Product Data Document225DS-25h / D301300X012April 2011 - Page 1
Website: www.EmersonProcess.com/Remote
Remote Automation Solutions
Bristol 3808 MVT Multivariable TransmitterModel 3808-30A With DP/P/T Variables
Featuring:Now featuring 4000 psi pressure range
Excellent measurement performance over the full range of operating pressure and temperature conditions
Extremely low power consumptionperfect for remote sites with battery and solar power systems
Bilingual Networking via BSAP and Modbus protocols with RS 485 interface
Two versions: RS485 with RS232 port for configurationorAnalogOutputwithFSKsignal
Intrinsically safe and explosion proof for operation in Class I Division 1 hazardous areas
Bidirectional DP measurement
DP/P wet end sensor assembly is independent of the top end assembly
Introduction
The Bristol 3808 MVT is Emerson Process Man-agements answer to industry demands for a trans-mitter with high reliability, high performance over real world pressure and temperature conditions, ease in use, networkability and very low power consumption. The 3808 MVT has been designed to provide the highest value in terms of all user consid-erations, including purchasing, installation, opera-tion and maintenance.
To maximize measurement accuracy, the 3808 com-bines a wet end with a low reference uncertainty of 0.075% URL, with a design that minimizes effects of pressure and temperature over the full range of operating conditions.
Forremotesitessuchasthoseintheenergyand
The Bristol 3808 MVT Multivariable Trans-mitter features accurate measurement of
DP, gauge pressure and temperature.
water industries, power consumption has been a key consideration. Costs of batteries and solar panels are proportional to current draw and many users are surprised at the capital expenses associ-ated with electronics, which have not been designed to conserve power. The sophisticated design employed by the 3808 MVT keeps current draw well below 2 mA and with a power source as low as 5 Vdc.
Forremotesites,powerbudgetingisoftenverytight. Since the power consumption is so low, the 3808 MVT can even be added to existing sites, which were designed with no extra capacity for power.
While the Bristol Synchronous and Asynchronous (BSAP) protocol ensures compatibility with Emerson measurement and SCADA systems, Modbus pro-vides compatibility with a wide variety of controllers, flowcomputers,RTUdevicesandSCADAsystemsfrom numerous suppliers.
Product Data Document225DS-25h / D301300X012April 2011 - Page 2 Bristol Multivariable Transmitter
Remote Automation SolutionsWebsite: www.EmersonProcess.com/Remote
Functionality OverviewEmersons Bristol 3808 MVT provides the following basic operations:
Conversion of sensor readings from the wet end DP/P sensor assembly into accurate floatingpointpressurevaluesforDPandP.Conversion calculations utilize correction coefficientscontainedinthesensorassemblyand are performed once per second for each process variable
Conversion of raw readings from an on-board A/DintoanaccuratefloatingpointRTDvalue.RTD conversions are performed once per second
Up to 19200 baud, 2-wire RS-485 serial communicationsinterface,ora1200baud,FSKmodem interface via the 4-20ma current loop for Network communication
Local RS-232 serial communications interface fixedat19200baud.(ConnectingtotheRS-232communications interface disables the RS-485 communications
A subset of the Emerson BSAP RDB and Peer-to-Peer communications interface:
CompletesetofUser/HostInterfacefunctionsforConfiguration,Calibration,and Data Collection
Floatingpointvaluesreturnedindividually,orinpre-definedLists
FloatingpointvaluesavailableforDP/GP,SP, T, Sensor Temperature, and Error Status
Floatingpoint,Logical,orStringvaluesalso available for other ST3808 user configurationparameters
Optional,4-to-20mAAnalogOutput:
LinearorSquareRootMode
ReversibleOutputAction
MaybecontrolledexternallytoprovidearemoteAO
Optional,on-boardLCDdisplaywithDP,PandT information
Physical Overview
Service:Flow,level,pressure,temperaturemea-surementsforliquidsandgases.
DiaphragmMaterial:316SSorHastelloyC
FlangeMaterial:316SSorHastelloyC
FlangeBoltMaterial:316SS
FillMedia:DC200SiliconeOil
ProcessConnections:NPTonflanges1/2NPTwith connection blocks.
Electrical Connections: NPT Conduit Connection
Housing:LowCopperAluminumwithepoxypaintNEMA 4X explosion proof.
Local indication: 4--Digit LCD display linear or squarerootinengineeringunits.
RTD sensor: 3-wire platinum 100-ohm per DIN 43760 25 feet max.
User connections: 10-terminal (2-rows) tri-barrier strip for + power, -power, RTD +, RTD-, RTD-, TXD, and RXD.
Power Supply Information
OperatingVoltageRange:542Vdc
Current Draw:
With RS 485: Less than 2 mA (typically 900 mA)
WithFSK,butwith420mAoutputdisabled:Lessthan 3.2 mA
Turn-on time:
Measuredinputvariableswillbewithinspecifica-tions less than two seconds after power is applied to the 3808 MVT.
Product Data Document225DS-25h / D301300X012April 2011 - Page 3 Bristol Multivariable Transmitter
Remote Automation SolutionsWebsite: www.EmersonProcess.com/Remote
Accuracy and Performance Specfications
Allspecificationsareforthedigital,floating-pointsignal.
Differential Pressure and Static Pressure
Combined effects of nonlinearity, nonrepeatability and hysteresis at reference pressure and over the operating temperature range:
DP and SP linear mode: 0.075% of Calibrated Span or 0.015% of URL, whichever is greater. 0.035% of span or 0.015% of URL for 1000 psi static pressure only, whichever is greater.
Temperature effect on Static and Differential pres-sure:
0.21%URL maximum combined shift of zero and span with an ambient temperature change of 60C (108F).0.17%URLmax.for1000psistaticpres-sure range.
StaticPressureEffectsOnDifferentialPressure:
Zero error: 0.1% URL, for a change in static pres-sure of 1000 psi
Span error: 0.1% reading, for a change in static pressure of 1000 psi
Long Term Stability at Constant Conditions:
0.1% URL/Year typical
Mountingpositioneffect:2inH2Omaximum,which can be calibrated out.
Ripple and noise: Per ISA 50.1 Section 4.6
Process Temperature - RTD Interface
A three-wire platinum RTD per DIN 43760 is sup-ported. The temperature, T, in degrees Celsius is calculated using the Resistance vs. Temperature Tables according to the DIN EN 60751 standard for ClassA&BRTDs.TheDINEN60751equationis:
R(t) = R0 * (1 + At +Bt2)
Where:A = 3.9083 * 10-3 oC-1B = -5.775 * 10-7 oC-2Ro = 100ohms
In addition, the user may enter the R0, A, and B coefficientsofacustomcalibratedRTD,anotherplatinum standard or a different material (Nickel, Balco or Copper). During the RTD calibration, the User will be able to set the R0,A,andBcoefficients,restorethefactorydefaultforthesecoefficients,andcalibrate the internal Reference resistor.
Process Temperature Input Specifications (for the interface, only, not including the RTD probe or wiring)
RTD Conversion Accuracy: 0.1C, or 0.1% of reading, whichever is greater
Ambient temperature effect on RTD measurement:
0.01C / C max
Long Term Stability at Constant Conditions:
0.25C / month max
Analog Output Specifications
Non-linearity: 0.1% max
Temperatureeffects:+/-0.25%FullScaleover60degrees C.
Environmental Specifications
OverPressureLimit:Equaltothestaticpressureupper range limit (URL).
Temperature limits:Wet End: -40 to +85CElectronics: -40 to +85CWith Display: -30 to +70CStorage Temperature: -40 to +100C
Humiditylimits:Whencoversareproperlyinstalled,
Product Data Document225DS-25h / D301300X012April 2011 - Page 4 Bristol Multivariable Transmitter
Remote Automation SolutionsWebsite: www.EmersonProcess.com/Remote
unitwillwithstand0to100%RH(NEMA4Xenclo-sure)
Vibration:0.1%URL/gmax10-500Hzinanyaxisper SAMA PMC-33-1C
Electromagnetic compatibility:
Conditions: Current output (only) twisted pair wires includes RTD. Covers installed and wiring run in groundedconduit.10V/M,20-500MHZperSAMAPMC-33-1C:
DP and SP: 0.25%URLRTD Temperature: 1C
Liquid Crystal Display (LCD)
The LCD displays the measured variables for DP, P, and T. The display will continually cycle though all measured variables. The value and Engineer-ing Units for a particular variable will be displayed for three seconds. An annunciator indicates which pressure variable is being displayed.
The LCD provides 4 1/2 digits of display precision with a decimal point. The following Engineering Units are included:
C
F
BAR
psi
inH 2O@60F
kg/cm 2
kPa
User Interface For The 3808 MVT
Usingalap-toppersonalcomputer,fieldpersonnelcanquicklycalibrateandconfigurea3808MVTtransmitter. The personal computer interfaces to the RS 232 port. Meanwhile, the RS 485 port wiring need not be disconnected. RS 485 communication is disabled only while the PC cable is connected to the RS 232 terminals.
Emersons LocalView Calibration Tool includes all calibrationandconfigurationoperations.Thistoolwill be familiar with users of Smartkit as well as all otherBristolflowcomputersandprovidesusersofall Bristol measurement products, from Emerson, a consistentandcompatibleHMI.
A variety of User Interface features are provided by the 3808 MVT. These include:
Set Communications Baud Rate
Set BSAP Local Address
SetBSAPGroupNumber
Set Modbus Node Address
Set Modbus Mode (ASCII/RTU)
Enable/Disable Static Pressure Reading
Enable/Disable RTD Temperature Reading
ReadcurrentDP/GP,SP,T,SensorTemperature, and Status values
ReadDP/GPandSPUpperRangeLimits
CalibrateZero/SpanforDP/GPandSP
Calibrate Zero for RTD
ConfigureRTDCoefficients
Configure4-20maAnalogOutput
Enable/Disable
SelectLinear/SquareRootMode
SelectForward/ReverseActing
SelectOutputVariable(DP/GP,SP,UserDefined,orNone)
CalibrateZero/Span
SelectEngineeringUnitsforDP/GP,SP,T
SetFloatingPointDampingFactor
Display Transmitter Information (Traceability information,RangeCodes,FirmwareRevision)
Product Data Document225DS-25h / D301300X012April 2011 - Page 5 Bristol Multivariable Transmitter
Remote Automation SolutionsWebsite: www.EmersonProcess.com/Remote
Communication Interface
BSAP Interface
The 3808 MVT will act as an immediate response BSAP Slave device. The 3808 MVT will function as a terminal node only in a BSAP Network. BSAP Globalmessagesreceivedwiththe3808MVTsLocal Address will be processed by the 3808 MVT. Notethatpassthrough,orrouting,ofBSAPGlobalmessages, Expanded BSAP messages, and Time-Sync/Node Routing Table messages are not sup-ported.
A subset of the RDB and Peer-to-peer messages are supported. This will provide the user both RDB and Peer-to-Peer List access to the 3808 MVT Pro-cess variables and parameters.
MODBUS Interface
The 3808 MVT will act as a Modbus compatible, slave device. The 3808 MVT provides support for both Modbus ASCII and Modbus Remote Terminal Unit (RTU) transmission modes, utilizing a subset of the Read/Write commands available via Modbus.
To provide support for a variety of Modbus compat-ible host controllers, the 3808 MVT data available via Modbus are mapped into Modbus Coils/Regis-ters. To accommodate the different types of Modbus hostsavailable(i.e.standardModbus,ENRONModbus)floatingpointdataitemsaremappedtoseveral different Modbus Register address ranges. This provides both 16-bit and 32-bit register access using the appropriate register address and function code.
Accessories
EmersonsBristolOpenBSI/LocalViewCalibrationandconfigurationsoftwareforaPC
CD part number: 395575-02-8
PC-to-3808-MVTCableConnectstotheRS232 port on the 3808 MVT, 10 foot, part number: 396596-01-0
TransmitterInterfaceUnit(TIU)Forcompatibilitywith the 3508, this module is used to connect a PC totheFSKsignalonthe3808MVT.
Part Number 389959-01-4
FortheTIU,pleasespecifythemodemcablelength:
6footpartnumber390929-01-812footpartnumber390929-02-625footpartnumber390929-03-4
Bendable RTD
The user can select a bendable RTD that attaches to the transmitter via an armored cable of 6-foot, 15-foot or 25-foot length. The individual wires connect to terminations on the termination plate. The RTD assemblyalsoincludesafitting,whichisinstalledinthe conduit port.
If ordered along with the transmitter, the bendable RTD assembly will be shipped in the same box as the transmitter.
ThebendableRTDisaonesizefitsallsolutionthat is perfect for most applications and excellent for depot-level inventory situations in which the ultimate installation (and, therefore, thermowell depth) is not necessarily known.
The12probecanquicklybeinsertedinathermowell, whereupon the user can tighten the in-cludedfittingtolockitinplaceandbendtheexcesslength out of the way.
NotethatathermowellisrequiredforthisbendableRTD!
Note also that the bendable RTD assembly is ap-proved only for use in Class I, Division 2 hazardous areas and is not explosion proof.
Product Data Document225DS-25h / D301300X012April 2011 - Page 6 Bristol Multivariable Transmitter
Remote Automation SolutionsWebsite: www.EmersonProcess.com/Remote
Model Number: 3808-30A - A B C - D E F - G H J - K L M - N P Q R3808-30A X380830A
DESCRIPTION CODEA B C Input Range Differential (inH2O) Static Pressure (PSI) A B C
10 0-7.5 to 0-150 1000 1210-7.5 to 0-150 2000 1220-15 to 0-300 1000 1410-15 to 0-300 2000 1420-15 to 0-300 3000 1450-15 to 0-300 4000 1440-1.25 to 0-25 PSID 2000 2020-1.25 to 0-25 PSID 3000 2050-1.25 to 0-25 PSID 4000 204
D Diaphragm Material D316 Stainless Steel 1
20 HastelloyC 2 E Filling Media E30 DC 200 Silicone 1 F Flange Material X3808FLA F
316 Stainless Steel Match D - diaphragm 140 HastelloyC material 2G Flange Vent Valve X3808VENT G
None 050 With Vent Valve - 316 SS Note: Flange Material, F = 1 1
WithVentValve-HastelloyC Note: Flange Material, F = 2 2H Manifold Adapter X3808MAN H
None Match F - 0 60 Stainless Steel Flange 1
HastelloyC Material 2J Comm / Output Options J 4-20mAcurrentoutput/FSK Note: Local calibration requires TIU. 1 70 RS 485 Note: Local calibration requires RS 232 cable. 2
Product Data Document225DS-25h / D301300X012April 2011 - Page 7 Bristol Multivariable Transmitter
Remote Automation SolutionsWebsite: www.EmersonProcess.com/Remote
Model Number: 3808-30A - A B C - D E F - G H J - K L M - N P Q R3808-30A
DESCRIPTION CODEK Local Indication X3808LIND K None 080 4 1/2 Digit LCD 1L Flange Orientation L
Standard (faces away from front) 190 90 degrees (down) (Default) 2
Note: Housing is very easy to rotate 180 degrees around in the field. M Mounting Bracket X3808MTG M
None 0With"L"FlangedMounting Not avail. with 90 deg. (down) 1
100 Bracket flange orientation (Option K=2)Neck Mounted Bracket With any Flange Orientation 2
N Certification N110 UL/CULClassI,Division1,GroupsC&D;ClassI,Division2,GroupsA,B,C,D 1
P Warning Plate PNone 0
120 Russian 1Q RTD / Cable Assembly Q
None Please refer to the notes, 0With RTD and 6-foot Cable below, concerning the RTD / 1
125 With RTD and 15-foot Cable Cable Assemblies. 2With RTD and 25-foot Cable 3
NOTES: RTD/CABLE ASSEMBLIESIf selected in "Q" above, the RTD/Cable assembly will be shipped in the same box as thetransmitter. Due to UL restrictions, they cannot be shipped "pre-connected."IMPORTANT:TheseparticularRTDassembliesarenotexplosion-proofbutareapprovedforClassI,Division2hazardousareas.Forexplosion-proofRTDcomponents,pleaserefer to "RTD Sensors and Related Accessories" in the Bristol price book.
RFactory Configuration Options RUse the Standard, Defaults - Please DO NOT fill-in attachment 3800-A010 0
130 SpecifyOtherConfigurationSettings-Please proceed to attachment 3800-A010. 1
To specify a 3808 MVT that is approved by Industry Canada for custody transfer installations when used in conjunction with a ControlWaveEFMorControlWaveXFC,pleaseusethefollowingmodelnumberandattachmentnumber:
3808-30A-142-111-102-020-1000 3808-B-1
Product Data Document225DS-25h / D301300X012April 2011 - Page 8 Bristol Multivariable Transmitter
Remote Automation SolutionsWebsite: www.EmersonProcess.com/Remote
Attachment Number: 3800-A - AB - CD - E - F - GH - J - KL - M - N - P - R - T - U3800-A
DESCRIPTION CODEA B DP Units for 3808-30A or GP units for 3808-10A A B
InH2O(Default) Special Note for 25 PSI DP range: If you use 00PSI this attachment, "In H2O" become the default 01mmH2O units. If you want "PSI," you must specify 02ftH20 that, here. 03inHg 04mmHg 05
90/160 KPa 06MPa 07BAR 08mBAR 09g/cm2 10kg/cm2 11
C D SP Units for 3808-30A - Please note that this field is N/A for the 3808-10A CDInH2O 00PSI (Default) 01mmH2O 02ftH20 03inHg 04mmHg 05
92/170 KPa 06MPa 07BAR 08mBAR 09g/cm2 10
kg/cm2 11E Temperature Units for RTD Input E
Degrees C (Default) 094/200 DegreesF 1
F Communications Baud Rate F9600 (Default) 01200 1
96/205 2400 24800 319,200 4
Product Data Document225DS-25h / D301300X012April 2011 - Page 9 Bristol Multivariable Transmitter
Remote Automation SolutionsWebsite: www.EmersonProcess.com/Remote
Attachment Number: 3800-A - AB - CD - E - F - GH - J - KL - M - N - P - R - T - U3800-A
DESCRIPTION CODEG H BSAP Local Address GH
Using two digits, including a leading zero for 1 - 9, please specify the address in98/210 'GH,'ie."01"through"32."Forreference,thedefaultaddressis1.
J BSAP Group Number J100/300 Pleasefill-inasingle-digitbetween1and8in'J.'Group1isthedefault.
K L MODBUS Node Address KLUsing two digits, including a leading zero for 1 - 9, please specify the address in
102/310 'GH,'e.g."01"through"32."Forreference,thedefaultaddressis1.M MODBUS Mode M
ASCII (Default) 0104/320 RTU 1
N ENABLE / DISABLE 4 - 20 mA Output NENABLE (Default) 0
106/330 DISABLE 1P 4 - 20 mA LINEAR or SQUARE ROOT P
LINEAR (Default) 0 108/340 SQUAREROOT 1
R 4 - 20 mA FORWARD or REVERSE ACTING RFORWARD(Default) 0
110/350 REVERSE 1 T 4 - 20 mA OUTPUT VARIABLE T
DP(in3808-30A)orGP(in3808-10A)(Default) 0112/360 SP (3808-30A only) 1
TEMPERATURE 2U RTS DELAY U
10 ms Bristol Default 0
115/365
50 ms that is known to work best for Chesapeake CW LP using Modbus
1
Product Data Document225DS-25h / D301300X012April 2011 - Page 10 Bristol Multivariable Transmitter
Remote Automation SolutionsWebsite: www.EmersonProcess.com/Remote
DIMENSIONED DRAWINGS
3808 MVT with Manifold Adapters Shown
2 11
/16"
2 1/
8"
1 5/
8"
Product Data Document225DS-25h / D301300X012April 2011 - Page 11 Bristol Multivariable Transmitter
Remote Automation SolutionsWebsite: www.EmersonProcess.com/Remote
3808 MVT with L Flanged Mounting Bracket
Product Data Document225DS-25h / D301300X012April 2011 - Page 12 Bristol Multivariable Transmitter
Remote Automation SolutionsWebsite: www.EmersonProcess.com/Remote
3808 MVT with Neck Mounted Bracket
2 1/
4"
3 5/
8"
1 7/
8"
2 7/
8"
13/1
6"
3 7/
8"
5 11
/16"
Product Data Document225DS-25h / D301300X012April 2011 - Page 13 Bristol Multivariable Transmitter
Remote Automation SolutionsWebsite: www.EmersonProcess.com/Remote
Simplified Diagram of 3808 MVT with 4 20 mA Signal
Product Data Document225DS-25h / D301300X012April 2011 - Page 14 Bristol Multivariable Transmitter
Remote Automation SolutionsWebsite: www.EmersonProcess.com/Remote
Simplified Diagram of 3808 MVT with RS 232 and RS 485 Interface
COMPENSATIONELECTRONICS
ELECTRONICS HOUSING
SENSOR MODULEASSY.
FLANGE(HI Side)
LO PORTOVERPRESSUREMECHANISM And
DIAPHRAGM
FLANGE(LO Side)
ISOLATIONDIAPHRAGM
ISOLATIONDIAPHRAGM
HI PORT
HIGH SIDE FLUID SYSTEM
LOW SIDE FLUID SYSTEM
CPU BOARD
5 to 42VdcPowerSupply
RS-232Interface
RS-485Interface
RTD
+
SPIBUS
Product Data Document225DS-25h / D301300X012April 2011 - Page 15 Bristol Multivariable Transmitter
Remote Automation SolutionsWebsite: www.EmersonProcess.com/Remote
3808 MVT Terminal Block Assignments
3808 MVT Wire Routing
Product Data Document225DS-25h / D301300X012April 2011 - Page 16 Bristol Multivariable Transmitter
Emerson Process ManagementRemote Automation Solutions
Watertown, CT 06795 USA T 1 (860) 945-2200Mississauga,ON06795Canada T1(905)362-0880WorcesterWR38YBUK T44(1)905-856950
Website: www.EmersonProcess.com/Remote
2007-2011 Remote Automation Solutions, division of Emerson Process Management. All rights reserved.
Bristol,Inc.,BristolCanada,BBISAdeCVandEmersonProcessManagementLtd,RemoteAutomationSolutionsdivision(UK),arewhollyownedsubsidiariesofEmersonElectricCo.doingbusinessasRemoteAutomationSolutions(RAS),adivisionofEmersonProcessManagement.FloBoss,ROCLINK,Bristol,BristolBabcock,ControlWave,TeleFlowandHelicoidare trademarks of RAS. AMS, PlantWeb and the PlantWeb logo are marks of Emerson Electric Co. The Emerson logo is a trademark and service mark of the Emerson Electric Co. All other marks are property of their respective owners.
The contents of this publication are presented for informational purposes only. While every effort has been made to ensure informational accuracy, they are not to be construed as war-ranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. RAS reserves the right to modify or improve the designs or specificationsofsuchproductsatanytimewithoutnotice.AllsalesaregovernedbyRAStermsandconditionswhichareavailableuponrequest.RASdoesnotassumeresponsibilityforthe selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any RAS product remains solely with the purchaser and end-user.
Recommended