Dr M A Panneerselvam, Professor, Anna University

1

HIGH VOLTAGE ENGINEERING

FOR

B.E.(EEE) STUDENTS

OF

ANNA UNIVERSITY

Dr M A Panneerselvam, Professor, Anna University

2

INTRODUCTION OF THE FACULTY

NAME : Dr. M.A. PANNEERSELVAM

QUALIFICATION : B.E., (ELECTRICAL) M.E (HIGH VOLTAGE

ENGINEERING) Ph.D (HIGH VOLTAGE

ENGINEERING)AREA OF SPECIALISATION : ELECTRICAL MACHINES

& HIGH VOLTAGE

ENGINEERING

Dr M A Panneerselvam, Professor, Anna University

3

NO. OF PAPERS : ABOUT 30 IN BOTH NATIONALPUBLISHED & INTERNATIONAL JOURNALS

NO. OF Ph.D’s PRODUCED : 4

CANDIDATES WORKING FOR Ph.D. CURRENTLY : 4

Dr M A Panneerselvam, Professor, Anna University

4

LIST OF REFERENCES 1. High Voltage Engineering -4 th Edition- M.S. Naidu and V.Kamaraju- Tata Mc.Graw-Hill Publishing Co. Ltd.,- New Delhi- 2009.2. High Voltage Engineering -3 rd Edition- C.L. Wadhwa - New Age International(P) Ltd. Publishers - New Delhi, Bangalore …- 2010.

Dr M A Panneerselvam, Professor, Anna University

5

3. High Voltage Engineering - J.R.Lucas - Sri Lanka - 2001.4. High Voltage Engineering- Kuffel,E and Abdullah,M - Pergomon Press, Oxford-1970.5. High Voltage Engineering Fundamentals - 2 nd Edition - Kuffel,E , Zaengl,W.S and Kuffel,J - Butterworths, London- 2000.

Dr M A Panneerselvam, Professor, Anna University

6

6. High Voltage Measurement Techniques - Schwab,A.J - M.I.T. Press, Cambridge - 1972.7. High voltage Technology - Alston,L.L - Oxford University Press, Oxford-1968.8. High Voltage Laboratory Techniques- Craggs, J.D. and Meek, J.M - Butterworths, London- 1954.

Dr M A Panneerselvam, Professor, Anna University

7

9. Indian Standards Specification on High Voltage Testing of Electrical Apparatus ( IS 1876-1961, IS 2071 Part I-1974, IS 2071 Part II-1974, IS 2071 Part III-1976, IS 2026 Part III- 1981, IS 3070 Part I-1985, IS 2516 Part II/Sec.2-1965 and IS 698 ).

Dr M A Panneerselvam, Professor, Anna University

8

THE SUBJECT DEALS WITH THE FOLLOWING TOPICS:

1.OVERVOLTAGES

2.BREAKDOWN IN GASES, SOLIDS , LIQUIDS AND VACUUM DIELECTRICS

Dr M A Panneerselvam, Professor, Anna University

9

3.GENERATION OF VERY HIGH VOLTAGES AND CURRENTS

4.MEASUREMENT OF VERY HIGH VOLTAGES AND CURRENTS

5.HIGH VOLTAGE TESTING &

INSULATION COORDINATION

Dr M A Panneerselvam, Professor, Anna University

10

UNIT 1 : OVERVOLTAGES

1.0 NATURE OF OVERVOLTAGES

1.External overvoltages / Lightning overvoltages

Dr M A Panneerselvam, Professor, Anna University

11

2.Internal overvoltages / Switching surges 3.Power frequency overvoltages due to system faults 4.DC overvoltages

Dr M A Panneerselvam, Professor, Anna University

12

1.1 LIGHTNING OVERVOLTAGES

+ + + + - - - + + + + - - - -+ + + + - - - - - + + + + - - -

- - - - ++++ - - - -++++- - - - +++++ - - - +++++

Due to lightning and thunder storms overvoltages are injected onto the transmission lines.

CLOUD

DISCHARGE

TYPE - I

Dr M A Panneerselvam, Professor, Anna University

13

+ + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + +

- - - - - - - - - - - - -- - - - - - - - - -- - - - - -- - - - - - - - - - -- - - - - - - -- - - - - - - -- - - - - - - - - -

CLOUD

DISCHARGE

TYPE - II

CLOUD

Dr M A Panneerselvam, Professor, Anna University

14

+ + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + +

- - - - - - - - - - - - -- - - - - - - - - -- - - - - -- - - - - - - - - - -- - - - - - - -- - - - - - - -- - - - - - - - - -

TYPE - III

I AMPSI AMPS

/ 2 / 2 / 2 / 2

ƵƵƵƵ

+++++++++++++++++++ - - - - - - - - - - - - - - - - - -

Dr M A Panneerselvam, Professor, Anna University

15

PROPAGATION OF LIGHTNING CHANNEL

Dr M A Panneerselvam, Professor, Anna University

16

1.1.1 Voltage developed due to lightning stroke:

EQUIVALENT CIRCUIT

Dr M A Panneerselvam, Professor, Anna University

17

For a lightning stroke current of 200 kA and assuming a surge impedance of 400 Ω for overhead line, the voltage developed is equal to( I x Z/ 2 ) = 200 x 103 x 400/2 = 40 x 106 = 40 MV.

1.1.2 Traveling waves on transmission lines :

Dr M A Panneerselvam, Professor, Anna University

18

TRANSMISSION LINE WITH SURGE IMPEDANCE ‘Z’

The velocity of traveling waves on overhead lines is 300 m / μs and on cables is approximately 150 m / μs.

Dr M A Panneerselvam, Professor, Anna University

19

1.1.3 Impulse voltage wave shape:

Dr M A Panneerselvam, Professor, Anna University

20

Specification for impulse voltage: ( AS PER INDIAN STANDARDS )

t1 Time to Front 1.2 s

t2 Time to Tail 50 s

Vp Peak voltage

Dr M A Panneerselvam, Professor, Anna University

21

Tolerances allowed:

For Front time, t1 ± 30%

For Tail time, t2 ± 20%

Oscillations around the peak ,Vp, ± 5 %

Dr M A Panneerselvam, Professor, Anna University

22

1.1.4 Types of impulse voltages :

FULL IMPULSE CHOPPED IMPULSE FRONT OF WAVE

IMPULSE

Dr M A Panneerselvam, Professor, Anna University

23

1.2 INTERNAL OVERVOLTAGES (SWITCHING SURGES)

1.2.1 Reasons for switching surge voltages:

• Sudden opening of a line

• Sudden closing of a line

Dr M A Panneerselvam, Professor, Anna University

24

•Connection of inductance /Capacitance

•Sudden connection and removal of loads , etc.

Any sudden disturbance taking place in a transmission line will cause switching surge .

Dr M A Panneerselvam, Professor, Anna University

25

For the range of values of the inductance and capacitance of overhead lines the frequency of the switching surges are generally in the range of kc/s and they exist for a duration of milliseconds.

Dr M A Panneerselvam, Professor, Anna University

26

1.2.2 Switching surges on transmission lines: Ex.1 Opening of an unloaded OH line:

Simply opening of an unloaded line transmission line may result in switching surge as shown in the fig.

Dr M A Panneerselvam, Professor, Anna University

27

Assume the switch ‘AB’ is opened

Dr M A Panneerselvam, Professor, Anna University

28

at time, t = 0, when the AC voltage is at its peak. During the next half cycle the voltage at terminal ‘A’ changes to negative peak of AC voltage , wheras the voltage at terminal ‘B’ remains at positive peak. Hence the voltage across the

Dr M A Panneerselvam, Professor, Anna University

29

2 Vp

t = 0

A

B

switch becomes 2 Vp .If the switch is unable withstand this voltage it breaks down and a switching surge

Dr M A Panneerselvam, Professor, Anna University

30

of magnitude 2 Vp travels on the line. At the terminations it gets reflected and refracted and builds up further to a higher level.

Another example for generation of switching surge is the operation of a circuit breaker as shown in the next figure.

Dr M A Panneerselvam, Professor, Anna University

31

Ex.2 Operation of a circuit breaker:

2Vp

RE STRIKING VOLTAGE

RECOVERY VOLTAGE

ARC VOLTAGE

FAULT CURRENT

Dr M A Panneerselvam, Professor, Anna University

32

RESTRIKING VOLTAGE ACROSS A CIRCUIT BREAKERThe maximum voltage across the breaker contacts = 2 Vp =2√2 VRMS

The voltage after reflection and refraction at the terminals of the transmission line may reach a maximum of 5 t0 6 times the system voltage.

Dr M A Panneerselvam, Professor, Anna University

33

1.3 PF OVERVOLTAGES DUE TO LOCAL SYSTEM FAULTS

1.3.1 Local faults in the systems are : Line to ground fault (3) Double line to ground fault (3)

Dr M A Panneerselvam, Professor, Anna University

34

Double line fault (3) Triple line fault (1) Triple line to ground fault (1)

Of the total 11 faults above, a double line to ground fault is more dangerous with respect to

Dr M A Panneerselvam, Professor, Anna University

35

overvoltages developed.Coefficient of earthing (COE) of a system is defined as the ratio of the

Dr M A Panneerselvam, Professor, Anna University

36

voltage of the healthy phase to

ground to that of the line voltage

in the event of a double line to ground fault.

The value of COE varies between 1/√3 to 1.0(i.e., 0.59 to 1.0) depending upon the neutral impedance.

Dr M A Panneerselvam, Professor, Anna University

37

When the value of ‘COE” is less than 70 % ,the system is said to be an effectively or solidly earthed system.

When the ‘COE’ is more than 70 %, the system is said to be a non effectively earthed system.

Dr M A Panneerselvam, Professor, Anna University

38

Systems above 230 kV are generally effectively earthed.

For System ratings above 230 kV the Switching surge voltages attain very high values and become more severe than impulse voltages.

Dr M A Panneerselvam, Professor, Anna University

39

Hence,the insulation design (i.e., insulation coordination) is based on switching surges rather than impulse voltages.

1.4 DC OVERVOLTAGES

During the past 2 to 3 decades HVDC systems came into existence.

Dr M A Panneerselvam, Professor, Anna University

40

HVDC systems have converters and inverters at the sending end and receiving end respectively employing thyristers. Switching surges are produced due to thyristers’ operation.

Dr M A Panneerselvam, Professor, Anna University

41

1.5 TRAVELLING WAVES ON TRANSMISSION LINES:

LONG TRANSMISSION LINE

Dr M A Panneerselvam, Professor, Anna University

42

Assuming a lossless line (i.e., R=0,G=0) when the wave has travelled a distance ‘x’ after a time ‘t’, the electrostatic flux associated with the voltage wave is, q = CxV ------------(1)

The current is given by the rate of charge flow , I = dq/dt = VC dx/dt---(2)

Dr M A Panneerselvam, Professor, Anna University

43

Here dx/dt is the velocity of the travelling wave represented by, I = VC v -------------------(3)

Similarly, the electromagnetic flux associated with the current wave, Φ = Lx I ---------------------(4)

Dr M A Panneerselvam, Professor, Anna University

44

The voltage is the rate of change of flux linkages, V = LI dx/dt = LIv --------------------(5) Dividing Eqn.(5) by (3), V/I= LIv/VCv = LI/CV V2/I2=L/C. i.e.,V/I=Z=√(L/C) --------(6)

Next multiplying Eqn. (5) and (6),

Dr M A Panneerselvam, Professor, Anna University

45

VI = VCv x LIv = VILC v2 v2 = VI / VILC = 1/ (LC) v = 1 / √ (LC) -----------------------(7)

Substituting the values for ‘L’ and ‘C’ of overhead lines we get,

v = 1 / ((2x10-7 ln d/r x 2πε/(ln d/r)) = 3x108 m/sec. = 300 m/μ sec.

Dr M A Panneerselvam, Professor, Anna University

46

which is the velocity of light.

Hence, travelling waves travel with velocity of light on overhead lines.

In cables, since εr >1, the velocity of travelling waves is lesser than overhead lines and is approximately 150 m/ μ sec.

Dr M A Panneerselvam, Professor, Anna University

47

Open ended line:

Dr M A Panneerselvam, Professor, Anna University

48

The voltage wave and current waves travelling towards the open end are related by, V / I = Z. Since the current at the open end is zero, the electromagnetic energy vanishes and is transformed into electrostatic energy:

Dr M A Panneerselvam, Professor, Anna University

49

i.e.,½ L(dx) I2 = ½ C(dx)e2 i.e.,(e/I)2 = L/C = Z2 . i.e., e=IZ=V. Hence, the potential at the open end is raised by ‘V’ volts and becomes V+V=2V. The incident wave = V, the reflected wave = V and the refracted (transmitted) wave = V+V= 2V

Dr M A Panneerselvam, Professor, Anna University

50

The refracted(transmitted) wave = Incident wave + Reflected wave.

For an open ended line the reflection coefficient for voltage wave is +1 and the reflection coefficient for current wave is -1.

Dr M A Panneerselvam, Professor, Anna University

51

VOLTAGE AND CURRENT WAVES OPEN ENDED LINE

Dr M A Panneerselvam, Professor, Anna University

52

Short circuited line:

For a short circuited line , the reflection coefficient for voltage wave is -1 and for current wave is +1.

Dr M A Panneerselvam, Professor, Anna University

53

VOLTAGE AND CURRENT WAVES FOR SHORT CIRCUITED LINE

Dr M A Panneerselvam, Professor, Anna University

54

Reflection and transmission coefficients for line terminated with impedance ‘R’ :

Dr M A Panneerselvam, Professor, Anna University

55

Let the incident voltage and current waves be V and I, the reflected waves V’ and I’ and the transmitted waves V’’ and I’’. It is seen in the earlier sections that whatever be the value of terminating impedance,whether it is open or short circuited , either the current wave or

Dr M A Panneerselvam, Professor, Anna University

56

voltage wave is reflected back with negative sign, i.e., I’ = - V’/Z

I=V/Z , I’=-V’/Z and I’’=V’’/ R. Since I’’=I+I’ and V’’= V+V’, we have, V’’/R = V/Z – V’/Z =V/Z – (V’’-V)/Z = 2V/Z – V’’/Z.

Dr M A Panneerselvam, Professor, Anna University

57

V’’(1/R +1/Z)= V’’(R+Z)/RZ = 2V/Z V’’= V 2R/(R+Z) and I’’ = I 2Z/(R+Z)

Hence , the refraction coefficients for voltage and current waves for open ended line respectively are:

Dr M A Panneerselvam, Professor, Anna University

58

2R / R+Z and 2Z / R+Z

Similarly, the reflection coefficients for voltage and current for open ended line are respectively:

(R-Z) / (R+Z) and - (R-Z) / (R+Z)

Dr M A Panneerselvam, Professor, Anna University

59

Bewley’s Lattice Diagram:

Dr M A Panneerselvam, Professor, Anna University

60

1.6 COMPARISON OF DIFFERENT TYPES OF OVERVOLTAGES

1 Lightning overvoltage :

Lightning overvoltage is an external overvoltage as it is independent of the system parameters. It injects

Dr M A Panneerselvam, Professor, Anna University

61

current on to the transmission lines producing a voltage ranging from kV to MV . It has a wave shape of 1.2/50 μs and exists for a period of microseconds. The very high rate of rise of the impulse voltage striking the line is

Dr M A Panneerselvam, Professor, Anna University

62

equivalent to applying a voltage at very high frequency of the order of Mc/s.

2 Switching Surge :

Switching surges are internal overvoltages as they are dependant upon the system

Dr M A Panneerselvam, Professor, Anna University

63

parameters (i.e., the voltage level, the values of R,L and C of the line). Their magnitudes range from 4 to 6 times the system voltage and they have damped oscillations of kc/s and exist for durations of milliseconds.

Dr M A Panneerselvam, Professor, Anna University

64

3 Power frequency overvoltage :

Due to local system faults such as ‘double line to ground faults’ the voltage of the healthy phase to ground will increase from phase voltage to line voltage depending upon the neural earthing impedance of the system.

1.7 PROTECTION OF TRANSMISSION LINES AGAINST

OVERVOLTAGES

1.5.0 Transmission lines are protected from lightning and switching surges by adopting the following methods :

Dr M A Panneerselvam, Professor, Anna University

66

1.Use of shielding wires

2. Reduction of tower footing resistance and use of counter poises

3.Using spark gaps ( sphere gap and horn gap )

4.Connection of surge absorbers

Dr M A Panneerselvam, Professor, Anna University

67

5.Overhead lines connected to cables

6.Using protector tubes ( Expulsion Arresters )

7.Using non-linear resister lightning arresters ( Valve Arresters)

Dr M A Panneerselvam, Professor, Anna University

68

1.7.1 Shielding wires:

Shielding wires are ground wires connected above phase wires.

The shielding angle should be less than 300 for effective protection of the transmission line against lightning stroke.

Dr M A Panneerselvam, Professor, Anna University

69 SHIELDING ARRANGEMENT OF TRANSMISSION LINES

Dr M A Panneerselvam, Professor, Anna University

70

1.7.2 Reduction of tower footing resistance and use of counter

poises :

ARRANGEMENT SHOWING COUNTER POISES

Dr M A Panneerselvam, Professor, Anna University

71

1.7.3 Spark gaps :

When Spark gaps are connected between phase to ground the gaps breakdown due to lightning overvoltage and lightning energy is diverted to ground through gaps.

Dr M A Panneerselvam, Professor, Anna University

72

Spark gaps are of the following types:

Rod gapsHorn gaps Sphere gaps

Dr M A Panneerselvam, Professor, Anna University

73

Sphere gaps are generally preferred as they have ,

Consistency in breakdown

Less affected by humidity and other atmospheric conditions.

Lesser impulse ratio

Dr M A Panneerselvam, Professor, Anna University

74

ROD GAP HORN GAP

Dr M A Panneerselvam, Professor, Anna University

75

IMPULSE HORN GAP SPHERE GAP

Dr M A Panneerselvam, Professor, Anna University

76

IMPULSE RATIO:

Impulse ratio is defined as the ratio of peak impulse breakdown voltage to that of peak power frequency breakdown voltage of a given insulation.

Dr M A Panneerselvam, Professor, Anna University

77

Sphere gaps have impulse ratio around unity and hence they offer better protection against lightning overvoltages and helps in reduction of insulation of equipment connected in the system.

Dr M A Panneerselvam, Professor, Anna University

78

1.7.4 Surge absorbers :•Power loss takes place due to corona at excess overvoltages and helps in the reduction of such overvoltages.

•In addition the front time of the impulse voltage is increased resulting in reduced stress on the equipment.

Dr M A Panneerselvam, Professor, Anna University

79

IMPULSE VOLTAGE AT DIFFERENT TIMES ON A TRANSMISSION LINE

Dr M A Panneerselvam, Professor, Anna University

80

Connection of resistance in series and Ferranti’s surge absorber :

FERRANTI’S SURGE ABSORBER

Dr M A Panneerselvam, Professor, Anna University

81

1.7.5 Connection of UG cable to overhead line :

The reflection coefficient, R = ZC – ZL / ZC + ZL .

Taking ZL as 400 ohms and Zc as 60 ohms

Dr M A Panneerselvam, Professor, Anna University

82

The reflection coefficient , R

= 60 – 400 / 60 + 400 = -340 / 460 = -0.739The voltage transmitted into the cable 1.0 - 0.739 = 0.261 pu = 26 % of the incident voltage.

Dr M A Panneerselvam, Professor, Anna University

83

1.7.6 Protector tubes ( Expulsion Arresters ) :

Spark gaps have the following draw backs:

They offer protection against overvoltages by diverting the lightning energy to ground but

Dr M A Panneerselvam, Professor, Anna University

84

they cannot arrest the power follow currents.

They are always used as secondary protection except for very small system voltages.

Dr M A Panneerselvam, Professor, Anna University

85

The drawbacks of expulsion arrestors are:They require certain minimum energy to produce gas to quench the arc.

For very high current values they may explode due to very high pressure of gas generated.

Dr M A Panneerselvam, Professor, Anna University

86

EXPULSION ARRESTER

Dr M A Panneerselvam, Professor, Anna University

87

1.7.7 Non linear resister lightning arresters( Valve Arresters ) :

These arresters act as valve in the sense that they offer very low impedance for lightning voltages and offer very high impedance for power frequency currents.

Dr M A Panneerselvam, Professor, Anna University

88 VALVE ARRESTER

Dr M A Panneerselvam, Professor, Anna University

89

CHARACTERISTIC CURVES FOR VALVE ARRESTORS

VOLTAGE TIME CHARACTERISTICS RESIDUAL VOLTAGE

Dr M A Panneerselvam, Professor, Anna University

90

REPRESENTATIVE PHOTOGRAPHS

OF

LIGHTNING DISCHARGE

Dr M A Panneerselvam, Professor, Anna University

91

Dr M A Panneerselvam, Professor, Anna University

92

Dr M A Panneerselvam, Professor, Anna University

93

Dr M A Panneerselvam, Professor, Anna University

94