Honeywell Subject to change EN0H-2608GE25 R0311
HyBO-HIUHydraulic Interface Unit
PRODUCT DATA
Overview The HIU (Hydraulic Interface Unit) series consist of the following products: • HIU Hydraulic Interface Unit (this datasheet) • HyBo Metering Box (see separate datasheet)To fullfil the plant requirements several options are available for each product range .
ApplicationThe HIU (Hydraulic Interface Unit) is designed to be applied in central heating systems for multi family dwellings where the domestic hot water is produced directly in the apartment.The typical heating systems where HIU can guarantee the maximum performances are designed based on the following criteria and principles:• High design delta-T conditions: emission terminals such as
radiators are designed considering a high water ΔT (for example 30-40or 50K).
• Minimise design water flow: high delta-T conditions allow minimising nominal water flow and a more flexible distribution system
• Contain pipeline dimensions: with minimised water flow it is possible to contain pipeline dimensions, containing cost and simplify installation
• Reduce insulation cost: smaller pipeline dimensions effect cost of insulation
• Minimise distribution pump dimension/consumption: a low flow system allows reduction of the pump size. Also electricity consumption is reduced when pipelines are designed for reducing total system pressure drop
• Facilitate balancing: a low flow system combined with low pressure drop pipelines facilitate balancing due to low pres-sure drop from the main risers of the plant
• Guarantee high performance for heat generation system: low return temperature conditions guarantee best performance for main generation system such as condensing boiler, district heating system, heat pump systems, etc.
• Guarantee heat and water metering accuracy high ΔT allow to reduce the measures errors (ref EN1434, UNI10200)
A: Apartment B: Room thermostat C: HyBo – Hydraulic inter- face Unit (HIU)D: Technical Space1. Centralize heat generator (cond boiler etc)2. water softener 3. Apartment heating plant4. Sanitary water plant5. TRV valve
HYBO-HIU HYDRAULIC INTERFACE UNIT
EN0H-2608GE25 R0311 2 Honeywell Subject to change
SpecificationsOS No. HIU……. HIU……..Option Ultrasonic options Mechanical optionsHeating / Exchanger Primary CircuitKind of fluid water of quality to VDI 2035 Max. temperature 90°CMax. operating pressure 6 barHeating min/max flow rate 0,006 m3/h - 3 m3/h 0,015 m3/h - 3 m3/hHeating nominal flow rate 1,5 m3/hWater linesKind of fluid waterMax. setting temperature 90°CMax. operating pressure 6 barMinimal flow rate 0,030 m3/h 0,020 m3/h Max. flow rate 3 m3/hDHW / Exchanger Secondary CircuitKind of fluid waterMax. setting temperature 90°CMax. operating pressure 6 barMinimal flow rate 0,24 m3/h Max. flow rate 3 m3/h PipesMaterial copperSize Ø18 x 1 mmHydraulic connectionsMaterial brassSize G 3/4"Metal frameMaterial galvanized sheet 15/10Electrical SupplyTension 230 V ±10%Frequency 50 HzMax. power consumption 7 WIP protection 40Ambient operationInstallation indoorTemperature range 5-55°CHumidity range 25-85%Motorized ValveOperation time ON/OFF type 10 secOperation time Modulating type 15 secFeaturesweight - Basic Unit 15 kgweight - in wall unit (Basic+template) 27 kgweight- wall hanging unit 23 kg
HYBO-HIU HYDRAULIC INTERFACE UNIT
Honeywell Subject to change 3 EN0H-2608GE25 R0311
Features• High accuracy ultrasonic or multijet heatmeter avoids
customer complaints and guarantees correct measurement for years (MID class 2)
• M-Bus ready heatmetering system: all versions are equipped with M-Bus devices ready for connection to M-Bus network reducing site effort
• Electronic watermeter with M-Bus output: use multijet tech-nology. Allow to measure flow, change reading date and simplify operation of commissioning and reading. This allows reduction of commissioning time by reading DHW water flow for each apartment • Insulated version to reduce heat losses
• Configuration options available
DesignThe Hydraulic Interface Unit consists of: • Shutoff valves for inlets and outlets (1)• Watermeter with M-bus interface (2 + 3)• Flow sensor (4)• Heatmeter with M-bus interface and MID approval (5)• Heatmeter sensor (6)• Flow sensor (7)• Circulation balancing valve (8)• Heat exchanger for production of domestic hot water (9)• Motorised modulating valve for control of hot water produc-
tion (10)• Motorised valve (on/off) for shutoff of central heating supply
(11)• Temperature sensor (12)• Strainer (13)• Non return valve for circulation loop (15)• Controller (16)• Balancing valve (17, optional)• Non return valve (18)• Piping• Baseplate for installation on or in the wall• Optional cabinet
NOTE: Numbers in brackets refer to Fig. 1
Materials• Baseplate and optional cabinet made of sheet steel. Cabinet
painted white according to RAL9010• Heat exchanger made of stainless steel, copper and copper
alloy • Pipes made of copper• Valve housings, fittings, union nuts and other components
made of brass or other copper alloys• Housings of electronic components, e.g. actuators,
controller and energy integrators, made of plastic
FunctionThe HIU Hydraulic Interface unit provides the following main functions: • Heat and water M-Bus metering system: the unit is equipped
with an ultrasonic or mechanical heatmeter with M-Bus communication output
• Domestic Water Production: the unit is equipped with a heat exchanger, electronic board, modulating valve. The PID algorithm guarantee safe, quick and efficient DHW produc-tion.
• Balancing: the unit is equipped with a Honeywell Kombi-3-plus in order to provide the right commissioning of the heating system
• Heating system control: the unit is equipped with a motorised valve that receives a command from an external thermostat (optional) will allow to open or close the heating circuits
Hydraulic scheme for the HIU Hydraulic Interface unit (full optional version):
Fig. 1. Functional schemeA Cold water supply, pipe dimension 3/4“
B Cold water supply, pipe dimension 3/4“
C Central heating supply , pipe dimension 3/4“
D Central heating return , pipe dimension 3/4“
E Potable water circulation return, pipe dimension 3/4“
F Appartment warm potable water supply , pipe dimen-sion 3/4“
G Appartment cold potable water supply , pipe dimension 3/4“
H Appartment radiator loop supply , pipe dimension 3/4“
I Appartment radiator loop return , pipe dimension 3/4“
A B C D
E GF H
HYBO-HIU HYDRAULIC INTERFACE UNIT
EN0H-2608GE25 R0311 4 Honeywell Subject to change
SpecificationsMounting optionsHIU Hydraulic Interface unit is design to be installed inside the building. The following indications must be respected: • Install the product in a vertical wall able to support the weight
in operating conditions• Hydraulic connections: primary circuit from the top, secon-
dary circuit to the apartment from the bottom (see hydraulic schema)
• Install the product in place protected from frost The HIU Hydraulic Interface unit can be installed in the following ways:• Basic Version: suitable for building were a dedicated space
has been reserved. (criteria for designing the space: space for maintenance avoid water leakage influence different critical components etc)
• Wall hanging: suitable for retrofitting wall hanging boilers in old buildings or for new buildings
• Template: in wall installation
Product options The HIU Hydraulic Interface unit product options are: • Installation options
• Basic• Wall hanging
• Heat exchanger:• Standard• High surface: for condensing boilers
• Additional water line: • With: An additional electronic water meter is installed to
allow counting the water consumption only for domestic hot water preparation. This option is usually used to mini-mize the water softener dimensions for the entire building.
• Without: an electronic water meter is installed to measure the total sanitary water consumption (cold and hot)
• Balancing valve option: with or without. • Insulation: with or without• Heatmeter type:
• Multijet EW447M1200 • Ultrasonic EW7730K1200
• Watermeter type:• Multijet EW743M1200 (always installed in combination
with EW447M1200) • Singlejet EW148P1201 (always installed in combination
with EW7730K1200)
• Template: must be order separately. Template is equipped with flushing pipes, ball valves and carton protection for the constructions work.
• Frame: must be ordered separately.
Fig. 2. Basic Version Fig. 3. Wall hanging
Fig. 4. In wall installation
Appartement 1 Appartement 2
Fig. 5. Spare space dimensions
Fig. 6. M-Bus configuration Fig. 7. M-Bus configuration
446
890
MJ
M-BUS
MJE MJE US
M-BUS
SJ SJ
HYBO-HIU HYDRAULIC INTERFACE UNIT
Honeywell Subject to change 5 EN0H-2608GE25 R0311
Heat Exchanger OptionsStandard
Fig. 8. Primary circuit - Ultrasonic standard heat exchanger, kv = 1,81 m3/h
INLET TEMP. PRIMARY CIRCUIT
COLD SANITARY WATER FLOW
PRIMARY CIRCUIT FLOW OUTLET TEMP. PRIMARY CIRCUIT
HEAT POWER
75 °C 0,5 m3/h 0,45 m3/h 36 °C 20 kW
0,75 m3/h 0,78 m3/h 42 °C 30 kW
1,0 m3/h 1,25 m3/h 47 °C 41 kW
70 °C 0,5 m3/h 0,55 m3/h 38 °C 20 kW
0,75 m3/h 1,0 m3/h 43 °C 30 kW
0,95 m3/h 1,5 m3/h 48 °C 39 kW
65 °C 0,5 m3/h 0,7 m3/h 40 °C 20 kW
0,75 m3/h 1,3 m3/h 45 °C 30 kW
0,8 m3/h 1,5 m3/h 46 °C 32 kW
10 2 4 5 6 7 8 100kg/hFlow rate
9
0.025 0.050.0028 0.010 0.50l/sec
3 2 4 5 6 7 8 100093 2 4 5 63 7 8 100009 2
0.10 0.25 2.51.0
1000
100
23
45
67
89
1000
02
34
56
Pres
sure
loss
10Pam
bar
HYBO-HIU HYDRAULIC INTERFACE UNIT
EN0H-2608GE25 R0311 6 Honeywell Subject to change
Fig. 9. Primary circuit - Mechanic standard heat exchanger, kv = 1,66 m3/h
Fig. 10. Heating circuit - ultrasonic and balancing valve version, kv = 2,82 m3/h
10 2 4 5 6 7 8 100kg/hFlow rate
9
0.025 0.050.0028 0.010 0.50l/sec
3 2 4 5 6 7 8 100093 2 4 5 63 7 8 100009 2
0.10 0.25 2.51.0
1000
100
23
45
67
89
1000
02
34
56
Pres
sure
loss
10Pam
bar
10 2 4 5 6 7 8 100kg/hFlow rate
9
0.025 0.050.0028 0.010 0.50l/sec
3 2 4 5 6 7 8 100093 2 4 5 63 7 8 100009 2
0.10 0.25 2.51.0
1000
100
23
45
67
89
1000
02
34
56
Pres
sure
loss
10Pam
bar
HYBO-HIU HYDRAULIC INTERFACE UNIT
EN0H-2608GE25 R0311 7 Honeywell Subject to change
Fig. 11. Heating circuit - ultrasonic version, kv = 3.14 m3/h
Fig. 12. Heating circuit - mechanic version, kv = 2.54 m3/h
10 2 4 5 6 7 8 100kg/hFlow rate
9
0.025 0.050.0028 0.010 0.50l/sec
3 2 4 5 6 7 8 100093 2 4 5 63 7 8 100009 2
0.10 0.25 2.51.0
1000
100
23
45
67
89
1000
02
34
56
Pres
sure
loss
10Pam
bar
10 2 4 5 6 7 8 100kg/hFlow rate
9
0.025 0.050.0028 0.010 0.50l/sec
3 2 4 5 6 7 8 100093 2 4 5 63 7 8 100009 2
0.10 0.25 2.51.0
1000
100
23
45
67
89
1000
02
34
56
Pres
sure
loss
10Pam
bar
HYBO-HIU HYDRAULIC INTERFACE UNIT
EN0H-2608GE25 R0311 8 Honeywell Subject to change
High Surface
Fig. 13. Primary circuit - ultrasonic large surface heat exchanger, kv = 1,92 m3/h
INLET TEMP. PRIMARY CIRCUIT
COLD SANITARY WATER FLOW
PRIMARY CIRCUIT FLOW
OUTLET TEMP. PRIMARY CIRCUIT
HEAT POWER
75 °C 0,6 m3/h 0,4 m3/h 18 °C 26 kW
0,9 m3/h 0,62 m3/h 20 °C 39,5 kW
1,14 m3/h 0,8 m3/h 21 °C 50 kW
70 °C 0,6 m3/h 0,45 m3/h 19 °C 26 kW
0,9 m3/h 0,7 m3/h 21 °C 39,5 kW
1,14 m3/h 0,92 m3/h 23 °C 50 kW
65 °C 0,6 m3/h 0,52 m3/h 21 °C 26 kW
0,9 m3/h 0,83 m3/h 24 °C 39,5 kW
1,14 m3/h 1,1 m3/h 25 °C 50 kW
10 2 4 5 6 7 8 100kg/hFlow rate
9
0.025 0.050.0028 0.010 0.50l/sec
3 2 4 5 6 7 8 100093 2 4 5 63 7 8 100009 2
0.10 0.25 2.51.0
1000
100
23
45
67
89
1000
02
34
56
Pres
sure
loss
10Pam
bar
HYBO-HIU HYDRAULIC INTERFACE UNIT
Honeywell Subject to change 9 EN0H-2608GE25 R0311
Fig. 14. Primary circuit - mechanic high surface heat exchanger, kv-value 1.74 m3/h
Fig. 15. Mechainc balancing - kv-value 2.36 m3/h
10 2 4 5 6 7 8 100kg/hFlow rate
9
0.025 0.050.0028 0.010 0.50l/sec
3 2 4 5 6 7 8 100093 2 4 5 63 7 8 100009 2
0.10 0.25 2.51.0
1000
100
23
45
67
89
1000
02
34
56
Pres
sure
loss
10Pam
bar
10 2 4 5 6 7 8 100kg/hFlow rate
9
0.025 0.050.0028 0.010 0.50l/sec
3 2 4 5 6 7 8 100093 2 4 5 63 7 8 100009 2
0.10 0.25 2.51.0
1000
100
23
45
67
89
1000
02
34
56
Pres
sure
loss
10Pam
bar
HYBO-HIU HYDRAULIC INTERFACE UNIT
Honeywell Subject to change 10 EN0H-2608GE25 R0311
Water line options
Fig. 16. Treated water line - ultrasonic and mechanical version, kv = 1,47 m3/h
Fig. 17. Secondary circuit - ultrasonic and mechanical version, kv = 1,24 m3/h
10 2 4 5 6 7 8 100kg/hFlow rate
9
0.025 0.050.0028 0.010 0.50l/sec
3 2 4 5 6 7 8 100093 2 4 5 63 7 8 100009 2
0.10 0.25 2.51.0
1000
100
23
45
67
89
1000
02
34
56
Pres
sure
loss
10Pam
bar
10 2 4 5 6 7 8 100kg/hFlow rate
9
0.025 0.050.0028 0.010 0.50l/sec
3 2 4 5 6 7 8 100093 2 4 5 63 7 8 100009 2
0.10 0.25 2.51.0
1000
100
23
45
67
89
1000
02
34
56
Pres
sure
loss
10Pam
bar
HYBO-HIU HYDRAULIC INTERFACE UNIT
Honeywell Subject to change 11 EN0H-2608GE25 R0311
Fig. 18. Secondary circuit - ultrasonic and mechanical version, kv = 1,24 m3/h
10 2 4 5 6 7 8 100kg/hFlow rate
9
0.025 0.050.0028 0.010 0.50l/sec
3 2 4 5 6 7 8 100093 2 4 5 63 7 8 100009 2
0.10 0.25 2.51.0
1000
100
23
45
67
89
1000
02
34
56
Pres
sure
loss
10Pam
bar
HYBO-HIU HYDRAULIC INTERFACE UNIT
EN0H-2608GE25 R0311 12 Honeywell Subject to change
Metering OptionsConfiguration 1: Mechanical heatmeter with multijet watermeters for warm and cold water: • Heatmeter: Honeywell EW447M1200 – see separate datasheet EW447-452 Mechanical Heatmeters• Watermeters: Honeywell EW743M1200 – see separate datasheet EW743 Series Potable Watermeters
Heat Meter Domestic Hot Water Meter Cold Water MeterHoneywell Os. Number EW447M1200 EW743M1200 EW743M1200
Type MultiJet MultiJet MultiJet
MID Approval MID (DE-07-MI004-PTB030) MID (DE-07-MI001-PTB008) MID (DE-07-MI001-PTB008)
MID Accuracy Class 2
Metereoloical Class - B B
Battery life time 12 years 10 years 10 years
Maximum flow rate (qs) 3 m3/h 3 m3/h 3 m3/h
Nominal flow rate (qp) 1,5 m3/h 1,5 m3/h 1,5 m3/h
Minimum flow rate (qi) 15 l/h 20 l/h 20 l/h
Starting flow rate 4 l/h 4 l/h 4 l/h
Δp at qp 243 mbar 243 mbar 243 mbar
Interfaces Optical ZVEI, M-BUS Optical ZVEI, M-BUS Optical ZVEI, M-BUS
Mounting position In any position In any position In any position
Adjustable reading date for billing YES YES YES
Measuring process direct electronic impeller scanning
direct electronic impeller scanning
direct electronic impeller scanning
Ambient operating temperature 0…55°C 0…55°C 0…55°C
Operating pressure PN16 PN10 PN10
Ambient class EN1434 class^ C - -Protection class IP54 IP54 IP54
Temperature sensor type Pt500 - -
Measuring cycle 32s - -
Min. temperature difference 3k - -
Starting difference temperature 0,25k - -
MJ
M-BUS
MJE MJE
qi Q2 qp qs-7-6-5-4-3-2-101234567
Flow rate [m3/h]
Erro
r [%
]
Q1 Q2 Q3 Q4-7-6-5-4-3-2-101234567
Flow rate [m3/h]
Erro
r [%
]
HYBO-HIU HYDRAULIC INTERFACE UNIT
Honeywell Subject to change 13 EN0H-2608GE25 R0311
Configuration 2: ultrasonic heatmeter with singlejet watermeters for warm and cold water:• Heatmeter: Honeywell EW7730K1200 – see separate datasheet EW773 Series Ultrasonic Heatmeters• Watermeters: Honeywell EW148P1201 – see separate datasheet EW147/EW148 Potable Watermeters
Heat Meter Domestic Hot Water Meter Cold Water MeterHoneywell Os. Number EW7730K1200 EW148P1201 EW148P1201
Type Ultrasonic Single jet Single jet
MID Approval MID (DE-10-MI004-PTB013) - -
MID Accuracy Class 2
Metereoloical Class - A/B•H A/B•H
Battery life time 12 years - -
Maximum flow rate (qs) 3 m3/h 3 m3/h 3 m3/h
Nominal flow rate (qp) 1.5 m3/h 1.5 m3/h 1.5 m3/h
Minimum flow rate (qi) 6 l/h 30 l/h -horizontal 30 l/h -horizontal
Starting flow rat [l/h] 2.5 l/h 8 l/h - horizontal 8 l/h - horizontal
Δp at qp 75 mbar 190 mbar 190 mbar
Interfaces Optical ZVEI, M-BUS,. Radio Pulse output (10lt/pulse) Pulse output (10lt/pulse)
Mounting position In any position
Adjustable reading date for billing YES
Measuring process direct electronic impeller scanning
Ambient operating temperature 0…55°C
Operating pressure PN16 PN10 PN10
Ambient class Class E1 + M1
Protection class IP54 IP55 IP56
Temperature sensor type Pt100 - -
Measuring cycle 32s - -
Min. temperature difference 3k - -
Starting differnce temperature 0.125k - -
US
M-BUS
SJ SJ
-7-6-5-4-3-2-101234567
QminB QtB Qn Qmax-7-6-5-4-3-2-101234567
Flow rate [m3/h]
Erro
r [%
]
HYBO-HIU HYDRAULIC INTERFACE UNIT
EN0H-2608GE25 R0311 14 Honeywell Subject to change
M-Bus network• Various M-Bus accessories available• Hydroset software: the basic version of the reading software
can be downloaded at the following address: http://prod-ucts.ecc.emea.honeywell.com/europe/….
• M-Bus cable: in most cases a standard telephone cable is used which is a twisted pair wire with a diameter of 0.75mm2 each (2 x 0.75mm2). This type of cable should be used for the main wiring. For wiring from the main wiring to the meters (last 1…5m to the meter) a cable with smaller diameter can be used
Template description
Electrical Specifications• Mains connection: min. 3 x 1.5mm2
• Room thermostat: 2 x 0.75mm2
• M-Bus connection: 2 x 0.75mm2
OS-No.Template box for LDHW Cold Boiler model without treated water line
HIU01
Template box for LDHW Cold Boiler model with treated water line
HIU02
1 Bypass pipe (temporary)2 Isolation valve3 Metal temporaty lida Outlet from centralized systemb Return to centralized systemc Hot sanitary water inletd Cold sanitary water inlete Heating outlet to housing unitf Heating return from housing unitg Hot sanitary water outleth Cold sanitary water outlet
927 88
9,4
161469
429
46,5 60 215 55 52,5
38
1
2
2
894
446
3
3
a b c d
e f g h
OS-No.Frame and Door for Hybo FD00
Frame and Door for Hybo-Insulated FD00I
1 Door2 Frame3 Lock
Fig. 19. Wiring scheme for 230V option
2
3
933
480,5 15
933
878
425,5
1
LV 230 50Hz
T.A.M
-BUS
N
HYBO-HIU HYDRAULIC INTERFACE UNIT
Honeywell Subject to change 15 EN0H-2608GE25 R0311
Dimensions
NOTE: Dimensions of standard and special version are identical
Ordering InformationTable 1. Selection chart – standard version to replace traditional boilers
Fig. 20. In wall unit dimensions Fig. 21. On wall unit dimensions Fig. 22. Cabinet dimensions
Shape Water line BV Insulation Heatmeter type OS-No.Basic Wallhung Multi Jet Ultrasonic
• • • HIU1YBN0MS• • • HIU1YBN0US• • • • HIU1YBN1MS• • • • HIU1YBN1US• • • • HIU1YBS0MS• • • • HIU1YBS0US• • • • • HIU1YBS1MS• • • • • HIU1YBS1US• • HIU1NBN0MS• • HIU1NBN0US• • • HIU1NBN1MS• • • HIU1NBN1US• • • HIU1NBS0MS• • • HIU1NBS0US• • • • HIU1NBS1MS• • • • HIU1NBS1US
• • • HIU2YBN0MS• • • HIU2YBN0US• • • • HIU2YBN1MS• • • • HIU2YBN1US• • • • HIU2YBS0MS• • • • HIU2YBS0US• • • • • HIU2YBS1MS• • • • • HIU2YBS1US• • HIU2NBN0MS• • HIU2NBN0US• • • HIU2NBN1MS• • • HIU2NBN1US• • • HIU2NBS0MS• • • HIU2NBS0US• • • • HIU2NBS1MS• • • • HIU2NBS1US
HYBO-HIU HYDRAULIC INTERFACE UNIT
EN0H-2608GE25 R0311 16 Honeywell Subject to change
Table 2. Selection chart – version with high surface heat exchanger to replace condensing boilers
Shape Water BV Insulation Heatmeter type OS-No.Basic Wallhung Multi Jet Ultrasonic
• • • HIU1YBN0MC• • • HIU1YBN0UC• • • • HIU1YBN1MC• • • • HIU1YBN1UC• • • • HIU1YBS0MC• • • • HIU1YBS0UC• • • • • HIU1YBS1MC• • • • • HIU1YBS1UC• • HIU1NBN0MC• • HIU1NBN0UC• • • HIU1NBN1MC• • • HIU1NBN1UC• • • HIU1NBS0MC• • • HIU1NBS0UC• • • • HIU1NBS1MC• • • • HIU1NBS1UC
• • • HIU2YBN0MC• • • HIU2YBN0UC• • • • HIU2YBN1MC• • • • HIU2YBN1UC• • • • HIU2YBS0MC• • • • HIU2YBS0UC• • • • • HIU2YBS1MC• • • • • HIU2YBS1UC• • HIU2NBN0MC• • HIU2NBN0UC• • • HIU2NBN1MC• • • HIU2NBN1UC• • • HIU2NBS0MC• • • HIU2NBS0UC• • • • HIU2NBS1MC• • • • HIU2NBS1UC
HYBO-HIU HYDRAULIC INTERFACE UNIT
Honeywell Subject to change 17 EN0H-2608GE25 R0311
Accessories
Heat meter accessories
Honeywell wireless individual room control system evohome including antenna BDR91 and table support ATF100
ATP921G1034
Honeywell thermostat
Thera-4 Classic T3001W0
Thera-4 Design T2001W0T2021W0
Thera-200 Design T4021T4221T4321T4111
Bluetooth optohead EWA3001799
Hydro-Center 25 SolarM-Bus master for max. 25 M-Bus meters, built in data logger with 2 MByte memory, for 12V solar power supply
EW535M0055
Hydro-Port PulseConverter for metering devices with pulse output to M-Bus, 2 pulse inputs
EW535M0056
Hydro-Port Analog Converter for metering devices, with analogue 0(4)..20 mA interface to M-Bus, 2 analogue inputs, 1 analogue output, 1 input for PT tempera-ture probe
EW535M0057
Hydro-Port ControlM-BUS relay module with digital state inputs. 2 bistable relay outputs and 2 digital state inputs
EW535M0059
Hydro-Center 25 M-Bus master for max. 25 M-Bus meters
EW535M0093
Hydro-Center 25 MemoryM-Bus master for max. 25 M-Bus meters, built-in data logger with 2 MByte memory
EW535M0094
M-Bus Receiver 868MHzHydro-Radio 868 receiver for stationary installation with Izar-Center 60/120/250 interface
EW535M0131
GSM Modem for Hydro-CenterGSM modem for Hydro-Center incl. accessories
EW535M0147
Izar-Center 60M-Bus master for max. 60 M-Bus meters
EW535M5777
Izar-Center 120M-Bus master for max. 120 M-Bus meters
EW535M5778
Izar-Center 250M-Bus master for max. 250 M-Bus meters
EW535M5780
Izar-Center 60Memory M-Bus master for max. 60 M-Bus meters, data logger with 256 MByte memory
EW535M5781
Izar-Center 120Memory M-Bus master for max. 120 M-Bus meters, data logger with 256 MByte memory
EW535M5782
Izar-Center 250Memory M-Bus master for max. 250 M-Bus meters, data logger with 256 MByte memory
EW535M5783