MODEL :FIRE ALARM CONTROL PANEL
ERTL TESTED AS PER IS:2189
Mfd By: National Security Devices
PART CODE :2011/MINI LEXUS
INDEX
[1] Introduction.................. General
[2] General Features.................. Mechanical Construction
[3] Installation & Commissioning.. Installation Commissioning
[4] Indicator and controls.. Indicator Controls
[5] Input and Output......... Zone Monitor Power Monitor Output Controls
[6] Technical Data........... [7] [8] Warranty [9] Test Report
About The product
TRADE MARK
INTRODUCTION
About The Product This manual intended as a complete
guide to the model fire control panel. This microprocessor based
fire alarm control Panel is implemented with wide range of
application required in basic alarm Automation .
System Design and Plan
This panel is designed to meet the general requirement of IS
2189:1999.Basically these system used in residential society
sensitive area where fire can prevented manual prevention or fire
fighting depart/duty persons.
About The Company
We heartily welcome you in the family of
NATIONAL SECURITY DEVICES , is well known name in the field of
mfg fire alarm systems . We came in to the field of manufacturing
and with in a short span of a decades time, We succeed to achieve
upper layer of the industry, got good response & respect from the
customer for quality product & timebond services . Still aiming to
keep the high standard with our professionals , advanced
technology, computerized R& D , in -house tool room/assambly
plant and of course our skilled workmanship with the strict quality
control.
1
GENERAL FEATURES
The microprocessor based fire alarm Control and indication panel is designed to individual zoning the fire input and evacuated /alert fire in earliest practicable moment with the help 24 V hooter output .
The panel operates on 220 V AC Mains with 24 V DC Battery as a stand by power , The built in circuit provide constant voltage charging to maintain the battery capacity.
v on 220 V AC supply. v Stand by battery backup with Built in charging. v Error free panel status in unambiguous colored LED indication. v System on Mains ON battery Low status indication. v Low battery visual warning with Audio able tone.v Zone wise fire fault Operating indication Facility. v Zone ON indication Facility. v 24 V Hooter Output with silence facility.v Manual test facility v Rugged CRCA sheet with powder coated finish. v Modular Construction. v Relay Output for associate gadgets.
MECHANICAL CONSTRUCTION
The enclosure of the panel is constructed by CRCA Sheet with powder-coated finish and its designed to afford the degree of protection as per IP54 , The 20 mm Knock outs are given for cable entry at the top of the cabinet.
The Panel has a built in battery space for 2Nos of 12 V , 7 AH Batteries.
The front side of the panel consist of the following 1) Control Switches 2) LED Indication
Operates
2
INSTALLATION AND COMMISSIONING
Installation The installation of the Fire detection and alarm should
comply with a)The installation of the Electrical engineers (IEE) wiring
regulation and standards. b)The Indian Standard of fire Detection and alarm for building. c)The installation cable should not be in the area of proximity of high voltage cable or induce electrical interference.
Place the panel in its outing Position and fix the panel to the wall using the slot of the screw , Ensure the enclosure and the inner parts of the panel are given sufficient protection during installation period . All external cables are to be entered via the 20 mm performed knockout located at the top of the panel .
After the installation of all cables has been completed , clean the interior of the enclosure ensuring all masonry debris and drilling swords are removed.
COMMISSIONING Check all entered wiring is correctly identified and also check all free from fault condition by a multi meter . Connect the external wiring into their respective terminal and ensure the end of line (EOL ) resistor is placed at the last device of circuit.
Prior to the power up of the panel conduct the following preliminary checks a) check for any external signs of damage caused during installation
b) Checks all PCBs are secure in its monitoring position. c) Check all cable are secure and correctly connected. d) Check all the cable termination is tight & Secure. e) Connect the batteries ensuring the correct polarity.
All damages / Fault must be rectified before proceeding
3
INDICATOR AND CONTROLS (uses and normal state)
ZONE MONITOR INDICATIONS
NORMAL: These are the green glowing LED of zone normal condition in case any events these LED’s goes off .
FIRE : These are the Red glowing LED for fire conditioning. These LED are in pair In case of fire LED’s glow . Normally these LED’s retain off .
OPEN :This is the yellow glowing LED for open conditioning. This LED is in individual with open mark. In case of zone wire open , cables/ wire or EOL is not connected this is indication for respective fault. These LED’s retain off.
SHORT : This is the yellow glowing LED for short conditioning. This LED is in individual with short mark. In case of zone wire short , cables/ wire or EOL is short this is indication for respective fault. These LED’s retain off.
POWER INDICATION
1) SYSTEM ON 2) CHARGING3) AC FAIL4) BATTERY LOW5) FUSE
4
CONTROL
RESET :- This switch has provided for restarting the system after any event or function .
SILENCE :- Whenever any signal comes from field’s device , the external buzzer beeping with the information on LED glow of respective zone . To mute that audio alarm press silence button or in case of fire the hooter sound can be muted by pressing this button.
LAMP TEST:- To check the LED in healthy position press this switch . All LED will be glow with the buzzer sound .
ISOLATE / OFF : This switch is provided for non functioning of respective zone..
TEST SWITCH
TEST: This switch is provided in individual zone & it is common for all test in that zone. It works with the combination of SHORT/OPEN/FIRE switch. If we press TEST switch & FIRE simultaneously then fire condition will occur in that zone.
FIRE: This switch is provided common for all zone. It works with the combination of TEST switch. If we press TEST switch & FIRE simultaneously then fire condition will occur in that zone.
OPEN: This switch is provided common for all zone. It works with the combination of TEST switch. If we press TEST switch & OPEN simultaneously then OPEN condition will occur in that zone.
SHORT: This switch is provided common for all zone. It works with the combination of TEST switch. If we press TEST switch & SHORT simultaneously then short condition will occur in that zone.
TERMINALS / OUTPUT
M.C.B. CONNECTOR :-These are the input terminal to connect the manual call box the panel system . If glass removed or break at any manual call box then system provide provide 24 volt D.C. to respective hooter & potential free contact changes it state . So this panel act for conducting further operation for air handling unit or other associated gadgets. Be sure for EOL at appropriate point for right function of manual call box.
HOOTER:-This connector provide power 24volt D.C. for alarming the hooter in case of break glass of manual call box . these are the individual zone wise activated along with one common hooter.Verify the hooter terminal protect form short circuit because it can damage the product.
COMMON HOOTER:- This terminals 24 D.C. output is activated with the any break
glass unit.
FIRE POTENTIAL FREE CONTACT :- These are relay contact that change over its position in case of
fire either it is multi zone or single zone.
FAULT POTENTIAL FREE CONTACT :- These are relay contact that change over its position in case of
fault either it is cross zone or single zone.
5
OPERATING VOLTAGE : 24 DC+ 10%
MAINS SUPPLY : 230V AC 190V AC
STAND BY SUPPLY : 24V/4.5Amper
HOOTER OUTPUT : 24V/2Amax
RELAY RATING : 24V/3Amp
POTENTIAL FREE CONTACT : FIRE & FAULT
VOLTAGE CHARGER : 26.6V
ZONE POWER NORMAL : 15.6MA/ZONE
ALARM CURRENT : 35MA ZONE
AC FUSE RATING : 500MA
DC FUSE RATING : 6 Amp
BATTERY FUSE RATING : 6Amp
DIMENSIONS : (420X325X120)MM.
WEIGHT : 10 KG APPROX..
TECHNICAL DATA
6
12
34
56
7
1413
1211
109
8GN
D
1WAT
T
GND
GND
12
34
56
7
1413
1211
109
8GN
D
1WAT
T
GND
ZON
E-2
GND
cN
O
GN
DFU
GN
DFI
ZON
E-1
cN
O
GN
DFI
L2+
L1+ L5+
GN
DFU
L3+
L4+
L7+
L8+
L6+
IC 2 IC 3
L16+
R12
D10
R17
R13
R14 R15
R16
D15
D16
D17
D18
D14
D11
D12
D13
R19
R21
R22
R23
R24
R25
R29
D25
D26
D27
D28
D19
R26
R27
R28D
22
D30
D24
D20
D21
R20
R18
RLY2
RLY
3
C3
C4
CR
OZ
C2
C5
Q1
Q2
SWIT
CH
1
SWIT
CH
2
DC
FU
SE
3AM
P
7Ic1
56GND
31Ic1
2
L9+
POW
ER IN
24
VOLT
BOX
TYPE
cNC
NO
GN
D
L13+
BATT
+
D1
D3
D4
D6
D7
D8
R1
R2
R3
R4
R5
R8
R9
R10
R11
RLY
1
FU
D5
D2
C1
Z1
D9
5408
24V 4
8
Q10
RESET SWICTH
cN
C
cN
O
GND
cN
CN
O
cN
CN
O
S
OL
EN
OID
(M
AIN
)
L15
+
L23+
AB
OR
T
S
OL
EN
OID
(ST
AN
DB
Y)
NOc
NC
BS
GND
GND
GND
GND
MANU
EL R
ELEA
SE
L24+
NC
NO
cN
O
12
3
4
56
78
FU
GND
GND
GND
L17+
L19+
I
NH
IBIT
c
L25+
PR
S OUT
L18+
PR
S IN
PR
ESSU
RE
LOW
(MAI
N C
YLIN
DER
)
(STA
NDBY
CYL
INDE
R)
PR
ESSU
RE
LOW
L22+
L21+
C7
D31
D32
D33
D34
D35
D37
D38
D39
D41
D40
D43
D42
D44
D47
D53
D50
D51
D52
D56
D55
D57
D58
D59
D60
D36
D30 R
30
R38
R36
R36
R37
R39
R40
R42
R41
RLY
4
RLY
5
RLY
6
RLY 7RLY8
RLY 9
RLY 11
GND
R34
HO
OTE
R
GND
RESE
T
GND
L +2
0
GND
FU
FI
12
34
56
7
8
GND
GND
BUZZ
ER
-
+
IC-5
12
34
56
7
8IC
-6
GND
GNDGND
c
NC
NO
RLY 10
GND
D45
D46
D49
D48D
54
R31
R32
R33
R35
R43
R44
R45
R46
R47
R48
PR 1
Q3
Q8
Q9
Ic4
C6
C8
C9
5408
R49
SILENCE SWITCH
KEY
MANUAL MODE
C
NC
NO
FIR
E
C
NO
NC
FA
ULT
+- WARNING SIGN
MODULE
CN
O
MAIN SOV
STANDBY SOV
+-
+-
+- GAS DISCHARGE
+- PRESSURE
SWITCH
COMMONHOOTER
+-
ZONE-1
REMTERELEASE
24 VOLT
ABORT
GND
ZONE-2
+-
+-
+-
+-
+-
PRESSURE LOWSTANDBY CYLINDER
(MAIN CYLINDER) PRESSURE LOW
+-
+-
L1
0+
L11
+
L1
4+
Z 1
ON
Z 1
FIR
EZ
ON
E 1
Z 1
OP
EN
Z 1
SH
OR
T
Z 2
ON
Z 2
FIR
E
Z 2
OP
EN
Z 2
SH
OR
T
SY
ST
EM
ON
CH
AR
GE
R
AC
FA
IL
BA
TT
LO
W
FU
SE
AB
OR
T
CR
OS
SZ
ON
E
MA
NU
AL
RE
LE
AS
E
GA
S D
ISC
HA
RG
ED
TIM
ER
SO
LE
NO
ID O
PE
N
PR
.LO
WM
AIN
CY
LIN
DE
R
PR
.LO
WS
TA
ND
BY
CY
LIN
DE
R
MA
NU
AL
AU
TO
NA
TIO
NA
L S
EC
UR
ITY
DE
VIC
ES
OF
FIC
E :
485/1
4,
SA
RP
AN
CH
KA
BA
RA
, M
AN
DA
WA
LI
FA
ZA
LP
UR
, D
EL
HI-
11092
PH
ON
E :
011-2
2751020,
64603599 F
AX
: 0
1122751020
MO
BIL
E :
9891222660,
E-M
AIL
- M
AIL
AN
ILR
AW
AT
@G
MA
IL.C
OM
TIT
LE
CO
2 G
AS
FL
OO
DIN
G S
YS
TE
MC
LIE
NT
PR
OJE
CT
FIR
E C
ON
TA
CT
OR
SR
L.
NO
.D
AT
E
Q4
Q7
Q6
GND
Q5
INH
IBIT
MO
DE
WARRANTY CERTIFICATE
Dear Customer , Your NATIONAL SECURITY DEVICE Fire alarm system is
guaranteed against manufacturing defects of parts and component for a
period of 12 months from the date of
purchase______________________________
During this period any items found defective will be repaired at
our works or though service center. Terms & Condition :
1) Serial o. Sticker should not be broken / tempered / mismatch
. as our record.2) Product not used as per described guideline or hassling with
electronic part.
Serial No :
Stamp :
NATIONAL SECURITY DEVICES
NATIONAL
SECURITY DEVICES
8
TEST REPORT ..............MANUAL ALARM CONTROL PANEL ................... SPARE ZONES .......................
CONTRACTOR NAME :CLIENT /SITE :BILL NO. / CHALLAN NO :QUANTITY :SERIAL NO. :AC FUSE : .5 AMP DC FUSE : 6 AMP FIRE CONDITION : SYSTEM OK FAULT CONDITION : SYSTEM OK FIRE & FAULT RELAY : SYSTEM OK DETECTION & HOOTER LINE : SYSTEM OK
This is to certify that the manual alarm control panel Supplied as per detail has been manufactured by NATIONAL SECURITY DEVICE at Delhi -92 .Test producer are conducted as per guideline by costumer. Although all products tested as per IS:2189 stranded.
Test Report No . ERTL
It is again certified that all the featured laid down in the panel as per customers specification have been provided and checked .
Date of Testing :
Date of Issued : Q. C. MANAGER
Client Copy
(N)/90 (4)-2K 7/Q0094 dated 14 May 2007.
9
Dealers Name & Address
Model No : Fire Alarm ControlSR No :
Sale date :
Security Devices
OFFICE : 485/14, SARPANCH KA BARA, MANDAWALI FAZALPUR, DELHI-110092
WORKS : 2-A, Patparganj, Mayur Vihar,
Phase - 1, Delhi - 110091PHONE : 011 - 22751020, 64603599, Fax: 011 - 22751020
MOBIL : 9891222660, E-mail : mailanilrawat@gmail.com
NATIONAL SECURITY DEVICES
Recommended