View
6
Download
0
Category
Preview:
Citation preview
Active Infeed Converter
ww
w.a
rtco
ncep
t-w
erbe
agen
tur.d
e
Technical Data
AIC rated power (100 % active power possible)
kVA 100 200 250 320 500
AC side
AC mains voltage V 400 / 230 V, ± 10 %, 3-phase, N, PE
AC power factor range 0.5 lag to 0.5 lead
Nominal AC output voltage V 400 / 230 V, 3-phase, N, PE
Frequency synchronized to the AC mains, 50 or 60 Hz ± 5 %
Waveform sinusoidal
Acoustic noise dB (A) < 75
Discharging mode
DC Voltage range 300 - 450 V (max. 200 kVA) or 450 - 600 V (max. 320 kVA) or 600 - 850 V
Emergency Stop via floating contact
Inverter efficiency % 94 95 95 95 95
Dimensions (600 - 850 VDC):
width mm 1200 2000 2000 2200 2400
depth mm 800 800 800 1000 1000
height mm 2000 2000 2000 2000 2000
Weight kg 900 1400 1500 1700 2300
EMCEN 61000-2-4 – Mains disturbance
EN 61000-6-2 – Noise immunityEN 62040-2 – Transient emission
Basic Norm EN 62040-1 partly
Permissible ambient temperature °C 0 to 40
Permissible climate 3K3 according to IEC/EN 60721
Permissible operating altitude 1000 m above m.s.l. with rated load
Protection class IP 20 to EN 60529
Paint finish RAL 7035, textured finish
Cooling „AF“ forced-air cooling
Display TFT-Panel
Interface:
Battery CAN-OPEN Slave
Operation system MODBUS TCP/IP
Subject to change without notice (tech)
TYP AIC-3868
NeuschwaNsteiN castle
ww
w.a
rtco
ncep
t-w
erbe
agen
tur.d
eInnovation and quality from Germany and Austria
GUSTAV KLEIN GMBH & CO. KG D-86956 Schongau · im Forchet 3D-86952 schongau, Postfach 12 48tel. +49(0)8861/209-0, Fax +49(0)8861/209-180e-Mail: vertrieb@gustav-klein.comwww.gustav-klein.com
a-6401 Inzing / tirol · schießstand 2tel. +43(0)5238/54209-0Fax +43(0)5238/54209-23e-Mail: vertrieb@gustav-klein.comwww.gustav-klein.com
Bloc DiagramDesign
Options
• Low ripple
• Electrical isolation (galvanic)
• Battery current limitation
• Power- and temperature-dependent fan control
• Disconnector DC
• Disconnector AC
• Low mains feed back through PFC
• Input power factor λ = 1 (without pre setting of reactive power)
• Parallel connectable
• Intelligent monitoring functions
• Suitable for any kind of battery with suitable BMS system
• Modbus TCP resp. profibus-interface to control system
Hardware:
• Earth fault supervision
• IT-Mains AC
• Cabinet lighting
• Mains switch AC (Grid)
• Battery interface Profibus DP / MODBUS TCP-IP
• External protection of mains and system according to DIN VDE V 0124-100 resp. VDE-AR-N 4105
Software:
Parallel to line:
• cos phi regulation
• P(f) characteristic
• Q(U) characteristic
Line leading:
• f(SOC) characteristic
• U(Q) characteristic
Storage system 100 - 500 kW – Total power without limit
Option
Option
Energystorage
< 1000 VDC
Energystorage
< 1000 VDCAIC
AIC
Grid Demand Controller
Emergency Stop
Interface Board
Battery
GridSupervision
TFT-Panel
Grid
Mains Protection and Control System (External)
According to DIN VDE-AR-N 4105AIC MODBUS TCP/IP
400 / 230 VCAN-OPEN
optional
optional~
–
Control and Applications
Parallel to Grid (VDE-AR-N 4105 or similar)
Demand control Ext. control
P(f) Q(U) Pdirect
Qdirect
cos φ direct
Without Grid connection (Island-grid)
Ext. controlDynamic
f(SOC) U(Q) U fixed f fixed
Black start via voltage and requency control, as well as successive addition of load.
Recommended