CAT GENSETS
Citation preview
EMCP IIEMCP II
Control panelControl panelIn previous generator control panels, relay are used in In previous generator control panels, relay are used in conjunction with switches to make a logic panel to protect conjunction with switches to make a logic panel to protect the engine and generator.the engine and generator.
ActuatorActuator
Engine Diode
T0T0 T1T1 T2T2 T3T3
MPMP
The typical logic, uses a signal to start the engine The typical logic, uses a signal to start the engine and a magnetic pickup that feed the ESSand a magnetic pickup that feed the ESS
The EMCP uses a similar type of logic but a microprocessor GSC The EMCP uses a similar type of logic but a microprocessor GSC performs the functions of all the relays and timers used before.performs the functions of all the relays and timers used before.
They are : EMCP I , EMCPII, EMCPII They are : EMCP I , EMCPII, EMCPII ++, EMCPII , EMCPII + + PP
GSCGSC
E M C PE M C P
Engine monitoring :Engine monitoring :System DC voltageSystem DC voltageEngine RPMEngine RPMOil pressureOil pressureEngine hour meterEngine hour meterCoolant temperatureCoolant temperature
Optional:Optional: Coolant lossCoolant lossExhaust temperatureExhaust temperature
Start/Stop controlStart/Stop control
Cycle crankingCycle cranking
AC monitoringAC monitoringAC voltageAC voltageAC currentAC currentFrequencyFrequency
Cooldown timerCooldown timer
System diagnosticsSystem diagnostics
Diesel and gas engine Diesel and gas engine functionalityfunctionality
Various system fault codesVarious system fault codes
Engine set point programmingEngine set point programming
Engine set point verificationEngine set point verification
EMCP EMCP FeaturesFeatures
Fault IndicatorsFault Indicators• Fault alarm indicator• Fault shutdown indicator• Dedicated shutdown
indicator -Low Oil Pressure -Emergency Stop -High Water Temp -Engine Overspeed -Low Coolant Level -Overcrank
RelaysRelays• K1-Electronic Governor Relay.• K2-Generator Fault Relay.• K3-Crank Termination Relay.• K4-Starting Motor Relay.• K5-Run Relay.• K6-Air Shutoff Relay.• K7-Fuel Control Relay.
Modes of OperationModes of Operation
• Normal Mode• Alarm Mode• Shutdown Mode• Service Mode
Engine Starting SequenceEngine Starting Sequence
Start or remote signal
Check sys for faults, engine is not already running, not in service mode
Activate SMR, FCR
Note: -FCR energize to run (K4, K5, K7) or to stop (K4, K5) -The relay status on the relay status indicators of the lower display. K1, K3, K5, K7 for ETR ; K1, K3, K5 for ETS
Deactivate SMR
-rpm=400& Activate CTR
Activate EG relay – oil press=set point
for low oil press.
Engine Stopping SequenceEngine Stopping Sequence
Stop or remote signal
Check sys for faults, begin the cool down time, and activate the spare output (if programmed)
Deactivate RR & EGR
oil press<set point for low oil press.
* Note: The relay status on the relay status indicators of the lower display. all relays are Off except on ETS K7 indicator remain On for 70 sec after 0 rpm and oil press is also 0
Deactivate CTR
(RPM = 0)
*Deactivate 0r activate
FCR
Service ModeService Mode
• Assist with troubleshooting • Satisfy special applications• Satisfy customer needs• Verify or calibrate or adjust genset functions
PHASEPHASESELECTSELECT
ENGINEENGINEMETERMETER
LAMPLAMPTESTTEST
ALARMALARMCODECODE EXITEXIT
SERVICESERVICEMODEMODE
SCROLLSCROLLRIGHTRIGHT
SCROLLSCROLLUPUP
SCROLLSCROLLDOWNDOWN
SELECTSELECT ENTERENTER
OP1
OP1
OP2
OP3
FAULT LOG VIEWING
SETPOINT VIEWING
PASSWORD ENTRY
PE: 13231
OP4
OP5
OP6
OP7
OP8
OP9
OP10
Fault log programming
Set point programming
Spare Input/Output programming
Hourmeter programming
Voltmeter/Ammeter programming
Engine setpoint verification
AC calibration
Service modeService mode
Recommended