View
6
Download
0
Category
Preview:
Citation preview
ELECTRICAL POLYMER
COVER STRIP
COMMUNICATIONS
MARKER TAPE
FINISHED GROUND LEVEL
1 2 3
FOOTPATH
4 5 6
ELECTRICAL POLYMER
COVER STRIP
COMMUNICATIONS
MARKER TAPE
FINISHED GROUND LEVEL
1 2 3
4 5 6
ROAD
50 TYP
250
MIN
100
600
MIN
50 T
YP
100
50 TYP
50 TYP
50 TYP
100
50 T
YP
50 TYP
400
MIN
750
MIN
TYPICAL ELECTRICAL & COMMSCONDUIT ARRANGEMENT (FOOTPATH)
TYPICAL ELECTRICAL & COMMSCONDUIT ARRANGEMENT (ROAD)
50 TYP
1 x Ø63mm UPVC ORANGE CONDUIT FORSTREET LIGHTING & POWER.2 x Ø63mm UPVC ORANGE CONDUIT FORPOWER PROVISION FOR FUTURE USE.
3 x Ø50mm UPVC WHITE CONDUITFOR COMMUNICATIONS CABLING.PROVISION FOR FUTURE USE
1 x Ø63mm UPVC ORANGE CONDUITFOR STREET LIGHTING & POWER.2 x Ø63mm UPVC ORANGE CONDUITFOR POWER PROVISION FORFUTURE USE.
3 x Ø50mm UPVC WHITE CONDUITFOR COMMUNICATIONS CABLING.PROVISION FOR FUTURE USE
100
SECTION 1:10
LIGHTINGDwg No.
5.1.1
GENERAL
CONDUITS IN FOOTWAY AND CARRIAGEWAY
NOTE: ALL DIMENSIONS IN MILLIMETRES UNLESS OTHERWISE STATED
Rev DDate 01.12.19
Approved P S
SCALE: NTS
LIGHTINGDwg No.
5.1.2
GENERAL
"ROCKS" TYPE COLUMN INCLUDING FOOTINGS
NOTE: ALL DIMENSIONS IN MILLIMETRES UNLESS OTHERWISE STATED
Rev DDate 01.12.19Approved P S
700 mm
700
mm
695
mm
1500
mm
75 mm
150 mm 150 mm
STAINLESS STEELPADLOCKABLE SWINGHANDLE
CHROME PLATTEDNUT SEALABLE
GALVANIZED PLINTH
CHROME PLATTEDLIFTING HANDLE
ANTI CONDENSATIONHEATER MOUNTEDON DIN RAIL
STAINLESS STEELPINTLE HINGE
FRONT ELEVATION(WITH DOORS FITTED)
700 mm
600x600x6mmMETER PANELFIXED WITH FLAPHINGES
THERMOSTAT
36WAY E&N LINK
WELDED CABLETRAY
INCOMING CABLETERMINAL
4x50mmBUSHED HOLESFOR INCOMINGCABLES
WELDED CABLETRAY
REMOVABLEGEARPAN
GALVANIZED PLINTH
695m
m70
0 m
m30
mm 400mm
475mm
FIT SCHEDULE HOLDERTO BACK OF DOOR
FRONT ELEVATION(WITH DOORS REMOVED)
GLAND PLATE GLAND PLATE
SECTION A-A
STREET LIGHTING MAIN SWITCHBOARDSUPPLY FED FROM: TO BE ADVISED
SUBMAIN:
CITY OF SYDNEYSITE LOCATIONSITE LOCATION
SWITCHBOARD & MANUFACTURERDETAILS. REFER TO CoS STREETLIGHTING STANDARD SECTION B8
ENERY AUTHORITYMETER ENCLOSURE MAIN ISOLATOR
GPO DISTRIBUTIONSECTION
LIGHTINGDISTRIBUTION
SECTION
MINOR EQUIPMENT SCHEDULEITEMS DESCRIPTION REFERENCE PART NO. QTY
SERVICE FUSES
THREE PHASE METER
SERVICE METER NEUTRAL LINK
MAIN ISOLATOR
3P 12-WAY COMB BUSBAR
3P 24-WAY COMB BUSBAR
36 WAY BRASS LINKS
ANTI CONDENSATION HEATER
THERMOSTAT
FUSE
A-O-M SWITCH
CONTRACTOR (C1)
TERMINAL
SS316 PADLOCKABLE HANDLE
MCB
MCB
MCB
IPD SERIES 7 SERVICE FUSE BACK CONNECTION + FUSE LINK #S71002BBWAI+RHLF100
SUPPLIED AND FITTED BY OTHERS
NETEC SEALABLE LINKS 3x35 & 2x16mm #AN100S-535-B
SCNEIDER 3P 12-WAY 100A COMB BUSBAR WITH ENDCAP #SN-A9XPH312
36 WAY N&E BRIBAR LINKS #DB-BRASSLINK-36
IPD - 15W ANTICONDENSATION HEATER #RACP-15
IPD - 100 - 250V AC 1NC THERMOSTAT #TRT-10A230V-NC
FUSE CARRIER #ACC-FUS-C10G10A FUSE LINK #ACC-FUS-10G-10
TELUX DIN RAIL MOUNTED 20A NON-LOCABLE 2P SWITCH #M10HEU1-SMA
LS CONTRACTOR 3P N/O AC3-85A 240V #BX-MC-85A
TERMINAL 2.5MM GREY #ACC-TERM-GREY-2.5
SWING HANDLE PADLOCKABLE - SS316 #GEN-HANDLE -SH-PL-316
SCHNEIDER - 1P 6A 6kA MCB C - CURVE #SN-A9F44106
SCHNEIDER - 3P 25A 6kA MCB C - CURVE #SN-A9F44350
SCHNEIDER - 2P 20A 10kA MCB WITH 30mA RCD PROTECTION C-CURVE
SCNEIDER 3P 12-WAY 100A COMB BUSBAR WITH ENDCAP #SN-A9XPH324
1 2 3 4 5 6 7 8 9 10 1112
131415161718192021 22 2324252627 28293031 323334 3536
OFF
AUTO MANUAL
METERINGEQUIPMENT ONLY
E3 E3
N N
HOLDER FUSE ALSTOMSERIES 7
S71002BBWAI
Colour - White - BlackSize- 200x40mm
1 OFF Colour - White - BlackSize- 200x50mm
1 OFF
Colour - White - BlackSize- 200x40mm
1 OFF
Colour - Black - WhiteSize- 80x25mm
1 OFF
Colour - White - BlackSize- 80x25mm
1 OFF
Colour - White - BlackSize- 80x25mm
1 OFF
10mm
5mm
5mm
10mm
10mm
10mm
10mm
10mm
6mm
6mm
6mm
6mm
6mm
LIGHTINGDwg No.
5.1.3Rev DDate 01.12.19Approved P G
NOTE:TO BE READ IN CONJUNCTION WITH DRAWING 5.1.4NOTE: ALL DIMENSIONS IN MILLIMETRES UNLESS OTHERWISE STATED
GENERALTHREE PHASE SWITCHBOARD DETAILS &SCHEMATICS (SHEET 1)
DOORS AND ESCUTCHEONS: 1.5mm GRADE 316 STAINLESS STEEL
OTHER BRACKETS: 1.6mm ZINC SEALED MILD STEEL MIN
BOTTOM GLAND PLATE: 6mm METER PANEL
FORM OF SECREGATION: FORM 1 - TO AS3439.1 - 2002
DEGREE OF PROTECTION: IP - 66 - REFER TO WEATHER PROOFING DETAIL
FAULT RATING: 6kA FOR 1 SECOND
FINISH:PREPERATION: DE-SCALE & DE-GREASE
EXTENRAL COLOUR: NATURAL FINISH
INTERNAL COLOUR: NATURAL FINISH
REMOVALBLE GEAR PANS & ESCUTCHEON: GLOSS WHITE
PLINTH: GALVANISED
LABELS: ENGRAVED PLASTIC LAMINATEFIXING: DOUBLE SIDED ADHESIVE & STAINLESS STEEL SCREWSCOLOUR: AS SHOWN
CONTROL WIRING: MINIMUM 1.5mm Cu V90POWER WIRING: MINIMUM 2.5mm Cu RE110 DOUBLE INSULATEDWIRE MARKERS: STANDARD FERRULESTERMINATIONS: BARE CABLE ENDS. WHERE TERMINALS REQUIRE LUGS, BOOTLACE
FERRULES OR PRE-INSULATED RING LUGS. FORK LUGS SHALL NOT BE USEDCOLOUR: 240 AC - PHASE COLOURED
NEUTRAL - BLACK EARTH - GREEN/YELLOW
CONSTRUCTION: FLOOR MOUNTED, FRONT CONNECTED, RATED AT 100ACABINET: 2mm 316 STAINLESS STEEL, FOLDED &
WELDED/MODULAR BOLTED CONSTRUCTION
DOOR
NEOPRENE GASKET
WEATHER PROOF CHANNEL
SWITCHBOARD CABINET
WEATHER PROOFING DETAIL
NOTES:MAIN ISOLATOR TO BE LOCATED IN THEENERGY AUTHORITY SECTION. BUS COMBTO BE FIXED SECURELY TO THE BUSBAR.
CONSTRUCTION NOTES:
160AMAIN ISOLATOR
20A 30mA RCD FOR GPO ON SMART POLES
100ASERVICE FUSE
SINGLE LINE DIAGRAM
ANTICONDENSATION HEATERSCHEMATIC DIAGRAM
PE CELL LIGHTING CONTROLSCHEMATIC DIAGRAM
E3 METER WIRING SCHEMATIC
GPO DISTRIBUTIONSECTION
LIGHTINGDISTRIBUTION SECTION
TO HEATER CIRCUIT
25mm Cu RE110 DOUBLE INSULATED CABLE
INCOMING SUPPLY
TOLIGHTINGCONTROL
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
CB12
16A MCB
25A 3P MCB
F1
10A
1 OFF
INCOMINGSUBMAINS
N A B C
N A B CE
EA
RTH
STU
D
SE
RV
ICE
NE
UTR
AL C
AB
LE
SE
RV
ICE
AC
TIVE
CA
BLE
SE
RV
ICE
AC
TIVE
CA
BLE
SE
RV
ICE
AC
TIVE
CA
BLE
kWhE3
a a b b c c N
250AMAIN ISOLATOR
TO 3 PHASE BUSCOMB
100A
100A
100A
25mm² Cu DOUBLE INSULATED CABLE
4mm² Cu CABLE
SEALABLE METERNEUTRAL LINK
OU
TPU
T NE
UTR
AL LIN
K
OU
TPU
T EA
RTH
LINK
M.E.N
25mm Cu CABLE
N A B C
2.5mm Cu TPI CABLE
TO NEUTRAL
HEATER
GREEN/YELLOW
A N
THERMOSTAT10/32A
F1 H-1 H-2
E
REMOTE PE CELL
N12 A2 A1 CB12CB12
N12 [A2] [A1]
SS1
2 [4] [3] 3 A3
2 [2] [1] CB12
C1
16A MCB
MA
NU
AL
OFF
AU
TO
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
31
32
33
34
35
36
C1
LIGHTINGDwg No.
5.1.4Rev DDate 01.12.19Approved P G
GENERALTHREE PHASE SWITCHBOARD DETAILS &SCHEMATICS (SHEET 2)
NOTE:TO BE READ IN CONJUNCTION WITH DRAWING 5.1.3NOTE: ALL DIMENSIONS IN MILLIMETRES UNLESS OTHERWISE STATED
FOOTPATH SLABPENETRATION
150mm(W) CONCRETE BEAM
SMARTPOLE FOOTING ASPER STRUCTURAL
ENGINEERS SPECIFICATION
℄
750@ MIDBLOCKOR 1000@
INTERSECTIONS
KERB
K(F)
G.L
6 SMARTPOLE HD BOLTS/RAGBOLT ASSEMBLY
NON SHRINK GROUT
Ø50mm TELECOM COMMUNICATIONSCONDUIT TO BE CAPPED OFF.
Ø50mm STREET LIGHTINGCOMMUNICATIONS CONDUIT
2 x Ø63mm ELECTRICALSTREET LIGHTING CONDUIT
IF APPLICABLE, Ø80mm RMSCONDUIT IN THE DIRECTION OF THE
NEAREST RMS PIT. REFER TO NOTE 3
21070
50
20
WEAK CEMENT MORTAR 1:5 MIX
SMARTPOLE
TE
RMS
E
KERB
ROAD
IN THE DIRECTIONOF THE NEAREST TELSTRA PIT
IN THE DIRECTION OF THE NEARESTRMS PIT. REFER TO NOTE 3.
Ø50mm TELECOM COMMUNICATIONSCONDUIT TO BE CAPPED OFF.
Ø63mm ELECTRICAL STREETLIGHTING CONDUIT
Ø50mm STREET LIGHTINGCOMMUNICATIONS CONDUIT
CONDUIT CONNECTED FROM ADJACENTSTREET LIGHTING POLE OR SWITCHBOARD
CONNECTED TO CoS STREETLIGHTING CONDUITS
Ø50mm STREET LIGHTINGCOMMUNICATIONS CONDUIT
Ø63mm ELECTRICAL STREETLIGHTING CONDUIT
SMARTPOLE FOOTING AS PERSTRUCTURAL ENGINEERS SPECIFICATION
Ø200mm MAX AREAFOR CONDUITS
750
/ 100
0mm
IF APPLICABLE,Ø80MM RMS CONDUIT
C
PLASTIC ELECTRICAL PIT715 x 410 x 800mm
A
Ø50mm STREET LIGHTINGCOMMUNICATIONS CONDUIT
40
AS
CLO
SE
AS
PR
AC
TIC
AL
Ø50mm STREET LIGHTINGCOMMUNICATIONS CONDUIT
CABLING
100 100
SECTION A-A
CONDUIT ARRANGEMENTS AT POLE BASE
PLAN 1:20
LIGHTINGDwg No.
5.1.5
GENERAL
CONDUITS ARRANGEMENT AT POLE BASE
NOTE: ALL DIMENSIONS IN MILLIMETRES UNLESS OTHERWISE STATED
Rev DDate 01.12.19
Approved P S
SECTION 1:20
FOOTPATH PAVEMENT
STANDARD CONDUIT
DEPTH FOR PATHWAYS
PLASTIC ELECTRICAL PIT
715 x 410 x 800mm
CONDUITS LOWER FOR
ROAD CROSSING
SCALE 1:20
CLASS C INFILL
PIT LID
250
MIN
400
MIN
COMMS CONDUIT
COMMS CONDUIT
ELECTRICAL CONDUIT ELECTRICAL CONDUIT
FOOTPATHROAD
CLASS D INFILL
PIT LID
ROAD PAVEMENT
750
MIN
600
MIN
LIGHTINGDwg No.
5.1.6
GENERAL
GENERAL LIGHTING PIT ARRANGEMENT
NOTE: ALL DIMENSIONS IN MILLIMETRES UNLESS OTHERWISE STATED
Rev DDate 01.12.19
Approved P S
LIGHTINGDwg No.
5.1.7Rev DDate 01.12.19Approved P G
NOTE:TO BE READ IN CONJUNCTION WITH DRAWING 5.1.8NOTE: ALL DIMENSIONS IN MILLIMETRES UNLESS OTHERWISE STATED
GENERALSINGLE PHASE SWITCHBOARD DETAILS &SCHEMATICS (SHEET 1)
LIGHTINGDwg No.
5.1.8Rev DDate 01.12.19Approved P G
GENERALSINGLE PHASE SWITCHBOARD DETAILS &SCHEMATICS (SHEET 2)
NOTE:TO BE READ IN CONJUNCTION WITH DRAWING 5.1.7NOTE: ALL DIMENSIONS IN MILLIMETRES UNLESS OTHERWISE STATED
Recommended