7/30/2019 Configuration of Class 300 Transmitters
1/44
User Manual
Configuration of TransmittersClass 300
Keypad Remote control Modbus network
weN
TH300 >Remote probe
TemperatureHumidity
Pressure
CP300 >
TH300 >Standard probe
Temperature
< TT300
Remote probe
TT300 >Standard probe
Air velocity
CTV310 >Standard probe
7/30/2019 Configuration of Class 300 Transmitters
2/44
7/30/2019 Configuration of Class 300 Transmitters
3/44
7/30/2019 Configuration of Class 300 Transmitters
4/44
Summary
10. Air velocity measurement configuration (CP300 + SQR) F600 . . . . . . . . P 2410.a - Temperature compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P 2410.b - Air velocity coefficient selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P 26
10.c - Air velocity correction coefficient input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P 27
11. Airflow measurement configuration F600 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P 28
12. Other functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P 3112.a - Activation / Deactivation of the RS 232 and home bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . P 3112.b - Serial number display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P 3112.c - Modification of Modbus communication speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P 3212.d - Purge Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P 33
13. Error codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P 36
14. Functions recap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P 37
Class 300 transmitter configuration via keypad / remote control / Modbus
7/30/2019 Configuration of Class 300 Transmitters
5/44
1. Prerequisite
Page 1Class 300 transmitter configuration via keypad / remote control / Modbus
1.a - Working principleUsing keypad / remote control / Modbus configuration, you can activate (or deactivate) a channel, change themeasuring range, set the set points and time-delay...
Principle: the configuration options are accessed via folders and sub-folders (similar to Windows ). Access ismade via a numerical code (full details in this manual).
Meaning of the keys
To increment a value or a level
To decrement a value or a level
To validate an input
To cancel an input or to return to the previous step
AL1 AL2
CODE:
0000
Visual alarm LED
Graphic display
Keypad
Infrared receiver
1.a.1 - Keypad
AL1 AL2
CODE:
0000
7/30/2019 Configuration of Class 300 Transmitters
6/44
Page 2 Class 300 transmitter configuration via keypad / remote control / Modbus
1. Prerequesite
1.a.2 - Infrared remote control
The remote control works like the keypad and the configuration method remains exactly the samewhichever you use (keypad or remote control).
=
Meaning of the remote control keys
To increment a value or a level
To decrement a value or a level
To validate an inputTo cancel an input or to return to the previous step
Channel selectorWith this selector, you can swap the transmission channel so that itmatchs with the transmitter reception channel. See page 6 to configurethe transmitter reception channel.
The Class 300 can output either a voltage or a current signal.Voltage or Current ?
Down
0-10 V
Up
4-20 mA
1.b - Output signal selection
With the on-off switch located onthe left top of the transmitter(when open), you can chooseanalogue output 0-10V (voltage)or 4-20 mA (current)
It's extremely unwise to remove the protection tip of our hygrometryprobes as the sensitive element is very fragile even to light contacts.However, if you have to remove the protection tip, take all possible
precautions and avoid any contact with the sensitive element.
To remove the protection tip, unscrew it or unclip it.
1.c - Protection tip of the sensor
Sensitiveelement
!
Protection tipto unscrew
Protection tipto unscrew
Sensitive
element
7/30/2019 Configuration of Class 300 Transmitters
7/44
Values formatting -Modbus code :1444 (channel 2)1448 (channel 3 or value 1 of the external transmitter)1452 (channel 4 or value 2 of the external transmitter)
1440 (channel 1)
Page 3Class 300 transmitter configuration via keypad / remote control / Modbus
2. Modbus parameters
2.a - Configuration parameters Communication speed. . . . . . . . . . . . . . . . . . . . . 19200 Bauds (see page 33 to configure the speed) Data bits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 bits Stop bit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 bit
Parity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . None Flow control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . None Transmitter addressing . . . . . . . . . . . . . . . . . between 1 and 255
default address 0 for single ended bus configurationto change the addressing, see page 8.
2.b - Functions Register reading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Function 03 Register writing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Function 16 Communication loop test . . . . . . . . . . . . . . . . . . . . . Function 08
2.c - Access codes to Registers Registers type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Signed long integer (32 bits), permuted (LSB, MSB)
Alarms status -Modbus code : 1436
Relay 1Relay 2
0 1 0 1Ex. The value sent by the transmitter is 5Alarm condition 1and relay 1 excited
Values -Modbus code : 1438 (channel 1)1442 (channel 2)
1446 (channel 3 or value 1 of the external transmitter)1450 (channel 4 or value 2 of the external transmitter)Ex. the value sent by the transmitter is 6321
... b4 b3 b2 b1 b0b31
b31 ... b12 b11 b10 b9 b8 b7 b5 b4 b3 b2 b1 b0b60 0 0 1 0 0 0 0 1 1 0 0
Unit of measurement (see chart)
Nr of digits after the comma
Value sign (0=>+, 1=> -)
Ex. The formatting displayed is 268.Unit of measurement => 12 (see chart)Figure(s) after the comma => 1Sign => positive
If the value measured is equal to 6231 :
Result => 623,1 mmH O2
Alarm 1Alarm 2
1 m/s 12 mmH O2
2 fpm 13 inWg
3 m3/h 14 Kpa
4 L/s 15 mmHg
5 cfm 16 mbar
6 m3/s 17 g/kg (absolute humidity.
7 C 18 C (dew temp. Td)
8 F 19 F (dew temp. Td)
9 %RH 20 C (wet temp.Tw)
10 PSI 21 F (wet temp. Tw)
11 Pa 22 KJ/Kg (Enthalpy i)
)
Units of measurement
7/30/2019 Configuration of Class 300 Transmitters
8/44
2. Modbus parameters
Page 4 Class 300 transmitter configuration via keypad / remote control / Modbus
2.c - Access code to Registers (sequel)
Serial number of sensing element (SPI - CP300 / Humidity - TH300)Modbus code: 1402
Other access codes to different registers are indicated on each function at stage n2.Shown as this pictogram: dbuo sM
202
7/30/2019 Configuration of Class 300 Transmitters
9/44
7/30/2019 Configuration of Class 300 Transmitters
10/44
4.b - BacklightWith the backlight, the reading is easier with more contrast, if the ambient light is weak.You can activate or deactivate it.
1
Step Go into the configuration mode (see page 5). The folder number displayedcorresponds to the last folder used.
2
StepSelect the folder 100 and validate with .
Select the sub-folfer 101 and validate with .The cursor> goes to the line of available choices.
3
Step With and keys, select 00 to deactivate the backlit or01 to activate.
Validate with .01F 101
>
014F 101
Step The cursor> returns to sub-folders line. press twice to return to reading mode.
press once to select another folder. with and keys, you can choose another sub-folder from the folder 100.
>
01
F 101>
100
100
4. Display and keypad configurationF100
dbuo sM
202
4.a - Transmitter channel for infrared remote controlYou can change the channel number for receiving the signal from the infrared remote control.The advantage is that only one remote controlis required to drive several transmitters, and that thereis no interference if 2 transmitters are located side by side.
1
Step Go into the configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.
2
StepSelect the folder 100 and validate with .
Select the sub-folder 100 and validate with .The cursor> goes to the line of available choices.
3
Step With and keys, select the channel number (from 00 to 09). Validate
with .03F 100
>
034F 100Step The cursor> returns to sub-folders line.
press twice to return to reading mode
press once to select another folder.
with and keys, you can choose another sub-folder from the folder 100.
>
00
F 100>
100
100
dbuo sM
200
By default, the channel number is 0.
Page 6 Class 300 transmitter configuration via keypad / remote control / Modbus
7/30/2019 Configuration of Class 300 Transmitters
11/44
7/30/2019 Configuration of Class 300 Transmitters
12/44
7/30/2019 Configuration of Class 300 Transmitters
13/44
CP 301, 302 et 303 CP 304 TH 300
00 Inactive channel
01 Pa Pa C C m/s
02 mmH O mmH O F F fpm2
03 inWg inWg %HR C
04 mbar mbar g/Kg (Hygro. absolue F
305 C mmHg C (Temp. de rose Td) m /h
06 F C F (Temp. de rose Td) L/s
07 m/s F C (Temp. humide Tw) cfm
308 fpm m/s F (Temp. humide Tw) m /s
309 m /h fpm KJ/Kg (Enthalpie i)
310 L/s m /h
11 cfm L/s
312 m /s cfm
313 m /s
TT 300 CTV 310
Inactive channel Inactive channel Inactive channel Inactive channel
2
)
5. Configuring channels and units of measurementF200
Class 300 transmitters have 4 measuring channels. You can activate 1, 2, 3 or 4 channels and select each unit ofmeasurement.
Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.
Select the folder 200 and validate with .
Channel 1 Channel 2 Channel 3 Channel 4Select sub-folder 200 201 202 203
With and keys, select the unit of measurement (see chart below).
Validate with .
The cursor> returns to sub-folders line. press twice to return to reading mode.
press once to return to another folder selection.
with and keys to choose another sub-folder from the folder 200.
and validate with . The
cursor>goes to choices line.
For a CP 300 transmitter (301, 302, 303 and 304),the SQR option is required in order to activate theunits of air velocity and airflow.
1
Step
2
Step
3
Step
06F 201
>
04
F 200>
200
200
dbuo sM
400
dbuo sM dbuo sM d
buo sM
402 404 406
064F 201Step >
Page 9Class 300 transmitter configuration via keypad / remote control / Modbus
7/30/2019 Configuration of Class 300 Transmitters
14/44
6. Analogue output managementF300
6.a - Output diagnosticsWith this function, you can check with a multimeter (or a regulator/display, or a PLC/BMS) if the transmitter outputsare working properly. The transmitter generates a voltage of 0 V, 5 V and 10 V or a current of 4 mA, 12 mA and 20mA.
6.a.1 - Multimeter connection configuration
Before carrying out the output diagnostics, all connections and configurations of the transmitter must beenabled, to avoid any damage on the transmitter and the multimeter !
1
Step First, select a channel for the output diagnostics.Selection of the channelto be checked
The channel numbers are indicated on theboard located below the terminal block.
Channel n1 Channel n2
2
Step Example of
connection
On the photo alongside, the multimeter isconnected to the 0-10 V output and channeln1.
NO....
.........n
ormall
yope
n
COM
..........
com
mon
NC....
........
.normal
lyclo
sed
Relay 1
NO....
.........n
ormall
yope
n
COM
..........
com
mon
NC....
........
.normal
lyclo
sed
Relay 2
B
-
A
+
0-10V
........
......volt
age
GN
D.....
........
....gro
und
4-20m
A .....
......curr
ent
Analogue output 1
0-10V
........
......volt
age
GN
D.....
........
....gro
und
4-20m
A .....
......curr
ent
Analogue output 2
The ticked box showsthe power supply typeof the transmitter(230 Vac shown above).
230 Vac
115 Vac
[24 Vdc / ac
Page 10 Class 300 transmitter configuration via keypad / remote control / Modbus
7/30/2019 Configuration of Class 300 Transmitters
15/44
6.a.2 - Output diagnostics
Once the connection of the transmitter to the multimeter (or regulator or PLC/BMS is complete, (see page6), you can carry out the analogue output diagnostics on several check points.
6. Analogue output management
Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.
Select the folder 300 and validate with .
Channel n 1 outputSelect sub-folder 300
and validate with .
The cursor> goes to available choices.
Channel n 2 outputSelect sub-folder 303
Diagnostic Output
00 0 V
01 5 V
02 10 V
03 4 mA
04 12 mA
05 20 mA
F300
With and keys, select the signal that the transmitter must output (see
chart below). Note : no need to validate with .
1
Step
2
Step
3
Step
01F 300
>
00
F 300>
300
100
!
If the deviations are too big (>0,05V or >0,05mA) between the signal issued and thevalue displayed on the multimeter, we recommend that you return the transmitter to
our factory.
The cursor> returns to sub-folders line. press twice to return to reading mode.
press once to return to another folder selection.
with and keys to choose another sub-folder from the folder 300.
4
Step > F 300
01
Page 11Class 300 transmitter configuration via keypad / remote control / Modbus
dbuo sM dbuo sM
600 606
7/30/2019 Configuration of Class 300 Transmitters
16/44
+500F 302
6. Analogue output managementF300
6.b - Analogue output settingsWith this function, you can modify the measuring range of the transmitter, and you can equate the new limits to theanalogue output (0-10V or 4-20mA).You can enter the measuring range required on your own !
Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.
Select the folder 300 and validate with .
Minimum of Channel n1output
Select sub-folder 301
With and keys, select the value sign: negative or positive, validate with
. Then, enter the minimum limit value and validate with .
and validate with . The cursor> returns to the input line.
of Channel n2output
Select sub-folder 304
Minimum
Maximumof Channel n1output
Select sub-folder 302
Etape
With and keys, select the value sign: negative or positive, validate with
.
Then, enter the maximum limit value and validate with .
and validate with . The cursor> goes to the input line.
Maximumof Channel n2output
Select sub-folder 305
!You must enter the values according to the units of measurement selected, notaccording to the measuring range of the transmitter.
Eg. on a CP 303 pressure transmitter (0 to 1000 Pa) with a reading in mmH2O, the minimum and maximum ranges must beconfigured on measuring range of 0 to 102 mmH2O. See conversion chart on following page.
6
Step The cursor> goes to sub-folders line. press twice to return to reading mode.
press once to return to another folder selection.
with and keys you can choose another sub-folder from the folder300.
>
After an analogue output setting, if the unit of measurement is modified (see page 5), you have to reconfigure theoutputs according to the new unit of measurement.
! We recommend that the interval between the minimum and maximum is > 5% of the measuring range.
1
Step
2
Step
3
Step
-000100
F 301
>
-100
F 301>
300
100
4
Step
5
Step
+000500F 302
>
+500
F 302
>
dbuo sM
602
dbuo sM
608
dbuo sM
604
dbuo sM
610
Page 12 Class 300 transmitter configuration via keypad / remote control / Modbus
7/30/2019 Configuration of Class 300 Transmitters
17/44
7/30/2019 Configuration of Class 300 Transmitters
18/44
7. Alarm / relay settingsF400
7.a - Activation / Deactivation of BEEP alarm
Go into configuration mode (page 5). The folder number displayedcorresponds to the last configuration folder used.
Select the folder 400 and validate with .
Select sub-folder 400 and validate with .
The cursor> goes to available choices.
With and keys, select 01 to activate the BEEP alarm or00to
disactivate. Validate with .
The cursor> goes to sub-folders line. press twice to return to reading mode.
press once to return to another folder selection.
with and keys you can choose another sub-folder from the folder 400.
7.b - Relay security
Enter in configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.
Select folder 400 and validate with .
Select sub-folder 401 and validate with .
The cursor> goes to available choices.
With the keys and , select 01 for a positive security or00for a
negative security. Validate with .
The cursor> returns to sub-folders line. press twice on to return to reading mode.
press once on to return to another folder selection.
with and keys, you can choose another sub-folder from the folder 400.
The relay outputs are by default, in negative security: the relay is energizedwhen a set point is reached.With the keypad, you can swap the relays inpositive security: then, the relay is de-energizedwhen a set point isreached or during a power outage.
The beep alarm (audible alarm) is activated when a set point is reached.For more details on the setpoint settings, see page 20.
1
Step
2
Step
3
Step
01F 400
>
014F 400Step >
01
F 400>
400
100
1
Step
2
Step
3
Step
01F 401
>
014F 401Step >
01
F 401>
400
100
dbuo sM
800
dbuo sM
802
Page 14 Class 300 transmitter configuration via keypad / remote control / Modbus
7/30/2019 Configuration of Class 300 Transmitters
19/44
7. Alarm / relay settingsF400
7.c - Alarm / relay functions and LED colour codes
7.c.1 - Visual / audible alarms
Class 300 transmitters have 2 visual / audible alarms located in front of the transmitter, allowing to know the
condition of the setpoints.
Alarm n2Alarm n1Alarm LED colour codes
Green The alarm function is activated andthe set point is not reached
Red The alarm function is activated andthe setpoint is reached
None The alarm function is not activated
The red LED appears when the setpoint is reached,taking into account the time-delay and the action type(falling or rising).
See page 17 for more details.
7.c.2 - The relaysClass 300 transmitters have 2 relays visible on the transmitter board. These 2 relays each have one LED to
allowreal-time checking.
Audible alarm
Once the alarm is activated, an alarm soundswhilst the setpoint is reached.
Relay LED colour codes
Red The relay is
None The relay is not energizedorhas not been configured
energized
The relay is energized when the setpoint is reached, takinginto account the time-delay, the action type and also thealarms security mode.Set points, time-delay and action type setting: see page 20Alarm security settings : see page 14
Relayn2LED
Relayn1LED
Relayn2Relay n1
The BEEP alarm function must be activated to use theaudible alarm. See page 14.
Page 15Class 300 transmitter configuration via keypad / remote control / Modbus
7/30/2019 Configuration of Class 300 Transmitters
20/44
7.d - Selection of the channel for visual and relays alarms
7. Alarm / relay settingsF400
Class 300 transmitters have 4 alarms: 2 visual (LED) and audible alarms and 2 relay alarms. The transmitter can beconfigured with 4 different alarms setups.
Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.
Select the folder 400 and validate with .
With and keys, select the channel number for which you want to
configure an alarm. Validate with .
The cursor> returns to sub-folders line. press twice to return to reading mode.
press once to return to another folder selection.
with and keys, you can choose another sub-folder from the folder 400(i.e. for example to configure another alarm / relay)
402 407 412 417Alarm 1 Alarm 2 Relay 1 Relay 2(LED 1) (LED 2)
Select sub-folder
and validate with .
1Step
2Step
3
Step
014F 402Step
>
01
F 402>
400
100
01
F 402>
dbu
os
M
804
dbuos
M
814
dbuos
M
824
dbuos
M
834
Page 16 Class 300 transmitter configuration via keypad / remote control / Modbus
Before any alarm setup, check that the corresponding channel(s) is activated.!
7/30/2019 Configuration of Class 300 Transmitters
21/44
7.e - Alarm mode details
7. Alarm / relay settingsF400
7.e.1 - DefinitionsSetpointThe setpoint is a limit which, on being reached and/or exceeded , activates an alarm or energizes a relay (in negative
security, see page 14 for more details).
Time-delay
Once the setpoint is reached and/or exceeded, the time-delay postpones the alarm activation (or relay excitation) for ashort period (in seconds). Once this period is elapsed, and if the setpoint is still exceeded, then the alarm is activated orthe relay is energized (in negative security).
Action type
For alarm activation or relay excitation, you can choose the action type: rising or falling action. Rising action: the alarm is activated once the measurement goes overthe setpoint Falling action: the alarm is activated once the measurement goes below the setpoint
7.e.2 - Available configurations
Configuration N1 : 2 setpoints and time-delay activated (Control Mode)
Setpoint 1
Setpoint 2
Time
Measurement
Energized
Not energized
Relay statusNegative security
Energized
Not energized
Relay statusPositive security
Alarm set
Time-delay
Setpoint 1 > Setpoint 2
Setpoint 2
Setpoint 1
Time
Measurement
Energized
Not energized
Relay status
Negative securityEnergized
Not energized
Status relayPositive security
Alarm set
Time-delay
Setpoint 2 > Setpoint 1
Page 17Class 300 transmitter configuration via keypad / remote control / Modbus
Control mode (or
regulation mode)=>you can regulate themeasurement within arange determined by 2setpoints.
7/30/2019 Configuration of Class 300 Transmitters
22/44
7. Alarm / relay settingsF400
Configuration N2 : 1 setpoint, time-delay and rising action activated
Setpoint 1
Time
Measurement
Energized
Not energized
Relay statusNegative security
Energized
Not energized
Relay statusPositive security
Alarm set
Time-delay
Configuration N3 : 1 setpoint, time-delay and falling action activated
Setpoint 1
Time
Energized
Not energized
Relay statusNegative security
Energized
Not energized
Relay statusPositive security
Alarm set
Time-delay
Page 18 Class 300 transmitter configuration via keypad / remote control / Modbus
Measurement
7/30/2019 Configuration of Class 300 Transmitters
23/44
7.f - Alarm mode selection
7. Alarm / relay settingsF400
Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.
Select the folder 400 and validate with .
With and keys, select the code relative to the alarm mode (see chart
below). Validate with .
The cursor> returns to sub-folders line. press twice to return to reading mode.
press once to return to another folder selection.
with and keys, you can choose another sub-folder from the folder400.
Code Alarm mode Drawing
00 No alarm
01 2 setpoints with time-delay (control mode) N 1 page 17
02 1 setpoint with time-delay and rising action
03 1 setpoint with time-delay and falling action N 3 page 18
N 2 page 18
1
Step
2
Step
3
Step
01F 403
>
014F 403Step >
01
F 403>
400
100
403 408 413 418Alarm 1 Alarm 2 Relay 1 Relay 2
Select sub-folder
and validate with .
dbuo sM
806
dbuo sM
816
dbuo sM
826
dbuo sM
836
Page 19Class 300 transmitter configuration via keypad / remote control / Modbus
7/30/2019 Configuration of Class 300 Transmitters
24/44
7.g - Setpoints and time-delay setting
7. Alarm / relay settingsF400
Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.
Select the folder 400 and validate with .
With and keys, select the value sign: negative or positive. Validate with
.
Then, enter the setpoint value and validate with .
The cursor> returns to sub-folders line. press twice to return to reading mode.
press once to return to another folder selection. with and keys, you can choose another sub-folder from the folder400.
7.g.1 - Setpoints
!You must enter values according to the units of measurement selected, notaccording to the measuring range of the transmitter.
Ex. on a CP 303 pressure transmitter (0 to 1000 Pa) with a reading in mmH2O, the minimum and maximum ranges must beconfigured on measuring range of 0 to 102 mmH2O. See conversion chart on page 13.
If after having set up a setpoint, the unit of measurement is modified (see page 9), then you have to reconfigurethe setpoints according to this new unit of measurement.
1
Step
2
Step
3
Step
-00100
F 404
>
-1004F 404Step >
02
F 404>
400
100
404 409 414 419Alarm 1 Alarm 2 Relay 1 Relay 2
To configure the setpoint 1, select sub-folder
and validate with .
dbuo sM
808
dbuo sM
818
dbuo sM
828
dbuo sM
838
405 410 415 420Alarm 1 Alarm 2 Relay 1 Relay 2
To configure the setpoint 2b-folder
(alarm in control mode, see p17),select su
and validate with .
dbuo sM
810
dbuo sM
820
dbuo sM
830
dbuo sM
840
Page 20 Class 300 transmitter configuration via keypad / remote control / Modbus
7/30/2019 Configuration of Class 300 Transmitters
25/44
7. Alarm / relay settingsF400
Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.
Select the folder 400 and validate with .
With and keys, set the required time-delay: from00 to60seconds.If you do not need the time-delay, enter00.
Validate with .
The cursor> returns to sub-folders line. press twice to return to reading mode.
press once to return to another folder selection.
with and keys , you can choose another sub-folder from the folder 400.
7.g.2 - Time-delay
1
Step
2
Step
3
Step
15F 406
>
154F 406Step >
02
F 406>
400
100
406 411 416 421Alarm 1 Alarm 2 Relay 1 Relay 2
Select sub-folder
and validate with .
dbuo sM
812
dbuo sM
822
dbuo sM
832
dbuo sM
842
Page 21Class 300 transmitter configuration via keypad / remote control / Modbus
7/30/2019 Configuration of Class 300 Transmitters
26/44
7/30/2019 Configuration of Class 300 Transmitters
27/44
7/30/2019 Configuration of Class 300 Transmitters
28/44
7/30/2019 Configuration of Class 300 Transmitters
29/44
Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.
Select the folder 600 and validate with .
Select the sub-folder 602 , validate with .
The cursor> returns to available choices.
With and keys, choose 01. Validate with .
10.a.1 - Automatic compensation
1Step
2
Step
3
Step
01
F 602>
014
F 602Step >
01
F 602>
600
100
The cursor> returns to sub-folders line. press twice to return to reading mode.
press once to return to another folder selection.
with and keys, you can choose another sub-folder from the folder 500
10. Air velocity measurement configurationF600
!Once the automatic temperature compensation configuration is complete, check carefullythe connection of the thermocouple K probe.
dbuo sM
1204
Page 25Class 300 transmitter configuration via keypad / remote control / Modbus
Before configuring the automatic compensation in temperature, you must connect thethermocouple K probe on the transmitter.!
7/30/2019 Configuration of Class 300 Transmitters
30/44
10. Air velocity measurement configurationF600
10.b - Air velocity coefficient selection (CP 300)Since the air velocity is calculated from the pressure (on a CP 300) and from a differential probe, you must enter thecoefficient value of the differential probe. For Pitot tubes and Debimo blades, the coefficient is already includedin the transmitter.
! Function only available on the pressure transmitters: CP 300 + SQR option
Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.
Select the folder 600 and validate with .
Select the sub-folder 603 and validate with .
The cursor> goes to available choices.
With and keys, select the differential probe type. Validate with .
The cursor> returns to sub-folders line. press twice to return to reading mode.
press once to return to another folder selection.
with and keys, you can choose another sub-folder from the folder600.
If you use Other differential probe please carefully follow the instructions below.
Code Differential probe Coef.
00 Pitot tube L (ISO 3966) 1
01 DEBIMO blade 0.8165
02 Other differential probe To be entered
Select the folder 600 and validate with .
Select the sub-folder 604 and validate with .
The cursor> goes to available choices.
With and keys, enter the coefficient relative to your differentialprobe. This coefficient is given by the manufacturer (from 0.0001 to 9.9999).Validate with .
The cursor> returns to sub-folders line. press twice to return to reading mode.
press once to return to another folder selection.
with and keys , you can choose another sub-folder from the folder 600.
10.b.1 - Manual coefficient input
1
Step
2
Step
3
Step
01
F 603
>
014F 603Step >
00
F 603>
600
100
1Step
2
Step
0.8165
F 604
>
0.81653
F 604Step >
00
F 604>
600
dbuo sM
1206
dbuo sM
1208
Page 26 Class 300 transmitter configuration via keypad / remote control / Modbus
7/30/2019 Configuration of Class 300 Transmitters
31/44
10. Air velocity measurement configurationF600
10.c- Air velocity coefficient inputWith this correction coefficient, you can adjust the transmitter according to the air velocity in your installation.
! Function only available on the transmitter : CP 300 + SQR option and CTV 310.
Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.
Select the folder 600 and validate with .
Select the sub-folder 605 and validate with .
The cursor> goes to available choices.
With and keys, enter the coefficient value calculated (from 0.200 to
2.000). Validate with .
The cursor> returns to the sub-folders line. press twice to return to reading mode.
press once to return to another folder selection.
with et keys, you can choose another sub-folder from the folder 600.
10.c.1 - How to calculate it ?If the air velocity in your duct is equal to 17 m/s, and if the transmitter indicates 16.6 m/s, then the
coefficient to apply is 17 / 16,6, ie 1.024
10.c.2 - Coefficient input
1Step
2
Step
3
Step
1.024
F 605
>
1.0244F 605Step >
00
F 605>
600
100
dbuo sM
1210
Page 27Class 300 transmitter configuration via keypad / remote control / Modbus
7/30/2019 Configuration of Class 300 Transmitters
32/44
11. Airflow measurement configurationF600
11.a - Selection of duct section type or airflow coefficient
! Function only available on transmitters: CP 300 + SQR option and CTV 310
Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.
Select the folder 600 and validate with .
Select the sub-folder 606 and validate with .The cursor> goes to available choices.
With and keys, select the section type (00 or01).
Validate with .
The cursor> returns to sub-folders line.
press twice to return to reading mode. press once to return to another folder selection.
with and keys to choose another sub-folder from the folder 600.
Code Section type
00 Rectangular
01 Circular
02 Airflow coefficient (to be entered, see p 29)
11.a.1 - Working from the section type
Section sizes input
Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.
Select the folder 600 and validate with .
Length Width Diameter
mm 607 608 609
inch 610 611 612
Select sub-folder
and validate with .
Rectangularsection Circularsection
1
Step
2
Step
3
Step
00
F 606
>
004
F 606Step
>
00
F 606>
600
100
1
Step
2
Step
1500
F 607>
600
100
dbuo sM
1212
dbuo sM
1214
Page 28 Class 300 transmitter configuration via keypad / remote control / Modbus
dbuo sM
1216
dbuo sM
1218
dbuo sM
1220
dbuo sM
1222
dbuo sM
1224
7/30/2019 Configuration of Class 300 Transmitters
33/44
7/30/2019 Configuration of Class 300 Transmitters
34/44
7/30/2019 Configuration of Class 300 Transmitters
35/44
12. Other functions
12.a- Activation / deactivation of the RS232 and home busClass 300 transmitters have one RS232 and one RS 485 digital output (Modbus protocol) - optional.With the RS 232, you can display 1 or 2 parameters which are measured by other Class 200 and 300 transmitters, oryou can send measurements to be displayed on another Class 300 transmitters.
Go into configuration mode (see page 5). The folder numberdisplayed corresponds to the last configurationfolder used.
Select the folder 100 and validate with .
Select the sub-folder 103 and validate with
.
With and keys, select 00 to receive data from another
transmitter or select01 to send data via RS 232. Validate withCAUTION !!
When the transmitter is configured to receive data, then the RS485 Modbus is active). When the transmitter is configured tosend data via RS 232, then the RS 485 Modbus is inactive.
The cursor> returns to sub-folders line. press twice to return to reading mode.
press once to return to another folder selection.
with and keys, you can choose another sub-folder from the folder 100.
12.b- Serial number display
Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.
Select the folder 100 and validate with .
Select the sub-folder 105
The serial number of the transmitter is displayed.The cursor> returns to sub-folders line. press twice to return to reading mode.
press once to return to another folder selection.
with and keys to choose another sub-folder from the folder 100.
!If you set up your transmitter to send measurements to another transmitter via RS 232, then you willnot be able to use the RS 485 digital output anymore (Modbus - optional).
1
Step
2
Step
3
Step
00
F 103
>
004
F 103Step >
00F 103>
100
100
dbuo sM
206
1
Step
2
Step
3
Step
03.12.2004
F 105>
100
100
03.12.2004
F 105>
Page 31Class 300 transmitter configuration via keypad / remote control / Modbus
dbuo sM
210
7/30/2019 Configuration of Class 300 Transmitters
36/44
12. Other functions
Page 32 Class 300 transmitter configuration via keypad / remote control / Modbus
12.c- Modification of Modbus communication speed
Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.
Select the folder 100 and validate with .
Select the sub-folder 107 and validate with .
The cursor> returns to sub-folders line. press twice to return to reading mode.
press once to return to another folder selection.
with and keys, you can choose another sub-folder from the folder 100.
1
Step
2
Step
3
Step
05
F 107
>
054F 107Step >
03
F 107>
100
100
dbuo sM
214With and keys, select a communication speed
(see chart below). Validate with .
00 2400 bauds 03 19200 bauds (speed by default)
01 4800 bauds 04 38400 bauds
02 9600 bauds 05 115200 bauds
7/30/2019 Configuration of Class 300 Transmitters
37/44
12. Other functions
12.d- Purge mode
Page 33Class 300 transmitters configuration via keypad / remote control / modbus
The purge mode enables to freeze the measurement when being displayed, enables to lock the analogue outputs,and to activate the relay 1, in order to actuate a de-dust system of an air movement conditions system and to activatethe relay 2 in order to isolate the transmitter.
! This function is only available on CP 300 pressure transmitters.
Here is the detailed process of purge mode :1 - Measurement is frozen.2 - Wait for three seconds.3 - Activation of relay 2 (isolation of the transmitter)4 - Wait for time-delay (e.g : 10 seconds).5 (sending compressed air
into the network to clean the installation)6 - Purge duration (
- Activation of relay 1
(e.g : 30 seconds)
7 - Deactivation of relay 1 (stop sendingcompressed air).
8 - Wait for time-delay .9 - Deactivation of relay 210 - Wait for three second.11 - Recovery of measurement
(e.g : 10 seconds)
Frozen measurement
3 seconds of time delay
Protection duration ofthe transmitter
Time-delay of advance of triggering oft h e r e l a y 2 c o r r e s p o n d i n g :Temporisation of 10 seconds bydefault
Time-delay of triggering of the relay 2corresponding : Temporisation of 10seconds by default
Purge time :30 secondsby default
Relay 1 : Command ofpurge electro-valve
Relay 2 : Command ofisolation electro-valve
To modify purge time and temporisation delay, see page 34-35.
7/30/2019 Configuration of Class 300 Transmitters
38/44
7/30/2019 Configuration of Class 300 Transmitters
39/44
12. Other functions
12.d- Mode Purge
Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.
Select the folder 300 and validate with .
Select the sub-folder 308 and validate with .
The cursor> returns to sub-folders line. press twice to return to reading mode.
press once to return to another folder selection.
with and , choose another sub-folder from the folder 300.
1
Step
2
Step
3
Step
60
F 308
>
604F 308
Step>
00
F 308>
300
100
dbuo sM
616With keys and , enter the value in minutes of the frequency
of each purge (from 01 to 9999). Validate with .
12.d.3 -Frequency
Go into configuration mode (see page 5).corresponds to the last configuration folder used.
The folder number displayed
Select the folder 300 and validate with .
Select the sub-folder 309 and validate with .
The cursor> returns to the sub-folders line. press twice to return to reading mode.
press once to return to another folder selection.
with and keys, choose another sub-folder from the folder 300.
1
Step
2
Step
3
Step
10
F 309
>
104F 309Step >
00
F 309>
300
100
dbuo sM
618With and keys, enter the value in seconds of the time-delay
required (from00 to60). Validate with .
12.d.4 - Time-delayTime-delay corresponds to the advanced and retardation lead time of triggering of the relay 2 relative tothe relay 1.
Page 35Class 300 transmitters configuration via keypad / remote control / modbus
7/30/2019 Configuration of Class 300 Transmitters
40/44
7/30/2019 Configuration of Class 300 Transmitters
41/44
00 2400 bds 02 9600 bds 04 38400 bds
01 4800 bds 03 19200 bds 05 115200 bds
14. Functions recap
Code Description Available settings
100 Channel n for IR remote control 0 to 9
101Backlight 0 or 1
102 Display contrast control from 0 to 10
103 Sending data via RS232 0 or 1
104 Keypad locking 0 or 1
105 Serial number display
106 Modbus slave number 1 to 255
107 Modbus communication speed
200
202204
206
208
210
212
214
F100
Code Description
200 Unit of channel 1
201 Unit of channel 2
202 Unit of channel 3
203 Unit of channel 4
Available settings
400
402
404
406
F200
bd uo sMxxx
bd uo sMxxx
CP301, 302 et 303 CP 304 TH300 CTV310
00 I
01 Pa Pa C m/s
02 mmH O mmH O F fpm2
03 inWg inWg %HR C
04 mbar mbar g/Kg (absolute humd. F3
05 C mmHg C (dew temperature Td) m /h
06F C F (dew temperature Td) L/s
07 m/s F C (wet temperature Tw) cfm3
08 fpm m/s F (wet temperature Tw) m /s3
09 m /h fpm KJ/Kg (Enthalpy i)3
10 L/s m /h
11 cfm L/s3
12 m /s cfm3
13 m /s
Inactive channel Inactive channel nactive channel Inactive channel
2
)
Page 37Class 300 transmitters configuration via keypad / remote control / modbus
7/30/2019 Configuration of Class 300 Transmitters
42/44
14. Functions recap
Code Description
300 Analogue output setting on channel 1 0=>0V, 1=>5V, 2=>10V3=>4mA, 4=>12mA, 5=>20mA
301 Analogue output minimum on channel 1
302 Analogue output maximum on channel 1
303 Analogue output setting on channel 1 0=>0V, 1=>5V, 2=>10V3=>4mA, 4=>12mA, 5=>20mA
304 Analogue output minimum on channel 2
305 Analogue output maximum on channel 2
306 Activation / Deactivation of purge mode 00 or 01
307 Working time of each purge from 01 to 60 seconds
308 Frequency of each purge from 01 to 9999 minutes
309 Time-delay before and after purge from 00 to 60 seconds
Available settings
600
602
604
606
608
610
612
614
616
618
F300
channel2
channe
l1
bd uo sMxxx
CP
300
Code Model Description
500 CP300 Measurement integration from 0 to 9
500 TH300 Offset in humidity -50,0 to +50,0
501 CP300 Self-calibration for time-delay from 0 to 60 minutes
501 TH200 Offset in temperature (C) from -50,0 to +50,0
502 TH200 Offset in temperature (F) from -90,0 to +90,0
Available settings
1000
1000
1002
1002
1004
F500dbuo
sM xxx
Page 38 Class 300 transmitters configuration via keypad / remote control / modbus
7/30/2019 Configuration of Class 300 Transmitters
43/44
7/30/2019 Configuration of Class 300 Transmitters
44/44
14. Functions recap
Code Description
600 Compensation temperature in C* -
601 Compensation temperature in F* -602 Compensation type* manual =>00 or automatic=>01
603 Air velocity measurement mean*
604 Air velocity coefficient value* from 0.0001 to 9.9999
605 Air velocity correction coefficient from 0.200 to 2.000606 Section type selection
607 Section length in mm from 0 to 3000 mm
608 Section width in mm from 0 to 3000 mm
609 Section diameter in mm from 0 to 3000 mm
610 Section length in inch from 0 to 118.11 inch
611 Section width in inch from 0 to 118.11 inch
612 Section diameter in inch from 0 to 118.11 inch
613 Airflow coefficient* from 0.1 to 9999.9
614 Units of pressurefor the pressure calculation*
Available settings
1200
12021204
1206
1208
12101212
1214
1216
1218
1220
1222
1224
1226
1228
F600
Code Differential probe
00 Pitot tube
01 DEBIMO blade
02 Other differential probe
Code Section type
00 Rectangular
01 Circular
02 Airflow coefficient
bd uo sMxxx
CP301/302/303 CP304
01 Pa Pa
02 mmH O2
03 inWg inWg
04 mbar mbar
05 - mmHg
mmH O2
Ref.NTAng-Classe300-13/07/10-
RCS(24)349282095Non-contractualdocume
nt-Wereservetherighttomodifythecharacteristicsofourproductswithoutpriornotice.
CP
300-CTV3
10
* : only for CP300 transmitter
Recommended