Global Power ProductsGlobal Power Products
Power Systems 2005Power Systems 2005Clemson University March 9-11, 2005Clemson University March 9-11, 2005
GenerLink OverviewGenerLink Overview
• Background
• Product Demonstration
• Technical Review
• Installation
• Marketing SWOT
• www.generlink.com
Mark MatyacPresidentGlobal Power Products, Inc.Phone: 770-736-8232FAX: 770-736-8231mark@globalpowerproducts.com
Global Power ProductsGlobal Power Products
GenerLink• GenerLink allows electrical customers to
safely connect a small generator to their homes during a power outage.
Global Power ProductsGlobal Power Products
GenerLink History
• PEPCO Technologies LLC Started in 1999
• Design, Development & UL Listing in 2002
• September 11, 2001
• PEPCO Donation to EPRI
• Global Power Products 2003
Global Power ProductsGlobal Power Products
• Distributed Reliability • 10 to 15 million portable generators already exist• Cost of Generators have come down• Typical yearly sales are approximately 2 million units• Three companies have 85% market share
– Coleman
– Honda
– Generac
Residential Reliability Market Exists Today
Global Power ProductsGlobal Power Products
Circuit OperationTechnical Discussion
Global Power ProductsGlobal Power Products
Four Basic Switch Components
• (1) 200 Ampere ASCO Switch
• (1) 30 Ampere Siemens T-92 Relay
• (2) Siemens RTE Relays
Global Power ProductsGlobal Power Products
Basics of GenerLink
• GenerLink is a “state” switch
• Generator has priority– Allows customer to test system– Operator becomes part of the process
• Special Electromechanical logic scheme insures “break-before-make”
• 160 amperes continuous current flow
Global Power ProductsGlobal Power Products
Basic Circuit Overview
ASCO SwitchControl Circuit
200 Amp ASCO Switch
Utility Sense Circuit
GeneratorSense Circuit
Hardware Interlock
CloseEnable
TripEnable
GeneratorClose Circuit
SiemensT92 Relay
Tripped?Yes
30 Amp Self-ResetCircuit Breaker
G
Generator
Fuse Fuse
LoadsUtility
R. Stewart Pepco Technologies 9/21/99
Global Power ProductsGlobal Power Products
Protection
•Control Function designed similar to relay protection scheme
• Control Circuits are fused and transformer isolated •“Stuck-Switch” Protection
• Hardware Interlock - Primary•Fuse with specific I2T Value - Secondary
•Generator Over Current Protection•Generator Breaker - Primary•Self-resetting Circuit Breakers - Secondary
Global Power ProductsGlobal Power Products
Utilities
• Sales– Mail marketing – Safety seminars
• Installation– Provide installation
Global Power ProductsGlobal Power Products
The Future
• Gateway– Fuel Cell– Generator
• Home Generation to Offset Peak Periods
Global Power ProductsGlobal Power Products
• A device that provides residential A device that provides residential customers an alternate means of customers an alternate means of service in the event of an electrical service in the event of an electrical power outage.power outage.
• Currently designed to fit most Currently designed to fit most 200-ampere ring and ringless 200-ampere ring and ringless meter cabinets.meter cabinets.
Product Vision
Installation Diagram200 Amp Ringless Cabinet
GenerLink
Cabinet Cover
Watthour Meter
8/2/00
SealingRing
ExteriorWall
Global Power ProductsGlobal Power Products
• Verify numbers, record required information.
• Remove cabinet cover.
Installation on Ringless Cabinet
Connector
Cord Set
Global Power ProductsGlobal Power Products
Installation on Ringless Cabinet
• Replace and tighten nut.
• Plug otherend of ground wire to the GenerLink™device.
Global Power ProductsGlobal Power Products
Installation on Ringless Cabinet
• Insert Watthour Meter into the GenerLink™.
Global Power ProductsGlobal Power Products
Installation on Ringless Cabinet
• Install sealing ring at the GenerLink™ - Watthour meter connection.
• Seal cabinet and sealing ring.
• The installation is now complete.
Global Power ProductsGlobal Power Products
Installation on Ring Style Cabinet
• Plug watthour
meter into the
GenerLink™
socket.
Global Power ProductsGlobal Power Products
Installation on Ring Style Cabinet
• Replace the cabinet sealing ring.
• Install additional ring at GenerLink™ - Meter connection.
Global Power ProductsGlobal Power Products
Installation Complete
• GenerLink™ makes
connecting your
home generator as
easy as using a plug
and flipping a
switch.
Global Power ProductsGlobal Power Products
Test Results
• 300,000 Operations, No Load• 92,586 Operations, Generator Relay, 30A Load• 12,140 Operations, ASCO Switch, 160A Load• 16,266 Operations, 65% - 100% Nominal Voltage @
185º F• 1248 Hours+, Generator Input, Continuous 30A, .76 pf• 2 Hours, 200A Continuous, 109 ºF Max Temp• 22 Hours, 163 A, 6 Sec. Cycle, 103 ºF Max Temp• No RFI Susceptibility• No Effect On Meter Accuracy
In-House Testing
Global Power ProductsGlobal Power Products
Test Results Generlink AEP Test Results
Test Parameters PassOperations 15,000 Operations at 240 V, 160 A, .78 pf Weathering 14 Day, Wet/Dry/UV Exposure per ANSI C-12-1995, Test #6 Salt Spray 25 Hour Salt Spray per ASTM B117-85 Raintightness 1 Hour per ANSI/UL 50 – 1987 Temperature Rise 160 A for 3.5 Hours, Jaw Temp 61 C
Short Circuit Withstand 6000 A RMS, 6 cycles Surge Withstand 2.5 kV Dielectric, C37.90.1 Oscillatory/Fast Transient, C62.41
Ring and Combination Wave
High Voltage Withstand 1.5kV ac for 60 Seconds, per ANSI/IEEE C37.90 Overload 50 Operations, 240 V, 300 A, .4-.5 pf Accuracy Per ANSI/IEEE C12-1995 Radio FrequencyInterference
Per ANSI C12.16
Global Power ProductsGlobal Power Products
Step 3
Global Power ProductsGlobal Power Products
Surge Suppression
• Tested 6 whole-house products with EPRI/PEAC
• Selected two manufacturers
• GPP UL Listed with Surge Protection 5/12/04
to Customer Load
TVSS
L1 L2
from Utility Source
L1’ G L2’
MOVs
Global Power ProductsGlobal Power Products
PanelBranch
TVComputerRefrigeratorMicrowaveetc.
ACFurnaceWater HeaterPumpsetc.
“wired-in”“plugged-in”
Zone “A” Zone “B” Zone “C”
Defined Zones of Protection for Surge Suppression
TelcoCATV
ANSI/IEEE 62.41
Global Power ProductsGlobal Power Products
GenerLink Marketing
• Strengths
• Weaknesses
• Opportunities
• Threats
Global Power ProductsGlobal Power Products
GenerLink Strengths
• Customer Acceptance– Cost of GenerLink vs Other Transfer Switch– Plug & Play with Portable Generators– Ease of use– Voltage to Customers Entire Electrical Panel– Insurance Premium Discount
Global Power ProductsGlobal Power Products
Portable Generator Market Defines Existing Residential Reliability Market Opportunity
• Simmons Market Research: 620,000 portables purchased in 1998 (4-5% of adults own portables)
• Robin/Subaru: 930,000 portables sold in 1998
• Generac: 1.0-1.6 million portables sold per year 1998-2000 ($600-900 million sales, 16% CAGR)
• RKS Research & Consulting: 11% of affluent households own generator
Estimates vary, but several hundred thousand generator units sold annually in U.S. seems likely – and growing at healthy pace
Global Power ProductsGlobal Power Products
Target MarketsDistributed Reliability Distributed Generation
Target Near-Term RDG Market
15.2 million owner occupied housing units with above
median income and high electricity costs
Potential Future RDG Market
72 million owner occupied U.S. Housing
Units (Out of 121 million total housing units)
Target Reliability Market
32 million owner occupied housing units
with above median income
Global Power ProductsGlobal Power Products
GenerLink
• Utility – Safety– Integrated Surge Module– Similar to a Meter Installation– Quality Parts in Manufacturing– UL Listed– Distributed Generation
Global Power ProductsGlobal Power Products
GenerLink Weaknesses
• Consumers– Cost – Sticker Shock
• Little if any Installation Cost
• GenerLink is Shipped with Power Cord
• Utility– What if
Global Power ProductsGlobal Power Products
GenerLink Opportunities
• Functionality – 40 Amps– Polyphase – Grid Gateway– Surge– Zigbee Communications
Global Power ProductsGlobal Power Products
GenerLink
• Sales Scenarios– Utility Buys and Leases– Utility Buys and Sells to Customer– Customer Buys and Utility Installs– Customer Buys and Contractor
Installs
Two fundamental thrusts:
• Assemble technology portfolio
• Establish distribution channels
Vision
Strategy
Product Plan
Global Power ProductsGlobal Power Products
GenerLink Opportunities• Acceptance
– FPL– AEP– NES– Northeast Utilities– Hydro 1 – Touch Stone Energy
• Midwest Electric St. Marys Ohio
Global Power ProductsGlobal Power Products
GenerLink Threats
• Conflict between Utility and Electrical Inspectors
• Utilities – Nobody Touches My Meter
• Contractors – A Ground has to be Installed– Extension of Meter Base
Global Power ProductsGlobal Power Products
Conclusion
• Safety for Utilities
• Safety for Consumers
• Simple Installation
• Cost Effective
• www.generlink.com