PG738EX-961212-0004
SOFTWARE VERSION 3.10CONTROL PANEL RESET:Installer lock must be unlocked. (Address 058: enter any value other than 147)
Power down reset(1) Remove battery and AC to power down the unit.(2) Connect a jumper between "reset jumper" pins.(3) Connect AC then the battery.(4) Wait 10 seconds.(5) Remove jumper.
Factory default installer and master codes will be reinstated. Values entered at addresses 008-043, 062-126 and 300-527as well as all user codes, will be erased ([2ND] [2ND]). Programmed values of all other addresses do not change.
HEXA PROGRAMMING:All digits from 0 to F are valid. Values are programmed intomemory locations from address 000 to 043 and from address300 to 527.
1) Press [ENTER] + installer code.2) [ENTER] will flash (programming mode).3) Enter 3 digit memory address.4) Current value will be displayed on keypad.5) Enter 2 digit data.6) Go to step 3 for next address.To exit programming mode, press [CLEAR].
STREAMLINED SECTION PROGRAMMINGCan be used to program sections 00 to 67. (addresses 000 to 043 and 300 to 527)Press [ENTER], installer code, and [7] . ([2ND] and [ENTER] keys alternately flash.)Enter a 2-digit section number, followed by 8 digits to program that section (confirmation beep). Data will be savedautomatically and the software advances to the next programming section. To exit programming mode press [CLEAR].
INSTALLER CODE: (reset code 737373) (addresses 000, 001, 002) SECTION 00Full access to programming, except access codes. (addresses 127-299) No access to arming/disarming. Can be used tomodify installer code. Use only numeric keys from [1] to [10] . (key [10] = 0)
PANEL ANSWER OPTIONS: (address 003) SECTION 00First digit disables “Answering Machine Override” (key [2ND] or key [1] ), or determines period of time between first andsecond call (see table below). Second digit determines number of rings required before panel will answer. If [2ND][2ND]is entered, panel will not answer. (Default value is [2ND] [8] .)
- 1 -
Value of2ND digit = 10( 8 + 2 = 10)
Value of 1ST digit = 3( 2 + 1 = 3)VALUE = "3A"
HEXA DISPLAY
No display = SKIP (empty) No light = 0
10 = [0] = [A]
If key is lit = 8 = 4 = 2 = 1
If key is lit = 8 = 4 = 2 = 1
TELEPHONE AND ACCOUNT NUMBERS: (reset empty )If only one central station phone number is used, program the same number for telephone number 1 and 2.
[10] = the number "0" [BYP] = switch from pulse to tone while dialing[11] = * [MEM] = pause 4 seconds[12] = # [TRBL] = end of number
COMPUTER TELEPHONE NUMBER: (View at addresses 008 to 015.)
02 __ / __ / __ / __ / __ / __ / __ / __ 03 __ / __ / __ / __ / __ / __ / __ / __1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
CENTRAL STATION TELEPHONE NUMBER 1: (View at addresses 016 to 023.)
04 __ / __ / __ / __ / __ / __ / __ / __ 05 __ / __ / __ / __ / __ / __ / __ / __1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
CENTRAL STATION TELEPHONE NUMBER 2: (View at addresses 024 to 031.)
06 __ / __ / __ / __ / __ / __ / __ / __ 07 __ / __ / __ / __ / __ / __ / __ / __1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
ACCOUNT "A" AND "B": (View at addresses 032 to 035.)
08 ___ / ___ / ___ / ___ ___ / ___ / ___ / ___1 2 3 4 5 6 7 8
A B
If only one account number is required, the same number must be entered for both account "A" and "B".
- 2 -
PG738EX
Press [ TRBL] to endphone number if lessthan 16 dig its areprogrammed.
Press [ TRBL] to endphone number if lessthan 16 dig its areprogrammed.
For 3 digit accountnumbers, enter "skip"([2ND]) as first digit.
Press [ TRBL] to endphone number if lessthan 16 dig its areprogrammed.
Streamlinesection
Streamlinesection
Streamlinesection
Streamlinesection
Streamlinesection
Streamlinesection
Streamlinesection
[2 ]ND
[2 ]ND [2 ]ND
Streamlinesection
Data Description Address
___/______/___
/
___/___
___ ___
Future use1st digit: value must be entered i.e.2nd digit: time correction (See table)1st digit: telephone 1 format2nd digit: telephone 2 format1st digit: PGM 1 type2nd digit: PGM 2 type
[2 ]ND
036037
038
039
09
PGM 1PGM 2PGM mask 1PGM mask 2
040041042043
___/______/___
/___/______ ___10
TIME CORRECTION:(address second digit)037
[2 ][1][2][3][4][5][6][7]
ND - No adjustment- Plus 4 sec.- Plus 8 sec.- Plus 12 sec.- Plus 16 sec.- Plus 20 sec.- Plus 24 sec.- Plus 28 sec.
[8][9][10][11][12][ ][ ][ ]
- Minus 4 sec.- Minus 8 sec.- Minus 12 sec.- Minus 16 sec.- Minus 20 sec.- Minus 24 sec.- Minus 28 sec.- Minus 32 sec.
BYP
MEM
TRBL
COMMUNICATOR FORMATSKey
[2 ][1][2][3][4][5]
ND [6][7][8][9]
[10][ ]TRBL
= slow (1400Hz, 1900Hz, 10bps)= (1400Hz, 1800Hz, 10bps)= fast (1400Hz, 1900Hz, 20bps)= (2300Hz, 1800Hz, 20bps)= (40bps with 1400Hz handshake)= (40bps with 2300Hz handshake)
ADEMCO
SILENT KNIGHTSESCOARADIONICSRADIONICS
= with PARITY (1400Hz, 40bps)= with PARITY (2300Hz, 40bps)= express= contact ID (programmable codes)= contact ID (all codes)= - no handshake (personal dialing)
RADIONICSRADIONICSADEMCOADEMCOADEMCODTMF
- 3 -
PG738EX
For addresses to , see pages 7 to 10.044 126
CID100:110:111:112:113114:115:116:117:118:120:121:122:123:130:131:132:133:136:137:138:140:150:151:152:153:154:155:156:157:158:159:161:
CID300:301:302305:306:309:320:321:323:350:351:354:370:371:372:373:382:383:400:401:402:403:404:407:410:441:570:572:573:574:601:602:625:
PROG. VALUE[2 ] / [1][2 ] / [2][2 ] / [3][2 ] / [4][2 ] / [5][2 ] / [6][2 ] / [7][2 ] / [8][2 ] / [9][2 ] / [10][2 ] / [11][2 ] / [12][2 ] / [ ][2 ] / [ ][2 ] / [ ][1] / [2 ][1] / [1][1] / [2][1] / [3][1] / [4][1] / [5][1] / [6][1] / [7][1] / [8][1] / [9][1] / [10][1] / [11][1] / [12][1] / [ ][1] / [ ][1] / [ ][2] / [2 ][2] / [1]
ND
ND
ND
ND
ND
ND
ND
ND
ND
ND
ND
ND
ND BYP
ND MEM
ND TRBL
ND
BYP
MEM
TRBL
ND
PROG. VALUE[2] / [2][2] / [3][2] / [4][2] / [5][2] / [6][2] / [7][2] / [8][2] / [9][2] / [10][2] / [11][2] / [12][2] [ ][2] [ ][2] [ ][3] / [2 ][3] / [1][3] / [2][3] / [3][3] / [4][3] / [5][3] / [6][3] / [7][3] / [8][3] / [9][3] / [10][3] / [11][3] / [12][3] [ ][3] [ ][3] [ ][4] / [2 ][4] / [1][4] / [2]
///
///
BYP
MEM
TRBL
ND
BYP
MEM
TRBL
ND
REPORTING CODEAUXILIARY ALARMFIRE ALARMFIRE SMOKECOMBUSTIONWATER FLOWHEATPULLSTATIONDUCTFLAMENEAR ALARMPANIC ALARMDURESSSILENT PANICAUDIBLE PANICBURGLARYPERIMETER BURG.INTERIOR BURG.24HR BURGLARYBURGLARY OUTDOORBURGLARY TAMPERBURGLARY NEAR ALARMGENERAL ALARM24 HOUR AUXGAS DETECTEDREFRIGERATIONLOSS OF HEATWATER LEAKAGEFOIL BREAK ALARMDAY TROUBLE ALARMLOW GAS LEVELHIGH TEMPERATURELOW TEMPERATURELOSS AIR FLOW
REPORTING CODESYSTEM TROUBLEAC LOSSLOW SYSTEM BATTERYSYSTEM RESETPROGRAM CHANGEDBATTERY TEST FAILSOUNDER/RELAY TROUBLEBELL 1 TROUBLEALARM RELAY TROUBLECOMMUNICATION TROUBLETELCO 1 FAULTFAIL TO COMMUNICATEPROTECTION LOOP TROUBLEPROTECTION LOOP OPENPROTECTION LOOP SHORTFIRE LOOP TROUBLESENSOR TROUBLESENSOR TAMPEROPEN/CLOSEOPEN/CLOSE BY USER #GROUP OPEN/CLOSEAUTOMATIC OPENING/CLOSINGLATE TO OPEN/CLOSEREMOTE ARM DOWNLOADREMOTE ACCESSOPEN/CLOSE - STAY MODEBYPASS24 HOUR ZONE BYPASSBURGLARY BYPASS #GROUP BYPASSMANUAL TESTPERIODIC TESTTIME/DATE RESET
PROGRAMMABLE CONTACT ID EVENT CODESAll addresses from to (sections to ) programmed with values other than will report the contactID codes corresponding to the values programmed. Values to be programmed should be selected from this table.
300 527 11 67 [2 ] [2 ]ND ND
- 4 -
REPORTING CODES: (reset code = “empty" )All digits from to are valid. Enter (skip) = digit will not be reported except for contact I.D. programmable codes.For single digit reporting enter "skip" ( ) as first digit.
(Select Contact I.D (all codes) - key for both central station numbers at section - address .)
[2 ] [2 ][1] [F] [2 ]
[2 ]
[10] 09 038
ND ND
NDND
If CONTACT I.D. format (all codes) is selected, addresses 300 to 527 (sections 11 to 67) do not have to be programmed.
PG738EX
___/______/___
/___/______ ___
Auto / EsploadMasterUser code 1User code 2
300301302303
Streamlinesection
Streamlinesection
Data DataDescription DescriptionAddress AddressARMING CODES:(closing)
___/______/___
/____/______ __
User code 23User code 24User code 25User code 26
324325326327
17
11
___/______/___
/___/______ ___
User code 3User code 4User code 5User code 6
304305306307
___/______/___
/____/______ __
User code 27User code 28User code 29User code 30
328329330331
12
18
User code 7User code 8User code 9User code 10
User code 15User code 16User code 17User code 18
308309310311
316317318319
User code 31User code 32User code 33User code 34
User code 39User code 40User code 41User code 42
332333334335
340341342343
___/______/___
/___/______ ___
___/______/___
/___/______ ___
___/______/___
/___/______ ___
___/______/___
/___/______ ___
13
15
19
21User code 11User code 12User code 13User code 14
User code 19User code 20User code 21User code 22
312313314315
320321322323
14
16
User code 35User code 36User code 37User code 38
User code 43User code 44User code 45User code 46
User code 47User code 48 /(Duress)
See next page
336337338339
344345346347
348349
___/______/___
/___/______ ___
___/______/___
/___/______ ___
___/______/___
___/______/___
/____/______ __
___/______/___
/____/______ __
20
22
23
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
___/______/___
/____/______ __
PG738EX
- 5 -
REPORTING CODES: (reset code )"empty"
Streamlinesection
Streamlinesection
Data DataDescription DescriptionAddress AddressDISARMING CODES:(opening)
___/______/___
/____/______ __
User code 21User code 22User code 23User code 24
372373374375
29
___/______/___
/___/______ ___
User code 1User code 2User code 3User code 4
352353354355
___/______/___
/____/______ __
User code 25User code 26User code 27User code 28
376377378379
24
30
User code 5User code 6User code 7User code 8
User code 13User code 14User code 15User code 16
356357358359
364365366367
User code 29User code 30User code 31User code 32
User code 37User code 38User code 39User code 40
380381382383
388389390391
___/______/___
/___/______ ___
___/______/___
/___/______ ___
___/______/___
/___/______ ___
___/______/___
/___/______ ___
25
27
31
33User code 9User code 10User code 11User code 12
User code 17User code 18User code 19User code 20
360361362363
368369370371
26
28
User code 33User code 34User code 35User code 36
User code 41User code 42User code 43User code 44
User code 45User code 46User code 47User code 48 /(Duress)
384385386387
392393394395
396397398399
___/______/___
/___/______ ___
___/______/___
/___/______ ___
___/______/______/______/___
___/______/___
/____/______ __
___/______/___
/____/______ __
32
34
35
EsploadMaster
See previous page
350351
___/______/___
Streamlinesection
Streamlinesection
Data DataDescription DescriptionAddress AddressALARM CODES ZONE 1 TO 12:
___/______/___
/___/______ ___
Zone 5Zone 6Zone 7Zone 8 Keypad 1
404405406407
N/AN/AN/AN/A
412413414415
37
39
Zone 9N/AN/AN/A
Keypad 2 408409410411
N/AN/AN/AN/A
416417418419
___/______/___
/___/______ ___
___/______/___
/___/______ ___38
40
N/AN/AN/AN/A
420421422423
___/______/___
/___/______ ___41
Zone 1Zone 2Zone 3Zone 4
(fire)
400401402403
(see add. 100)
___/______/______/______/___
36
23
ALARM CODES ZONE 13 TO 24:
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND
[ ]2ND [ ]2ND
PG738EX
- 6 -
REPORTING CODES: (reset code )"empty"
Streamlinesection
Streamlinesection
Streamlinesection
Streamlinesection
Data
Data
Data
Data
Description
Description
Description
Description
Address
Address
Address
Address
ZONE 1 TO 12 RESTORE CODES: ZONE 13 TO 24 RESTORE CODES:
ZONE 1 TO 12 SHUTDOWN CODES: ZONE 13 TO 24 SHUTDOWN CODES:
___/______/___
/___/______ ___
___/______/___
/___/______ ___
Zone 5Zone 6Zone 7Zone 8 Keypad 1
Zone 5Zone 6Zone 7Zone 8 Keypad 1
428429430431
452453454455
___/______/___
/____/______ __
___/______/___
/____/______ __
N/AN/AN/AN/A
N/AN/AN/AN/A
436437438439
460461462463
43
49
45
51
Zone 9N/AN/AN/A
Keypad 2
Zone 9N/AN/AN/A
Keypad 2
432433434435
456457458459
N/AN/AN/AN/A
N/AN/AN/AN/A
440441442443
464465466467
___/______/___
/___/______ ___
___/______/___
/___/______ ___
___/______/___
/___/______ ___
___/______/___
/___/______ ___
44
50
46
52
N/AN/AN/AN/A
N/AN/AN/AN/A
444445446447
468469470471
___/______/___
/___/______ ___
___/______/___
/___/______ ___
47
53
Zone 1Zone 2Zone 3Zone 4
(fire)
Zone 1Zone 2Zone 3Zone 4
424425426427
(see add. 100)
448449450451
___/______/______/______/___
___/______/______/______/___
42
48
Streamlinesection
Streamlinesection
Data DataDescription DescriptionAddress AddressTAMPER 1 TO 12 TROUBLE CODES: TAMPER 13 TO 24 TROUBLE CODES:
___/______/___
/___/______ ___
Tamper 5Tamper 6Tamper 7N/A
476477478479
___/______/___
/____/______ __
N/AN/AN/AN/A
484485486487
55
57
N/AN/AN/AN/A
480481482483
N/AN/AN/AN/A
488489490491
___/______/___
/___/______ ___
___/______/___
/___/______ ___56
58
N/AN/AN/AN/A
492493494495
___/______/___
/___/______ ___59
Tamper 1Tamper 2Tamper 3Tamper 4
472473474475
___/______/______/______/___
54
DECIMAL PROGRAMMING3 Digit Decimal Value ProgrammingUsed to program addresses 044 to 061. Values entered must contain 3 digits between "000" and "255". ([10] = 0)
Decimal value programming:1) Press [ENTER] + installer code. ([ENTER] key will flash.)2) Enter 3 digit address (044 to 061).3) Current value will be displayed on keypad.4) Enter 3 digit DECIMAL value.5) Repeat from step 2 onward for next address. To exit programming mode press [CLEAR].
044: ___/___/___ (hours) Auto arm time (between "000" and "023")
045: ___/___/___ (minutes) Auto arm time (between "000" and "059")
046: ___/___/___ (days) Auto test report every ? days (between "001" and "255") (000 = disabled)
047: ___/___/___ (hours) Auto test report (between "000" and "023")
048: ___/___/___ (minutes) Auto test report (between "000" and "059")
- 7 -
PG738EX
DECIMAL PROGRAMMING049: ___/___/___ (seconds) Exit delay (factory default 60 seconds)
050: ___/___/___ (seconds) Entry delay 1 (factory default 45 seconds)
051: ___/___/___ (seconds) Entry delay 2 (factory default 45 seconds)
052: ___/___/___ (minutes) Bell cut-off time (factory default 5 minutes)
053: ___/___/___ ( x 15 mSec.) Zone speed (factory default 600 mSec.)
054: ___/___/___ (minutes) Power failure report delay (factory default 30 minutes) (000 = disabled)
055: ___/___/___ ( x 15 minutes) "No movement" report time (factory default 8 hours) (000 = disabled)
056: ___/___/___ PGM timer setting (001 to 127 for seconds and 129 to 255 for minutes) (factory default 5 seconds)Add 128 to desired value in minutes (i.e. for 5 minutes: enter 5 + 128 = 133)
057: ___/___/___ Intellizone delay (in seconds, minimum = 10 seconds) (factory default 48 seconds)
058: ___/___/___ Installer code lock (147 = locked, 000 = unlocked)
059: ___/___/___ (seconds) Programmable delay before alarm transmission (5 to 63 seconds) (000 = disabled)
060: ___/___/___ (seconds) Recent closing delay (000 = disabled)
061: ___/___/___ Future Use
FEATURE SELECT PROGRAMMINGAddresses 062-126. "ON"/"OFF" status of the key lights determines feature selection. In programming mode, enter 3 digit memory address (062 to 126). To save entries, press [ENTER]. To exit programming mode press [CLEAR]. Reset = “OFF” for addresses 062 to 126.
Addresses 080 to 085 for future use.
- 8 -
PG738EX
[5]
[2]
[4]
[2 ]ND
[1]
[3]
[6]
[11]
[8]
[10]
[7]
[9]
[12]
[ ]BYP
[ ]BYP
[ ]MEM
[ ]MEM
[ ]TRBL
[ ]TRBL
- 9 -
stay arm / System A
enabledenabled
Bell squawk on arm/disarmAuto zone shutdown
See "Reporting" table
(1:1.5) Pulse USA(1:2) Pulse Europe
enabledenabledenabled
Auto arm on timeAuto arm on no movement
[5]
[2]PS1/Keyswitch = regular arm
[4] enabledCall back
[2 ]ND
[1]See "TLM" table
[3] enabledPS1/keyswitch arming
[6]
generates only a reportSilent zone/panic generates a silent alarm
[11]
[8]
[10]
[7]Pulse dialingPartitioning
Tone dialing (DTMF)enabled
[9]
[12]
086:KEY
[ ]BYP
[ ]MEM
[ ]TRBL
OFF / ON
only after alarm
audible
enabled
audibleenabled
fire
on zone closure
4 digit
enabled
enabled
enabled
088: OFF / ON
enabledenabled
KEY
no EOL
Report zone restore on bell cut-off
Panic 2Panic 3
Tamper Recognition
Panic 1Automatic event buffer transmission
Always report disarm
Panic 2 silentPanic 1 silent (PS1)
Panic 3 silent
6 digit access codes
Key regular arm[10]Key stay or system A arm[11]
Beep on exit delay
Zones with EOL (1K )Ω
(keys & , )[1] [3] PS1(keys &[4] [6])
(keys & )[7] [9]
TELEPHONE LINE MONITOR
TLM generates trouble onlyTLM disabled
generates an alarm if armedsilent alarm becomes audible
(address , key has to be )086 [9] OFF
KEY
[2 ]ND [1]
OFF OFFONOFF
ONON
OFFON
Address 086, Key [2 ] [1]ND
OFF OFFONOFF
ON
ON
OFF
ON
REPORTING OPTIONS
Regular reportingReporting disabled
Split reporting: AlarmsSystem report
Double reporting
KEY DIALING SEQUENCE (tel. No.)TYPE[11] [12]
1,2,1,2,1,2,1,2, fail to comm.1,1,1,1,1,1,1,1, fail to comm.2,2,2,2,2,2,2,2, fail to comm.1,1,1,1,1,1,1,1, fail to comm.,2,2,2,2,2,2,2,2, fail to comm.
*
On alarm, all reports are made to Tel. #1 until system is disarmed.(Once disarmed, system reports are made to Tel. #2)
*
Address 086, Key [11] [12]
N/A N/A
090:Exclude power failure from trouble display [2 ]ND
OFF / ON
[3]
[1]
enabled
[2] stay / System AAuto arm = regular arm
KEY
[6] tamper follows zone bypass definitionNo tamper bypass
[5]
[4]
enabled
enabled
enabledenabled
[7]
[8]
[9]
[10]
[11]
[12]
FEATURE SELECT PROGRAMMING (continued)(On/off status of key lights determines which feature is selected.)
Audible trouble warning
Duress
Keypad 1 zone supervision
Keypad 2 zone supervision
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
PS1 software versionKeypad software versions prior to
1.14.0 Keypad supervision must be OFF
PS1 software versions onwardKeypad software versions onward
2.04.0 Keypad supervision must be ON
(See Wiring Diagram)
PG738EX
TAMPER / WIRE FAULT DEFINITIONS
Exception: for 24 hour zones the tamper definition will follow theaudible/silent alarm definition of the 24 hour zone.Silent zones will generate a silent alarm.
Tamper supervisiondisabled
Alarm as per individualzone definitions
No alarm, trouble codereported
Audible alarm. Trouble andalarm codes reported
Silent alarm. Trouble andalarm codes reported
Always generate troubleand alarm, audible orsilent as per individualzone definitions
SYSTEM ARMED
**
**
Address 088, Key [10] [11]
*
SYSTEM DISARMED*KEY
[11][10]
OFF OFF
OFF ON
ON OFF
ON ON
Note: Do not use the Intellizone feature and an entry delay for the same zone, otherwise an alarm may occur as a usertries to disarm the system.
KEY ACCESS PROGRAMMINGPrograms features quickly, without entering addresses or section numbers.To activate “key access programming”, press [ENTER], followed by installer, master or user code 1. (Code required depends on the feature you wish to access - see below.) Press the key corresponding to the desired feature. Press [ENTER] or [CLEAR] to exit.
key
[8] Installer test mode (installer code only)In installer test mode, a confirmation beep (intermittent) indicates test is "on", a "rejection" beep (long) indicates test is "off". The bell will squawk during walk testing to indicate opened, functional zones.
[9] "Auto arming" time program (all 3 codes)Key [9] flashes. Enter two digits (00 to 23) for hours + 2 digits (00 to 59) for minutes.
[MEM] "Panel time" and clear "trouble 8" (all 3 codes)Key [MEM] flashes. Enter two digits (00 to 23) for hours + 2 digits (00 to 59) for minutes.
[BYP] Test report (all 3 codes)Reporting is enabled at address 086, keys [11] , [12] . A value must be entered at address 512, and both telephone and account numbers must be programmed.
[TRBL] Call Espload via telephone (all 3 codes)Panel identifier and PC password (addresses 004-007) and computer telephone number (addresses 008-015) must be programmed.
[AWAY] Answer Espload (all 3 codes)This feature is available when using the ADP-1 adapter. In Espload, "blind dial" must be activated in "modem setup" section, and panel phone number programmed (works also without ADP-1).
[STAY] Cancel communication attempts (master code and user 1 can only stop calls to Espload)Until next reportable event (installer code - all communications)
When communicating with Espload, it is impossible to enter programming mode.
PG738EX
- 10 -
The system hardware will recognize the following zone conditions:Note: Keypad zones always use (1K OHM) EOL resistor.
SINGLE ZONE CONNECTIONS
ZONE connection, without EOL resistor (N.C. contacts)address 088, key [MEM] = "on"
key [10] = "off " (reset)key [11] = "off " (reset)
N.C. contacts see Figure 1
ZONE connection, with EOL resistor (N.C. and N.O. contacts)address 088, key [MEM] = "off" (reset)
key [10] = "off " (reset)key [11] = "off " (reset)
N.C. and/or N.O. contacts, see Figure 2
ZONE connection, without EOL resistor, with tamper recognition (N.C. contacts)address 088, key [MEM] = "on"
key [10] = key [11] =
Tamper transmits separate code, see Figure 3
ZONE connection, with EOL resistor, with tamper recognition, and with wire fault (short circuit) recognition (N.C. contacts)address 088, key [MEM] = "off "
key [10] = key [11] =
Tamper/wire fault transmits separate code, see Figure 4
- 11 -
PG738EX
See "Tamper/wire Fault Definitionsand Options"
See "Tamper/wire Fault Definitionsand Options"
ESPRIT 738 EXPRESS CONNECTION DIAGRAMS
ESPRIT 738 EXPRESS WIRING DIAGRAM
BLK
GRN
YEL
RED
To cabinet andgrounding rod
-+
BLACK
Charging and battery test LED(every 60 seconds)
RED
RECHARGEABLEBATTERY
SIREN
BELL
-+
TRANSFO
A.C.POWER
16.5VAC 40VA
Address 100Zone 3 = Fire zone if zonedefinition is "24 hour".
- +
BR
N
GR
Y
RE
D
GR
N
RJ31XCA 38A
BELL OUTPUTwill shut downif currentexceeds 3A.
UL/ULC12VDC / 7AH
UL: K12 model T16 V4OULC: Frost model FTC 1637
AUX POWER 400mA max.250mA max. for 24 hr. standby.
Aux power will shut down if current exceeds 1A.
To connect additional wiring to auxiliary power, usethe red (+) and black (-) keypad connectors.
Caution: Disconnect batterybefore replacing fuse.
"TLM" LED: Short flash = OK OFF = DisabledLong flash = Fault Constant = On Line
UL/ULCWheelock
46T-12
Warning:Disconnecttelephone linebefore servicing.
N.C.N.O. 1KEOL
Ω
PS1
ZONE8 or 9
KEYSWITCH CONNECTION
KEYSWITCHKYPD GRN
KYPD BLK
220Ω
S E C U R I T Y S Y S T E M S
780 Industrial Blvd., St-Eustache, Montreal, Quebec, Canada J7R 5V3 Fax: (514) 491-2313 http://www.paradox.caParadox Security Systems Graphic Dept
PRINTED IN CANADA
*
N.C.
ZONE8 or 9
N.O.
1KEOL
Ω
*
1KEOL
ΩN.C. N.C.
ZONE 8 ZONE 9
PS1 software versionKeypad software versions prior to
1.14.0 Keypad supervision must be OFF
PS1 software versions onwardKeypad software versions onward
2.04.0 Keypad supervision must be ON
*
(See Address , key )090 [11] [12]
FIRE RESETTo program PGM1 to conduct 4 second smoke detector reset when
and are pressed simultaneously:[ ] [ ]CLEAR ENTER
Address = (first digit)Address =
039 [ ]040 [5] [10]
BYP Address =Address =
042 [2 ] [6]056 [10] [10] [4]
ND
FIRE ALARM ZONE CONNECTIONS* PGM maximum 50mA
Smoke detectorpower supervision
relay, 12VDC
COMSmokedetector
Smokedetector
PGMZ3
AUX+
1KEOL
Ω
+
+
--
Smoke detector must be 4 wire latching -UL Falcon model 5454, ULC BRK 2412.Power supervision relay model MR3-UL.
*
P R DOXRMED RE DY
MAX 5per system
For resistor values,refer to 639/640installation manuals.
Smoke and heat detectors
1KEOL
Ω
N.O. contacts
GROUND START CIRCUIT
RNG
WHT
BLK RED
YEL
MR3-UL
+AUXPGM
WHT
BLK RED
MR3-UL
+AUXPGM
PGM OUTPUT RELAY
YELBRN
COM N.C. N.O.
Four pin connectorcan be used forquick installation ofan Esprit keypad.
Service Keypad
+ AUX - GRN YEL
Warning: Improper connectionmay result in damage to thesystem.
Keyswitch can be used inparallel with keypad (Not onUL systems).
BE
LLR
ELA
YO
PT
ION
RESETJUMPER
DIALER
BATT5 AMP
+
+
+
+
+
SERIALOUTPUT
SERVICEKEYPAD
COMAUX --+
BELLPG1AC PG2N.C. N.0. C CCC1 2 3 4 5 6 7GRN YEL T - 1R - 1 TIPRING
738 EXPRESSESPRIT
PARADOXSECURITY
SYSTEMS
+ +
BATT
KEYPAD639/640
MAX 2 per system
The 640 keypad canbe used with thepanels but will notdisplay correct eventlist codes.
KEYPAD616/626/633
MAX 5 per system
Recommended