Plug fans with EC motor version 10/2009
The engineer’s choice
2
New Plug fans with EC motor
The newly improved ebm-papst Plug Fans meet the ever tougher specifications in air-conditioning
and ventilation. Our Plug Fans are designed for operation without scroll housing and for use in air-
conditioning units. Further fields of applikation are, for instance, cooling of power electronics and
various other applications in industry.
In view of the upcoming directives on minimum efficiencies, the overall efficiency of the fans was
optimised. On top of this, the acoustic characteristics of the new line were adjusted to more deman-
ding market requirements.
There are 8 sizes available, with their outer diameters ranging from 250 to 560 mm, which are
driven by energy-saving EC external rotor motors with drive capacities between 400 W and 6 kW.
The welded impellers with their 7 backward curved blades are made of aluminium as this mini-
mises the bearing load of the motors and maximises durability with high circumferential velocity.
The position of the impellers on the EC external-rotor motors has been optimised to in terms of
aerodynamics and installation requirements.
Additional, and for selecting the proper fan, you
can take advantage of the ebm-papst software
"Product Selector" with integrated “Black-Box"
module for integration in system configuration
programmes on customer side. For more de-
tailed information, simply ask your ebm-papst
contact!
3
Text for tenders 4
New Plug Fans with EC motor 2
Size 250 6
Size 280 10
Size 310 16
Size 355 18
Table of content
Size 400 22
Size 500 30
Size 450 26
Design for use in sanitation units, size 310 and 450 38
Accessories (inlet rings, air intake guard grilles) 42
Electrical connections 44
ebm-papst representatives & subsidiaries 48
Size 560 34
4
Text for tenders
EC Centrifugal fan modulesK3G 250 to K3G 560
ebm-papst high performance centrifugal fan modules
Single inlet; direct drive; 2D centrifugal impeller with circumferential
diffuser mounted on an electronically commutated external-rotor motor
with integrated electronics; backward curved impeller blades; inlet
nozzle made of galvanised sheet steel with pressure relief; complete
unit statically and dynamically balanced in two planes according to
DIN / ISO 1940 and to balancing quality G 6.3; EC external-rotor motor
with maintenance-free ball bearings and permanent lubrication; wide
voltage input 1~200-277V, 50/60 Hz respectively 3~380-480V,
50/60Hz; unit can be operated on all standard Electricity Board net-
works at identical air performance; optimised motor technology; soft
start; integrated current limitation; connection via brought-out variable
cable connector (motor size 084) or via easy-to-mount and robust inte-
grated terminal box made of aluminium with spring loaded terminals
(motor sizes 112 and 150); extremely compact electronics; with adju-
stable PID controller (motor sizes 112 and 150); meets all necessary
EMC directives and all requirements as to current reverse transfer; no
complicated installation with shielded cables required; very low-noise
commutation logic; 100% controllability.
If structure-borne noise needs to be decoupled, any such action has to
be taken by the customer.
Optionally: Modules with higher protection against corrosion.
For technical details, dimensions and connection -
see data sheet
K3G 250-AT39 -72 / -74 K3G 400-AQ23 -01 / -31K3G 250-AV29 -B2 / -B4 K3G 450-AY86 -02 / -32K3G 280-AT04 -72 / -74 K3G 450-AQ24 -01 / -31K3G 280-AU06 -B2 / -B4 K3G 500-AP25 -01 / -31K3G 280-AU06 -C2 / -C4 K3G 500-AQ12 -03 / -33K3G 310-AX52 -02 / -32 K3G 560-AP23 -01 / -31K3G 355-AX56 -02 / -32 K3G 560-AQ04 -03 / -33K3G 355-AY40 -02 / -32 K3G 310-AZ88 -02K3G 400-AY87 -02 / -32 K3G 450-AZ26 -03
Protective features
- Alarm relay with zero-potential change-over contacts
(250 V AC/2 A, cos ϕ = 1)
- Locked-rotor protection
- Phase failure detection
- Soft start of motors
- Mains under-voltage detection
- Over-temperature protection of electronics and motor
- Short-circuit protection
Technical data
- Air flow V = __________m3/h
- Static pressure ∆PF = __________Pa
- Voltage range U = V
- Frequenzy f = Hz
- Fan speed n = __________min-1
- Power input P1 = __________kW
- Current input I = __________A
- Noise level LP = __________dBA
- Perm. ambient temperature t = °C
- Fan mass = __________kg
- Approvals =
Fan type
_______________________________
5
EC centrifugal fansR3G 250 to R3G 560
ebm-papst high performance centrifugal fans
Single inlet; direct drive; 2D centrifugal impeller with circumferential
diffuser mounted on an electronically commutated external-rotor motor
with integrated electronics; backward curved impeller blades; inlet
nozzle made of galvanised sheet steel; complete unit statically and
dynamically balanced in two planes according to DIN / ISO 1940 and to
balancing quality G 6.3; EC external-rotor motor with maintenance-free
ball bearings and permanent lubrication; wide voltage input
1~200-277V, 50/60 Hz respectively 3~380-480V, 50/60Hz; unit can be
operated on all standard Electricity Board networks at identical air per-
formance; optimised motor technology; soft start; integrated current
limitation; connection via brought-out variable cable connector (motor
size 084) or via easy-to-mount and robust integrated terminal box
made of aluminium with spring loaded terminals (motor sizes 112 and
150); extremely compact electronics; with adjustable PID controller
(motor sizes 112 and 150); meets all necessary EMC directives and all
requirements as to current reverse transfer; no complicated installation
with shielded cables required; very low-noise commutation logic;
100% controllability.
For technical details, dimensions and connection -
see data sheet
Protective features
- Alarm relay with zero-potential change-over contacts
(250 V AC/2 A, cos ϕ = 1)
- Locked-rotor protection
- Phase failure detection
- Soft start of motors
- Mains under-voltage detection
- Over-temperature protection of electronics and motor
- Short-circuit protection
Technical Data
- Air flow V = __________m3/h
- Static pressure ∆PF = __________Pa
- Voltage range U = V
- Frequenzy f = Hz
- Fan speed n = __________min-1
- Power input P1 = __________kW
- Current input I = __________A
- Noise level LP = __________dBA
- Perm. ambient temperature t = °C
- Fan mass = __________kg
- Direction of rotation = clockwise
- Approvals =
Fan type
_______________________________
Text for tenders
6
EC centrifugal fans and modulesbackward curved, Ø 250
– Material: Support bracket: Steel, coated in blackSupport plate: Sheet aluminiumImpeller: Sheet aluminium, laser-weldedRotor: Coated in blackElectronics enclosure: Die-cast aluminium
– Number of blades: 7– Direction of rotation: Clockwise, seen on rotor– Type of protection: IP 54– Insulation class: "B"– Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request– Condensate discharges: None– Mode of operation: Continuous operation (S1)– Bearings: Maintenance-free ball bearings
Nominal data
Type Motor
*3G 250 M3G 084-DF
subject to alterations
400 800 1200 1600 2000 2400
0 [CFM]
[Pa]
100
200
300
400
500
0,4
1,2
[inH 2O
]0,
81,
62,
0
600 2,4
700 2,8
800 3,2
900 3,6
[m3/h]
200 400 600 800 1000 1200 1400
10
11
126
7
8
3
4
2
159
Curves
(1) Nominal data in operating point with maximum load and 230 VAC
VAC Hz rpm W A °C
1~ 200-277 50/60 2920 420 2,50 -25..+40
n[rpm]
P1[W]
p. 44
K1)
I[A]
1
2
3
4
5
6
7
8
9
10
11
12
A
A
A
A
A
A
A
A
A
A
A
A
A
LwA[dB(A)]
3095
2965
2920
2935
2270
2220
2180
2220
1565
1525
1510
1520
360
396
420
404
137
163
180
169
56
62
68
64
2,15
2,35
2,50
2,40
0,88
1,03
1,14
1,07
0,40
0,43
0,47
0,44
86
81
73
73
80
78
70
70
74
72
67
60
A
Curve
Nominal
voltage
range
Frequency
Speed/rpm
(1)
Perm.amb.temp.
Max.pow
erinput(1
)
Max.current
draw
(1)
Electr.connection
7
– Technical features: • Output 10 VDC max. 1.1 mA• PFC (passive) • Alarm relay• Control input 0-10 VDC / PWM • Over-temperature protected electronics / motor
– EMC: Interference emission acc. to EN 61000-6-3Interference immunity acc. to EN 61000-6-2Harmonics acc. to DIN EN 61000-3-2/3
– Leakage current: < 3.5 mA acc. to EN 61800-5-1– Cable exit: Variable– Protection class: I– Product conforming to standards: EN 61800-5-1, CE– Approvals: UL, CSA; VDE, CCC, GOST are applied for
Centrifugal fan
R3G 250-AT39 -71
kg
4,5
Inlet nozzle with onepressure tap
25075-2-4013
Massof
centrifugalfan
Centrifugal modulew. support bracket
K3G 250-AT39 -72
kg
9,4
Massofcentrifugal
modulewith
support
bracket
Centrifugal modulew. support bracket (2)
K3G 250-AT39 -74
kg
9,4
Massofcentrifugal
modulewith
support
bracket
Depth of screw 8-10 mm
Core-end sleeves
Guard grillep. 43
Inlet nozzlep. 42
Electr. connectionp. 44
6
201,5±3
48 153,5 ±2
130±1
(Ø25
1)
Ø102
Ø176
Ø284
80
112
Ø100
Ø150
±0.
25
Ø178
4x90˚30˚
45˚
4x90
˚
Ø6.5
M6
600+
20
85
Ø164±0.35
Ø290
Ø260
Ø166
.2
43
4xØ4
.5
400-1
295
350
4xØ1
1
2187±1
235±3
R3G 250-AT39 -71
K3G 250-AT39 -72 / -74
(2) Centrifugal module with higher protection against corrosion
8
EC centrifugal fans and modulesbackward curved, Ø 250
– Material: Support bracket: Steel, coated in blackSupport plate: Sheet aluminiumImpeller: Sheet aluminium, laser-weldedRotor: Coated in blackElectronics enclosure: Die-cast aluminium
– Number of blades: 7– Direction of rotation: Clockwise, seen on rotor– Type of protection: IP 54– Insulation class: "B"– Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request– Condensate discharges: None– Mode of operation: Continuous operation (S1)– Bearings: Maintenance-free ball bearings
400 800 1200 1600 2000 2400 2800
0 [CFM]
[Pa]
200
400
[inH 2O
]0,
81,
6
600 2,4
800 3,2
1000 4,0
[m3/h]
400 800 16001200
10
11
12
6
7
8
3
4
2
159
Curves n[rpm]
P1[W]
I[A]
LwA[dB(A)]
A
Nominal data
Type Motor
*3G 250 M3G 084-FA
subject to alterations (1) Nominal data in operating point with maximum load and 230 VAC
VAC Hz rpm W A °C
1~ 200-277 50/60 3450 690 4,12 -25..+40
p. 47
L7)A
Curve
Nominal
voltage
range
Frequency
Speed/rpm
(1)
Perm.amb.temp.
Max.pow
erinput(1
)
Max.current
draw
(1)
Electr.connection
1
2
3
4
5
6
7
8
9
10
11
12
A
A
A
A
A
A
A
A
A
A
A
A
3450
3450
3450
3450
2865
2865
2865
2865
2275
2275
2275
2275
496
620
690
649
284
355
396
372
142
178
198
186
2,96
3,67
4,12
3,86
1,70
2,10
2,36
2,21
0,85
1,05
1,18
1,11
88
85
76
77
84
81
72
73
79
76
67
68
9Electr. connectionp. 47
5x72˚
Ø5.5
226.9±3170.4±256.5
155.9±1
Ø165
±0.
25Ø1
30
Ø197
80
112
Ø176
Ø102
Ø284
Ø166
.24x
Ø4.5
43
Ø260
Ø290
8
Ø186±0,5
258.5±3
207±12 295
350
4xØ1
1
400-1
Depth of screw 12-16 mm
Cable gland
Centrifugal fan kg Inlet nozzle with onepressure tap
Massof
centrifugalfan
Centrifugal modulew. support bracket kg
Massofcentrifugal
modulewith
support
bracket
kg
Massofcentrifugal
modulewith
support
bracket
Centrifugal modulew. support bracket (2)
(2) Centrifugal module with higher protection against corrosion
– Technical features: • Slave output 0-10 V max. 3 mA • Line undervoltage detection• PFC (active) • Output 20 VDC (±20 %) max. 50 mA • Motor current limitation• Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Electronics / motor overtemperature protection• Control input 0-10 VDC / PWM • RS485 MODBUS • Locked-rotor protection• Input for sensor 0-10 V or 4-20 mA • Alarm relay • Soft start
– EMC: Interference emission acc. to EN 61000-6-3Interference immunity acc. to EN 61000-6-2Harmonics acc. to DIN EN 61000-3-2/3
– Leakage current: < 3.5 mA acc. to EN 61800-5-1– Connection leads: Via terminal strip– Protection class: I (acc. to EN 61800-5-1)– Product conforming to standard: CE– Approvals: VDE, UL, CSA, CCC, GOST are applied for
Guard grillep. 43
Inlet nozzlep. 42
R3G 250-AV29 -B1
K3G 250-AV29 -B2 / -B4
R3G 250-AV29 -B1 5,7 25075-2-4013 K3G 250-AV29 -B2 10,6 K3G 250-AV29 -B4 10,6
10
EC centrifugal fans and modulesbackward curved, Ø 280
– Material: Support bracket: Steel, coated in blackSupport plate: Sheet aluminiumImpeller: Sheet aluminium, laser-weldedRotor: Coated in blackElectronics enclosure: Die-cast aluminium
– Number of blades: 7– Direction of rotation: Clockwise, seen on rotor– Type of protection: IP 54– Insulation class: "B"– Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request– Condensate discharges: None– Mode of operation: Continuous operation (S1)– Bearings: Maintenance-free ball bearings
Nominal data
Type Motor
*3G 280 M3G 084-FA
subject to alterations
400 800 1200 1600 2000 2400 2800
0 [CFM]
[Pa]
100
200
300
400
500
0,4
1,2
[inH 2O
]0,
81,
62,
0
600 2,4
700 2,8
[m3/h]
200 400 600 800 1000 1200 1400 1600
10
11
126
7
8
3
4
2
159
Curves
(1) Nominal data in operating point with maximum load and 230 VAC
VAC Hz rpm W A °C
1~ 200-277 50/60 2290 390 2,30 -25..+40
n[rpm]
P1[W]
p. 44
K1)
I[A]
A
LwA[dB(A)]
1
2
3
4
5
6
7
8
9
10
11
12
A
A
A
A
A
A
A
A
A
A
A
A
2420
2320
2290
2340
1770
1730
1730
1760
1195
1175
1165
1155
320
367
390
361
124
148
156
143
49
56
54
53
1,94
2,20
2,30
2,17
0,81
0,95
1,00
0,93
0,36
0,40
0,39
0,38
82
75
69
75
75
70
63
67
68
64
55
56
A
Curve
Nominal
voltage
range
Frequency
Speed/rpm
(1)
Perm.amb.temp.
Max.pow
erinput(1
)
Max.current
draw
(1)
Electr.connection
11
– Technical features: • Output 10 VDC max. 1.1 mA• PFC (passive) • Alarm relay• Control input 0-10 VDC / PWM • Over-temperature protected electronics / motor
– EMC: Interference emission acc. to EN 61000-6-3Interference immunity acc. to EN 61000-6-2Harmonics acc. to DIN EN 61000-3-2/3
– Leakage current: < 3.5 mA acc. to EN 61800-5-1– Cable exit: Variable– Protection class: I– Product conforming to standards: EN 61800-5-1, CE– Approvals: UL, CSA; VDE, CCC, GOST are applied for
R3G 280-AT04 -71
kg
5,4 28075-2-4013 K3G 280-AT04 -72
kg
10,4
Depth of screw 8-10 mm
Core-end sleeves
Centrifugal fan Inlet nozzle with onepressure tap
Massof
centrifugalfan
Centrifugal modulew. support bracket
Massofcentrifugal
modulewith
support
bracket
10
227±3
48 179±2
145±1
(Ø28
2)
Ø102
Ø197
.4Ø3
19
90
131
Ø100
Ø150
±0.
25
Ø178
4x90˚30˚
45˚
4x90
˚
Ø6.5
M6
600+
20
85
Ø164±0.35
Ø325
Ø280
Ø187
.2
53
4xØ4
.5
400-1
295
350
4xØ1
1
max
.Ø32
1
2218±1
266±3
R3G 280-AT04 -71
K3G 280-AT04 -72 / -74
Electr. connectionp. 44
K3G 280-AT04 -74
kg
10,4
Massofcentrifugal
modulewith
support
bracket
Centrifugal modulew. support bracket (2)
(2) Centrifugal module with higher protection against corrosion
Guard grillep. 43
Inlet nozzlep. 42
12
EC centrifugal fans and modulesbackward curved, Ø 280
– Material: Support bracket: Steel, coated in blackSupport plate: Sheet aluminiumImpeller: Sheet aluminium, laser-weldedRotor: Coated in blackElectronics enclosure: Die-cast aluminium
– Number of blades: 7– Direction of rotation: Clockwise, seen on rotor– Type of protection: IP 54– Insulation class: "B"– Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request– Condensate discharges: None– Mode of operation: Continuous operation (S1)– Bearings: Maintenance-free ball bearings
500 1000 1500 2000 2500 3000
0 [CFM]
[Pa]
200
400
[inH 2O
]0,
8
100 0,4
300 1,2
500 2,0
700 2,8
1,6
600 2,4
800 3,2
[m3/h]
1000500 1500
10
11
12
6
7
8
3
4
2
159
Curves n[rpm]
P1[W]
I[A]
LwA[dB(A)]
A
Nominal data
Type Motor
*3G 280 M3G 084-GF
subject to alterations (1) Nominal data in operating point with maximum load and 230 VAC
VAC Hz rpm W A °C
1~ 200-277 50/60 2800 670 2,93 -25..+40
p. 47
L7)A
Curve
Nominal
voltage
range
Frequency
Speed/rpm
(1)
Perm.amb.temp.
Max.pow
erinput(1
)
Max.current
draw
(1)
Electr.connection
1
2
3
4
5
6
7
8
9
10
11
12
A
A
A
A
A
A
A
A
A
A
A
A
2800
2800
2800
2800
2325
2325
2325
2325
1850
1850
1850
1850
435
580
670
629
260
349
396
355
138
179
207
183
1,90
2,52
2,93
2,74
1,14
1,53
1,74
1,55
0,64
0,81
0,92
0,83
83
79
76
79
79
75
73
72
74
71
69
68
13Electr. connectionp. 47
Depth of screw 12-16 mm
Cable gland
5x72˚
Ø5.5
250±3194±256.5
185.9±1
Ø165
±0.
25Ø1
30
Ø197
90
132
Ø197
.4
Ø102
Ø319
Ø187
.24x
Ø4.5
53
Ø280
Ø325
10
Ø186±0,5
289.5±3
233±12 295
350
4xØ1
1
400-1
max
.Ø31
9
kg kgCentrifugal fan Inlet nozzle with onepressure tap
Massof
centrifugalfan
Centrifugal modulew. support bracket
Massofcentrifugal
modulewith
support
bracket
kg
Massofcentrifugal
modulewith
support
bracket
Centrifugal modulew. support bracket (2)
(2) Centrifugal module with higher protection against corrosion
– Technical features: • Slave output 0-10 V max. 3 mA • Line undervoltage detection• PFC (active) • Output 20 VDC (±20 %) max. 50 mA • Motor current limitation• Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Electronics / motor overtemperature protection• Control input 0-10 VDC / PWM • RS485 MODBUS • Locked-rotor protection• Input for sensor 0-10 V or 4-20 mA • Alarm relay • Soft start
– EMC: Interference emission acc. to EN 61000-6-3Interference immunity acc. to EN 61000-6-2Harmonics acc. to DIN EN 61000-3-2/3
– Leakage current: < 3.5 mA acc. to EN 61800-5-1– Connection leads: Via terminal strip– Protection class: I (acc. to EN 61800-5-1)– Product conforming to standard: CE– Approvals: VDE, UL, CSA, CCC, GOST are applied for
Guard grillep. 43
Inlet nozzlep. 42
R3G 280-AU06 -B1
K3G 280-AU06 -B2 / -B4
R3G 280-AU06 -B1 6,7 28075-2-4013 K3G 280-AU06 -B2 12,0 K3G 280-AU06 -B4 12,0
14
EC centrifugal fans and modulesbackward curved, Ø 280
– Material: Support bracket: Steel, coated in blackSupport plate: Sheet aluminiumImpeller: Sheet aluminium, laser-weldedRotor: Coated in blackElectronics enclosure: Die-cast aluminium
– Number of blades: 7– Direction of rotation: Clockwise, seen on rotor– Type of protection: IP 54– Insulation class: "B"– Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request– Condensate discharges: None– Mode of operation: Continuous operation (S1)– Bearings: Maintenance-free ball bearings
500 1000 1500 2000 2500 3000 3500
0 [CFM]
[Pa]
200
400
[inH 2O
]0,
81,
6
600 2,4
800 3,2
1000 4,0
[m3/h]
500 1000 20001500
10
11
12
6
7
8
3
4
2
159
Curves n[rpm]
P1[W]
I[A]
LwA[dB(A)]
A
Nominal data
Type Motor
*3G 280 M3G 084-GF
subject to alterations (1) Nominal data in operating point with maximum load and 230 VAC
VAC Hz rpm W A °C
3~ 380-480 50/60 3100 940 1,60 -25..+60
p. 45
L6)A
Curve
Nominal
voltage
range
Frequency
Speed/rpm
(1)
Perm.amb.temp.
Max.pow
erinput(1
)
Max.current
draw
(1)
Electr.connection
1
2
3
4
5
6
7
8
9
10
11
12
A
A
A
A
A
A
A
A
A
A
A
A
3100
3100
3100
3100
2575
2575
2575
2575
2045
2045
2045
2045
603
816
940
835
337
456
529
468
169
229
265
234
0,99
1,30
1,60
1,33
0,55
0,73
0,83
0,75
0,28
0,36
0,42
0,37
87
83
80
82
83
79
76
78
78
74
71
73
15Electr. connectionp. 45
Depth of screw 12-16 mm
Cable gland
5x72˚
Ø5.5
250±3194±256.5
185.9±1
Ø165
±0.
25Ø1
30
Ø197
90
132
Ø197
.4
Ø102
Ø319
Ø187
.24x
Ø4.5
53
Ø280
Ø325
10
Ø186±0,5
289.5±3
233±12 295
350
4xØ1
1
400-1
max
.Ø31
9
kg kgCentrifugal fan Inlet nozzle with onepressure tap
Massof
centrifugalfan
Centrifugal modulew. support bracket
Massofcentrifugal
modulewith
support
bracket
kg
Massofcentrifugal
modulewith
support
bracket
– Technical features: • Slave output 0-10 V max. 3 mA • Line undervoltage / phase failure detection• PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Motor current limitation• Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Electronics / motor overtemperature protection• Control input 0-10 VDC / PWM • RS485 MODBUS • Locked-rotor protection• Input for sensor 0-10 V or 4-20 mA • Alarm relay • Soft start
– EMC: Interference emission acc. to EN 61000-6-3Interference immunity acc. to EN 61000-6-2Harmonics acc. to DIN EN 61000-3-2/3
– Leakage current: < 3.5 mA acc. to EN 61800-5-1– Connection leads: Via terminal strip– Protection class: I (acc. to EN 61800-5-1)– Product conforming to standard: CE– Approvals: VDE, UL, CSA, CCC, GOST are applied for
Centrifugal modulew. support bracket (2)
(2) Centrifugal module with higher protection against corrosion
Guard grillep. 43
Inlet nozzlep. 42
R3G 280-AU06 -C1
K3G 280-AU06 -C2 / -C4
R3G 280-AU06 -C1 6,7 28075-2-4013 K3G 280-AU06 -C2 12,0 K3G 280-AU06 -C4 12,0
16
EC centrifugal fans and modulesbackward curved, Ø 310
Nominal data
Type Motor
*3G 310 M3G 112-EA
subject to alterations
1000 2000 3000 4000
0 [CFM]
[Pa]
100
200
300
400
500
0,4
1,2
[inH 2O
]0,
81,
62,
0
600 2,4
700 2,8
800 3,2
900 3,6
[m3/h]
500 1000 1500 2000 2500
10
11
12 6
7
8
3
4
2
159
Curves
(1) Nominal data in operating point with maximum load and 400 VAC
VAC Hz rpm W A °C
3~ 380-480 50/60 2580 990 1,70 -25..+55
n[rpm]
P1[W]
p. 45
L2)
I[A]
A
LwA[dB(A)]
– Material: Support bracket: Steel, coated in blackSupport plate: Galvanised sheet steelImpeller: Sheet aluminium, laser-weldedRotor: Coated in blackElectronics enclosure: Die-cast aluminium
– Number of blades: 7– Direction of rotation: Clockwise, seen on rotor– Type of protection: IP 54 (acc. to EN 60529)– Insulation class: "F"– Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request– Condensate discharges: Rotor-side– Mode of operation: Continuous operation (S1)– Bearings: Maintenance-free ball bearings
1
2
3
4
5
6
7
8
9
10
11
12
A
A
A
A
A
A
A
A
A
A
A
A
2580
2580
2580
2580
1930
1910
1900
1905
1305
1305
1305
1300
669
862
990
907
288
348
396
360
123
144
151
151
1,17
1,46
1,70
1,53
0,57
0,69
0,77
0,72
0,28
0,33
0,34
0,34
88
81
77
79
80
74
70
71
72
67
62
62
A
Curve
Nominal
voltage
range
Frequency
Speed/rpm
(1)
Perm.amb.temp.
Max.pow
erinput(1
)
Max.current
draw
(1)
Electr.connection
17
R3G 310-AX52 -01
kg
9,3 31575-2-4013 K3G 310-AX52 -02
kg
15,9
Depth of screw 12-16 mm
Cable gland
– Technical features: • Slave output 0-10 V max. 3 mA • Line undervoltage / phase failure detection• PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Motor current limitation• Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Electronics / motor overtemperature protection• Control input 0-10 VDC / PWM • RS485 ebmBUS • Locked-rotor protection• Input for sensor 0-10 V or 4-20 mA • Alarm relay • Soft start
– EMC: Interference emission acc. to EN 61000-6-3Interference immunity acc. to EN 61000-6-2Harmonics acc. to DIN EN 61000-3-2/3
– Leakage current: < 3.5 mA acc. to EN 61800-5-1– Connection leads: Via terminal strip– Protection class: I (acc. to EN 61800-5-1)– Product conforming to standard: CE– Approvals: VDE, UL, CSA, CCC, GOST are applied for
Centrifugal fan Inlet nozzle with onepressure tap
Massof
centrifugalfan
Centrifugal modulew. support bracket
Massofcentrifugal
modulewith
support
bracket
10
Ø186±0,5
147
100
(Ø31
7)
Ø138
Ø222
Ø360
160,5±1
56,5 197,2±2
253,7±3
5x72˚
5xM6
Ø168
Ø211
,7
Ø325
Ø350
4xØ4
,5
55
450
4xØ1
1
380500-1
15237,5±2
294±3
R3G 310-AX52 -01
K3G 310-AX52 -02 / -32
Electr. connectionp. 45
K3G 310-AX52 -32
kg
15,9
Massofcentrifugal
modulewith
support
bracket
Centrifugal modulew. support bracket (2)
(2) Centrifugal module with higher protection against corrosion
Guard grillep. 43
Inlet nozzlep. 42
18
EC centrifugal fans and modulesbackward curved, Ø 355
Nominal data
Type Motor
*3G 355 M3G 112-EA
subject to alterations
1000 2000 3000 4000 5000
0 [CFM]
[Pa]
100
200
300
400
500
0,4
1,2
[inH 2O
]0,
81,
62,
0
600 2,4
700 2,8
800 3,2
[m3/h]
500 1000 1500 2000 30002500
10
11
126
7
8
3
4
2
159
Curves
(1) Nominal data in operating point with maximum load and 400 VAC
VAC Hz rpm W A °C
3~ 380-480 50/60 2140 1000 1,75 -25..+60
n[rpm]
P1[W]
p. 45
L2)
I[A]
A
LwA[dB(A)]
– Material: Support bracket: Steel, coated in blackSupport plate: Galvanised sheet steelImpeller: Sheet aluminium, laser-weldedRotor: Coated in blackElectronics enclosure: Die-cast aluminium
– Number of blades: 7– Direction of rotation: Clockwise, seen on rotor– Type of protection: IP 54 (acc. to EN 60529)– Insulation class: "F"– Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request– Condensate discharges: Rotor-side– Mode of operation: Continuous operation (S1)– Bearings: Maintenance-free ball bearings
1
2
3
4
5
6
7
8
9
10
11
12
A
A
A
A
A
A
A
A
A
A
A
A
2140
2140
2140
2140
1610
1595
1580
1585
1080
1065
1065
1060
656
893
1000
918
286
350
387
366
113
133
143
135
1,14
1,50
1,75
1,54
0,57
0,68
0,74
0,70
0,28
0,31
0,33
0,32
87
77
75
78
79
70
69
70
71
64
60
61
A
Curve
Nominal
voltage
range
Frequency
Speed/rpm
(1)
Perm.amb.temp.
Max.pow
erinput(1
)
Max.current
draw
(1)
Electr.connection
19
R3G 355-AX56 -01
kg
9,8 35675-2-4013 K3G 355-AX56 -02
kg
17,6
– Technical features: • Slave output 0-10 V max. 3 mA • Line undervoltage / phase failure detection• PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Motor current limitation• Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Electronics / motor overtemperature protection• Control input 0-10 VDC / PWM • RS485 ebmBUS • Locked-rotor protection• Input for sensor 0-10 V or 4-20 mA • Alarm relay • Soft start
– EMC: Interference emission acc. to EN 61000-6-3Interference immunity acc. to EN 61000-6-2Harmonics acc. to DIN EN 61000-3-2/3
– Leakage current: < 3.5 mA acc. to EN 61800-5-1– Connection leads: Via terminal strip– Protection class: I (acc. to EN 61800-5-1)– Product conforming to standard: CE– Approvals: VDE, UL, CSA, CCC, GOST are applied for
Depth of screw 12-16 mm
Cable gland
Centrifugal fan Inlet nozzle with onepressure tap
Massof
centrifugalfan
Centrifugal modulew. support bracket
Massofcentrifugal
modulewith
support
bracket
12
Ø186±0,5
164
112
(Ø35
7)Ø4
05
Ø138
Ø250
,3Ø4
04
160,5±1
56,5 214,2±2
270,7±3
5x72˚
5xM6
Ø168
Ø239
Ø345
Ø370
4xØ4
,5
64,5
Ø405
450
4xÈ11
380500-1
15263±2319,5±3
R3G 355-AX56 -01
K3G 355-AX56 -02 / -32
Electr. connectionp. 45
K3G 355-AX56 -32
kg
17,6
Massofcentrifugal
modulewith
support
bracket
Centrifugal modulew. support bracket (2)
(2) Centrifugal module with higher protection against corrosion
Guard grillep. 43
Inlet nozzlep. 42
20
EC centrifugal fans and modulesbackward curved, Ø 355
Nominal data
Type Motor
*3G 355 M3G 112-GA
subject to alterations
1000 2000 3000 4000 5000 6000
0 [CFM]
[Pa]
200
400
[inH 2O
]0,
81,
6
600 2,4
800 3,2
1000 4,0
1200 4,8
[m3/h]
500 1000 1500 2000 3000 35002500
10
11
12 6
7
8
3
4
2
159
Curves
(1) Nominal data in operating point with maximum load and 400 VAC
VAC Hz rpm W A °C
3~ 380-480 50/60 2600 1700 2,60 -25..+45
n[rpm]
P1[W]
p. 46
L5)
I[A]
A
LwA[dB(A)]
– Material: Support bracket: Steel, coated in blackSupport plate: Galvanised sheet steelImpeller: Sheet aluminium, laser-weldedRotor: Coated in blackElectronics enclosure: Die-cast aluminium
– Number of blades: 7– Direction of rotation: Clockwise, seen on rotor– Type of protection: IP 54 (acc. to EN 60529)– Insulation class: "F"– Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request– Condensate discharges: Rotor-side– Mode of operation: Continuous operation (S1)– Bearings: Maintenance-free ball bearings
1
2
3
4
5
6
7
8
9
10
11
12
A
A
A
A
A
A
A
A
A
A
A
A
2600
2600
2600
2600
1940
1910
1885
1905
1330
1315
1305
1305
1140
1510
1700
1594
436
541
533
558
194
226
239
236
1,74
2,30
2,60
2,42
0,73
0,88
0,95
0,91
0,40
0,45
0,47
0,46
92
83
79
83
84
76
73
76
76
70
66
66
A
Curve
Nominal
voltage
range
Frequency
Speed/rpm
(1)
Perm.amb.temp.
Max.pow
erinput(1
)
Max.current
draw
(1)
Electr.connection
21
R3G 355-AY40 -01
kg
13,0 35675-2-4013 K3G 355-AY40 -02
kg
23,0
– Technical features: • Slave output 0-10 V max. 3 mA • Line undervoltage / phase failure detection• PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Electronics / motor overtemperature protection• Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Locked-rotor protection, Soft start• Control input 0-10 VDC / PWM • RS485 MODBUS • Digital inputs for day/night switch,• Input for sensor 0-10 V or 4-20 mA • Motor current limitation, Alarm relay enabling, cooling / heating
– EMC: Interference emission acc. to EN 61000-6-3Interference immunity acc. to EN 61000-6-2Harmonics acc. to DIN EN 61000-3-2/3
– Leakage current: < 3.5 mA acc. to EN 61800-5-1– Connection leads: Via terminal strip– Protection class: I (acc. to EN 61800-5-1)– Product conforming to standard: CE– Approvals: VDE, UL, CSA, CCC, GOST are applied for
Depth of screw 12-16 mm
Cable gland
Centrifugal fan Inlet nozzle with onepressure tap
Massof
centrifugalfan
Centrifugal modulew. support bracket
Massofcentrifugal
modulewith
support
bracket
6xM10182±1
Ø252±0.5
Ø232±0.3
6x60˚
(Ø35
7)Ø
405
112163.7 12
Ø40
4
Ø25
0.3
Ø13
8
57.5 234.2±2
291.7±3
64.4
4xØ4
.5
Ø370
Ø345
Ø239
500-1
380
450
4xØ1
1
15282.5±2
340±3
R3G 355-AY40 -01
K3G 355-AY40 -02 / -32
Electr. connectionp. 46
K3G 355-AY40 -32
kg
23,0
Massofcentrifugal
modulewith
support
bracket
Centrifugal modulew. support bracket (2)
(2) Centrifugal module with higher protection against corrosion
Guard grillep. 43
Inlet nozzlep. 42
22
EC centrifugal fans and modulesbackward curved, Ø 400
– Material: Support bracket: Steel, coated in blackSupport plate: Galvanised sheet steelImpeller: Sheet aluminium, weldedRotor: Coated in blackElectronics enclosure: Die-cast aluminium
– Number of blades: 7– Direction of rotation: Clockwise, seen on rotor– Type of protection: IP 54 (acc. to EN 60529)– Insulation class: "F"– Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request– Condensate discharges: Rotor-side– Mode of operation: Continuous operation (S1)– Bearings: Maintenance-free ball bearings
1000 2000 3000 4000 5000 6000 7000
0 [CFM]
[Pa]
200
400
[inH 2O
]0,
81,
6
600 2,4
800 3,2
1000 4,0
[m3/h]
1000 2000 40003000
10
11
126
7
8
3
4
159
2
Curves n[rpm]
P1[W]
I[A]
LwA[dB(A)]
A
Nominal data
Type Motor
*3G 400 M3G 112-IA
subject to alterations (1) Nominal data in operating point with maximum load and 400 VAC
VAC Hz rpm W A °C p. 46
L5)
Curve
Nominal
voltage
range
Frequency
Speed/rpm
(1)
Perm.amb.temp.
Max.pow
erinput(1
)
Max.current
draw
(1)
Electr.connection
3~ 380-480 50/60 2180 1850 2,90 -25..+50A
1
2
3
4
5
6
7
8
9
10
11
12
A
A
A
A
A
A
A
A
A
A
A
A
2180
2180
2180
2180
1850
1850
1850
1850
1470
1470
1470
1470
1178
1748
1850
1638
720
1063
1132
1001
361
533
568
502
1,81
2,66
2,90
2,49
1,10
1,62
1,72
1,52
0,55
0,81
0,86
0,76
89
82
81
84
85
78
77
80
80
73
72
75
23Electr. connectionp. 46
6xM10202±1
Ø252±0.5
Ø232±0.3
6x60˚
(Ø40
3)Ø
455
125182 9
Ø45
5
Ø28
2
Ø13
8
57.5 273±2
330.5±3
68
6xØ9
Ø413
Ø390
Ø270
.9
500-1
380
450
4xØ1
1
15327±2
284.5±3
R3G 400-AY87 -01
K3G 400-AY87 -02 / -32
Depth of screw 12-16 mm
Cable gland
kg kgCentrifugal fan Inlet nozzle with onepressure tap
Massof
centrifugalfan
Centrifugal modulew. support bracket
Massofcentrifugal
modulewith
support
bracket
kg
Massofcentrifugal
modulewith
support
bracket
R3G 400-AY87 -01 14,0 40075-2-4013 K3G 400-AY87 -02 25,0 K3G 400-AY87 -32 25,0
– Technical features: • Slave output 0-10 V max. 3 mA • Line undervoltage / phase failure detection• PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Electronics / motor overtemperature protection• Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Locked-rotor protection, Soft start• Control input 0-10 VDC / PWM • RS485 MODBUS • Digital inputs for day/night switch,• Input for sensor 0-10 V or 4-20 mA • Motor current limitation, Alarm relay enabling, cooling / heating
– EMC: Interference emission acc. to EN 61000-6-3Interference immunity acc. to EN 61000-6-2Harmonics acc. to DIN EN 61000-3-2/3
– Leakage current: < 3.5 mA acc. to EN 61800-5-1– Connection leads: Via terminal strip– Protection class: I (acc. to EN 61800-5-1)– Product conforming to standard: CE– Approvals: VDE, UL, CSA, CCC, GOST are applied for
Centrifugal modulew. support bracket (2)
(2) Centrifugal module with higher protection against corrosion
Guard grillep. 43
Inlet nozzlep. 42
24
EC centrifugal fans and modulesbackward curved, Ø 400
Nominal data
Type Motor
*3G 400 M3G 150-FF
subject to alterations
2000 4000 6000 8000
0 [CFM]
[Pa]
200
400
[inH 2O
]0,
81,
6
600 2,4
800 3,2
1000 4,0
1200 4,8
1400
[m3/h]
1000 2000 40003000
10
11
12
6
7
8
3
4
2
159
Curves
(1) Nominal data in operating point with maximum load and 400 VAC
VAC Hz rpm W A °C
n[rpm]
P1[W]
p. 46
L5)
I[A]
LwA[dB(A)]
– Material: Support bracket: Steel, coated in blackSupport plate: Galvanised sheet steelImpeller: Sheet aluminium, weldedRotor: Coated in blackElectronics enclosure: Die-cast aluminium
– Number of blades: 7– Direction of rotation: Clockwise, seen on rotor– Type of protection: IP 54 (acc. to EN 60529)– Insulation class: "F"– Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request– Condensate discharges: Rotor-side– Mode of operation: Continuous operation (S1)– Bearings: Maintenance-free ball bearings
A
Curve
Nominal
voltage
range
Frequency
Speed/rpm
(1)
Perm.amb.temp.
Max.pow
erinput(1
)
Max.current
draw
(1)
Electr.connection
3~ 380-480 50/60 2550 3000 4,60 -25..+60A
1
2
3
4
5
6
7
8
9
10
11
12
A
A
A
A
A
A
A
A
A
A
A
A
2550
2550
2550
2550
2115
2115
2115
2115
1680
1680
1680
1680
1989
2578
3000
2890
1135
1471
1709
1649
569
737
857
826
3,03
3,92
4,60
4,41
1,73
2,24
2,61
2,52
0,87
1,12
1,31
1,26
93
87
85
87
89
83
81
83
84
78
76
78
25
R3G 400-AQ23 -01
kg
22,0 40075-2-4013 K3G 400-AQ23 -01
kg
34,0
Centrifugal fan Inlet nozzle with onepressure tap
Massof
centrifugalfan
Centrifugal modulew. support bracket
Massofcentrifugal
modulewith
support
bracket
Electr. connectionp. 46
K3G 400-AQ23 -31
kg
34,0
Massofcentrifugal
modulewith
support
bracket
Depth of screw max. 25 mm
Cable gland
R3G 400-AQ23 -01
K3G 400-AQ23 -01 / -31
±3
±2
8x45˚
22.5˚
6x60
˚
14xM10
Ø232-2
Ø252±0,3
Ø275
220.5±1
182
125 9
Ø282
Ø455
Ø270
.9
Ø390
Ø413
68
6xØ9265.6
335.670
(Ø40
3)
Ø188
4xØ1
1
450
380500-1
15320±2
390±3
– Technical features: • Slave output 0-10 V max. 3 mA • Line undervoltage / phase failure detection• PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Electronics / motor overtemperature protection• Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Locked-rotor protection, Soft start• Control input 0-10 VDC / PWM • RS485 MODBUS • Digital inputs for day/night switch,• Input for sensor 0-10 V or 4-20 mA • Motor current limitation, Alarm relay enabling, cooling / heating
– EMC: Interference emission acc. to EN 61000-6-3Interference immunity acc. to EN 61000-6-2Harmonics acc. to DIN EN 61000-3-2/3
– Leakage current: < 3.5 mA acc. to EN 61800-5-1– Connection leads: Via terminal strip– Protection class: I (acc. to EN 61800-5-1)– Product conforming to standard: CE– Approvals: VDE, UL, CSA, CCC, GOST are applied for
Centrifugal modulew. support bracket (2)
(2) Centrifugal module with higher protection against corrosion
Guard grillep. 43
Inlet nozzlep. 42
26
EC centrifugal fans and modulesbackward curved, Ø 450
– Material: Support bracket: Steel, coated in blackSupport plate: Galvanised sheet steelImpeller: Sheet aluminium, weldedRotor: Coated in blackElectronics enclosure: Die-cast aluminium
– Number of blades: 7– Direction of rotation: Clockwise, seen on rotor– Type of protection: IP 54 (acc. to EN 60529)– Insulation class: "F"– Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request– Condensate discharges: Rotor-side– Mode of operation: Continuous operation (S1)– Bearings: Maintenance-free ball bearings
2000 4000 6000 8000
0 [CFM]
[Pa]
200
400
[inH 2O
]0,
8
100 0,4
300 1,2
500 2,0
700 2,8
1,6
600 2,4
800 3,2
[m3/h]
1000 2000 4000 50003000
10
11
12
6
7
8
3
4
2
159
Curves n[rpm]
P1[W]
I[A]
LwA[dB(A)]
A
Nominal data
Type Motor
*3G 450 M3G 112-IA
subject to alterations (1) Nominal data in operating point with maximum load and 400 VAC
VAC Hz rpm W A °C p. 46
L5)
Curve
Nominal
voltage
range
Frequency
Speed/rpm
(1)
Perm.amb.temp.
Max.pow
erinput(1
)
Max.current
draw
(1)
Electr.connection
1
2
3
4
5
6
7
8
9
10
11
12
A
A
A
A
A
A
A
A
A
A
A
A
1750
1750
1750
1750
1450
1450
1450
1450
1155
1155
1155
1155
1036
1457
1616
1524
571
812
906
810
306
427
462
411
1,61
2,25
2,50
2,33
0,92
1,28
1,42
1,27
0,56
0,73
0,77
0,70
87
80
77
80
82
75
73
76
76
69
67
69
3~ 380-480 50/60 1750 1616 2,50 -25..+50A
27Electr. connectionp. 46
6xM10202±1
Ø252±0.5
Ø232±0.3
6x60˚
(Ø45
3)Ø
505
140204 9
Ø50
5
Ø31
7
Ø13
8
57.5 295±2
352.5±3
76
6xØ9
Ø480
Ø430
Ø303
.4
630-1
548
580
8xØ1
1
15357±2
414.5±3
R3G 450-AY86 -01
K3G 450-AY86 -02 / -32
Depth of screw 12-16 mm
Cable gland
kg kgCentrifugal fan Inlet nozzle with onepressure tap
Massof
centrifugalfan
Centrifugal modulew. support bracket
Massofcentrifugal
modulewith
support
bracket
kg
Massofcentrifugal
modulewith
support
bracket
R3G 450-AY86 -01 15,0 45075-2-4013 K3G 450-AY86 -02 31,0 K3G 450-AY86 -32 31,0
– Technical features: • Slave output 0-10 V max. 3 mA • Line undervoltage / phase failure detection• PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Electronics / motor overtemperature protection• Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Locked-rotor protection, Soft start• Control input 0-10 VDC / PWM • RS485 MODBUS • Digital inputs for day/night switch,• Input for sensor 0-10 V or 4-20 mA • Motor current limitation, Alarm relay enabling, cooling / heating
– EMC: Interference emission acc. to EN 61000-6-3Interference immunity acc. to EN 61000-6-2Harmonics acc. to DIN EN 61000-3-2/3
– Leakage current: < 3.5 mA acc. to EN 61800-5-1– Connection leads: Via terminal strip– Protection class: I (acc. to EN 61800-5-1)– Product conforming to standard: CE– Approvals: VDE, UL, CSA, CCC, GOST are applied for
Centrifugal modulew. support bracket (2)
(2) Centrifugal module with higher protection against corrosion
Guard grillep. 43
Inlet nozzlep. 42
28
EC centrifugal fans and modulesbackward curved, Ø 450
Nominal data
Type Motor
*3G 450 M3G 150-FF
subject to alterations
2000 4000 6000 8000 10000
0 [CFM]
[Pa]
200
400
[inH 2O
]0,
81,
6
600 2,4
800 3,2
1000 4,0
1200 4,8
[m3/h]
1000 2000 4000 5000 60003000
10
11
126
7
8
3
4
2
159
Curves
(1) Nominal data in operating point with maximum load and 400 VAC
VAC Hz rpm W A °C
n[rpm]
P1[W]
p. 46
L5)
I[A]
LwA[dB(A)]
– Material: Support bracket: Steel, coated in blackSupport plate: Galvanised sheet steelImpeller: Sheet aluminium, weldedRotor: Coated in blackElectronics enclosure: Die-cast aluminium
– Number of blades: 7– Direction of rotation: Clockwise, seen on rotor– Type of protection: IP 54 (acc. to EN 60529)– Insulation class: "F"– Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request– Condensate discharges: Rotor-side– Mode of operation: Continuous operation (S1)– Bearings: Maintenance-free ball bearings
A
Curve
Nominal
voltage
range
Frequency
Speed/rpm
(1)
Perm.amb.temp.
Max.pow
erinput(1
)
Max.current
draw
(1)
Electr.connection
3~ 380-480 50/60 2040 2730 4,20 -25..+60A
1
2
3
4
5
6
7
8
9
10
11
12
A
A
A
A
A
A
A
A
A
A
A
A
2040
2040
2040
2040
1695
1695
1695
1695
1345
1345
1345
1345
1773
2500
2730
2587
991
1428
1548
1450
495
713
774
725
2,71
3,80
4,20
3,96
1,52
2,17
2,35
2,22
0,76
1,09
1,18
1,11
92
83
81
83
88
79
77
79
83
74
72
74
29
R3G 450-AQ24 -01
kg
22,5 45075-2-4013 K3G 450-AQ24 -01
kg
38,5
Centrifugal fan Inlet nozzle with onepressure tap
Massof
centrifugalfan
Centrifugal modulew. support bracket
Massofcentrifugal
modulewith
support
bracket
Electr. connectionp. 46
K3G 450-AQ24 -31
kg
38,5
Massofcentrifugal
modulewith
support
bracket
Depth of screw max. 25 mm
Cable gland
R3G 450-AQ24 -01
K3G 450-AQ24 -01 / -31
±3
±2
8x45˚
22.5˚
6x60
˚
14xM10
Ø232-2
Ø252±0,3
Ø275
220.5±1
204
140 9
Ø317
Ø505
Ø303
.4
Ø430
Ø480
76
6xØ9287.2
357.270
(Ø45
3)
Ø188
8xØ1
1
580
548630-1
15349±2
419±3
– Technical features: • Slave output 0-10 V max. 3 mA • Line undervoltage / phase failure detection• PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Electronics / motor overtemperature protection• Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Locked-rotor protection, Soft start• Control input 0-10 VDC / PWM • RS485 MODBUS • Digital inputs for day/night switch,• Input for sensor 0-10 V or 4-20 mA • Motor current limitation, Alarm relay enabling, cooling / heating
– EMC: Interference emission acc. to EN 61000-6-3Interference immunity acc. to EN 61000-6-2Harmonics acc. to DIN EN 61000-3-2/3
– Leakage current: < 3.5 mA acc. to EN 61800-5-1– Connection leads: Via terminal strip– Protection class: I (acc. to EN 61800-5-1)– Product conforming to standard: CE– Approvals: VDE, UL, CSA, CCC, GOST are applied for
Centrifugal modulew. support bracket (2)
(2) Centrifugal module with higher protection against corrosion
Guard grillep. 43
Inlet nozzlep. 42
30
EC centrifugal fans and modulesbackward curved, Ø 500
– Material: Support bracket: Steel, coated in blackSupport plate: Galvanised sheet steelImpeller: Sheet aluminium, weldedRotor: Coated in blackElectronics enclosure: Die-cast aluminium
– Number of blades: 7– Direction of rotation: Clockwise, seen on rotor– Type of protection: IP 54 (acc. to EN 60529)– Insulation class: "F"– Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request– Condensate discharges: Rotor-side– Mode of operation: Continuous operation (S1)– Bearings: Maintenance-free ball bearings
2000 4000 6000 8000 10000
0 [CFM]
[Pa]
200
400
[inH 2O
]0,
81,
6
600 2,4
800 3,2
1000 4,0
1200 4,8
[m3/h]
1000 2000 4000 5000 60003000
10
11
12
6
7
8
3
4
2
159
Curves n[rpm]
P1[W]
I[A]
LwA[dB(A)]
A
Nominal data
Type Motor
*3G 500 M3G 150-FF
subject to alterations (1) Nominal data in operating point with maximum load and 400 VAC
VAC Hz rpm W A °C p. 46
L5)
Curve
Nominal
voltage
range
Frequency
Speed/rpm
(1)
Perm.amb.temp.
Max.pow
erinput(1
)
Max.current
draw
(1)
Electr.connection
1
2
3
4
5
6
7
8
9
10
11
12
A
A
A
A
A
A
A
A
A
A
A
A
1780
1780
1780
1780
1475
1475
1475
1475
1175
1175
1175
1175
1746
2490
2825
2582
985
1411
1600
1452
498
713
809
734
2,70
3,82
4,30
3,96
1,52
2,16
2,46
2,23
0,77
1,09
1,24
1,13
94
85
80
83
89
81
76
79
84
76
71
74
3~ 380-480 50/60 1780 2825 4,30 -25..+60A
31Electr. connectionp. 46
Depth of screw max. 25 mm
Cable gland
R3G 500-AP25 -01
K3G 500-AP25 -01 / -31
8x45˚
22.5˚
6x60
˚
14xM10
Ø232-2
Ø252±0,3
Ø275
220.5±1
220.5
150 12
Ø352
.5
Ø566
Ø337
.2
Ø445
Ø470
75
6xØ9303.5
373.570
(Ø50
4)
Ø188
±3
±2
8xØ1
1
580
548630-1
15362,5±2
432,5±3
kg kgCentrifugal fan Inlet nozzle with onepressure tap
Massof
centrifugalfan
Centrifugal modulew. support bracket
Massofcentrifugal
modulewith
support
bracket
kg
Massofcentrifugal
modulewith
support
bracket
R3G 500-AP25 -01 25,0 64025-2-4013 K3G 500-AP25 -01 41,5 K3G 500-AP25 -31 41,5
– Technical features: • Slave output 0-10 V max. 3 mA • Line undervoltage / phase failure detection• PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Electronics / motor overtemperature protection• Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Locked-rotor protection, Soft start• Control input 0-10 VDC / PWM • RS485 MODBUS • Digital inputs for day/night switch,• Input for sensor 0-10 V or 4-20 mA • Motor current limitation, Alarm relay enabling, cooling / heating
– EMC: Interference emission acc. to EN 61000-6-3Interference immunity acc. to EN 61000-6-2Harmonics acc. to DIN EN 61000-3-2/3
– Leakage current: < 3.5 mA acc. to EN 61800-5-1– Connection leads: Via terminal strip– Protection class: I (acc. to EN 61800-5-1)– Product conforming to standard: CE– Approvals: VDE, UL, CSA, CCC, GOST are applied for
Centrifugal modulew. support bracket (2)
(2) Centrifugal module with higher protection against corrosion
Guard grillep. 43
Inlet nozzlep. 42
32
EC centrifugal fans and modulesbackward curved, Ø 500
Nominal data
Type Motor
*3G 500 M3G 150-IF
subject to alterations
2000 4000 6000 8000 10000 12000
0 [CFM]
[Pa]
200
400
[inH 2O
]0,
81,
6
600 2,4
800 3,2
1000 4,0
1200 4,8
1400
[m3/h]
2000 4000 6000
10
11
12 6
7
8
3
4
2
159
Curves
(1) Nominal data in operating point with maximum load and 400 VAC
VAC Hz rpm W A °C
n[rpm]
P1[W]
p. 47
M2)
I[A]
LwA[dB(A)]
– Material: Support bracket: Steel, coated in blackSupport plate: Galvanised sheet steelImpeller: Sheet aluminium, weldedRotor: Coated in blackElectronics enclosure: Die-cast aluminium
– Number of blades: 7– Direction of rotation: Clockwise, seen on rotor– Type of protection: IP 54 (acc. to EN 60529)– Insulation class: "F"– Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request– Condensate discharges: Rotor-side– Mode of operation: Continuous operation (S1)– Bearings: Maintenance-free ball bearings
A
Curve
Nominal
voltage
range
Frequency
Speed/rpm
(1)
Perm.amb.temp.
Max.pow
erinput(1
)
Max.current
draw
(1)
Electr.connection
3~ 380-480 50/60 2000 4300 6,60 -25..+45A
1
2
3
4
5
6
7
8
9
10
11
12
A
A
A
A
A
A
A
A
A
A
A
A
2000
2000
2000
2000
1660
1660
1660
1660
1320
1320
1320
1320
2683
4038
4300
3813
1509
2042
2233
2001
801
1067
1134
1033
4,07
6,15
6,60
5,79
2,33
3,13
3,41
3,07
1,32
1,71
1,80
1,66
98
87
84
87
92
82
79
82
85
76
74
75
33
R3G 500-AQ12 -03
kg
33,8 64025-2-4013 K3G 500-AQ12 -03
kg
61,7
– Technical features: • Slave output 0-10 V max. 3 mA • Line undervoltage / phase failure detection• PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Motor current limitation• Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Electronics / motor overtemperature protection• Control input 0-10 VDC / PWM • RS485 ebmBUS • Locked-rotor protection• Input for sensor 0-10 V or 4-20 mA • Alarm relay • Soft start
– EMC: Interference emission acc. to EN 61000-6-3Interference immunity acc. to EN 61000-6-2Harmonics acc. to DIN EN 61000-3-2/3
– Leakage current: < 3.5 mA acc. to EN 61800-5-1– Connection leads: Via terminal strip– Protection class: I (acc. to EN 61800-5-1)– Product conforming to standard: CE– Approvals: VDE, UL, CSA, CCC, GOST are applied for
Depth of screw max. 20 mm
Cable gland
Centrifugal fan Inlet nozzle with onepressure tap
Massof
centrifugalfan
Centrifugal modulew. support bracket
Massofcentrifugal
modulewith
support
bracket
451.5±3
113 338.5±2
298.5±1
150220.5
Ø188
Ø352
.5Ø5
66
(Ø50
4)
12
Ø280-2
Ø304±0.5
6x60˚
6xM10
756xØ9
Ø337
.2
Ø445
Ø470
630-1
520.5
580
8xØ1
1
15396.5±2
509±3
R3G 500-AQ12 -03
K3G 500-AQ12 -03 / -33
Electr. connectionp. 47
K3G 500-AQ12 -33
kg
61,7
Massofcentrifugal
modulewith
support
bracket
Centrifugal modulew. support bracket (2)
(2) Centrifugal module with higher protection against corrosion
Guard grillep. 43
Inlet nozzlep. 42
34
EC centrifugal fans and modulesbackward curved, Ø 560
– Material: Support bracket: Steel, coated in blackSupport plate: Galvanised sheet steelImpeller: Sheet aluminium, weldedRotor: Coated in blackElectronics enclosure: Die-cast aluminium
– Number of blades: 7– Direction of rotation: Clockwise, seen on rotor– Type of protection: IP 54 (acc. to EN 60529)– Insulation class: "F"– Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request– Condensate discharges: Rotor-side– Mode of operation: Continuous operation (S1)– Bearings: Maintenance-free ball bearings
4000 8000 12000
0 2000 4000 6000 [CFM]
[Pa]
200
0,5
1,0
1,5
2,0
[inH 2O
]2,
53,
0
[m3/h]
3,5
4,0
400
600
800
1000
8000
6
5 1
2
3
4
7
8
9
10
11
12
Curves n[rpm]
P1[W]
I[A]
LwA[dB(A)]
A
Nominal data
Type Motor
*3G 560 M3G 150-IF
subject to alterations (1) Nominal data in operating point with maximum load and 400 VAC
VAC Hz rpm W A °C p. 46
L5)
Curve
Nominal
voltage
range
Frequency
Speed/rpm
(1)
Perm.amb.temp.
Max.pow
erinput(1
)
Max.current
draw
(1)
Electr.connection
1
2
3
4
5
6
7
8
9
10
11
12
A
A
A
A
A
A
A
A
A
A
A
A
1500
1500
1500
1500
1245
1245
1245
1245
990
990
990
990
1830
2485
2965
2629
1023
1402
1660
1458
515
705
835
733
2,82
3,78
4,60
4,02
1,58
2,14
2,53
2,23
0,79
1,07
1,27
1,12
95
87
81
84
91
82
77
79
86
77
72
74
3~ 380-480 50/60 1500 2965 4,60 -25..+50A
35Electr. connectionp. 46
Depth of screw max. 25 mm
Cable gland
R3G 560-AP23 -01
K3G 560-AP23 -01 / -31
8x45˚
22.5˚
6x60
˚
14xM10
Ø232-2
Ø252±0,3
Ø275
250.5±1
±3
±2
238.7
160 16
Ø395
Ø636
Ø385
Ø490
Ø515
82
6xØ9351.7
421.770
(Ø56
4)
Ø188
8xØ1
1
750
550800-1
15413±2
483±3
kg kgCentrifugal fan Inlet nozzle with onepressure tap
Massof
centrifugalfan
Centrifugal modulew. support bracket
Massofcentrifugal
modulewith
support
bracket
kg
Massofcentrifugal
modulewith
support
bracket
R3G 560-AP23 -01 30,0 64030-2-4013 K3G 560-AP23 -01 52,5 K3G 560-AP23 -31 52,5
– Technical features: • Slave output 0-10 V max. 3 mA • Line undervoltage / phase failure detection• PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Electronics / motor overtemperature protection• Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Locked-rotor protection, Soft start• Control input 0-10 VDC / PWM • RS485 MODBUS • Digital inputs for day/night switch,• Input for sensor 0-10 V or 4-20 mA • Motor current limitation, Alarm relay enabling, cooling / heating
– EMC: Interference emission acc. to EN 61000-6-3Interference immunity acc. to EN 61000-6-2Harmonics acc. to DIN EN 61000-3-2/3
– Leakage current: < 3.5 mA acc. to EN 61800-5-1– Connection leads: Via terminal strip– Protection class: I (acc. to EN 61800-5-1)– Product conforming to standard: CE– Approvals: VDE, UL, CSA, CCC, GOST are applied for
Centrifugal modulew. support bracket (2)
(2) Centrifugal module with higher protection against corrosion
Guard grillep. 43
Inlet nozzlep. 42
36
EC centrifugal fans and modulesbackward curved, Ø 560
Nominal data
Type Motor
*3G 560 M3G 150-NA
subject to alterations
4000 8000 12000 16000
0 [CFM]
[Pa]
200
400
[inH 2O
]0,
81,
6
600 2,4
800 3,2
1000 4,0
1200 4,8
1400
[m3/h]
2000 4000 6000 8000
10
11
12
6
7
8
3
4
2
159
Curves
(1) Nominal data in operating point with maximum load and 400 VAC
VAC Hz rpm W A °C
n[rpm]
P1[W]
p. 47
M2)
I[A]
LwA[dB(A)]
– Material: Support bracket: Steel, coated in blackSupport plate: Galvanised sheet steelImpeller: Sheet aluminium, weldedRotor: Coated in blackElectronics enclosure: Die-cast aluminium
– Number of blades: 7– Direction of rotation: Clockwise, seen on rotor– Type of protection: IP 54 (acc. to EN 60529)– Insulation class: "F"– Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request– Condensate discharges: Rotor-side– Mode of operation: Continuous operation (S1)– Bearings: Maintenance-free ball bearings
A
Curve
Nominal
voltage
range
Frequency
Speed/rpm
(1)
Perm.amb.temp.
Max.pow
erinput(1
)
Max.current
draw
(1)
Electr.connection
3~ 380-480 50/60 1750 5030 7,70 -25..+40A
1
2
3
4
5
6
7
8
9
10
11
12
A
A
A
A
A
A
A
A
A
A
A
A
1750
1750
1750
1750
1450
1450
1450
1450
1150
1150
1150
1150
3212
4247
5030
4806
1723
2247
2577
2417
922
1171
1304
1222
4,89
6,47
7,70
7,30
2,66
3,43
3,93
3,69
1,51
1,85
2,04
1,93
98
91
84
85
94
86
82
82
87
79
75
75
37
R3G 560-AQ04 -03
kg
38,2 64030-2-4013 K3G 560-AQ04 -03
kg
68,4
– Technical features: • Slave output 0-10 V max. 3 mA • Line undervoltage / phase failure detection• PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Motor current limitation• Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Electronics / motor overtemperature protection• Control input 0-10 VDC / PWM • RS485 ebmBUS • Locked-rotor protection• Input for sensor 0-10 V or 4-20 mA • Alarm relay • Soft start
– EMC: Interference emission acc. to EN 61000-6-3Interference immunity acc. to EN 61000-6-2Harmonics acc. to DIN EN 61000-3-2/3
– Leakage current: < 3.5 mA acc. to EN 61800-5-1– Connection leads: Via terminal strip– Protection class: I (acc. to EN 61800-5-1)– Product conforming to standard: CE– Approvals: VDE, UL, CSA, CCC, GOST are applied for
Depth of screw max. 20 mm
Cable gland
Centrifugal fan Inlet nozzle with onepressure tap
Massof
centrifugalfan
Centrifugal modulew. support bracket
Massofcentrifugal
modulewith
support
bracket
504.7±3
113 391.7±2
333±1
160238.7
Ø188
Ø395
Ø636
(Ø56
4)
16
Ø280-2
Ø304±0.5
6x60˚
6xM10
826xØ9
Ø385
Ø490
Ø515
800-1
570
750
8xØ1
1
15453±2
566±3
R3G 560-AQ04 -03
K3G 560-AQ04 -03 / -33
Electr. connectionp. 47
K3G 560-AQ04 -33
kg
68,4
Massofcentrifugal
modulewith
support
bracket
Centrifugal modulew. support bracket (2)
(2) Centrifugal module with higher protection against corrosion
Guard grillep. 43
Inlet nozzlep. 42
38
EC centrifugal fans and modulebackward curved, Ø 310 - Design for use in sanitation units -
– Material: Support bracket: Steel, coated in whiteSupport plate: Galvanised sheet steel, coatedImpeller: Sheet aluminium, laser-welded, coatedRotor: Coated in blackElectronics enclosure: Die-cast aluminium, coated
– Number of blades: 7– Direction of rotation: Clockwise, seen on rotor– Type of protection: IP 54 (acc. to EN 60529)– Insulation class: "F"– Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request– Condensate discharges: Rotor-side– Mode of operation: Continuous operation (S1)– Bearings: Maintenance-free ball bearings
1000 2000 3000 4000 5000
0 [CFM]
[Pa]
400
[inH 2O
]1,
6
800 3,2
1200 4,8
1600 6,4
2000 8,0
[m3/h]
500 1000 2000 2500 30001500
10
11
12
6
7
8
3
4
2
159
Curves n[rpm]
P1[W]
I[A]
LwA[dB(A)]
A
Nominal data
Type Motor
*3G 310 M3G 112-IA
subject to alterations (1) Nominal data in operating point with maximum load and 400 VAC
VAC Hz rpm W A °C p. 46
L5)
Curve
Nominal
voltage
range
Frequency
Speed/rpm
(1)
Perm.amb.temp.
Max.pow
erinput(1
)
Max.current
draw
(1)
Electr.connection
1
2
3
4
5
6
7
8
9
10
11
12
A
A
A
A
A
A
A
A
A
A
A
A
4100
4100
4100
4100
3400
3400
3400
3400
2700
2700
2700
2700
1976
2488
2915
2750
1127
1428
1659
1566
564
715
831
784
3,03
3,77
4,50
4,19
1,73
2,17
2,53
2,39
0,87
1,08
1,27
1,19
97
91
89
93
93
87
85
89
88
82
80
84
3~ 380-480 50/60 4100 2915 4,50 -25..+40A
39Electr. connectionp. 46
6xM10
Ø252±0.5
Ø232±0.3
6x60˚
Ø36
0
80127 10
Ø36
0
Ø22
2
Ø13
8
69.5 217.5 ±2
287±3
55
4xØ4
.5
Ø350
Ø325
Ø211
.7
500-1
380
450
4xØ1
1
15258.5±2
328±3
R3G 310-AZ88 -01
K3G 310-AZ88 -02
Depth of screw 12-16 mm
Cable gland
kg kgCentrifugal fan (2) Inlet nozzle with onepressure tap
Massof
centrifugalfan
Centrifugal modulew. support bracket (2)
Massofcentrifugal
modulewith
support
bracket
R3G 310-AZ88 -01 15,0 31576-1-4013 K3G 310-AZ88 -02 25,0
– Technical features: • Slave output 0-10 V max. 3 mA • Line undervoltage / phase failure detection• PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Electronics / motor overtemperature protection• Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Locked-rotor protection, Soft start• Control input 0-10 VDC / PWM • RS485 MODBUS • Digital inputs for day/night switch,• Input for sensor 0-10 V or 4-20 mA • Motor current limitation, Alarm relay enabling, cooling / heating
– EMC: Interference emission acc. to EN 61000-6-3Interference immunity acc. to EN 61000-6-2Harmonics acc. to DIN EN 61000-3-2/3
– Leakage current: < 3.5 mA acc. to EN 61800-5-1– Connection leads: Via terminal strip– Protection class: I (acc. to EN 61800-5-1)– Product conforming to standard: CE– Approvals: VDE, UL, CSA, CCC, GOST are applied for
(2) With higher protection against corrosion
Guard grillep. 43
Inlet nozzlep. 42
40
EC centrifugal fans and modulebackward curved, Ø 450 - Design for use in sanitation units -
– Material: Support bracket: Steel, coated in whiteSupport plate: Galvanised sheet steel, coatedImpeller: Sheet aluminium, welded, coatedRotor: Coated in blackElectronics enclosure: Die-cast aluminium, coated
– Number of blades: 7– Direction of rotation: Clockwise, seen on rotor– Type of protection: IP 54 (acc. to EN 60529)– Insulation class: "F"– Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request– Condensate discharges: Rotor-side– Mode of operation: Continuous operation (S1)– Bearings: Maintenance-free ball bearings
2000 4000 6000 8000 10000 12000
0 [CFM]
[Pa]
[inH 2O
]
[m3/h]
1000 2000 4000 5000 700060003000
10
11
126
7
8
3
4
2
159
400 1,6
800 3,2
1200 4,8
1600 6,4
2000 8,0
Curves n[rpm]
P1[W]
I[A]
LwA[dB(A)]
A
Nominal data
Type Motor
*3G 450 M3G 150-IF
subject to alterations (1) Nominal data in operating point with maximum load and 400 VAC
VAC Hz rpm W A °C p. 47
M2)
Curve
Nominal
voltage
range
Frequency
Speed/rpm
(1)
Perm.amb.temp.
Max.pow
erinput(1
)
Max.current
draw
(1)
Electr.connection
1
2
3
4
5
6
7
8
9
10
11
12
A
A
A
A
A
A
A
A
A
A
A
A
2750
2750
2750
2750
2280
2280
2280
2280
1815
1815
1815
1815
3105
4841
5370
5060
1769
2759
3058
2884
893
1392
1543
1455
4,79
7,47
8,30
7,80
2,73
4,26
4,70
4,44
1,38
2,15
2,37
2,24
100
90
89
93
96
86
85
89
91
81
80
84
3~ 380-480 50/60 2750 5370 8,30 -25..+40A
41Electr. connectionp. 47
406.5±3
113 293.5±2
112176
Ø188
Ø317
Ø505
9
Ø280-2
Ø304±0.5
6x60˚
6xM10
766xØ9
Ø303
.4
Ø430
Ø480
630-1
520.5
580
8xØ1
1
15355.5±2
469±3
R3G 450-AZ26 -03
K3G 450-AZ26 -03
Depth of screw max. 20 mm
Cable gland
kg Inlet nozzle with onepressure tap
Massof
centrifugalfan
Centrifugal modulew. support bracket
R3G 450-AZ26 -03 31,5 45076-1-4013 K3G 450-AZ26 -03
– Technical features: • Slave output 0-10 V max. 3 mA • Line undervoltage / phase failure detection• PFC (passive) • Output 20 VDC (±20 %) max. 50 mA • Motor current limitation• Integrated PID controller • Output 10 VDC (+10 %) max. 10 mA • Electronics / motor overtemperature protection• Control input 0-10 VDC / PWM • RS485 ebmBUS • Locked-rotor protection• Input for sensor 0-10 V or 4-20 mA • Alarm relay • Soft start
– EMC: Interference emission acc. to EN 61000-6-3Interference immunity acc. to EN 61000-6-2Harmonics acc. to DIN EN 61000-3-2/3
– Leakage current: < 3.5 mA acc. to EN 61800-5-1– Connection leads: Via terminal strip– Protection class: I (acc. to EN 61800-5-1)– Product conforming to standard: CE– Approvals: VDE, UL, CSA, CCC, GOST are applied for
kgCentrifugal fan (2) Centrifugal modulew. support bracket (2)
Massofcentrifugal
modulewith
support
bracket
55,0
(2) With higher protection against corrosion
Guard grillep. 43
Inlet nozzlep. 42
42
Accessories
Air flow determination:
k-value
70
93
116
148
188
240
281
348
Inlet nozzles with measuring device to determine air flow for backward curved centrifugal fans
Part no. Part no.
25075-2-4013(1) / 25080-2-4013(2)
28075-2-4013(1) / 28080-2-4013(2)
31575-2-4013(1) / 31580-2-4013(2)
35675-2-4013(1) / 35680-2-4013(2)
40075-2-4013(1) / 40080-2-4013(2)
45075-2-4013(1) / 45080-2-4013(2)
64025-2-4013(1) / 64002-2-4013(2)
64030-2-4013(1) / 64001-2-4013(2)
Size
250
280
310
355
400
450
500
560
For dimensions, see
page 7
page 11
page 17
page 19
page 23
page 27
page 31
page 35
subject to alterations(1)
with one pressure tap(2)
with piezometer ring (4 pressure taps connected by tubing)
The differential pressure approach compares the static pressure before theinlet nozzle with the static pressure inside the inlet nozzle. Air flow can becalculated on the basis of the differential pressure (difference in pressure ofthe static pressures) in keeping with the following equation:
V = k . ∆pW V in [m3/h] und ∆pW in [Pa]
If constant air flow is to be controlled to, then the nozzle pressure has to bekept constant:
∆pW = V2 : k2
k takes into account the specific nozzle characteristics.Differences in static pressure are measured in 1/4 measuring point(s) alongthe circumference of the inlet nozzle. Connection on the customer side isacomplished via a pre-mounted T tube connector. This tube connector issuited for pneumatic hoses with an internal diameter of 4 mm.
Size
250
280
310
355
400
450
500
560
Vers.
1
1
1
1
2
2
2
2
For dimensions, see
page 7
page 11
page 17
page 19
page 23
page 27
page 31
page 35
subject to alterations
- Material: galvanised sheet steelVers. 1 Vers. 2
6x60
˚
4x90˚
Part no.
25070-2-4013
28070-2-4013
31570-2-4013
35670-2-4013
40070-2-4013
45070-2-4013
63072-2-4013
63071-2-4013
Inlet nozzles without measuring device for backward curved centrifugal fans
∆p W
0,5xD
D
43
Accessories
a
e
Ød
be
Ød
b
a
Part no.
78129-2-4039
78130-2-4039
78131-2-4039
78132-2-4039
78133-2-4039
78134-2-4039
78139-2-4039
78137-2-4039
Size
250
280
310
355
400
450
500
560
Vers.
1
1
1
1
2
2
2
2
a b d e Strut pitch
260 4,5 191 2,8 4 x 90°
280 4,5 229 2,8 4 x 90°
325 4,5 248 2,8 4 x 90°
345 4,5 305 2,8 4 x 90°
390 8,5 343 3,8 3 x 120°
430 8,5 381 3,8 3 x 120°
445 8,5 410 3,8 3 x 120°
490 8,5 430 3,8 3 x 120°
subject to alterations
- Material: sheet steel, plastic coated,silver-metallic gloss
Air intake guard grilles for backward curved centrifugal fans (according to EN 294)
Vers. 1 Vers. 2
Effects of installation space
When mounting our product in a rectangular box, air performance
might be reduced.
dh = Hydraulic diameter
Formula: dh = 2 x B x H / (B + H)
B = Width of box
H = Height of box
D = Outer diameter of the fan
1,4 1,6 1,8 2,0 2,2 2,4 2,6 2,8
Hydraulic diameter dh/D
Corr
ectio
nfa
ctor
fora
irflo
w
1,00
0,99
0,98
0,97
0,96
0,95
0,94
0,93
0,92
Curve
DH
B
0,5xD
D
D
44
Electrical connections EC
K1)
+
-
+
-
NC
10 K
PWM
12 V
U
PE
N
L
GND
Imax =10 mA
Umin = 15 V
1 µF
white1
white2
Speed setting
PWM 1 - 10 kHz
Speed settingwith variableresistance
Full speed
100% PWM -> n=maxapprox. 10% PWM -> n=min
< 10% PWM -> n=0
start up at > 14 %
Speed setting
1 V - 10 V
10 V -> n=maxapprox. 1 V -> n=min
< 1 V -> n=0
start up at > 1.4 V
yellow
blue
Lin/PWM control input
0-10 VDC /PWM
green/yellow
blue
black
redVoltage output
+10 Vmax. 1.1 mA
Customer circuit
Notes on various control possibilities and their applications
Connection Fan
Mains50/60 Hz
Alarm relay:Break for failure(2 A, 250 VAC, AC1)
L PEN
Line Connection Colour Assignment / function Line Connection Colour Assignment / function1 2L black Mains 50/60 Hz, phase +10 V red
0-10 V / PWM yellow Control input (Impedance 100 kΩ)N blue Mains 50/60 Hz, neutral
PE green/yel Protective earth
Line 1
black green/yellowblue
+10
V
0-10
VPW
M
Line 2
red yellow
Voltage output +10 V max. 1.1 mA
NC white1 Alarm relay, break for failure
COM white2 Alarm relay, COMMON
GND blue GND
NC GND
white1
COM
white2 blue
45
L2)
Connector Connection Assignment / function Connector Connection Assignment / functionPE KL3PE Protective earth OUT
KL1 L3 Mains; L3
L2 Mains; L2
L1 Mains; L1
GND GND
GND GND
KL2
0-10 V / PWM
COM Alarm relay, COMMON (2A, 250 VAC, AC1)
+10 V
+20 V
4-20 mA Control / Actual value input
RSB RS485 interface for ebmBUS; RS B
RSA RS485 interface for ebmBUS; RS A
RSB RS485 interface for ebmBUS; RS B
RSA RS485 interface for ebmBUS; RS A
NC
NO
Control / Actual value input (Impedance 100 kΩ)
0-10 V / PWM Control / Actual value input
Alarm relay, break for failure
Alarm relay, make for failure
Master output 0-10 V max. 3 mA
Supply for external potentiometer,
10 VDC (+10 %) max. 10 mA
Supply for external sensor,
20 VDC (±20 %) max. 50 mA
RSA
RSB
RSA
RSB
GND
0-10
VPW
M
4-20
mA
+20
V
+10
V
0-10
VPW
M
GND
OUT
NO COM
NC L1 L2 L3 PE
KL3 KL2 KL1
L6)
Connector Connection Assignment / function Connector Connection Assignment / functionPE KL3PE Protective earth OUT
KL1 L3 Mains; L3
L2 Mains; L2
L1 Mains; L1
GND GND
GND GND
KL2
0-10 V / PWM
COM Alarm relay, COMMON (2A, 250 VAC, AC1)
+10 V
+20 V
4-20 mA Control / Actual value input
RSB RS485 interface for MODBUS RTU; RS B
RSA RS485 interface for MODBUS RTU; RS A
RSB RS485 interface for MODBUS RTU; RS B
RSA RS485 interface for MODBUS RTU; RS A
NC
NO
Control / Actual value input (Impedance 100 kΩ)
0-10 V / PWM Control / Actual value input
Alarm relay, break for failure
Alarm relay, make for failure
Master output 0-10 V max. 3 mA
Supply for external potentiometer,
10 VDC (+10 %) max. 10 mA
Supply for external sensor,
20 VDC (±20 %) max. 50 mA
RSA
RSB
RSA
RSB
GND
0-10
VPW
M
4-20
mA
+20
V
+10
V
0-10
VPW
M
GND
OUT
NO COM
NC L1 L2 L3 PE
KL3 KL2 KL1
46
Electrical connections EC
L5)
PE
KL3
PE
+10 V
KL1 L3
L2
L1
GND
Ain2 I
GND
KL2
Ain1U
COM
RSB
GND
RSA
Aout
RS485 interface for MODBUS RTU; RS B
+20 V
RS485 interface for MODBUS RTU; RS A
GND
NC
NO
Supply for external potentiometer,
10 VDC (±3 %) max. 10 mA
Analogue output 0-10 V max. 5 mA, reading of current
motor speed / current motor control factor
Din2
Din3
GND
Ain2
U
+20
V
Ain2
I
Aout
KL3 KL2 KL1
RSA
RSB
GND
Ain1
U
+10
V
Ain1
I
Din1 NO COM
NC PE L1 L2 L3
Analogue set value input, 0-10 V (impedance 100 kΩ),
only to be used as alternative to terminal Ain1 I
Analog. actual value input, 4-20mA (impedance 100Ω),
only to be used as alternative to terminal Ain2 U
Supply for external sensor,
20 VDC (+25 % / -10%) max. 40 mA
Din1
Ain1 I Analogue set value input, 4-20 mA (impedance 100 Ω),
only to be used as alternative to terminal Ain1 U
Digital input 1 (enabling / disabling of electronics),,
Enabling: Pin open or applied voltage 5...50 VDC
Disabling: Bridge to GND or applied voltage < 1 VDC
Ain2 U Analog. actual value input, 0-10 V (impedance 100 kΩ),
only to be used as alternative to terminal Ain2 I
Din3 Digital input 3 (switch Normal / Inverse),
The preset effective direction of the integrated
controller can be selected via BUS or via digital input
Normal/Inverse.
Normal: Pin open or applied voltage 5...50 VDC
Inverse: Bridge to GND or applied voltage < 1 VDC
Din2 Digital input 2 (switch Day / Night),
The preset set of parameters can be selected via BUS
or via digital input Day/Night.
Day: Pin open or applied voltage 5...50 VDC
Night: Bridge to GND or applied voltage < 1 VDC
Connector Connection Assignment / function Connector Connection Assignment / function
Protective earth
Mains; L3
Mains; L2
Mains; L1
Alarm relay, COMMON (2A, 250 VAC, AC1)
Alarm relay, break for failure
Alarm relay, make for failure
47
M2)
PE
KL3
PE
+10 VKL1 L3
L2
L1
GND
Ain2 I
GND
KL2
Ain1U
COM RSB
GND
RSA
Aout
+20 V
GND
NC
NO
Supply for external potentiometer,
10 VDC (±3 %) max. 10 mA
Analogue output 0-10 V max. 5 mA,
reading of the current motor control factor
GND
+20
V
Ain2
I
Aout
KL3 KL2 KL1
RSA
RSB
GND
Ain1
U
+10
V
NO COM
NC PE L1 L2 L3
Analogue set value input, 0-10 V (impedance 100 kΩ),
only to be used as alternative to terminal Ain2 I
Analog. actual value input, 4-20mA (impedance 100Ω),
only to be used as alternative to terminal Ain1 U
Supply for external sensor,
20 VDC (+25 % / -10%) max. 40 mA
Connector Connection Assignment / function Connector Connection Assignment / function
Protective earth
Mains; L3
Mains; L2
Mains; L1
Alarm relay, COMMON (2A, 250 VAC, AC1) RS485 interface for ebmBUS; RS B
RS485 interface for ebmBUS; RS A
Alarm relay, break for failure
Alarm relay, make for failure
L7)
Connector Connection Assignment / function Connector Connection Assignment / functionPE KL3PE Protective earth OUT
KL1 N Mains 50/60 Hz. neutral
L Mains 50/60 Hz, phase
GND GND
GND GND
KL2
0-10 V / PWM
COM Alarm relay, COMMON (2A, 250 VAC, AC1)
+10 V
+20 V
4-20 mA Control / Actual value input
RSB RS485 interface for MODBUS RTU; RS B
RSA RS485 interface for MODBUS RTU; RS A
RSB RS485 interface for MODBUS RTU; RS B
RSA RS485 interface for MODBUS RTU; RS A
NC
NO
Control / Actual value input (Impedance 100 kΩ)
0-10 V / PWM Control / Actual value input
Alarm relay, break for failure
Alarm relay, make for failure
Master output 0-10 V max. 3 mA
Supply for external potentiometer,
10 VDC (+10 %) max. 10 mA
Supply for external sensor,
20 VDC (±20 %) max. 50 mA
RSA
RSB
RSA
RSB
GND
0-10
VPW
M
4-20
mA
+20
V
+10
V
0-10
VPW
M
GND
OUT
NO COM
NC L N PE
KL3 KL2 KL1
48
ebm-papst representatives & subsidiaries
Germany
ebm-papstMulfingen GmbH & Co. KG
Bachmühle 2D-74673 MulfingenPhone +49 7938 81-0Fax +49 7938 81-110info1@de.ebmpapst.com
www.ebmpapst.com
ebm-papstSt. Georgen GmbH & Co. KG
Hermann-Papst-Straße 1D-78112 St. GeorgenPhone +49 7724 81-0Fax +49 7724 81-1309info2@de.ebmpapst.com
www.ebmpapst.com
ebm-papstLandshut GmbH
Hofmark-Aich-Straße 25D-84030 LandshutPhone +49 871 707-0Fax +49 871 707-465info3@de.ebmpapst.com
www.ebmpapst.com
KasselDipl.-Ing. (FH) Ralph BrückHoherainstraße 38D-35075 GladenbachPhone +49 6462 4071-10Fax +49 6462 4071-11Ralph.Brueck@de.ebmpapst.com
KoblenzWinfried SchaeferHinter der Kirch 10D-56767 UersfeldPhone +49 2657 16-96Fax +49 2657 16-76Winfried.Schaefer@de.ebmpapst.com
MunichDipl.-Wirtsch.-Ing. (FH) Jens PeterSteinbergweg 6D-82285 HattenhofenPhone +49 8145 8092-25Fax +49 8145 8092-26Jens.Peter@de.ebmpapst.com
NurembergFriedrich KleinAdlerstraße 49/1D-73540 HeubachPhone +49 7173 4983Fax +49 7173 8053Friedrich.Klein@de.ebmpapst.com
OffenburgDipl.-Ing. (FH) Ralf BraunHubeneck 21D-77704 OberkirchPhone +49 7802 9822-52Fax +49 7802 9822-53Ralf.Braun@de.ebmpapst.com
StuttgartDipl.-Ing. (FH) Rudi WeinmannHindenburgstraße 100/1D-73207 PlochingenPhone +49 7153 9289-80Fax +49 7153 9289-81Rudi.Weinmann@de.ebmpapst.com
UlmDipl.-Wirt.-Ing. (FH) Axel ReschBachmühle 2D-74673 MulfingenPhone +49 7938 81-7092Fax +49 7938 81-110Axel.Resch@de.ebmpapst.com
Distributors
FrankfurtR.E.D. Handelsgesellschaft mbHGutenbergstraße 3D-63110 Rodgau - JügesheimPhone +49 6106 841-0Fax +49 6106 841-111info@red-elektromechanik.dewww.red-elektromechanik.de
HamburgBreuell + Hilgenfeldt GmbHGrützmühlenweg 40D-22339 HamburgPhone +49 40 538092-20Fax +49 40 538092-84info@breuell-hilgenfeldt.de
MunichA. Schweiger GmbHOhmstraße 1D-82054 SauerlachPhone +49 8104 897-0Fax +49 8104 897-90info@schweiger-gmbh.dewww.schweiger-gmbh.com
(1 to 5 pieces)
NorthBreuell + Hilgenfeldt GmbHGrützmühlenweg 40D-22339 HamburgPhone +49 40 538092-20Fax +49 40 538092-84ebmpapst@breuell-hilgenfeldt.de
SouthHDS Ventilatoren Vertriebs GmbHGlaswiesenstraße 1D-74677 DörzbachPhone +49 7937 802968Fax +49 7937 802578info@hds-gmbh.net
Agencies
BerlinDipl.-Ing. (TH) Jens DuchowHändelstraße 7D-16341 PanketalPhone +49 30 944149-62Fax +49 30 944149-63Jens.Duchow@de.ebmpapst.com
BielefeldDipl.-Ing. (FH) Wolf-Jürgen WeberNiehausweg 13D-33739 BielefeldPhone +49 5206 91732-31Fax +49 5206 91732-35Wolf-Juergen.Weber@de.ebmpapst.com
DortmundDipl.-Ing. (FH) Hans-Joachim PundtAuf den Steinern 3D-59519 Möhnesee-VöllinghausenPhone +49 2925 800-407Fax +49 2925 800-408Hans-Joachim.Pundt@de.ebmpapst.com
FrankfurtDipl.-Ing. Christian KleffmannDr.-Hermann-Krause-Straße 23D-63452 HanauPhone +49 6181 1898-12Fax +49 6181 1898-13Christian.Kleffmann@de.ebmpapst.com
HalleDipl.-Ing. (TU) Michael HanningLerchenweg 4D-06120 LieskauPhone +49 345 55124-56Fax +49 345 55124-57Michael.Hanning@de.ebmpapst.com
HamburgIngenieurbüro Breuell GmbHIng. Dirk KahlElektroingenieurGrützmühlenweg 40D-22339 HamburgPhone +49 40 538092-19Fax +49 40 538092-84Dirk.Kahl@de.ebmpapst.com
fan agent
compact fan agent
motor specialist
motor agent
49
Europe
Austriaebm-papst Motoren & Ventilatoren GmbHWestbahnstraße 5A-4490 St. FlorianPhone +43 7224 66011-0Fax +43 7224 66011-20info@at.ebmpapst.comwww.ebmpapst.at
Belarusebm-papst Bel AgmbHP.O. Box 117BY-220138 MinskPhone +375 17 3851556Fax +375 17 3851556info@by.ebmpapst.comwww.ebmpapst.by
BelgiumVIBO Benelux B. V.Sales office Belgium-LuxemburgRomeinsestraat 6/0101Research Park HaasrodeB-3001 Heverlee-LeuvenPhone +32 16 396-200Fax +32 16 396-220info@vibobenelux.comwww.vibobenelux.com
Bulgariaebm-papst Romania S.R.L.Str. Tirnavei Nr. 20RO-500327 BrasovPhone +40 268 312-805Fax +40 268 312-805dudasludovic@xnet.ro
Croatiaebm-papst Industries Kft.Ezred u. 2.H-1044 BudapestPhone +36 1 8722-190Fax +36 1 8722-194office@hu.ebmpapst.comwww.ebmpapst.hu
CyprusMATERO LTD37, St. Kyriakides AvenueP.O. Box 51744CY-3080 LimassolPhone +357 25 870030Fax +357 25 381366matero@cytanet.com.cywww.matero.com.cy
Czech Republic / Slovakiaebm-papst CZ s.r.o.Krátká 379CZ-66461 Rajhradice u BrnaPhone +420 547 232-617Fax +420 547 232-622info@ebmpapst.czwww.ebmpapst.cz
DenmarkJenk A/SVallensbækvej 21DK-2605 BrøndbyPhone +45 43 63-1111Fax +45 43 63-0505jenk@jenk.dkwww.jenk.dk
Estoniaebm-papst Oy Eesti FiliaalKadaka tee 3EST-10621 TallinnPhone +372 65569-78Fax +372 65569-79www.ebmpapst.ee
Finlandebm-papst OyPuistotie 1FIN-02760 EspooPhone +358 9 887022-0Fax +358 9 887022-13mailbox@ebmpapst.fiwww.ebmpapst.fi
Franceebm-papst SARLZI Nord - rue A. MohlerBP 62F-67212 Obernai-CedexPhone +33 820 326266Fax +33 3 88673883info@ebmpapst.frwww.ebmpapst.fr
GreeceHelcomaTh. Rotas & Co OEDavaki 65GR-17672 Kallithea-AttikiPhone +30 210 9513-705Fax +30 210 9513-490contact@helcoma.grwww.helcoma.gr
Hungaryebm-papst Industries Kft.Ezred u. 2.H-1044 BudapestPhone +36 1 8722-190Fax +36 1 8722-194office@hu.ebmpapst.comwww.ebmpapst.hu
IcelandRJ EngineersStangarhyl 1AIS-110 ReykjavikPhone +354 567 8030Fax +354 567 8015rj@rj.iswww.rj.is
Irelandebm-papst LimitedPortlaoise Business & Technology ParkMountrath RoadIRL-Portlaoise, Co. LaoisPhone +353 5786 643-43Fax +353 5786 643-46sales@ie.ebmpapst.comwww.ebmpapst.ie
Italyebm-papst SrlVia Cornaggia 108I-22076 Mozzate (Co)Phone +39 0331 836201Fax +39 0331 821510info@it.ebmpapst.comwww.ebmpapst.it
Macedoniaebm-papst Industries Kft.Ezred u. 2.H-1044 BudapestPhone +36 1 8722-190Fax +36 1 8722-194office@hu.ebmpapst.comwww.ebmpapst.hu
50
ebm-papst representatives & subsidiaries
Russiaebm-papst Ural GmbHPosadskaja-Strasse, 23(E), 3RU-620102 EkaterinburgPhone +7 343 2338000Fax +7 343 2337788Konstantin.Molokov@ru.ebmpapst.comwww.ebmpapst.ur.ru
ebm-papst Rus GmbHNizhegorodskaya 32, str. 15 office 420RU-109029 MoskauPhone +7 495 9807524Fax +7 495 6715395info@ebmpapst.ruwww.ebmpapst.ru
Serbia & Montenegroebm-papst Industries Kft.Ezred u. 2.H-1044 BudapestPhone +36 1 8722-190Fax +36 1 8722-194office@hu.ebmpapst.comwww.ebmpapst.hu
Spainebm-papst Ibérica S.L.Avda. del Sistema Solar, 29E-28830 San Fernando de Henares (Madrid)Phone +34 91 6780894Fax +34 91 6781530ventas@ebmpapst.es
Swedenebm-papst ABÄggelundavägen 2S-17562 JärfällaPhone +46 8 7619400Fax +46 8 362306info@ebmpapst.sewww.ebmpapst.se
Switzerlandebm-papst AGRütisbergstrasse 1CH-8156 OberhasliPhone +41 44 73220-70Fax +41 44 73220-77verkauf@ebmpapst.chwww.ebmpapst.ch
TurkeyAkantel Elektronik San. Tic. LTD. Sti.Atatürk Organize SanayiBölgesi 10007 SK. No.:6TR-35620 Cigli-IzmirPhone +90 232 3282090Fax +90 232 3280270akantel@akantel.com.trwww.ebmpapst.com.tr
Ukraineebm-papst Ukraine LLCLepse Boulevard, 4, Building 47UA-03067 KievPhone +38 044 2063091Fax +38 044 2063091mail@ebmpapst.uawww.ebmpapst.ua
United Kingdomebm-papst UK Ltd.Chelmsford Business ParkGB-Chelmsford Essex CM2 5EZPhone +44 1245 468555Fax +44 1245 466336sales@uk.ebmpapst.comwww.ebmpapst.co.uk
ebm-papst Automotive & Drives (UK) Ltd.The SmithyFidlers Lane, East IlsleyGB-Berkshire RG20 7LGPhone +44 1635 2811-11Fax +44 1635 2811-61A&Dsales@uk.ebmpapst.comwww.ebmpapst-ad.com
NetherlandsVIBO Benelux B. V.Engelseweg 127Postbus 230NL-5705 AC HelmondPhone +31 492 502-900Fax +31 492 502-950verkoop@vibobenelux.comwww.vibobenelux.com
Norwayebm-papst ASP.B. 173 HolmliaN-1203 OsloPhone +47 22 763340Fax +47 22 619173mailbox@ebmpapst.nowww.ebmpapst.no
Polandebm-papst Polska Sp. z o.o.ul. Annopol 4APL-03236 WarszawaPhone +48 22 6757819Fax +48 22 6769587office@ebmpapst.plwww.ebmpapst.pl
Portugalebm-papst (Portugal), Lda.Av. Marechal Gomes da Costa, 35 eRua Conselheiro Emidio NavarroP-1800-255 LisboaPhone +351 218 394-880Fax +351 218 394-759info@pt.ebmpapst.comwww.ebmpapst.pt
Romaniaebm-papst Romania S.R.L.Str. Tirnavei Nr. 20RO-500327 BrasovPhone +40 268 312-805Fax +40 268 312-805dudasludovic@xnet.ro
fan agent
compact fan agent
motor specialist
motor agent
51
America
Argentinaebm-papst de Argentina S.A.Hernandarias 148 Lomas del MiradorPcia. de Buenos Aires (1752)Phone +54 11 46576135Fax +54 11 46572092ventas@ar.ebmpapst.comwww.ebmpapst.com.ar
Brasilebm-papst Motores Ventiladores Ltda.Av. José Giorgi, 301 Galpões B6+B7Condominio Logical CenterBR-06707-100 Cotia - São PauloPhone +55 11 3164-8900Fax +55 11 3164-8924vendas@br.ebmpapst.comwww.ebmpapst.com.br
Canadaebm-papst Canada Inc.1800 Ironstone Manor, Unit 2CDN-Pickering, Ontario, L1W3J9Phone +1 905 420-3533Fax +1 905 420-3772sales@ca.ebmpapst.comwww.ebmpapst.ca
Mexicoebm Industrial S.de R.L. de C.V.Paseo de Tamarindos 400-A-5to PisoCol. Bosques de las LomasMEX-Mexico 05120, D.F.Phone +52 55 3300-5144Fax +52 55 3300-5243sales@mx.ebmpapst.comwww.ebmpapst.com.mx
USAebm-papst Inc.P.O. Box 4009100 Hyde RoadUSA-Farmington, CT 06034Phone +1 860 674-1515Fax +1 860 674-8536sales@us.ebmpapst.comwww.ebmpapst.us
ebm-papst Automotive & Drives, Inc.3200 Greenfield, Suite 255USA-Dearborn, MI 48120Phone +1 313 406-8080Fax +1 313 406-8081automotive@us.ebmpapst.comwww.ebmpapst-automotive.us
Africa
South Africaebm-papst South Africa (Pty) Ltd.P.O. Box 31241119 Yacht AvenueZA-2040 HoneydewPhone +27 11 794-3434Fax +27 11 794-5020info@za.ebmpapst.comwww.ebmpapst.co.za
52
ebm-papst representatives & subsidiaries
Asia
Chinaebm-papst Ventilator (Shanghai) Co., Ltd.No. 418, Huajing RoadWaiGaoQiao Free Trade ZoneNo. 2001, Yang Gao (N) RoadVRC-200131 Shanghai, P.R. of ChinaPhone +86 21 5046-0183Fax +86 21 5046-1119sales@cn.ebmpapst.comwww.ebmpapst.com.cn
Hong Kongebm-papst Ventilator (Shanghai) Co., Ltd.Hong Kong Representative OfficeUnit Nos. 13-15, 9/F, Technology Park18 On Lai Street, Siu Lek Yuen, Shatin,N.T. Hong Kong P.R. of ChinaPhone +852 2145-8678Fax +852 2145-7678info@hk.ebmpapst.com
Indiaebm NADI International Pvt Ltd.26/3, G.N.T. Road, ErukkencherryIND-Chennai-600118Phone +91 44 25372556Fax +91 44 25371149ebmnadi@md2.vsnl.net.inwww.ebmnadi.com
Indonesiaebm-papst IndonesiaWisma Slipi Building 14th Floor, No. 1410Jl. Letjend S. Parman Kav. 12RI-Jakarta Barat 11480Phone +62 21 536619-01Fax +62 21 536619-05salesdept@id.ebmpapst.com
IsraelPolak Bros. Import Agencies Ltd.9 Hamefalsim StreetIL-Kiryat Arie, Petach-Tikva 49514Phone +972 3 9100300Fax +972 3 5796679polak@polak.co.ilwww.polak.co.il
Japanebm-papst Industries Japan K.K.12 Floor, Benex S-3 Bldg.3-20-8 Shinyokohama, Kohoku-kuJ-222-0033 YokohamaPhone +81 45 47057-51Fax +81 45 47057-52info@jp.ebmpapst.comwww.ebmpapst.jp
Koreaebm-papst Korea Co. Ltd.6F, Trutec Bldg.B 6-2, Digital Media City (DMC)Sangam-Dong, Mapo-GuROK-Seoul 121-270Phone +82 2 366213-24Fax +82 2 366213-26info@kr.ebmpapst.comwww.ebmpapst.co.kr
Malaysiaebm-papst MalaysiaRepresentative OfficeBlock F1, 9A-4, Jln PJU 1/42Dataran PrimaMAL-47301 Petaling JayaPhone +60 3 780654-40Fax +60 3 780654-41salesdept@my.ebmpapst.com
Singaporeebm-papst SEA Pte. Ltd.No. 23 Ubi Road 4#06-00 Olympia Industrial BuildingSGP-Singapore 408620Phone +65 65513789Fax +65 68428439salesdept@sg.ebmpapst.com
TaiwanETECO Engineering & Trading Corp.10F-I, No. 92, Teh-Wei Str.RC-Tsow-Inn District, KaohsiungPhone +886 7 557-4268Fax +886 7 557-2788eteco@ms22.hinet.net
Thailandebm-papst Thailand Co., Ltd.99/349 Na-Nakorn Bldg., 4th FloorChaeng Wattana Road, Thungsonghong,THA-10210 Laksi, BKKPhone +66 2 57615-24Fax +66 2 57615-42salesdept@th.ebmpapst.com
United Arab Emiratesebm-papst Middle East FZEPO Box 17755Jebel Ali Free Zone / FZS1 / AP05UAE-DubaiPhone +971 4 88608-26Fax +971 4 88608-27info@ae.ebmpapst.comwww.ebmpapst.ae
Vietnamebm-papst VietnamRepresentative OfficeRoom #102, 25 Nguyen Van Thu StreetDistrict 1VN-Ho Chi Minh CityPhone +84 8 39104099Fax +84 8 39103970linh.nguyen@vn.ebmpapst.com
fan agent
compact fan agent
motor specialist
motor agent
53
Australia
Australiaebm-papst A&NZ Pty Ltd.10 Oxford RoadAUS-Laverton North, Victoria, 3026Phone +61 3 9360-6400Fax +61 3 9360-6464sales@ebmpapst.com.auwww.ebmpapst.com.au
New Zealandebm-papst A&NZ Pty Ltd.102 Henderson Valley RoadNZ-Henderson, Auckland 1230Phone +64 9 837-1884Fax +64 9 837-1899sales@ebmpapst.com.auwww.ebmpapst.com.au
54
Notes
55
37797-7-8811 · RA-10/09-3’Printed in Germany
ebm-papst
Mulfingen GmbH & Co. KG
Bachmühle 2
D-74673 Mulfingen
Phone +49 7938 81-0
Fax +49 7938 81-110
info1@de.ebmpapst.com
www.ebmpapst.com
Recommended