�..............................................................................�25�FIGURE�38��FRESH�WATER�COOLING�PUMP�1�POPUP�WINDOW�..........................................................................�25�FIGURE�39�FRESH�WATER�COOLING�PUMP�2�POPUP�WINDOW�...........................................................................�25�FIGURE�40��BUFFER�LIQUID�CIRCULATION�PUMP�1�POPUP�WINDOW�.................................................................�25�FIGURE�41�BUFFER�LIQUID�CIRCULATION�PUMP�2�POPUP�WINDOW�..................................................................�25�FIGURE�42�LOCAL�PANEL�MAIN�WINDOW�............................................................................................................�26�FIGURE�43�LOCAL�PANEL�SYSTEM�INFO�POPUP�WINDOW�...................................................................................�27�FIGURE�44�PASSWORD�POPUP�WINDOW�FOR�CONTROL�ACCESS�........................................................................�27�FIGURE�45�POPUP�KEYBOARD�...............................................................................................................................�28�FIGURE�46�LOCAL�PANEL�OPERATION�WINDOW�..................................................................................................�28�FIGURE�47�LOCAL�PANEL�MENU�AND�BACK�BUTTONS�.........................................................................................�29�FIGURE�48�LOCAL�PANEL�MENU�WINDOW�...........................................................................................................�29�FIGURE�49�LOCAL�PANEL�OPERATION�1�WINDOW�...............................................................................................�30�FIGURE�50�LOCAL�PANEL�HYDRAULIC�MAIN�PUMPS�POPUP�WINDOW�................................................................�31�FIGURE�51�HYDRAULIC�MAIN�PUMPS�READY�CONDITIONS�POPUP�WINDOW�.....................................................�31�
Page 5 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
FIGURE�52�LOCAL�PANEL�HCC�PUMP�POPUP�WINDOW�.......................................................................................�32�FIGURE�53�LOCAL�PANEL�HFC�PUMP�POPUP�WINDOW�........................................................................................�32�FIGURE�54�LOCAL�PANEL�OPERATION�2�WINDOW�...............................................................................................�33�FIGURE�55��LOCAL�PANEL�SEA�WATER�COOLING�PUMP�1�POPUP�WINDOW�........................................................�34�FIGURE�56��LOCAL�PANEL�SEA�WATER�COOLING�PUMP�2�POPUP�WINDOW�........................................................�34�FIGURE�57�LOCAL�PANEL�FRESH�WATER�COOLING�PUMP�1�POPUP�WINDOW�....................................................�34�FIGURE�58�LOCAL�PANEL��FRESH�WATER�COOLING�PUMP�2�POPUP�WINDOW�...................................................�34�FIGURE�59�LOCAL�PANEL�BUFFER�LIQUID�CIRCULATION�PUMP�1�POPUP�WINDOW�............................................�34�FIGURE�60�LOCAL�PANEL��BUFFER�LIQUID�CIRCULATION�PUMP�2�POPUP�WINDOW�...........................................�34�FIGURE�61�LOCAL�PANEL�OPERATION�3�WINDOW�...............................................................................................�35�FIGURE�62�LOCAL�PANEL�DRAIN�VALVE�POPUP�WINDOW�...................................................................................�36�FIGURE�63�LOCAL�PANEL�HYDRAULIC�OIL�HEATER�POPUP�WINDOW�...................................................................�36�FIGURE�64�LOCAL�PANEL�OPERATION�WINDOW�4�...............................................................................................�37�FIGURE�65�LOCAL�PANEL�CARGO�PUMPS�WINDOW�.............................................................................................�38�FIGURE�66�LOCAL�PANEL�CARGO�PUMP�1�WINDOW�............................................................................................�39�FIGURE�67�LOCAL�PANEL�CARGO�PUMP�2�WINDOW�............................................................................................�40�FIGURE�68�LOCAL�PANEL�STRIPPING�PUMP�WINDOW�.........................................................................................�40�FIGURE�69�LOCAL�PANEL�ALARM�WINDOW�..........................................................................................................�41�FIGURE�71�LOCAL�PANEL�SETTINGS�WINDOW�......................................................................................................�42�FIGURE�70�LOCAL�PANEL�SETTINGS�PASSWORD�POPUP�WINDOW�......................................................................�42�FIGURE�72�POPUP�KEYBOARD�FOR�VALUE�INPUT�.................................................................................................�43�FIGURE�73�CARGO�PUMP�1�SETTINGS�WINDOW�..................................................................................................�44�FIGURE�74�CARGO�PUMP�2�SETTINGS�WINDOW�..................................................................................................�44�FIGURE�75�STRIPPING�PUMP�SETTINGS�WINDOW�................................................................................................�45�FIGURE�76�SYSTEM�SETTINGS�WINDOW�...............................................................................................................�45�FIGURE�77�LOCAL�PANEL�TREND�WINDOW�..........................................................................................................�46� �
Page 6 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
1. GENERAL DESCRIPTION
The CARGO WATCH II system is designed for Cargo Pump Controlling and Cargo
Pumps Conditions Monitoring. The system comprises 3 pieces of motor starter cabinet, 1
piece of controller cabinet and 1 piece of 15” touch screen located in Cargo Control Room.
Each of motor starter cabinets includes a soft starter for hydraulic pump motor starting.
Controller cabinet includes controlling and monitoring unit (5.7” touch screen). The system
can be controlled by locally manual from controller cabinet and also locally from 5.7” touch
screen on the controller cabinet. 15” touch screen is used with customized GUI1 to have a user
friendly and compact design for controlling and monitoring of all the system components.
With an option of access to all major system parameters such as alarm set points through the
graphical display unit, system can be easily adjusted according to system components
characteristics. All system components are approved and tested for marine use.
2. INSTALLATION INSTRUCTIONS
� Installation of the control system must be executed by the yard in accordance with
valid drawings.
� It is important that all the wires are connected according to electrical drawings.
3. ADJUSTMENT
� Adjustment points are the alarm set points, analog and digital ranges for pressure,
temperature, level sensors, valves’ feedbacks and throttle valves controller and
feedback signals. Final adjustment will be done during commissioning by Yard.
4. COMMISSIONING
� Check that all connections are done in accordance with the drawings.
� Dry-test the system without running the electrical motor connected to pump/pumps.
� Full function test of the system with the electrical motor running.
� Enter set points according to the desired timing settings for alarms, alarms set points
and function delays.
1 Graphical User Interface
Page 7 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
5. OPERATION BASICS 5.1. General
The CARGO WATCH II control system is capable of controlling and monitoring all the
components involved in the external cargo pumps system depending on the components that
are used in. The system is designed for safe and easy operation in order to ensure proper
monitoring and operation of the related equipment. If remote operated equipment is used it is
possible to have semi automatic start and stop of the pumps, valves and heaters. All major
functions are operated and monitored from the control panels with feedbacks. System can be
controlled from 3 independent station which are local cabinet, local operator panel (5.7’’
touch screen) and Remote operator panel (15’’ touch screen). While the control is under a
station other stations will be only the monitoring element for the system.
� The controlled components consist of;
o 3 pieces of 230kW HPP Unit Drive Motors
o 1 piece of 11kW Hydraulic Cool and Circulation Pump
o 1 piece of 3,5kW Hydraulic Filter and Circulation Pump
o 2 pieces of 8,6 kW Sea Water Cooling Pumps
o 2 pieces of 3,5 kW Fresh Water Cooling Pumps
o 2 pieces of 8,6 kW Buffer Liquid Circulation Pump
o 2 pieces of 6 kW Hydraulic Oil Haters
o 4 pieces of proportional valves
o 4 pieces of solenoid valves
� The monitored components consist of;
o 3 pieces of HPP Unit Drive Motors Conditions
o 8 pieces of Auxiliary Pumps Conditions
o 2 pieces of Hyd. Oil Heater Conditions
o 3 pieces of proportional valves feedback positions
o 6 pieces of valves feedbacks
o 8 pieces of filters feedbacks
o 4 pieces of Hydraulic Oil tank level and temperature feedbacks
o 1 piece of Hyd. System Pressure alarm feedback
Page 8 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
o 15 pieces of Cargo Pumps Temperature Feedbacks
o 6 pieces of Cargo Pumps Pressure Feedbacks
o 3 pieces of Cargo Pumps Speed Feedbacks
5.2. Control panels
� The operator panels are available for the system as a suite of HMI solutions. The
controller system comprises 2 pieces of control panel, 1 of 5.7” touch screen located
on controller panel, 1 of 15” touch screen located in cargo control room.
� Controlling and monitoring of the system is made via operator panels
� Remote controllable valves, motors, pumps, and heaters
� Alarms are monitored from the operators panels alarm page
5.2.1. Remote Panel
Remote operator panel is 15” touch screen controlling and monitoring equipment for the
system. Remote panel control access is permitted from the local operator panel.
5.2.1.1. Main Window
Figure 1 Remote Panel Main Window
Page 9 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Main window includes shortcuts to Operation window, Cargo Pumps window, Alarm
Page (animated with red color on alarm states) and Settings window which has the allowance
for only the service engineer. If the local cabinet or the local operator panel is in operation
warnings on the main window for the controller will be seen easily. From the question mark
symbol system info popup window can be seen as below figure 2.
Figure 2 System Info Popup Window
Page 10 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
HYDRAULIC OPERATION
CARGOPUMP 2
STRIPPINGPUMP
FLOWVALVE 1
CARGOPUMP 1
0-315 bar
P. FILTER 1 P. FILTER 2 P. FILTER 3
P. FILTER 4PRESSUREVALVE
R. FILTER 1 R. FILTER 2 R. FILTER 3
R. FILTER 4
HYD. OILTANK TEMP.
HYD. OIL TANKHEATER 1 & 2
SUCTIONVALVE 1
SUCTIONVALVE 2
SUCTIONVALVE 3
DRAINVALVE 1
DRAINVALVE 4
HYD.PUMP 1 HYD.PUMP 2 HYD.PUMP 3
FLOW VALVE 4
HYD. COOL &CIRCULATION
PUMP
HYD. FILTER &CIRCULATION
PUMP
Hyd.Pump 2Running Hours
Hrs
Hyd.Pump 1Running Hours
Hrs
Hyd.Pump 3Running Hours
Hrs
FLOWVALVE 2
FLOWVALVE 3
DRAINVALVE 2
DRAINVALVE 3
MMM
RUNNING RUNNING RUNNING RUNNING RUNNINGHEATING
RETURN BALLVALVE 1
RETURN BALLVALVE 2
HYD. PUMPSDRAIN VALVE
CARGO PUMP 1RPM
CARGO PUMP 2RPM
STRIPPING PUMPRPM SP
AP
SP
AP
SP
AP
HYDRAULICSYSTEM PRESSURE
HP3HP1 HP2
5.2.1.2. Hydraulic Operation Window All of the system controllable and monitor able devices can be controlled and monitored
from the Hydraulic Operation window.
On window, cargo pumps instantaneous speed, hydraulic pumps running hours,
proportional valves set positions and actual positions (feedback positions), hydraulic system
pressure, hydraulic oil tank temperature, filters situations, manual controllable valves
situations, and auxiliary pumps conditions can be seen.
By touching the cyan back grounded icons operator can reach the popup windows for
controllable devices.
From Cargo Pumps icons operator can reach Cargo Pump1, Cargo Pump 2, and Stripping
Pump temperature and pressure values. Operator can also adjust the speed of the Cargo pumps
by using proportional valves position increment or decrement. Each of the cargo pumps
Figure 3 Remote Panel Hydraulic Operation Window
Figure 4 Cargo Pumps Touch places on window
Page 11 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
CARGO PUMP 1
BEARING TEMP.1
BEARING TEMP.2
BEARING TEMP.3
SPEED
CARGO MEDIA PRESSURE & TEMP.
SUCTION PRESSURE & TEMP.
RUNNING HOURS
FLOW VALVE 1
SPEEDADJUSTMENT
SP
AP
popup window have the alarm banner for itself. If the alarms for the temperature and pressure
values are active indicating values will get red color. When cargo pumps are running
animated arrows will be visible. Running hours of the Cargo Pumps can be seen on the popup
windows.
Figure 5 Cargo Pump 1 Popup Window
Page 12 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
STRIPPING PUMP
SPEEDADJUSTMENT
BEARING TEMP.1
BEARING TEMP.2
BEARING TEMP.3
SPEED
CARGO MEDIA PRESSURE & TEMP.
SUCTION PRESSURE & TEMP.
RUNNING HOURS
FLOW VALVE 3
SP
AP
CARGO PUMP 2
SPEEDADJUSTMENT
BEARING TEMP.1
BEARING TEMP.2
BEARING TEMP.3
SPEED
CARGO MEDIA PRESSURE & TEMP.
SUCTION PRESSURE & TEMP.
RUNNING HOURS
FLOW VALVE 2
SP
AP
Figure 6 Cargo Pump 2 Popup Window
Figure 7 Stripping Pump Popup Window
Page 13 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Operator can see the proportional valves set positions and actual (feedback) positions
from the hydraulic operation window during operations.
Operator can see the speed of the cargo pumps from hydraulic operation window and
alarm point for the speed set on the indicators and colored with red.
Filter Situations can be seen from the hydraulic operation window. When a filter clogged
the filter color will get red.
Hydraulic system pressure can be seen and controlled
from hydraulic operation window. Proportional pressure
valve position is monitored on the window and pressure of
the system is controlled by increment and decrement of the
valve position. If the alarm for the system pressure is active
value for the hydraulic system pressure will get red color.
Figure 8 Proportional Valves Positions
Figure 9 Cargo Pumps Speed Feedback
Figure 10 Filter situations
Figure 11 Hydraulic System Pressure
Page 14 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Solenoids valves popup window will be visible when the operator touches the cyan back
grounded places on the window. Operator can control the solenoids valves from the popup
window of drain valves. These valves have no feedback for situations opened/closed. But
the operator can see the open or close order from the open, close text colored with green.
By touching the cyan back grounded place on the window the hydraulic main pumps
popup windows will be visible for the hydraulic main pumps control. By pressing the green
square specified with HP1 text will show the ready conditions for the main pumps. Ready
conditions are;
o Power available
o Suction valve of the pump is opened
o Hydraulic oil tank level not low
o Hydraulic oil tank temperature not low
o Emergency stop not active
Figure 12 Solenoids Valves Touch Places on Window
Figure 13 Drain Valves Popup Window
Page 15 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Operator will give the order for power request from the popup window for each main pump.
Operator can see the start or stop order from the start, stop text colored with green. And the
power request order from the power request on, power request off circle colored with green
If ready conditions will be satisfied, controller will let for start operation of the main
pumps. The running text and arrows will be visible when pumps are running.
Figure 14 Hydraulic Main Pumps Touch Places on Window
Figure 16 Hydraulic Main Pumps Popup Window
Figure 15 Hydraulic Main Pumps Ready Conditions Popup Window
Page 16 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Suction valves feedbacks can be seen from the window if a suction valve is opened, red
colored shapes will get green color on valve icons.
From cyan back grounded place for heaters operator can reach the popup window for
controlling of heaters. For both two heaters there is one popup control window. Operator can
see the start or stop order from the start, stop text colored with green. Heating text will be
visible while feedback received from heaters. Heaters start and stop functions are controlled
automatically for undesired temperature values for the hydraulic oil.
Figure 17 Suction Valves on Window
Figure 18 Hydraulic Oil Heater Touch place on Window
Figure 19 Hydraulic Oil Heater Popup Window
Figure 20 Hydraulic Oil Tank Temperature Indicator
Page 17 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
From the indicator for hydraulic oil tank temperature operator can see temperature for the
Hydraulic oil. If the alarm for the hydraulic oil temperature is active, value for the hydraulic
system pressure will get red color.
On the operation window feedbacks of the valves are simulated for the opened or closed
situation.
From cyan back grounded place for auxiliary pumps operator can reach the popup
window for controlling of auxiliary pumps. There are only two auxiliary pump controls on the
Figure 21 Valves Feedback
Figure 22 Auxiliary Pumps Popup Touch Places
Page 18 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
hydraulic operation window. Other auxiliary pumps are controlled from the Auxiliary Pumps
window.
Hydraulic cool & circulation pump and hydraulic filter &circulation pumps are protected
for dry run when the oil level of the hydraulic oil tank is low pumps will be stopped
automatically. Ready condition for these two pumps is the hydraulic oil tank low level.
On the operation window running hours for the main hydraulic pumps can be seen for
unexpected running hours of the main pumps.
Figure 24 HCC Pump Popup Window Figure 23 HFC Pump Popup Window
Page 19 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
From all window operator can reach Menu and Back button for fast responses. From
Menu button operator can reach all separate monitoring and controlling windows easily
By pressing the menu button operator can reach the menu, then operator can choose
window that is wanted. Operator can choose;
� Trend window
� Alarm Page (toggles to alarm page ,back color of the icon is
animated with red color when any alarm is active)
� Settings (display password for settings popup window)
� Auxiliary Pumps(toggles to auxiliary pumps window)
� Operation (toggles to hydraulic operation window)
� Cargo Pumps(toggles to cargo pumps window)
� Back to Main Menu(toggles to main menu window)
When settings button on main window or on menu window is
pressed password popup window will be visible. By pressing white back grounded place on password popup window, popup keyboard will be visible
Figure 25 Menu and Back Buttons
Figure 27 Remote Panel Menu Window
The password can be entered by the help of the keypad. This password is only for service engineers who are authorized for the commissioning of the system.
Figure 26 Settings Password Popup Window
Page 20 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
5.2.1.3. Cargo Pumps Window
From cargo pumps window operator can reach all the values for cargo pumps like
temperature, pressure, speed, proportional valve positions and running hours. Operator has
ability to make speed adjustment by increasing or decreasing valve position. All of the system
pumps and heaters on/off states are seen from the window. For each pump values are getting
red when it is in alarm state which is set from the settings window. Alarm banners are
indicating the related pumps alarms only.
Figure 28 Remote Panel Cargo Pumps Window
Figure 30 Speed Adjust ButtonsFigure 29 Alarm State Animated Value
Page 21 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
5.2.1.4. Alarm Window
Alarms are monitored when active ACK2 button will stop the buzzer. Reset button will
delete the alarm message from the alarm list if the alarm state is not active. By up and down
arrow buttons operator can reach the alarms that are not fit on the list. Any of the alarms can’t
be reset automatically operator must see the alarm and reset from the alarm window. Alarm
list’s Columns are;
� Date of the alarm
� Time of the alarm
� ACK time of the alarm
� Alarm message
� State
2 Acknowledge
Figure 31 Remote Panel Alarm Window
Page 22 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
5.2.1.5. Settings Window
Alarm points for all analog variables can be set from the settings window. By pressing on
the value popup keyboard will be visible and input of the new value will be available.
Running hours of the hydraulic main pumps and cargo pumps can be reset from the window.
Temperature points for automatic start of the heaters can be set from the window. If the input
value for the points are not in the range of the sensor, warning about the range will be visible.
Figure 32 Remote Panel Settings Window
Figure 33 Popup Keyboard for Value Input
Page 23 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
5.2.1.6. Trend Window
In the trend window operator can see Cargo Pumps speed in RPM and Throttle valve
feedback positions. Operator can reach past log for the variables that trend graph records.
Figure 34 Remote Panel Trend Window
Page 24 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
5.2.1.7. Auxiliary Pumps Window
From auxiliary pump window operator can control and see conditions for;
� Sea water cooling pump 1
� Sea water cooling pump 2
� Fresh water cooling pump 1
� Fresh water cooling pump 2
� Buffer liquid circulation pump 1
� Buffer liquid circulation pump 2
By pressing cyan back grounded places on the window popup windows will be visible for
the pressed pump. Operator can see the start or stop order from animated text color of the
start/stop button will get green (order) or red (no order) from the popup window. Animated
arrows on the pumps will be visible when related pump is running.
Figure 35 Remote Panel Auxiliary Pump Window
Page 25 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Figure 36 Sea Water Cooling Pump 1 Popup Window
Figure 37 Sea Water Cooling Pump 2 Popup Window
Figure 38 Fresh Water Cooling Pump 1 Popup Window
Figure 39 Fresh Water Cooling Pump 2 Popup Window
Figure 40 Buffer Liquid Circulation Pump 1 Popup Window
Figure 41 Buffer Liquid Circulation Pump 2 Popup Window
Page 26 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
5.2.2. Local Panel Remote operator panel is 5.7” touch screen controlling and monitoring equipment for the
system. Local panel control access is permitted from the local operator panel.
5.2.2.1. Main Window
Main window includes shortcuts to Operation window, Cargo Pumps window, Alarm
Page (animated with red color on alarm states) and Settings window which has the allowance
for only the service engineer. If the local cabinet, the remote operator panel or the local panel
is in operation warnings on the main window for the controller will be seen easily. From
operation modes buttons operator can change the control place with password protect like
local operator panel or remote operator panel. When pressed on local panel activate or remote
panel activate password popup will be visible for give or take over command. Local cabinet
control will be available from the switch that is positioned on control cabinet. While the
Local Cabinet is active, other control panels will be only the monitoring station for the
system
Figure 42 Local Panel Main Window
Page 27 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
PROJECT No TRM-PCM V.01
PUMP CONTROL AND MONITORING v.01APPLICATION
SHIPYARD GISAN
HULL No NB48
From the question mark symbol system info popup window can be seen as below figure
43.
When local panel is active, remote panel is only used for monitoring device and local
panel will be the controller panel. Likely the remote panel is active local panel is only used
for monitoring device and remote will be the controller panel.
From Password popup window for control access operator can change the controlling
device like local operator panel or remote operator panel. By pressing white back grounded
place on the popup window, popup keyboard for the password input will be visible.
Figure 44 Password Popup Window for Control Access
Figure 43 Local Panel System Info Popup Window
PRPRPRPRROJOJOJOO ECECECECECT TT NoNoNoNoNo
APAPAPAPAPPLPLPPLP ICICICICCATATATATA IOIOIOIOONNNNN
SHSHSSHS IPIPIPIPPYAYAYAYAARDRDRRDR
HUHUHULLLL NNNNNooooo
Page 28 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
When operator enters the right password for control access change, animated buttons will
turn into green for indicating active operator panel.
5.2.2.2. Operation Window
Operation window includes the shortcuts for four pages of operation windows. By
pressing on shortcuts operator can reach four operation pages separately.
Figure 45 Popup Keyboard
Figure 46 Local Panel Operation Window
Page 29 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
From all window operator can reach Menu and Back button for fast responses. From
Menu button operator can reach all separate monitoring and controlling windows easily
By pressing the menu button operator can reach the menu, then operator can choose
window that is wanted. Operator can choose;
� Trend window
� Alarm Page (toggles to alarm page ,back color of the icon is animated with red color
when any alarm is active)
� Operation (toggles to hydraulic operation window)
� Cargo Pumps(toggles to cargo pumps window)
� Back to Main Menu(toggles to main menu window)
Figure 47 Local Panel Menu and Back Buttons
Figure 48 Local Panel Menu Window
Page 30 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
5.2.2.2.1. Operation Window 1
From operation 1 window operator can control and see conditions for;
� Main hydraulic pump 1
� Main hydraulic pump 2
� Main hydraulic pump 3
� Hydraulic Cool & Circulation Pump
� Hydraulic Filter & Circulation Pump
� Hydraulic system pressure
By pressing buttons for the controlled equipments on the window popup windows will be
visible for the pumps control. Operator can see the start or stop order from animated text color
of the start/stop button will get green (order) or red (no order) from the popup window.
Animated ON text will be visible on the button of the controlled pumps when pumps are
running.
Figure 49 Local Panel Operation 1 Window
Page 31 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
On the window operator has ability to see the situation of the controlled equipments. By
pressing the green square positioned on the popup window of the hydraulic pumps, texts will
show the ready conditions for the main pumps. Ready conditions are;
o Power available
o Suction valve of the pump is opened
o Hydraulic oil tank level not low
o Hydraulic oil tank temperature not low
o Emergency stop not active Operator will give the order for power request from the popup window for each main
pump. Operator can see the start or stop order from the start, stop text colored with green.
And the power request order from the power request on, power request off circle colored with
green.
If ready conditions will be satisfied, controller will let for start operation of the main
pumps. Animated ON text will be visible on the button of the controlled pumps when pumps
are running.
Figure 50 Local Panel Hydraulic Main Pumps Popup Window
Figure 51 Hydraulic Main Pumps Ready Conditions Popup Window
Page 32 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Hydraulic system pressure can be seen and controlled from operation window 1.
Proportional pressure valve position is monitored on the window and pressure of the system is
controlled by increment and decrement of the valve position. If the alarm for the system
pressure is active value for the hydraulic system pressure will get red color.
Hydraulic cool & circulation pump and hydraulic filter &circulation pumps are protected
for dry run when the oil level of the hydraulic oil tank is low pumps will be stopped
automatically. Ready condition for these two pumps is the hydraulic oil tank low level.
Figure 52 Local Panel HCC Pump Popup Window
Figure 53 Local Panel HFC Pump Popup Window
Page 33 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
5.2.2.2.2. Operation Window 2
From operation 2 window operator can control and see conditions for;
� Sea water cooling pump 1
� Sea water cooling pump 2
� Fresh water cooling pump 1
� Fresh water cooling pump 2
� Buffer liquid circulation pump 1
� Buffer liquid circulation pump 2
By pressing buttons for the controlled pumps on the window pumps popup windows will
be visible for the pumps control. Operator can see the start or stop order from animated text
color of the start/stop button will get green (order) or red (no order) from the popup window.
Animated ON text will be visible on the button of the controlled pumps when pumps are
running.
Figure 54 Local Panel Operation 2 Window
Page 34 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Figure 56 Local Panel Sea Water Cooling Pump 2 Popup Window
Figure 57 Local Panel Fresh Water Cooling Pump 1 Popup Window
Figure 58 Local Panel Fresh Water Cooling Pump 2 Popup Window
Figure 59 Local Panel Buffer Liquid Circulation Pump 1 Popup Window
Figure 60 Local Panel Buffer Liquid Circulation Pump 2 Popup Window
Figure 55 Local Panel Sea Water Cooling Pump 1 Popup Window
Page 35 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
5.2.2.2.3. Operation Window 3 From operation 3 window operator can control
� Hydraulic Oil heater 1 & 2
� Drain Valve 1
� Drain Valve 2
� Drain Valve 3
� Drain Valve 4
By pressing buttons for the controlled equipment on the window, popup windows will be
visible for the heaters and valves control. Operator can see the open or close order from
animated text color of the open/close button will get green (order) or red (no order) from the
popup window of drain valves. These valves have no feedback for situations
opened/closed.
For the heaters control, operator can see the start or stop order from animated text color
of the start/stop button will get green (order) or red (no order) from the popup window.
Animated ON text will be visible on the button of the controlled heaters when running. For
Figure 61 Local Panel Operation 3 Window
Page 36 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
both two heaters there is one popup control window. Heaters start and stop functions are
controlled automatically for undesired temperature values for the hydraulic oil.
From the indicator for hydraulic oil tank temperature operator can see temperature for the
Hydraulic oil. If the alarm for the hydraulic oil temperature is active, value for the hydraulic
system pressure will get red color.
Figure 62 Local Panel Drain Valve Popup Window
Figure 63 Local Panel Hydraulic Oil Heater Popup Window
Page 37 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
5.2.2.2.4. Operation Window 4
Figure 64 Local Panel Operation Window 4
From operation 4 window operators can control and see conditions for;
� Suction valve 1
� Suction valve 2
� Suction valve 3
� Return ball valve 1
� Return ball valve 2
� Hydraulic pumps drain valve
On the operation 4 window feedbacks of the valves are simulated for the opened or
closed situation.
Page 38 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
5.2.2.3. Cargo Pumps Window
Figure 65 Local Panel Cargo Pumps Window
Operator can see the speed of the cargo pumps from cargo pumps window and
alarm point for the speed set on the indicators and colored with red.
By touching the cyan back grounded icons operator can reach the windows for Cargo
Pump1, Cargo Pump 2, and Stripping Pump temperature and pressure values.
Page 39 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
5.2.2.3.1. Cargo Pump 1 Window
Figure 66 Local Panel Cargo Pump 1 Window
From cargo pumps windows operator can reach all the values for cargo pumps like
temperature, pressure, speed, proportional valve positions and running hours. Operator has
ability to make speed adjustment by increasing or decreasing valve position.
Operator can see the proportional valves set positions and actual (feedback) positions
from the Cargo Pumps window during operations. On the cargo pumps windows running
hours for the main hydraulic pumps can be seen for unexpected running hours of the main
pumps.
Each of the cargo pumps window have the alarm banner for itself. If the alarms for the
temperature and pressure values are active indicating values will get red color.
Page 40 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
5.2.2.3.2. Cargo Pump 2 Window
Figure 67 Local Panel Cargo Pump 2 Window
5.2.2.3.3. Stripping Pump Window
Figure 68 Local Panel Stripping Pump Window
Page 41 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
5.2.2.4. Alarm Window
Figure 69 Local Panel Alarm Window
Alarms are monitored when active ACK3 button will stop the buzzer. Reset button will
delete the alarm message from the alarm list if the alarm state is not active. By up and down
arrow buttons operator can reach the alarms that are not fit on the list. Any of the alarms can’t
be reset automatically operator must see the alarm and reset from the alarm window. Alarm
list’s Columns are;
� Time of the alarm
� Alarm message
3 Acknowledge
Page 42 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
5.2.2.5. Settings Window When settings button on main window, password popup window will be visible. By
pressing white back grounded place on password popup window, popup keyboard will be visible
Figure 71 Local Panel Settings Window
Figure 70 Local Panel Settings Password Popup Window
The password can be entered by the help of the keypad. This password is only for service engineers who are authorized for the commissioning of the system.
Page 43 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
By touching the cyan back grounded icons operator can reach the windows for Cargo
Pump1, Cargo Pump 2, and Stripping Pump settings window. By touching the button for
System settings running hours, Hydraulic oil tank alarms and Hydraulic oil pressure alarms
can be adjusted.
Alarm points for all analog variables can be set from the settings window. By pressing on
the value popup keyboard will be visible and input of the new value will be available.
Running hours of the hydraulic main pumps and cargo pumps can be reset from the window.
Temperature points for automatic start of the heaters can be set from the window. If the input
value for the points are not in the range of the sensor, warning about the range will be visible.
Figure 72 Popup Keyboard for Value Input
Page 44 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
5.2.2.5.1. Cargo Pump 1 Settings Window
Figure 73 Cargo Pump 1 Settings Window
5.2.2.5.2. Cargo Pump 2 Settings Window
Figure 74 Cargo Pump 2 Settings Window
Page 45 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
5.2.2.5.3. Stripping Pump Settings Window
Figure 75 Stripping Pump Settings Window
5.2.2.5.4. System Settings Window
Figure 76 System Settings Window
Page 46 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
5.2.2.6. Trend Window
Figure 77 Local Panel Trend Window
In the trend window operator can see Cargo Pumps speed in RPM and Throttle valve
feedback positions.
6. OPERATION MODES
6.1. Local (manual) Control Operation Local Control operation can be done from the main control cabinet. By using pushbuttons,
switches and potentiometers, operators can control the equipments on the system
When Local Control operation is active, local control panel and remote control panel are
only the monitoring device controlling of the equipments will not be available from the touch
screen control panels.
6.2. Local Control Panel Operation When operation command from the main cabinet is given to the PLC controller local
control panel will be in command for control. If it is not in command, operator can take
command by using activation buttons from the main window of the Local Control Panel.
Page 47 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
When Local Control Panel is active for control of the system, Local (manual) Operation
from main cabinet and remote control operation will not be available. Remote control panel
will be only the monitoring device for the system while local control panel is active.
6.3. Remote Control Panel Operation When operation command from the main cabinet is given to the PLC controller remote
control panel will be in command for control. If it is not in command, operator can give
command by using activation buttons from the main window of the Local Control Panel.
When Remote Control Panel is active for control of the system, Local (manual) Operation
from main cabinet and local control operation will not be available. Local control panel will
be only the monitoring device for the system while remote control panel is active.
7. ALARM LIST
� ALARM�/�MESSAGE�DESCRIPTION� EXPLANATION� REQUIRED�ACTION�
� Main�hydraulic�pumps�alarms�
1� Hydraulic�main�pump�1�overload� Main�pump�1�electric�motor�is�overloaded� Stop�motor�and�check�electric�motor
2� Hydraulic�main�pump�1�fault� Main�pump�1�electric�motor�is�faulty� Stop�motor�and�check�electric�motor
3� Hydraulic�main�pump�1�on�fail� Main�pump�1��electric�motor�is�not�started Check�the�cabling�and�electric�motor
4� Hydraulic�main�pump�1�off�fail� Main�pump�1�electric�motor�is�not�stopped�
Check�the�cabling�and�electric�motor
5� Hydraulic�main�pump�2�overload� Main�pump�2�electric�motor�is�overloaded� Stop�motor�and�check�electric�motor
6� Hydraulic�main�pump�2�fault� Main�pump�2�electric�motor�is�faulty� Stop�motor�and�check�electric�motor
7� Hydraulic�main�pump�2�on�fail� Main�pump�2�electric�motor�is�not�started� Check�the�cabling�and�electric�motor
8� Hydraulic�main�pump�2�off�fail� Main�pump�2�electric�motor�is�not�stopped�
Check�the�cabling�and�electric�motor
9� Hydraulic�main�pump�3�overload� Main�pump�3�electric�motor�is�overloaded� Stop�motor�and�check�electric�motor
10� Hydraulic�main�pump�3�fault� Main�pump�3�electric�motor�is�faulty� Stop�motor�and�check�electric�motor
11� Hydraulic�main�pump�3�on�fail� Main�pump�3�electric�motor�is�not�started� Check�the�cabling�and�electric�motor
12� Hydraulic�main�pump�3�off�fail� Main�pump�3�electric�motor�is�not�stopped�
Check�the�cabling�and�electric�motor
13� �� �� ��
� Hydraulic�oil�heater�alarms�
14� Hydraulic�oil�heater�1�on�fail� Hydraulic�oil�tank�heater�1�is�not�started� Check�the�cabling�and�heater�
15� Hydraulic�oil�heater�1�off�fail� Hydraulic�oil�tank�heater�1�is�not�stopped� Check�the�cabling�and�heater�
16� Hydraulic�oil�heater�2�on�fail� Hydraulic�oil�tank�heater�2�is�not�started� Check�the�cabling�and�heater�
17� Hydraulic�oil�heater�2�off�fail� Hydraulic�oil�tank�heater�1�is�not�stopped� Check�the�cabling�and�heater�
Page 48 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
18� �� �� ��
� Filters�alarms�
19� Pressure�filter�1�clugged� Pressure�filter�1�is�blocked� Check�and�clean�the�filter�
20� Pressure�filter�2�clugged� Pressure�filter�2�is�blocked� Check�and�clean�the�filter�
21� Pressure�filter�3�clugged� Pressure�filter�3�is�blocked� Check�and�clean�the�filter�
22� Pressure�filter�4�clugged� Pressure�filter�4�is�blocked� Check�and�clean�the�filter�
23� Return�filter�1�clugged� Return�filter�1�is�blocked� Check�and�clean�the�filter�
24� Return�filter�2�clugged� Return�filter�2�is�blocked� Check�and�clean�the�filter�
25� Return�filter�3�clugged� Return�filter�3�is�blocked� Check�and�clean�the�filter�
26� Return�filter�4�clugged� Return�filter�4�is�blocked� Check�and�clean�the�filter�
27� �� �� ��
� Hydraulic�oil�tank�alarms�
28� Hydraulic�oil�tank�low�level�alarm� Hydraulic�oil�level�is�low� Check�hydraulic�oil�tank�and�fill�with�oil�
29� Hydraulic�oil�tank�low�low�level�alarm�
Hydraulic�oil�level�is�too�low� Check�hydraulic�oil�tank�and�fill�with�oil�
30� Hydraulic�oil�tank�low�temperature�alarm�
Hydraulic�oil�temperature�is�low� Check�hydraulic�oil�tank�temp�and�heaters�
31� Hydraulic�oil�tank�high�temperature�alarm�
Hydraulic�oil�temperature�is�high� Check�hydraulic�oil�tank�temp�and�heaters�
32� �� �� ��
� Hydraulic�cooling�and�circulation�pump�alarms�
33� Hydraulic�cooling�and�circulation�pump�overload�
Hydraulic�cooling�and�circulation�pump�electric�motor�is�overloaded�
Stop�motor�and�check�electric�motor
34� Hydraulic�cooling�and�circulation�pump�on�fail�
Hydraulic�cooling�and�circulation�pump�electric�motor�is�not�started�
Check�the�cabling�and�electric�motor
35� Hydraulic�cooling�and�circulation�pump�off�fail�
Hydraulic�cooling�and�circulation�pump�electric�motor�is�not�stopped�
Check�the�cabling�and�electric�motor
36� �� �� ��
� Hydraulic�filter�and�circulation�pump�
37� Hydraulic�filter�and�circulation�pump�overload�
Hydraulic�filter�and�circulation�pump�electric�motor�is�overloaded�
Stop�motor�and�check�electric�motor
38� Hydraulic�filter�and�circulation�pump�on�fail�
Hydraulic�filter�and�circulation�pump�electric�motor�is�not�started�
Check�the�cabling�and�electric�motor
39� Hydraulic�filter�and�circulation�pump�off�fail�
Hydraulic�filter�and�circulation�pump�electric�motor�is�not�stopped�
Check�the�cabling�and�electric�motor
40� �� �� ��
� Sea�water�cooling�pumps�alarms�
41� Sea�water�cooling�pump�1�overload� Sea�water�cooling�pump�1�electric�motor�is�overloaded�
Stop�motor�and�check�electric�motor
42� Sea�water�cooling�pump�1�on�fail� ����water�cooling�pump�1�electric�motor�is�not�started�
Check�the�cabling�and�electric�motor
Page 49 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
43� Sea�water�cooling�pump�1�off�fail� Sea�water�cooling�pump�1�electric�motor�is�not�stopped�
Check�the�cabling�and�electric�motor
44� Sea�water�cooling�pump�2�overload� Sea�water�cooling�pump�2�electric�motor�is�overloaded�
Stop�motor�and�check�electric�motor
45� Sea�water�cooling�pump�1�on�fail� Sea�water�cooling�pump�2�electric�motor�is�not�started�
Check�the�cabling�and�electric�motor
46� Sea�water�cooling�pump�1�off�fail� Sea�water�cooling�pump�2�electric�motor�is�not�stopped�
Check�the�cabling�and�electric�motor
47� �� �� ��
� Fresh�water�cooling�pumps�alarms�
48� Fresh�water�cooling�pump�1�overload�
Fresh�water�cooling�pump�1�electric�motor�is�overloaded�
Stop�motor�and�check�electric�motor
49� Fresh�water�cooling�pump�1�on�fail� Fresh�water�cooling�pump�1�electric�motor�is�not�started�
Check�the�cabling�and�electric�motor
50� Fresh�water�cooling�pump�1�off�fail� Fresh�water�cooling�pump�1�electric�motor�is�not�stopped�
Check�the�cabling�and�electric�motor
51� Fresh�water�cooling�pump�2�overload�
Fresh�water�cooling�pump�2�electric�motor�is�overloaded�
Stop�motor�and�check�electric�motor
52� Fresh�water�cooling�pump�2�on�fail� Fresh�water�cooling�pump�2�electric�motor�is�not�started�
Check�the�cabling�and�electric�motor
53� Fresh�water�cooling�pump�1�off�fail� Fresh�water�cooling�pump�2�electric�motor�is�not�stopped�
Check�the�cabling�and�electric�motor
54� �� �� ��
� Buffer�liquid�circulation�pumps�alarms�
55� Buffer�liquid�circulation�pump�1�overload�
Buffer�liquid�circulation�pump�1�electric�motor�is�overloaded�
Stop�motor�and�check�electric�motor
56� Buffer�liquid�circulation�pump�1�on�fail�
Buffer�liquid�circulation�pump�1�electric�motor�is�not�startes�
Check�the�cabling�and�electric�motor
57� Buffer�liquid�circulation�pump�1�off�fail�
Buffer�liquid�circulation�pump�1�electric�motor�is�not�stopped�
Check�the�cabling�and�electric�motor
58� Buffer�liquid�circulation�pump�2�overload�
Buffer�liquid�circulation�pump�2�electric�motor�is�overloaded�
Stop�motor�and�check�electric�motor
59� Buffer�liquid�circulation�pump�2�on�fail�
Buffer�liquid�circulation�pump�2�electric�motor�is�not�started�
Check�the�cabling�and�electric�motor
60� Buffer�liquid�circulation�pump�2�off�fail�
Buffer�liquid�circulation�pump�2�electric�motor�is�not�stopped�
Check�the�cabling�and�electric�motor
61� �� �� ��
� Cargo�pump�1�alarms�
62� Cargo�pump�1�bearing�temperature�1�fail�
Cargo�pump�1�bearing�temperature�1�exceeded�the�alarm�set�point�
Check�the�sensor��
63� Cargo�pump�1�bearing�temperature�2�fail�
Cargo�pump�1�bearing�temperature�2�exceeded�the�alarm�set�point�
Check�the�sensor��
Page 50 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
64� Cargo�pump�1�bearing�temperature�3�fail�
Cargo�pump�1�bearing�temperature�3�exceeded�the�alarm�set�point�
Check�the�sensor��
65� Cargo�pump�1�cargo�media�pressure�fail�
Cargo�pump�1�cargo�media�pressure�exceeded�the�alarm�set�point�
Check�the�sensor��
66� Cargo�pump�1�cargo�media�temperature�fail�
Cargo�pump�1�cargo�media�temperature�exceeded�the�alarm�set�point�
Check�the�sensor��
67� Cargo�pump�1�suction�pressure�fail�� Cargo�pump�1�suction�pressure�exceeded�the�alarm�set�point�
Check�the�sensor��
68� Cargo�pump�1�suction�temperature�fail�
Cargo�pump�1�suction�temperature�exceeded�the�alarm�set�point�
Check�the�sensor��
69� Cargo�pump�1�speed�response�fail� Cargo�pump�1�speed�exceeded�the�alarm�set�point�
Check�the�sensor��
70� Cargo�pump�1�high�cargo�media�pressure�increase�rpm�;�blocked�
Cargo�pump�1�high�cargo�media�pressure�exceeded�the�set�point�for�rpm�block�
Check�the�sensor��
71� Cargo�pump�1�low�suction�pressure�increase�rpm�;�blocked�
Cargo�pump�1�low�suction�pressure�decreased�under�the�set�point�for�rpm�block�
Check�the�sensor��
72� �� �� ��
� Cargo�pump�2�alarms�
73� Cargo�pump�2�bearing�temperature�1�fail�
Cargo�pump�2�bearing�temperature�1�exceeded�the�alarm�set�point�
Check�the�sensor��
74� Cargo�pump�2�bearing�temperature�2�fail�
Cargo�pump�2�bearing�temperature�2�exceeded�the�alarm�set�point�
Check�the�sensor��
75� Cargo�pump�2�bearing�temperature�3�fail�
Cargo�pump�2�bearing�temperature�3�exceeded�the�alarm�set�point�
Check�the�sensor��
76� Cargo�pump�2�cargo�media�pressure�fail�
Cargo�pump�2�cargo�media�pressure�exceeded�the�alarm�set�point�
Check�the�sensor��
77� Cargo�pump�2�cargo�media�temperature�fail�
Cargo�pump�2�cargo�media�temperature�exceeded�the�alarm�set�point�
Check�the�sensor��
78� Cargo�pump�2�suction�pressure�fail�� Cargo�pump�2�suction�pressure�exceeded�the�alarm�set�point�
Check�the�sensor��
79� Cargo�pump�2�suction�temperature�fail�
Cargo�pump�2�suction�temperature�exceeded�the�alarm�set�point�
Check�the�sensor��
80� Cargo�pump�2�speed�response�fail� Cargo�pump�2�speed�exceeded�the�alarm�set�point�
Check�the�sensor��
81� Cargo�pump�2�high�cargo�media�pressure�increase�rpm�;�blocked�
Cargo�pump�2�high�cargo�media�pressure�exceeded�the�set�point�for�rpm�block�
Check�the�sensor��
82� Cargo�pump�2�low�suction�pressure�increase�rpm�;�blocked�
Cargo�pump�1�low�suction�pressure�decreased�under�the�set�point�for�rpm�block�
Check�the�sensor��
83� �� �� ��
� Stripping�pump�alarms�
84� Stripping�pump�bearing�temperature�1�fail�
Stripping�pump�bearing�temperature�1�exceeded�the�alarm�set�point�
Check�the�sensor��
Page 51 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
85� Stripping�pump�bearing�temperature�2�fail�
Stripping�pump�bearing�temperature�2�exceeded�the�alarm�set�point�
Check�the�sensor��
86� Stripping�pump�bearing�temperature�3�fail�
Stripping�pump�bearing�temperature�3�exceeded�the�alarm�set�point�
Check�the�sensor��
87� Stripping�pump�cargo�media�pressure�fail�
Stripping�pump�cargo�media�pressure�exceeded�the�alarm�set�point�
Check�the�sensor��
88� Stripping�pump�cargo�media�temperature�fail�
Stripping�pump�cargo�media�temperature�exceeded�the�alarm�set�point�
Check�the�sensor��
89� Stripping�pump�suction�pressure�fail�� Stripping�pump�suction�pressure�exceeded�the�alarm�set�point�
Check�the�sensor��
90� Stripping�pump�suction�temperature�fail�
Stripping�pump�suction�temperature�exceeded�the�alarm�set�point�
Check�the�sensor��
91� Stripping�pump�speed�response�fail� Stripping�pump�speed�exceeded�the�alarm�set�point�
Check�the�sensor��
92� Stripping�pump�high�cargo�media�pressure�increase�rpm�;�blocked�
Stripping�pump�high�cargo�media�pressure�exceeded�the�set�point�for�rpm�block�
Check�the�sensor��
93� Stripping�pump�low�suction�pressure�increase�rpm�;�blocked�
Stripping�pump�low�suction�pressure�decreased�under�the�set�point�for�rpm�block�
Check�the�sensor��
94� �� �� ��
� Hydraulic�system�pressure�alarms�
95� Hydraulic�system�pressure�h�gh�alarm�
Hydraulic�system�pressure�exceeded�the�alarm�set�point�
Check�the�sensor��
96� Hydraulic�system�pressure�low�alarm� Hydraulic�system�pressure�decreased�under�the�alarm�set�point�
Check�the�sensor��
97� �� �� ��
� Common�alarms�
98� Emergency�stop� One�of�the�emergency�stop�button�is�pressed�
Check�emergency�stop�buttons�
99� Replace�ram�battery� Plc�battery�is�ended� Replacement�needed(refer�to�plc�manual)�
100� �� �� ��
8. MAINTANENCE
Change the battery in the PLC every 2 years. Refer to PLC manual.
9. TROUBLE SHOOTING � Replace battery every 2 years or immediately when the BAT led on the power supply
is in red color. � Refer to PLC manual
Page 52 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
10. PLC MANUAL
Page 53 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Page 54 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Page 55 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Page 56 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Page 57 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Page 58 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Page 59 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Page 60 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Page 61 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Page 62 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Page 63 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Page 64 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Page 65 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Page 66 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Page 67 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Page 68 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Page 69 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Page 70 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Page 71 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Page 72 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Page 73 / 73
Rauf Orbay Cad. No:37 34944 Tuzla – �STANBUL Tel: (0216) 446 2328(pbx) Fax: (0216) 446 23 27
www.tr-marine.com info@tr-marine.com
Recommended