Page 2 of 42Test report no. HS64.181.15.00764.13 Rev.01
Test sample ...................................... ..: Heat Pump
Type of test object .............................. : Heat Pump
Trademark .......................................... : Hiseer
Model and/or type reference .............. : AS10S-DPNHE
Rating(s) ............................................. : 380-415 V 3N~; 50Hz; other rating refer to page 6
Manufacturer ...................................... : Guangzhou Hiseer Air conditioning Co,. LTD
Client number… ................................. : 1Address .............................................. : No.9 Huasheng Road Xicheng industry zone, Renhe Town, Baiyun
District, 510470 Guangzhou City, P.R. China
Order description .............................. ..: Complete test
Partial test according to manufacturer's specifications
Preliminary test
Spot check
Others:
Date of order ................................... ..: 2017-04-16
Date of receipt of test item ............... ..: 2017-04-20
Date(s) of performance of test ........... : 2017-04-22 to 2017-04-30
Test item particulars: (declared)
Product type……… ...................................................... : Heat pump space heater
Heat pump combination heater
Split type
All in one
others:
Capacity control……… ................................................ : Variable capacity
Fixed capacity
Staged capacity
Power source……… .................................................... : Single phase
Three phase
Heat source type……… ............................................... : air/water heat pump
water/water heat pump
brine/water heat pump
Low-temperature heat pump……… ............................ : Yes
No
Page 3 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Water outlet type:……… .............................................. : Fixed outlet
Variable outlet
Equipped with a supplementary heater……… ........... : Yes
No
Storage volume (l)……… ............................................ : N/A
Load profile (if for combination heater)……… ............ : 3XS
XXS
XS
S
M
L
XL
XXL
3XL
4XL
Control type ……… ...................................................... : Smart control (smart: 1)
Non-smart control (smart: 0)
Refrigerant .................................................................. ..: R410A
Refrigerant load .......................................................... ..: 2000 g
Sound power level LWA(dB(A)) / (indoor /outdoor) ..... ..:
WA ............................................................................... ..:
68 dB(A)
Characteristic data Dimensions and weight:
Models Indoor unit
(dimensions(L ×W ×H)(mm) and weight(kg))
Outdoor unit
(dimensions(L ×W ×H)(mm) and weight(kg))
AS10S-DPNHE N/A 1050x450x1050 mm; 132kg
Page 4 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Purpose of the product
used for heating air, medium-temperature heat pumps.
Name and address of Factory (ies) Guangzhou Hiseer Air conditioning Co,. LTD
No.9 Huasheng Road Xicheng industry zone, Renhe Town, Baiyun District, 510470 Guangzhou City, P.R. China.
Summary of testing:
deviation(s) found
no deviations found (see additional information)
The product meets the Stage 2 (26 September 2017) requirement of the implementation measure.
Remark:
Requirement (Annex II) Stage 1 Stage 2
26 September 2015 26 September 2017
Seasonal space heating energy efficiency Clause 1(a) Clause 1(b)
Energy efficiency of combination heaters Clause 2(a) Clause 2(b)
Sound power level Clause 3 No change
Product information related to heat pump space heater Clause 4 No change
Note: stage 3 is not applicable to electric using only products
If additional information is necessary, please provide: N/A
Page 5 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Copy of marking plate:
Picture of the product:
Page 6 of 42Test report no. HS64.181.15.00764.13 Rev.01
Attachments: 1. Key components table
2. Test equipment list
General remarks:
"(see remark #)" refers to a remark appended to the report. "(see appended table)" refers to a table appended to the report. Throughout this report a comma is used as the decimal separator. The test results presented in this report relate only to the object tested. This report shall not be reproduced except in full without the written approval of the testing laboratory.
Measurement uncertainty budgets have been determined for applicable test methods and are available upon request.
Model rating:
Model Rated power input Rated current Protection Against Moisture
AS10S-DPNHE 2.54 kW 4.82A; IPX4
Possible test case verdicts:
- test case does not apply to the test object ................. : N/A
- test object does meet the requirement....................... : P(ass)
- test object does not meet the requirement ................ : F(ail)
Possible suffixes to the verdicts:
- suffix for detailed information for the client……………..: - C(omment)
- suffix for important information for factory inspection...: - M(anufacturing)
Page 7 of 42Test report no. HS64.181.15.00764.13 Rev.01
Clause Requirement − Test Measuring result − Remark Verdict
EC Regulation 813/2013 -
Article 1 Subject matter and scope -
1. This Regulation establishes ecodesign requirements for the placing on the market and/or putting into service of space heaters and combination heaters with a rated heat output ≤ 400 kW, including those integrated in packages of space heater, temperature control and solar device or packages of combination heater, temperature control and solar device as defined in Article 2 of Commission Delegated Regulation (EU) No 811/2013.
Space heater P
2. This Regulation shall not apply to: -
(a) Heaters specifically designed for using gaseous or liquid fuels predominantly produced from biomass;
N/A
(b) Heaters using solid fuels; N/A
(c) Heaters within the scope of Directive 2010/75/EU of the European Parliament and of the Council;
N/A
(d) Heaters generating heat only for the purpose of providing hot drinking or sanitary water;
N/A
(e) Heaters for heating and distributing gaseous heat transfer media such as vapour or air;
N/A
(f) Cogeneration space heaters with a maximum electrical capacity of 50kW or above;
N/A
(g) Heat generators designed for heaters and heater housings to be equipped with such heat generators placed on the market before 1 January 2018 to replace identical heat generators and identical heater housings. The replacement product or its packaging shall clearly indicate the heater for which it is intended.
N/A
Annex II Ecodesign requirements -
1 Requirements for seasonal space heating energy efficiency (ηs) -
(a) From 26 September 2015 the seasonal space heating energy efficiency shall not fall below the following values:
Tested ηs(%): 113% Limit ηs(%):100%
P
- Heat pump space heaters, with the exception of low-temperature heat pumps: 100%;
P
Page 8 of 42Test report no. HS64.181.15.00764.13 Rev.01
Clause Requirement − Test Measuring result − Remark Verdict
- Low-temperature heat pumps: 115%. N/A
(b) From 26 September 2017 the seasonal space heating energy efficiency of heat pump space heaters and heat pump combination heaters shall not fall below the following values:
Tested ηs(%): 113%
Limit ηs(%):110%P
- Heat pump space heaters, with the exception of low-temperature heat pumps: 110%;
P
- Low-temperature heat pumps: 125%. N/A
2 Requirements for water heating energy effiency (ηwh) -
(a) (a) From 26 September 2015 the water heating energy efficiency of combination heaters shall not fall below the following values: ηwh(%):
Load profile: Tested ηwh(%):
Limited ηwh(%):
N/A
D clared load profile
3XS XXS XS S M L XL XXL 3XL 4XL
ηwh 22% 23% 26% 26% 30% 30% 30% 32% 32% 32%
N/A
(b) (a) From 26 September 2017 the water heating energy efficiency of combination heaters shall not fall below the following values: ηwh(%):
Load profile: Tested ηwh(%):
Limited ηwh(%):
N/A
Declared load profile
3XS XXS XS S M L XL XXL 3XL 4XL
ηwh 32 32% 32% 32% 36% 37% 38% 60% 64% 64%
N/A
3 Requirements for sound power level (LWA) -
From 26 September 2015 the sound power level of heat pump space heater and heat pump combination heaters shall not exceed the following values:
P
Page 9 of 40Test report no. HS64.181.15.00764.13 Rev.01
Clause Requirement − Test Measuring result − Remark Verdict
Rated heat output
LWA,indoors LWA,outdoors
≤ 6 kW ≤ 60 dB ≤ 65 dB
>6 kW and ≤ 12 kW
≤ 65 dB ≤ 70 dB
> 12 kW and ≤ 30 kW
≤ 70 dB ≤ 78 dB
> 30 kW and ≤ 70 kW
≤ 8 dB ≤ 88 dB
Rated heat output:
10kW
Tested:
LWA,outdoors (dB): 68 dB(A)
P
4 Requirements for product information -
From 26 September 2015 the following product information on heater shall be provided:
P
(a) The instruction manuals for installers and end-users, free access websites of manufacturers, their authorised representatives and importers shall contain the following elements:
P
- For heat pump space heaters and heat pump combination heaters, the technical parameters set out in Table 2 of clause 5 in Annex II , measured and calculated in accordance with Annex III;
Heat pump space heater P
(b) The technical documentation for the purposes of conformity assessment pursuant to Aticle 4 shall contain the following elements:
-
-The elements specified in point(a); P
-For heat pump space heaters and heat pump combination heaters where the information relating to a specific model comprising a combination of indoor and outdoor units has been obtained by calculation on the basis of design and/or extrapolation from other combinations, the details of such calculations and/or extrapolations, and of any tests undertaken to verify the accuracy of the calculations, including details of the mathematical model for calculating the performance of such combinations and details of the measurements taken to verify this model.
N/A
ANNEX III
Measurements and calculations -
1. For the purposes of compliance and verification of compliance with the requirements of this Regulation, measurements and calculations shall
Standards considered:
See OJ (2014/C 207/02): 2014-07-03
P
Page 10 of 42Test report no. HS64.181.15.00764.13 Rev.01
Clause Requirement − Test Measuring result − Remark Verdict
be made using harmonised standards the reference numbers of which have been published for this purpose in the Official Journal of the European Union, or using other reliable, accurate and reproducible methods that take into account the generally recognised state-of-the-art methods. They shall meet the conditions and technical parameters set out in points 2 to 5.
2. General conditions for Measurements and calculations -
(a) For the purposes of the measurements set out in point 2 to 5, the indoor ambient temperature shall be set at 20˚C±1˚C.
P
(b) For the purposes of the calculations set out in point 3 to 5, consumption of electricity shall be multiplied by a conversion coefficient CC of 2,5.
P
(c) Emissions of nitrogen oxides shall be measured as the sum of nitrogen monoxide and nitrogen dioxide, and expressed in nitrogen dioxide.
NA
(d) For heaters equipped with supplementary heaters, the measurement and calculation of rated heat output, seasonal space heating energy efficiency, water heating energy efficiency, sound power level and emissions of nitrogen oxides shall take account of the supplementary heater.
P
(e) Declared values for rated heat output, seasonal space heating energy efficiency, water heating energy efficiency,sound power level and emissions of nitrogen oxides shall be rounded to the nearest integer.
P
(f) Any heat generator designed for a heater, and heater housing to be equipped with such a heat generator, shall be tested with an appropriate heater housing and heat generator respectively.
N/A
3. Seasonal space heating energy efficiency of boiler space heaters, boiler combination heater and cogeneration space heaters
-
4 Seasonal space heating energy efficiency of heat pump space heaters and heat pump combination heaters
-
(a) For establishing the rated coefficient of performance COPrated or rated primary energy ratio PERrated, the sound power lever or emissions of nitrogen oxides, the operating conditions shall be the standard rating conditions set out in Table 3 of ANNEX III and the same declared capacity for heating shall be used;
P
Table 3
Heat source
Outdoor heat exchanger Indoor heat exchanger
Page 11 of 42Test report no. HS64.181.15.00764.13 Rev.01
Clause Requirement − Test Measuring result − Remark Verdict
Inlet dry bulb (Web bulb) temperature
Heat pump space heates and heat pump combination
heaters, except low-temperature heat heat pump
Low-temperature heat pump
Outdoor air
+7˚C(+6˚C) Inlet
temperature Outlet
temperature Inlet
temperature Outlet
temperature
Exhaust air
+20˚C(+12˚C)
+47˚C +55˚C +30˚C +35˚C --
Inlet/outl t temperature
Water +10˚C/+7˚C
Brine 0˚C/-3˚C
P
(b) The active mode coefficient of performance SCOPon or active mode primary energy ratio SPERon shall be calculated on the basis of the part load for heating Ph(Tj), the supplem entary capacity for heating sup(Tj) (if applicable) and the bin-specific coefficient of performance COPbin (Tj) or bin-specific primary energy ratio PERbin(Tj), weighted by the bin-hours for which the bin conditions apply, using the following conditions:
P
-The reference design conditions set out in Table 4;
-The European reference heating season under average climate conditions set out in Table 5 of ANNEX III;
-If applicable, the effects of any degradation of energy efficiency caused by cycling depending on the type of control of the heating capacity;
P
Table 4
Reference design temperature
Bivalent temperature Operation limit temperature
Tdesign Tbiv TOL
-10 (-11)˚C Maximum +2˚C Maximum -7˚C
P
(c) The reference annual heat demand QH shall be the design load for heating Pdesignh multiplied by the annual equivalent active mode hours HHE of 2066;
QH=Pdesignh*HHE
P
(d) The annual energy consumption QHE shall be calculated as the sum of:
P
-The ratio of the reference annual heating demand QH and the active mode coefficient of performance SCOPon or active mode primary energy ratio SPERon and
P
Page 12 of 42Test report no. HS64.181.15.00764.13 Rev.01
Clause Requirement − Test Measuring result − Remark Verdict
-The energy consumption for off, thermostat-off, standby, and crankcase heater mode during the heating season;
QHE=QH/(SCOPon(SPERon)+PTO+PSB+PCK+POFF)
P
(e) The seasonal coefficient of performance SCOP or seasonal primary energy ratio SPER shall be calculated as the ratio of the reference annual heat demand QH and the annual energy consumption QHE;
SCOP(SPER)= QH/QHE
P
(f) The seasonal space heating energy efficiency ηs
shall be calculated as the seasonal coefficient of performance SCOP divided by the conversion coefficient CC or the seasonal primary energy ratio SPER, corrected by contributions accounting for temperature controls and, for water-/brine-to-water heat pump space heaters and heat pump combination heaters, the electricity consumption of one or more ground water pumps.
ηs=SCOP/CC-ΣF(i)
ηs=SPER/CC-ΣF(i)
P
5 Water heating enerty efficiency of combination heaters -
(a) The water heating energy efficiency ηwh of a combination heater shall be calculated as the ratio between the reference energy Qref of the declared load profile and the energy required for its generation under the following conditions:
N/A
(b) measurements shall be carried out using the load profiles set out in Table 7;
N/A
measurements shall be carried out using a 24-hour measurement cycle as follows: — 00:00 to 06:59: no water draw-off; — from 07:00: water draw-offs according to the declared load profile; — from end of last water draw-off until 24:00: no water draw-off;
N/A
(c) the declared load profile shall be the maximum load profile or the load profile one below the maximum load profile;
N/A
(d) for heat pump combination heaters, the following additional conditions apply:
N/A — heat pump combination heaters shall be tested under the conditions set out in Table 3;
N/A
Page 13 of 42Test report no. HS64.181.15.00764.13 Rev.01
Clause Requirement − Test Measuring result − Remark Verdict — heat pump combination heaters which use ventilation exhaust air as the heat source shall be tested under the
conditions set out in Table 6.
N/A
Additional requirements from Commission communication (2014/C 207/02): 2014-07-03 -
5 Additional elements for calculations related to the seasonal space heating energy efficiency of heat pump space heaters and heat pump combination heaters
-
5.1 Calculation of the seasonal space heating energy efficiency -
The seasonal space heating energy efficiency η s is defined as
P
(a) for heat pump space heaters and heat pump combination heaters using electricity:
ηs= (100/CC) x COP-ΣF(i)
Heat pump space heater P
(b) for heat pump space heaters and heat pump combination heaters using fuels:
N/A
F(i) are corrections calculated according to point 5.2 and expressed in %. SCOP and SPER shall be calculated according to the tables in 5.3, and are expressed in %.
N/A
5.2 Calculation of F(i) P
(a) For heat pump space heaters
and heat pump combination heaters, the correction is F(1) = 3 %.
P
(b) The correction F(2) accounts for a negative contribution to the seasonal space heating energy effciency by electricity consumption of ground water pump(s) expressed in %. For water-/brine-to-water heat pump space heaters and heat pump combination heaters, the correction is F(2) = 5 %.
N/A
5.3 Hours for the calculation of SCOP or SPER -
For the calculation of SCOP or SPER the following reference number of hours that the units work in active mode, thermostat off mode, standby mode, off more and crankcase heater mode shall be used:
-
Number of hours used for heating only
On mode Thermostat-off mode
Standby mode
Off mode Crankcase heater mode
HHE HTO HSB HOFF HCK
Average climate (h/y)
2066 178 0 3672 3850
Warwmer climate (h/y)
1336 754 0 4416 5170
Colder climate (h/Y)
2465 106 0 2208 2314
P
Page 14 of 42Test report no. HS64.181.15.00764.13 Rev.01
Clause Requirement − Test Measuring result − Remark Verdict
Number of hours used for reversible heat pumps
On mode Thermostat-off mode
Standby mode
Off mode Crankcase heater mode
HHE HTO HSB HOFF HCK
Average climate (h/y)
2066 178 0 0 178
Warwmer climate (h/y)
1336 754 0 0 754
Colder climate (h/Y)
2465 106 0 0 106
H HE, HTO, HSB, HCK, HOFF = Number of hours the unit is considered to work in respectively, active mode, thermostat off mode, standby mode, crankcase heater mode and off mode.
N/A
Table 1
Model:
General testconditions
Unit A B C D E F G
Part-Load % 88 54 35 15 100 81 -
Voltage v 398.9 399.5 400.6 399.1 398.4 398.9 -
Frequency Hz 50.0 50.0 50.0 50.0 50.0 50.0 -
Total power input KW 3.626 3.184 2.809 2.654 3.583 3.556 -
Inlet dry bulb(wet bulb) ℃ -7/-8.05 2.10/1.03 7.00/6.01
12.01/10.99
-10.00/- 11.05
-5.02/-6.03 -
Inlet/outlettemperature
℃ . . . . . . .water/brine flowrate m3/s . . . . . . .
Inlet/outlettemperature
℃ 46.6/52.1 38.0/44.9* 33.5/41.6* 28.9/38.3* 50.8/55.1 43.9/49.8 -
Water flowrate m3/s 3.25x10-4 3.25x10-4 3.25x10-4 3.25x10-4 3.25x10-4 3.25x10-4 -
Total heatingcapacity
kW 7.360 9.360 10.870 12.740 5.840 7.930 -
Effective powerinput
kW 3.626 3.184 2.809 2.654 3.583 3.556 -
Coefficient ofperformance - 2.03 2.94 3.87 4.80 1.63 2.23 -
Compressorfrequency
Hz 50 50 50 50 50 50 -
test conditions for indoor side heat exchanger
test conditions for outdoor side heat exchanger for air to water
test conditions for outdoor side heat exchanger for water/brine to water
Supplementary information: Auxiliary electric heater 6KWRemark: *:according to EN 14825: 2016 formulas (21) of clause 8.4.1 calculated average outlet temperature.
Parl load test (For the reference heating season "A"=average, 55°Capplication)
P
AS10S-DPNHE Fixed outlet , variable outlet
Page 15 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Table 2 P
Model:
Part load(KW)
Measuredcapacity(kW)
COP atmeasuredcapacity
Cdh CR COP at part load
G - - - - - -
E 9.820 5.840 1.63 0.987 1.00 1.63
F 7.932 7.930 2.23 0.987 1.00 2.23
A 8.687 7.360 2.03 0.987 1.00 2.03
B 5.288 9.360 2.94 0.998 0.56 2.94
C 3.400 10.870 3.87 0.997 0.31 3.84
D 1.510 12.740 4.80 0.997 0.12 4.70
Crankcaseheater (PCK)W
60
Calculation for seasonal space heating energy efficiency(For the reference heating season "A"=average, 55°C application)
AS10S-DPNHE Heat pump only, reversible heat pump
SCOPon: 3.00 SCOP:2.89
Thermostat-off mode(PTO)W
Standby mode (PSB) W OFF mode (POFF) W
10 10
Tdesignh (℃): -10
Pdesignh (kW): 10
Tbiv(℃): -5
10
Low power mode power consumption
TOL(℃): -10
Supplementary information: auxiliary electric heater 6KW CR: Part load divided by capacity.
Correction F(1) = 3%Correction F(2) = 5% (for water/brine towater heat pump)
ηs=113%
Page 16 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Information requirements for heat pump space heaters and heat pump combination heaters
Model(s):AS10S-DPNHE
Air-to-water heat pump: [yes]
Water-to-water heat pump: [no]
Brine-to-water heat pump: [no]
Low-temperature heat pump: [no]
Equipped with a supplementary heater: [yes]
Heat pump combination heater: [no]
Parameters are declared for medium-temperature application.
Parameters are declared for average climate conditions.
Item Symbol Value Unit Item Symbol Value Unit
Rated heat output (*) Prated 10 kW Seasonal space heatingenergy efficiency
ηs 113 %
Declared capacity for heating for part load at indoortemperature 20 °C and outdoor temperature Tj
Tj = – 7 °C Pdh 7.36 kW
Declared coefficient of performance or primary energyratio for part load at indoor temperature 20 °C andoutdoor temperature Tj
Tj = – 7 °C COPd
COPd
COPd
COPd
COPd
2.94
3.87
4.80
2.23
2.03
Tj = + 2 °C Pdh 9.36 kW Tj = + 2 °C
Tj = + 7 °C Pdh 10.87 kW Tj = + 7 °C
Tj = + 12 °C Pdh 12.74 kW Tj = + 12 °C
Tj = bivalent temperature Pdh 7.93 kW Tj = bivalent temperature
Page 17 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Tj = operation limittemperature
For air-to-water heat pumps:Tj = – 15 °C (if TOL < – 20 °C)
Bivalent temperature
Cycling interval capacity forheating
Degradation co-efficient (**)
Pdh 5.84 kW Tj = operation limittemperature
For air-to-water heat pumps:Tj = – 15 °C (if TOL< – 20 °C)
For air-to-water heat pumps:Operation limit temperature
Cycling interval efficiency
COPd
COPd
TOL
COPcyc orPERcyc
WTOL
1.63
x,xx
-10
x,xx orx,x
55
°C
– or%
°C
Pdh x,x kW
Tbiv
Pcych
-5
x,x
°C
kW
Cdh 0.987 — Heating water operating limittemperature
Supplementary heater
Rated heat output (*)
Power consumption in modes other than active mode
Off mode
Thermostat-off mode
Standby mode
Crankcase heater mode
Other items
Capacity control
Sound power level, outdoors
Annual energy consumption (QHE)
fixed
LWA 68
7032
dB
kWh
POFF
PTO
PSB
PCK
0.01
0.01
0.01
0.06
kW
kW
kW
kW
Psup 4.2 kW
Type of energy input
For air-to-water heat pumps:Rated air flow rate, outdoors
water flow rate
—
— 1.17
m3/h
m3/h
For heat pump combination heater:
Declared load profile
Daily electricity consumption
Contact details
Qelec
x
x,xxx kWh
Water heating energy effi-ciency
Daily fuel consumption
ηwh
Qfuel
x
x,xxx
%
kWh
Guangzhou Hiseer Air Conditioning Co.,Ltd. Address: Xicheng Industry Zone, Renhe Town,Baiyun District, Guangzhou, Guangdong, China
(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).
(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
3000
Electric heater
Page 18 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Table 3
Model:
General testconditions
Unit A B C D E F G
Part-Load % - 100 64 29 100 86 -
Voltage v - 397.9 400.9 400.5 397.9 395.9 -
Frequency Hz - 50.0 50.0 50.0 50.0 50.0 -
Total power input KW - 4.100 3.544 2.933 4.100 3.631 -
Inlet dry bulb(wet bulb) temperature
℃ - 2.10/1.01 7.01/5.99 12.00/10.99 2.10/1.01 4.02/3.01 -
Inlet/outlettemperature
℃ . . . . . . .
water/brine flow rate m3/s . . . . . . .
Inlet/outlettemperature
℃ - 47.8/55.1 40.4/48.1* 31.5/41* 47.8/55.1 43.8/51.2 -
Water flowrate m3/s - 3.25x10-4 3.25x10-4 3.25x10-4 3.25x10-4 3.25x10-4 -
Total heatingcapacity
kW - 9.840 10.420 12.790 9.840 9.950 -
Effective power input kW - 4.100 3.544 2.933 4.100 3.631 -
Coefficient ofperformance - - 2.40 2.94 4.36 2.40 2.74 -
Compressorfrequency
Hz - 50 50 50 50 50 -
test conditions for indoor side heat exchanger
test conditions for outdoor side heat exchanger for air to water
test conditions for outdoor side heat exchanger for water/brine to water
Supplementary information: Auxiliary electric heater 6KWRemark:1. *:according to EN 14825: 2016 formulas (21) of clause 8.4.1 calculated average outlet temperature.2. The test result for the reference heating season "W"=warmer is only for reference.
Parl load test
(For the reference heating season "W"=warmer , 55℃ application)P
AS10S-DPNHE Fixed outlet , variable outlet
Page 19 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Table 4 P
Model:
Part load(KW)
Measuredcapacity(kW)
COP atmeasuredcapacity
Cdh CR COP at part load
G - - - - - -
E 11.610 9.840 2.40 0.985 1.00 2.40
F 9.951 9.950 2.74 0.983 1.00 2.74
A - - - - - -
B 11.610 9.840 2.40 0.985 1.00 2.40
C 7.464 10.420 2.94 0.983 0.72 2.92
D 3.317 12.790 4.36 0.997 0.26 4.32
Crankcaseheater (PCK)W
60
TOL(℃): 2
Supplementary information: auxiliary electric heater 6KWRemark:1.).CR: Part load divided by capacity.2.) The test result for the reference heating season "W"=warmer is only for reference.
Calculation for seasonal space heating energy efficiency(For the reference heating season "W"= warmer, 55℃ application)
AS10S-DPNHE Heat pump only , reversible heat pump
SCOPon: 3.52 SCOP: 3.25
Thermostat-off mode(PTO)W
Standby mode (PSB) W OFF mode (POFF) W
10 10 10
Low power mode power consumption
Tdesignh (℃): 2
Pdesignh (kW): 12
Tbiv(℃): 4
Page 20 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Information requirements for heat pump space heaters and heat pump combination heaters
Model(s):AS10S-DPNHE
Air-to-water heat pump: [yes]
Water-to-water heat pump: [no]
Brine-to-water heat pump: [no]
Low-temperature heat pump: [no]
Equipped with a supplementary heater: [yes]
Heat pump combination heater: [no]
Parameters are declared for medium-temperature application.
Parameters are declared for warmer climate conditions.
Item Symbol Value Unit Item Symbol Value Unit
Rated heat output (*) Prated 12 kW Seasonal space heatingenergy efficiency
ηs 127 %
Declared capacity for heating for part load at indoortemperature 20 °C and outdoor temperature Tj
Tj = – 7 °C Pdh XX kW
Declared coefficient of performance or primary energyratio for part load at indoor temperature 20 °C andoutdoor temperature Tj
Tj = – 7 °C COPd
COPd
COPd
COPd
COPd
2.40
2.94
4.36
2.74
XX
Tj = + 2 °C Pdh 9.84 kW Tj = + 2 °C
Tj = + 7 °C Pdh 10.42 kW Tj = + 7 °C
Tj = + 12 °C Pdh 12.79 kW Tj = + 12 °C
Tj = bivalent temperature Pdh 9.95 kW Tj = bivalent temperature
Page 21 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Tj = operation limittemperature
For air-to-water heat pumps:Tj = – 15 °C (if TOL < – 20 °C)
Bivalent temperature
Cycling interval capacity forheating
Degradation co-efficient (**)
Pdh 9.84 kW Tj = operation limittemperature
For air-to-water heat pumps:Tj = – 15 °C (if TOL< – 20 °C)
For air-to-water heat pumps:Operation limit temperature
Cycling interval efficiency
COPd
COPd
TOL
COPcyc orPERcyc
WTOL
2.40
x,xx
2
x,xx orx,x
55
°C
– or%
°C
Pdh x,x kW
Tbiv
Pcych
4
x,x
°C
kW
Cdh 0.985 — Heating water operating limittemperature
Supplementary heater
Rated heat output (*)
Power consumption in modes other than active mode
Off mode
Thermostat-off mode
Standby mode
Crankcase heater mode
Other items
Capacity control
Sound power level, outdoors
Annual energy consumption (QHE)
fixed
LWA 68
4768
dB
kWh
POFF
PTO
PSB
PCK
0.01
0.01
0.01
0.06
kW
kW
kW
kW
Psup 2.2 kW
Type of energy input
For air-to-water heat pumps:Rated air flow rate, outdoors
water flow rate
—
—
3000
1.17
m3/h
m3/h
For heat pump combination heater:
Declared load profile
Daily electricity consumption
Contact details
Qelec
x
x,xxx kWh
Water heating energy effi-ciency
Daily fuel consumption
ηwh
Qfuel
x
x,xxx
%
kWh
Guangzhou Hiseer Air Conditioning Co.,Ltd. Address: Xicheng Industry Zone, Renhe Town,Baiyun District, Guangzhou, Guangdong, China
(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).
(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
Electric heater
Page 22 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Table 5
Model:
General testconditions
Unit A B C D E F G
Part-Load % 61 37 24 11 82 82 82
Voltage v 399.9 399.5 401.3 401.3 395.9 395.9 395.9
Frequency Hz 50.0 50.0 50.0 50.0 50.0 50.0 50.0
Total power input KW 3.422 3.227 2.843 2.680 3.724 3.724 3.724
Inlet dry bulb(wet bulb) temperature
℃ -7.01/-8.05 2.01/1.03 7.03/6.0212.00/10.98
-15.02/-16.00
-15.02/-16.00
-15.02/-16.00
Inlet/outlet temperature ℃ . . . . . . .
water/brine flow rate m3/s . . . . . . .
Inlet/outlettemperature
℃ 40.3/45.8* 34.8/41.8* 30.5/38.6* 27.3/36.9* 44.4/49.1 44.4/49.1 44.4/49.1
Water flowrate m3/s 3.25x10-4 3.25x10-4 3.25x10-4 3.25x10-4 3.25x10-4 3.25x10-4 3.25x10-4
Total heatingcapacity
kW 7.460 9.390 10.890 13.000 6.330 6.330 6.330
Effective power input kW 3.422 3.227 2.843 2.680 3.724 3.724 3.724
Coefficient ofperformance - 2.18 2.91 3.83 4.85 1.70 1.70 1.70
Compressorfrequency
Hz 50 50 50 50 50 50 50
test conditions for indoor side heat exchanger
test conditions for outdoor side heat exchanger for air to water
test conditions for outdoor side heat exchanger for water/brine to water
Supplementary information: Auxiliary electric heater 6KWRemark:1. *:according to EN 14825: 2016 formulas (21) of clause 8.4.1 calculated average outlet temperature.2. The test result for the reference heating season "C"=colder is only for reference.
Parl load test(For the reference heating season "C"=colder, 55℃ application)
P
AS10S-DPNHE Fixed outlet , variable outlet
Page 23 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Table 6 P
Model:
Part load(KW)
Measuredcapacity(kW)
COP atmeasuredcapacity
Cdh CR COP at part load
G 6.632 6.330 1.70 0.984 1.00 1.70
E 6.632 6.330 1.70 0.984 1.00 1.70
F 6.632 6.330 1.70 0.984 1.00 1.70
A 4.921 7.460 2.18 0.982 0.66 2.16
B 2.995 9.390 2.91 0.981 0.32 2.80
C 1.925 10.890 3.83 0.979 0.18 3.50
D 0.856 13.000 4.85 0.996 0.07 4.61
Crankcaseheater (PCK)W
60
-22
Pdesignh (kW): 8
Tbiv(℃): -15
TOL(℃): -15
Supplementary information: auxiliary electric heater 6KWRemark:1.).CR: Part load divided by capacity.2.) The test result for the reference heating season "C"=colder is only for reference.
Calculation for seasonal space heating energy efficiency(For the reference heating season "C"= colder,55℃ application)
AS10S-DPNHE Heat pump only , reversible heat pump
SCOPon: 2.41 SCOP:2.36
Thermostat-off mode(PTO)W
Standby mode (PSB) W OFF mode (POFF) W
10 10 10
Low power mode power consumption
Tdesignh (℃):
Page 24 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Information requirements for heat pump space heaters and heat pump combination heaters
Model(s):AS10S-DPNHE
Air-to-water heat pump: [yes]
Water-to-water heat pump: [no]
Brine-to-water heat pump: [no]
Low-temperature heat pump: [no]
Equipped with a supplementary heater: [yes]
Heat pump combination heater: [no]
Parameters are declared for medium-temperature application.
Parameters are declared for colder climate conditions.
Item Symbol Value Unit Item Symbol Value Unit
Rated heat output (*) Prated 8 kW Seasonal space heatingenergy efficiency
ηs 91 %
Declared capacity for heating for part load at indoortemperature 20 °C and outdoor temperature Tj
Tj = – 7 °C Pdh 7.46 kW
Declared coefficient of performance or primary energyratio for part load at indoor temperature 20 °C andoutdoor temperature Tj
Tj = – 7 °C COPd
COPd
COPd
COPd
COPd
2.91
3.83
4.85
1.70
2.18
Tj = + 2 °C Pdh 9.39 kW Tj = + 2 °C
Tj = + 7 °C Pdh 10.89 kW Tj = + 7 °C
Tj = + 12 °C Pdh 13.00 kW Tj = + 12 °C
Tj = bivalent temperature Pdh 6.33 kW Tj = bivalent temperature
Page 25 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Tj = operation limittemperature
For air-to-water heat pumps:Tj = – 15 °C (if TOL < – 20 °C)
Bivalent temperature
Cycling interval capacity forheating
Degradation co-efficient (**)
Pdh 6.33 kW Tj = operation limittemperature
For air-to-water heat pumps:Tj = – 15 °C (if TOL< – 20 °C)
For air-to-water heat pumps:Operation limit temperature
Cycling interval efficiency
COPd
COPd
TOL
COPcyc orPERcyc
WTOL
1.70
XX
-15
x,xx orx,x
55
°C
– or%
°C
Pdh XX kW
Tbiv
Pcych
-15
x,x
°C
kW
Cdh 0.984 — Heating water operating limittemperature
Supplementary heater
Rated heat output (*)
Power consumption in modes other than active mode
Off mode
Thermostat-off mode
Standby mode
Crankcase heater mode
Other items
Capacity control
Sound power level, outdoors
Annual energy consumption (QHE)
fixed
LWA 68 dB
kWh
POFF
PTO
PSB
PCK
0.01
0.01
0.01
0.06
kW
kW
kW
kW
Psup 8 kW
Type of energy input
For air-to-water heat pumps:Rated air flow rate, outdoors
water flow rate
—
—
3000
1.17
m3/h
m3/h
For heat pump combination heater:
Declared load profile
Daily electricity consumption
Contact details
Qelec
x
x,xxx kWh
Water heating energy effi-ciency
Daily fuel consumption
ηwh
Qfuel
x
x,xxx
%
kWh
Guangzhou Hiseer Air Conditioning Co.,Ltd. Address: Xicheng Industry Zone, Renhe Town,Baiyun District, Guangzhou, Guangdong, China
(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).
(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
8478
Electric heater
Page 26 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Page 27 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Table: 7 Part load test (For the reference heating season "A"=average, 35℃ application) P
Model: AS10S-DPNHE Fixed outlet , variable outlet
General test conditions Unit A B C D E F G
Part-Load % 88 54 35 15 100 88 -
Voltage V 397.2 398.5 398.2 396.7 398.8 397.2 -
Frequency Hz 50.0 50.0 50.0 50.0 50.0 50.0 -
Total power input kW 3.057 2.477 2.461 2.361 3.018 3.057 -
Test conditions for outdoor side heat exchange for air to water
Inlet dry bulb (wet bulb) temperature
°C -7.00/ -8.02
2.06/1.03 7.00/6.02 12.00/ 11.00
-10.00/ -11.06
-7.00/ -8.02
-
Test conditions for outdoor side heat exchange for water/brine to water
Inlet/outlet temperature °C - - - - - - -
Water/brine flow rate m³/s - - - - - - -
Test conditions for indoor side heat exchange
Inlet/outlet temperature °C 30.4/34.0 27.8/31.9*
2.361
12.420
2.461
10.830
25.6/30.8* 23.4/29.3* 31.8/35.1 30.4/34.0 -
Water flow rate m³/s 5.06x10-4 5.06x10-4 5.06x10-4 5.06x10-4 5.06x10-4 5.06x10-4 -
Total heating capacity kW 7.460 8.5477 6.760 7.460 -
Effective power input kW 3.057 2.477 3.018 3.057 -
Coefficient of performance - 2.44 3.45 4.40 5.26 2.24 2.44 -
Compressor frequency Hz 50 50 50 50 50 50 -
Supplementary information: electric heater 6KWRemark: *: According to EN 14825: 2016 formulas (21) of clause 8.4.1 calculated average outlet temperature.
Table 8 Calculation for seasonal space heating energy efficiency (For the reference heating season "A"=average , 35℃ application) P
Model: AS10S-DPNHE Heat pump only , reversible heat pump
Tdesignh (°C): -10
Pdesignh (kW): 8
Tbiv(°C): -7
TOL(°C): -10
Part load (kW) Measured ca-pacity (kW)
COP at measured capacity
Cdh CR COP at part load
G - - - - - -
E 8.430 6.760 2.24 0.980 1.00 2.24
F 7.457 7.460 2.44 0.980 1.00 2.44
A 7.457 7.460 2.44 0.980 1.00 2.44
B 4.540 8.5477 3.45 0.976 0.53 3.38
C 2.918 10.830 4.40 0.976 0.27 4.13
D 1.297 12.420 5.26 0.996 0.10 5.08
Low power mode power consumption
Thermostat-off mode [PTO] W Standby mode [PSB] W
Crankcase heater [PCK] W Off mode [POFF] W
10 10 60 10
SCOPon: 3.44 SCOP: 3.27
Correction F(1) = 3% Correction F(2) = 5% (for water/brine to water heat pump )
ηs=128%
Supplementary information: Electric heater 6KW CR: part load divided by capacity.
Page 28 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Information requirements for heat pump space heaters and heat pump combination heaters
Model(s):AS10S-DPNHE
Air-to-water heat pump: [yes]
Water-to-water heat pump: [no]
Brine-to-water heat pump: [no]
Low-temperature heat pump: [no]
Equipped with a supplementary heater: [yes]
Heat pump combination heater: [no]
Parameters are declared for low-temperature application.
Parameters are declared for average climate conditions.
Item Symbol Value Unit Item Symbol Value Unit
Rated heat output (*) Prated 8 kW Seasonal space heatingenergy efficiency
ηs 128 %
Declared capacity for heating for part load at indoortemperature 20 °C and outdoor temperature Tj
Tj = – 7 °C Pdh 7.460 kW
Declared coefficient of performance or primary energyratio for part load at indoor temperature 20 °C andoutdoor temperature Tj
Tj = – 7 °C COPd
COPd
COPd
COPd
COPd
3.45
4.40
5.26
2.44
2.44
Tj = + 2 °C Pdh 8.547 kW Tj = + 2 °C
Tj = + 7 °C Pdh 10.83 kW Tj = + 7 °C
Tj = + 12 °C Pdh 12.42 kW Tj = + 12 °C
Tj = bivalent temperature Pdh 7.46 kW Tj = bivalent temperature
Page 29 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Tj = operation limittemperature
For air-to-water heat pumps:Tj = – 15 °C (if TOL < – 20 °C)
Bivalent temperature
Cycling interval capacity forheating
Degradation co-efficient (**)
Pdh 6.76 kW Tj = operation limittemperature
For air-to-water heat pumps:Tj = – 15 °C (if TOL< – 20 °C)
For air-to-water heat pumps:Operation limit temperature
Cycling interval efficiency
COPd
COPd
TOL
COPcyc orPERcyc
WTOL
2.24
x,xx
-10
x,xx orx,x
55
°C
– or%
°C
Pdh x,x kW
Tbiv
Pcych
-7
x,x
°C
kW
Cdh 0.980 — Heating water operating limittemperature
Supplementary heater
Rated heat output (*)
Power consumption in modes other than active mode
Off mode
Thermostat-off mode
Standby mode
Crankcase heater mode
Other items
Capacity control
Sound power level, outdoors
Annual energy consumption (QHE)
fixed
LWA 68
5332
dB
kWh
POFF
PTO
PSB
PCK
0.01
0.01
0.01
0.06
kW
kW
kW
kW
Psup 1.2 kW
Type of energy input
For air-to-water heat pumps:Rated air flow rate, outdoors
water flow rate
—
—
3000
1.82
m3/h
m3/h
For heat pump combination heater:
Declared load profile
Daily electricity consumption
Contact details
Qelec
x
x,xxx kWh
Water heating energy effi-ciency
Daily fuel consumption
ηwh
Qfuel
x
x,xxx
%
kWh
Guangzhou Hiseer Air Conditioning Co.,Ltd. Address: Xicheng Industry Zone, Renhe Town,Baiyun District, Guangzhou, Guangdong, China
(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).
(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
Electric heater
Page 30 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Table 9 Parl load test (For the reference heating season "C"=colder, 35℃ application)
P
Model:
General testconditions
Unit A B C D E F G
Part-Load % 61 37 24 11 82 82 82
AS10S-DPNHE Fixed outlet , variable outlet
Voltage v 398.1 399.5 400.2 401.1 395.0 395.0 395.0
Frequency Hz 50.0 50.0 50.0 50.0 50.0 50.0 50.0
Total power input KW 2.656 2.355 2.421 2.405 2.696 2.696 2.696
test conditions for outdoor side heat exchanger for air to water
Inlet dry bulb(wet bulb)temperalure
℃ -7/-8.05 2.11/1.03 7.00/6.0212.01/10.97
-15.02/-16.00
-15.02/-16.00
-15.02/-16.00
Inlet/outlettemperature
℃ . . . . . . .
test conditions for outdoor side heat exchanger for air to water
test conditions for outdoor side heat exchanger for water/brine to water
water/brine flowrate m3/s . . . . . . .
Inlet/outlettemperature
℃ 27.7/31.4* 25.4/29.8* 24.1/29.7* 23.6/30.1* 28.9/31.9 28.9/31.9 28.9/31.9
Water flowm3/s 5 06x10-4 5 06x10-4 5 06x10-4 5 06x10-4 5 06x10-4 5 06x10-4 5 06x10-4
test conditions for indoor side heat exchanger
rate m3/s 5.06x10 5.06x10 5.06x10 5.06x10 5.06x10 5.06x10 5.06x10
Total heatingcapacity
kW 7.810 9.160 11.740 13.590 6.390 6.390 6.390
Effective powerinput
kW 2.656 2.355 2.421 2.405 2.696 2.696 2.696
Coefficient of2 94 3 89 4 85 5 65 2 37 2 37 2 37
performance - 2.94 3.89 4.85 5.65 2.37 2.37 2.37
Compressorfrequency
Hz 50 50 50 50 50 50 50
Supplementary information: Auxiliary electric heater 6KWRemark:1.1. *: According to EN 14825: 2016 formulas (21) of clause 8.4.1 calculated average outlet temperature.2. The test result for the reference heating season "C"=colder is only for reference.
Page 31 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Table 10 P
Model:
Part load(KW)
Measuredcapacity(kW)
COP atmeasuredcapacity
Cdh CR COP at part load
G 6.390 6.390 2.37 0.978 1.00 2.37
E 6.390 6.390 2.37 0.978 1.00 2.37
F 6.390 6.390 2.37 0.978 1.00 2.37
A 4.740 7.810 2.94 0.977 0.61 2.90
B 2.890 9.160 3.89 0.975 0.32 3.69
C 1.860 11.740 4.85 0.975 0.16 4.28
D 0.820 13.590 5.65 0.996 0.06 5.31
Crankcaseheater (PCK)W
60
-22
Pdesignh (kW): 8
Tbiv(℃): -15
TOL(℃): -15
Supplementary information: auxiliary electric heater 6KWRemark:1.).CR: Part load divided by capacity.2.) The test result for the reference heating season "C"=colder is only for reference.
Calculation for seasonal space heating energy efficiency (For the reference heating season "C"= colder, 35℃ application)
AS10S-DPNHE Heat pump only , reversible heat pump
SCOPon: 3.08 SCOP:3.00
Thermostat-off mode(PTO)W
Standby mode (PSB) W OFF mode (POFF) W
10 10 10
Low power mode power consumption
Tdesignh (℃):
Page 32 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Information requirements for heat pump space heaters and heat pump combination heaters
Model(s):AS10S-DPNHE
Air-to-water heat pump: [yes]
Water-to-water heat pump: [no]
Brine-to-water heat pump: [no]
Low-temperature heat pump: [no]
Equipped with a supplementary heater: [yes]
Heat pump combination heater: [no]
Parameters are declared for low-temperature application.
Parameters are declared for colder climate conditions.
Item Symbol Value Unit Item Symbol Value Unit
Rated heat output (*) Prated 8 kW Seasonal space heatingenergy efficiency
ηs 117 %
Declared capacity for heating for part load at indoortemperature 20 °C and outdoor temperature Tj
Tj = – 7 °C Pdh 7.81 kW
Declared coefficient of performance or primary energyratio for part load at indoor temperature 20 °C andoutdoor temperature Tj
Tj = – 7 °C COPd
COPd
COPd
COPd
COPd
3.89
4.85
5.65
2.37
2.94
Tj = + 2 °C Pdh 9.16 kW Tj = + 2 °C
Tj = + 7 °C Pdh 11.74 kW Tj = + 7 °C
Tj = + 12 °C Pdh 13.59 kW Tj = + 12 °C
Tj = bivalent temperature Pdh 6.39 kW Tj = bivalent temperature
Page 33 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Tj = operation limittemperature
For air-to-water heat pumps:Tj = – 15 °C (if TOL < – 20 °C)
Bivalent temperature
Cycling interval capacity forheating
Degradation co-efficient (**)
Pdh 6.39 kW Tj = operation limittemperature
For air-to-water heat pumps:Tj = – 15 °C (if TOL< – 20 °C)
For air-to-water heat pumps:Operation limit temperature
Cycling interval efficiency
COPd
COPd
TOL
COPcyc orPERcyc
WTOL
2.37
XX
-15
x,xx orx,x
55
°C
– or%
°C
Pdh XX kW
Tbiv
Pcych
-15
x,x
°C
kW
Cdh 0.978 — Heating water operating limittemperature
Supplementary heater
Rated heat output (*)
Power consumption in modes other than active mode
Off mode
Thermostat-off mode
Standby mode
Crankcase heater mode
Other items
Capacity control
Sound power level, outdoors
Annual energy consumption (QHE)
fixed
LWA 68 dB
kWh
POFF
PTO
PSB
PCK
0.01
0.01
0.01
0.06
kW
kW
kW
kW
Psup 8 kW
Type of energy input
For air-to-water heat pumps:Rated air flow rate, outdoors
water flow rate
—
—
3000
1.82
m3/h
m3/h
For heat pump combination heater:
Declared load profile
Daily electricity consumption
Contact details
Qelec
x
x,xxx kWh
Water heating energy effi-ciency
Daily fuel consumption
ηwh
Qfuel
x
x,xxx
%
kWh
Guangzhou Hiseer Air Conditioning Co.,Ltd. Address: Xicheng Industry Zone, Renhe Town,Baiyun District, Guangzhou, Guangdong, China
(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).
(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
6438
Electric heater
Page 34 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Table 11Parl load test (For the reference heating season "W"=warmer, 35℃ application) P
Model:
General testconditions
Unit A B C D E F G
Part-Load % - 100 64 29 100 86 -
AS10S-DPNHE Fixed outlet , variable outlet
Voltage v - 398.9 400.8 401.1 398.9 395.0 -
Frequency Hz - 50.0 50.0 50.0 50.0 50.0 -
Total power input KW - 2.532 2.588 2.438 2.532 2.477 -
test conditions for outdoor side heat exchanger for air to water
Inlet dry bulb(wet bulb) ℃ - 2.10/1.02 7.00/6.02 12.01/10.99 2.10/1.02 4.02/3.04 -
Inlet/outlettemperature
℃ . . . . . . .
water/brine flowm3/s
test conditions for outdoor side heat exchanger for air to water
test conditions for outdoor side heat exchanger for water/brine to water
rate m3/s . . . . . . .
Inlet/outlettemperature
℃ - 30.5/34.9 27.4/32.9* 24.4/30.9* 30.5/34.9 28.8/33.4 -
Water flowrate m3/s - 5.06x10-4 5.06x10-4 5.06x10-4 5.06x10-4 5.06x10-4 -
test conditions for indoor side heat exchanger
Total heatingcapacity
kW - 9.240 11.750 13.630 9.240 9.660 -
Effective powerinput
kW - 2.532 2.588 2.438 2.532 2.477 -
Coefficient ofperformance - - 3.65 4.54 5.59 3.65 3.90 -
Compressorfrequency
Hz - 50 50 50 50 50 -
Supplementary information: Auxiliary electric heater 6KWRemark:1. *:according to EN 14825: 2016 formulas (21) of clause 8.4.1 calculated average outlet temperature.2. The test result for the reference heating season "W"=warmer is only for reference.
Page 35 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Table 12 P
Model:
Part load(KW)
Measuredcapacity(kW)
COP atmeasuredcapacity
Cdh CR COP at part load
G - - - - - -
E 11.270 9.240 3.65 0.976 1.00 3.65
F 9.660 9.660 3.90 0.976 1.00 3.90
A - - - - - -
B 11.270 9.240 3.65 0.976 1.00 3.65
C 7.250 11.750 4.54 0.977 0.62 4.48
D 3.220 13.630 5.59 0.996 0.24 5.52
Crankcaseheater (PCK)W
60
2
Pdesignh (kW): 11
Tbiv(℃): 4
TOL(℃): 2
Supplementary information: auxiliary electric heater 6KWRemark:1.).CR: Part load divided by capacity.2.) The test result for the reference heating season "W"=warmer is only for reference.
Calculation for seasonal space heating energy efficiency (For the reference heating season "W"= warmer, 35℃ application)
AS10S-DPNHE Heat pump only , reversible heat pump
SCOPon: 4.89 SCOP: 4.38
Thermostat-off mode(PTO)W
Standby mode (PSB) W OFF mode (POFF) W
10 10 10
Low power mode power consumption
Tdesignh (℃):
Page 36 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Information requirements for heat pump space heaters and heat pump combination heaters
Model(s):AS10S-DPNHE
Air-to-water heat pump: [yes]
Water-to-water heat pump: [no]
Brine-to-water heat pump: [no]
Low-temperature heat pump: [no]
Equipped with a supplementary heater: [yes]
Heat pump combination heater: [no]
Parameters are declared for low-temperature application.
Parameters are declared for warmer climate conditions.
Item Symbol Value Unit Item Symbol Value Unit
Rated heat output (*) Prated 11 kW Seasonal space heatingenergy efficiency
ηs 172 %
Declared capacity for heating for part load at indoortemperature 20 °C and outdoor temperature Tj
Tj = – 7 °C Pdh XX kW
Declared coefficient of performance or primary energyratio for part load at indoor temperature 20 °C andoutdoor temperature Tj
Tj = – 7 °C COPd
COPd
COPd
COPd
COPd
3.65
4.54
5.59
3.90
XX
Tj = + 2 °C Pdh 9.24 kW Tj = + 2 °C
Tj = + 7 °C Pdh 11.75 kW Tj = + 7 °C
Tj = + 12 °C Pdh 13.63 kW Tj = + 12 °C
Tj = bivalent temperature Pdh 9.66 kW Tj = bivalent temperature
Page 37 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Tj = operation limittemperature
For air-to-water heat pumps:Tj = – 15 °C (if TOL < – 20 °C)
Bivalent temperature
Cycling interval capacity forheating
Degradation co-efficient (**)
Pdh 9.24 kW Tj = operation limittemperature
For air-to-water heat pumps:Tj = – 15 °C (if TOL< – 20 °C)
For air-to-water heat pumps:Operation limit temperature
Cycling interval efficiency
COPd
COPd
TOL
COPcyc orPERcyc
WTOL
3.65
x,xx
2
x,xx orx,x
55
°C
– or%
°C
Pdh x,x kW
Tbiv
Pcych
4
x,x
°C
kW
Cdh 0.976 — Heating water operating limittemperature
Supplementary heater
Rated heat output (*)
Power consumption in modes other than active mode
Off mode
Thermostat-off mode
Standby mode
Crankcase heater mode
Other items
Capacity control
Sound power level, outdoors
Annual energy consumption (QHE)
fixed
LWA 68
3441
dB
kWh
POFF
PTO
PSB
PCK
0.01
0.01
0.01
0.06
kW
kW
kW
kW
Psup 1.8 kW
Type of energy input
For air-to-water heat pumps:Rated air flow rate, outdoors
water flow rate
—
—
3000
1.82
m3/h
m3/h
For heat pump combination heater:
Declared load profile
Daily electricity consumption
Contact details
Qelec
x
x,xxx kWh
Water heating energy effi-ciency
Daily fuel consumption
ηwh
Qfuel
x
x,xxx
%
kWh
Guangzhou Hiseer Air Conditioning Co.,Ltd. Address: Xicheng Industry Zone, Renhe Town,Baiyun District, Guangzhou, Guangdong, China
(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).
(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
Electric heater
Page 38 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Table :1 Water heating energy efficiency (ηwh) N/A
Model : Declared load profile:
Heat source, Air temperature DB/WB …...... (°C): /
Ambient temperature of storage tank …........ (°C):
Voltage …........................................................ (V):
Frequency ….................................................. (Hz):
Measured quantity Result Remark
Standby heat loss Pstby***
Reference energy Qref***
Daily electricity consumption Qelec***
Weekly electricity consumption with smart controls Qelec,week,smart***
Weekly electricity consumption without smart controls Qelec,week ***
Smart control factor SCF *
Smart control compliance smart
Ambient correction term Qcor *
Water heating energy efficiency (smart=0) ηwh *
Water heating energy efficiency (smart=1) ηwh *
Supplementary information: -
Number of brine pump considered:-
Setting of controls: -
Duct connection:-
Note: ηwh , Qref, Qelec are calculated acc. to (EU) 814/2013 Annex IV §3.a and OJ (2014/C 207/03)
Rounding to: *) 1 decimal places; **) 2 decimal places; ***) 3 decimal places; ****) nearest integer
Page 39 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Table 2: Sound power level measurement P
Model : AS10S-DPNHE
Heat source, Air temperature DB/WB ......... (°C): 7/6
Voltage ........................................................... (V): 398.8
Frequency ..................................................... (Hz): 50
Working condition class...................................: Class A
Acoustical environment...................................: Reverberation test room
Windshield type.............................................: Sponge
Measured position amount ...............…...........: 6
Measured quantity LWA,indoors LWA,outdoors Remark
Sound pressure level Lpf**** - 61dB
Spheres radius r * - -
Sound power level LwA**** - 68dB
Supplementary information: water inlet/outlet temperature: 47/55°C
Setting of controls: -
Duct connection:-
Rounding to: *) 1 decimal places; **) 2 decimal places; ***) 3 decimal places; ****) nearest integer
Page 40 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Attachment No.1: Key Components Table
Model AS10S-DPNHE
Part Technical data
1. Compressor
Manufacture Hitachi Compressor Products (Guangzhou) Co.,Ltd
Type E404DH-38D2G Rated capacity 9870W Serial-number / Rated input 380-415V~, 50Hz, 3300W
2.Condenser Type B25TH X 28/1P-NSC-M Manufacture SWEP Technology(Suzhou)Co.,Ltd.
Bauart Construction Plate heat exchanger Number of plate 28 Plate spacing 2.24mm
Water pip specification G1 1/4″
Max. permissible pressure 5.0MPa
Dimension 119±1(L)mmX526±2(H)mmX71±1(D)mm
3. Evaporator
Manufacture Foshan Nanhai Tianshida cooling equipment co.,ltd
Type AW09-08-01-00 Fan type Axial Bauart Construction Finned-coil heat exchanger Fin type Hydrophilic aluminum Fin spacing 2.0±0.02 mm Tube pitch x row pitch 25mm X12.7mm Pip specification Φ 9.52mm Max. permissible pressure 4.5MPa Dimension 808(L)mmX968(H)mmX418(D)mm
4. Fan motor ofevaporator
Manufacture Hangzhou Panasonic motor co.,ltd Type EHDS83AZD Specification 120W Serial-number /
5. Controller Manufacture CAREL Electronic(suzhou)co.,Ltd Type CPPB006DS0
Page 41 of 42 Test report no. HS64.181.15.00764.13 Rev.01
Attachment No.2: Equipment List
Equipment ID No. Model Brand/Manufacturer Calibration due date
R&A performance measuring system -- 20kW guangzhoupinxin 2017-08-05
- Flowmeter S5J607346925 AXF025G YOKOGAWA 2017-06-25 - Platinum resistance -- PT-100 YINUO 2017-08-05 - Multi-function digital power meter 91MB20642 WT230 YOKOGAWA 2017-08-05
-Pressure transmitter 240502 MPM489 MICRO 2017-08-05 -Pressure transmitter 240503 MPM489 MICRO 2017-08-05 Water pressure difference transmitter 291459 MDM3051 MICRO 2017-08-05
AC source Supply -- 40KVA Qiaodong 2018-03-14
Temperature and humidity meter
H5110021 HMD42 VAISALA 2017-08-05
Reverberation test rooms
ZYS13101154 7.86m*3.26m*4.94m GD Midea 2017-11-12
-PULSE System 3050-107994 3050-A-040 B & K 2017-11-06
-Microphone 2915712 4942-A-021 B & K 2017-10-16
-Microphone 2915714 4942-A-021 B & K 2017-10-16
-Microphone 2915711 4942-A-021 B & K 2017-10-16
-Microphone 2915713 4942-A-021 B & K 2017-10-16
-Sound Calibrator 2637378 4231 B & K 2017-05-15
-Reference sound source
2931701 4204 B & K 2017-11-23
- Temperature measuring system
ZYS13101152 UT35A YOKOGAWA 2017-09-23
- AC source Supply 119708382 AN97090TT Ainuo 2017-08-24
- Multi-function digital power meter
891303091 8904F Qingdao Qingzhi 2017-09-03
-Humidity sensor H2250026 HMD60Y VAISALA 2017-09-15
-Humidity sensor H2250027 HMD60Y VAISALA 2017-09-15
-Vibration Calibrator 2627037 4294 B&K 2018-04-25
-- End of report ---
Page 42 of 42 Test report no. HS64.181.15.00764.13 Rev.01