E3T Efficiency Emerging Technologies Commercial HVAC

Preview:

Citation preview

E3TE3T EnergyEfficiencyEmerging Technologies

Commercial HVACEmerging Technologies

1

Emerging Technologies ShowcaseCommercial HVAC Webinar #2April 14, 2015

Welcome. Today’s webinar is being recorded and will be posted at:• www.E3Tnw.org• www.ConduitNW.org

E3TE3T EnergyEfficiencyEmerging Technologies

2

GoToWebinar Logistics

• Minimize or maximize controlpanel

• Phone lines are muted

• Please use question pane to askquestions during Q & A or if youhave any technical issues

NOTE: Today’s presentation is beingrecorded and will be available at

http://e3tnw.org/Webinarswithin 48 hours

E3TE3T EnergyEfficiencyEmerging Technologies

Variable Capacity Heat Pumps(VCHP – VRF, VRV, DHP…)

Jonathan HellerEcotope

Variable Refrigerant Flow Systems (VRF)Variable Split System Heat Pumps

April 14, 2015

E3TE3T EnergyEfficiencyEmerging Technologies

Presentation Overview

Variable Refrigerant Flow Systems (VRF) andVariable Split System Heat Pumps

1. Present Range of VCHP Equipment2. Present Features of VCHP that Enable Highly

Efficient System Designs3. Case Studies of Efficient and Inefficient Buildings4. Make Case for Design-based Savings as Opposed

to Widget-based Savings for VCHP Systems

E3TE3T EnergyEfficiencyEmerging Technologies

Variable Capacity Heat Pumps (VCHP)

1. Outdoor Compressor Unit2. Refrigerant distribution System3. Indoor Heating/Cooling Dist. System

E3TE3T EnergyEfficiencyEmerging Technologies

Outdoor Compressor Units

E3TE3T EnergyEfficiencyEmerging Technologies

Refrigerant Distribution System

R-410a

E3TE3T EnergyEfficiencyEmerging Technologies

Heat Recovery 2 vs. 3-pipe

E3TE3T EnergyEfficiencyEmerging Technologies

Indoor Units

E3TE3T EnergyEfficiencyEmerging Technologies

Fan Coil Energy Use

165

120

8 15 15

96 85

0

20

40

60

80

100

120

140

160

180

PSC Fan Coil ECM Fan Coil VRF WallCassette

VRF CeilingCassette

VRF FloorCassette

VRF LowProfileDucted

VRF MediumStatic

Ducted

Wat

ts

Fan Coil Type

(Fan Watts for delivery of 8000 Btuh cooling)

E3TE3T EnergyEfficiencyEmerging Technologies

Variable Speed Split System Heat Pumps

E3TE3T EnergyEfficiencyEmerging Technologies

E3TE3T EnergyEfficiencyEmerging Technologies

Electric Heat and Duct Losses

“Box Only” Efficiency

COP ~ 2.7 vs. 2.2

23% Improvement

“System” Efficiency

COP ~ 1.8 vs. 1.5

20% Improvement

E3TE3T EnergyEfficiencyEmerging Technologies

R-410a: No Need for Back-up or Reheat

E3TE3T EnergyEfficiencyEmerging Technologies

Move Away from Large Central HVAC Systems

E3TE3T EnergyEfficiencyEmerging Technologies

Towards Smaller Zonal Systems

E3TE3T EnergyEfficiencyEmerging Technologies

Move Away from All-In-One HVAC Systems

E3TE3T EnergyEfficiencyEmerging Technologies

Towards Dedicated Ventilation Systems

E3TE3T EnergyEfficiencyEmerging Technologies

Right-Size Mechanical Systems

E3TE3T EnergyEfficiencyEmerging Technologies

Smaller Equipment

E3TE3T EnergyEfficiencyEmerging Technologies

EUI of Seattle Fire Stations

0

20

40

60

80

100

120

140

160

180

200

kBtu

/sf-y

r

Seattle Median (97)

E3TE3T EnergyEfficiencyEmerging Technologies

Why are New Stations so Inefficient?

• Continuous ducted central fansystems

• Ventilation at 3x ASHRAE 62• No heat recovery, electric heat on

ventilation air

E3TE3T EnergyEfficiencyEmerging Technologies

Ecotope Case Studies

0102030405060708090

100

2003 CBECS 2008 CBSA 1980s MPR 2002-2004Baseline

KCHA RFM

EUI:

kBtu

/sf-y

r

E3TE3T EnergyEfficiencyEmerging Technologies

Rice Fergus Miller Office: Bremerton, WA

EUI = 21

E3TE3T EnergyEfficiencyEmerging Technologies

Now What?

E3TE3T EnergyEfficiencyEmerging Technologies

Load Reduction Measures

1. Insulation2. Daylighting3. VRF Heat Pumps4. Heat recovery ventilation5. Operable windows – Passive/Active

E3TE3T EnergyEfficiencyEmerging Technologies

Non-Heat Recovery Heat Pump

E3TE3T EnergyEfficiencyEmerging TechnologiesE3TE3T EnergyEfficiencyEmerging Technologies

Fan Energy Load Reduction:Ceiling Fans vs. Ducts to Move Air

E3TE3T EnergyEfficiencyEmerging Technologies

End Use Reductions

0

10

20

30

40

50

60

70

80

90

100

CBECS Avg. Office RFM

CoolingHeatingPumpsFansDHWLightsExt UsagePlugs, Elev, Misc.

E3TE3T EnergyEfficiencyEmerging Technologies

Heating Load ~ 12 tons (1350 sf/ton)

Cooling Load ~ 22 Tons (850 sf/ton)

Smaller Mechanical Systems

E3TE3T EnergyEfficiencyEmerging Technologies

Construction Costs breakdown ($/sf)Fire

Protection$1.97

Electrical$17.11

HVAC $9.75

Plumbing$4.83

EverythingElse $71.34

E3TE3T EnergyEfficiencyEmerging Technologies

LEED Platinum

EUI = 21

E3TE3T EnergyEfficiencyEmerging Technologies

King County Housing Authority: Tukwila, WA

EUI = 26

E3TE3T EnergyEfficiencyEmerging Technologies

1980’s Level Envelope

• R-11 Walls

• R-20 Roof

• Uninsulated Slab

• U-0.4 Double Glaze

E3TE3T EnergyEfficiencyEmerging Technologies

No Economizers

E3TE3T EnergyEfficiencyEmerging Technologies

No Direct Digital Controls

E3TE3T EnergyEfficiencyEmerging Technologies

High Efficiency Lights & Plugs

E3TE3T EnergyEfficiencyEmerging Technologies

2-Pipe VRF with Heat Recovery

48 Tons3 Outdoor Units36 Ductless Units14 Ducted Units50 Zones Total1.33 Ratio Indoor/Outdoor Units

E3TE3T EnergyEfficiencyEmerging Technologies

DOAS via High Efficiency ERV

E3TE3T EnergyEfficiencyEmerging Technologies

High Performance, Low Cost

Lights32%

Computers28%Misc.

15%

ERV Fans6%

Heat12%

Cool7%

Energy End Use (EUI 26 kBtu/sf-yr)

HVAC, $14Electric,

$13

Plumbing,$2

Fire, $2

Other, $64

KCHA Construction Budget ($95/sf)

E3TE3T EnergyEfficiencyEmerging Technologies

System Comparison (KCHA)

E3TE3T EnergyEfficiencyEmerging Technologies

Summary – Variable Speed Splits

• Energy Savings

• Non-Energy Benefits

• Technology Readiness

• Ease of Adoption

• Value

E3TE3T EnergyEfficiencyEmerging Technologies

Summary – VRF

• Energy Savings

• Non-Energy Benefits

• Technology Readiness

• Ease of Adoption

• Value

E3TE3T EnergyEfficiencyEmerging Technologies

35 26 19 18

58

42

7 4

0102030405060708090

100

2003 CBECSAvg. Office

Seattle Avg.Office

KCHA Rice FergusMiller Office

EUI (

kBtu

/sf-y

r)Lights, Plugs, Misc. HVAC

Energy Savings

** Design-Based vs. Widget-Based Approach

E3TE3T EnergyEfficiencyEmerging Technologies

Non-Energy Benefits

• Smaller equipment and distribution systemspossible. Enables lower floor-to-floor heightsand easier retrofit.

• Greater individual zone control possible• Pre-manufactured systems allow for easier

installation, coordination, commissioning• Quiet

E3TE3T EnergyEfficiencyEmerging Technologies

Technology Readiness

E3TE3T EnergyEfficiencyEmerging Technologies

Ease of Adoption

E3TE3T EnergyEfficiencyEmerging Technologies

Value

E3TE3T EnergyEfficiencyEmerging Technologies

49

Questions?

Jonathan Heller

Principal EngineerEcotopejheller@ecotope.com

E3TE3T EnergyEfficiencyEmerging Technologies

GoToWebinar Logistics for TAG Members

• Minimize or maximize control panel

• ComTAG members – choose“telephone” and dial using the infoprovided

• Mute your phone when notspeaking

• Click on the hand icon when youwant to ask a question

• Please use question pane to askquestions during Q & A or if youhave any technical issues

50

E3TE3T EnergyEfficiencyEmerging Technologies

51

Criteria

1) How significant and reliable are the energy savings per unit?

2) How great are the non-energy advantages for the end userfor adopting this technology?

3) How ready are the products(s) and providers to scale up forwidespread use in the Pacific Northwest?

4) How easy is it for the end user to change to the proposedtechnology?

5) Considering all costs and all benefits, how good of a buy isthis technology for the owner?