PC-based Energy Automation with IEC 61850

11/13/2013

Me

Hello!

Jürgen ReschIndustry Manager Energyjuergenr@copadata.com

COPA-DATAThe Future is Ergonomics

Ergonomic and highly-dynamic process solutions for HMI/SCADA, dynamic production reporting and integrated PLC systems

11 offices, international network with distributors and partners, active in more than 40 countries

do it your way since 1987

More flexibility and safety for your projects

Ing. Thomas PunzenbergerCOPA-DATA CEO

International network, local contact persons

COPA-DATAHeadquarters

COPA-DATA Group

60

40

20

0

1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013

80

100

140

120

160

180

160

Number of Employees

84

For us, being close to the customer means Decentralized Growth

What we do

One System – Many Solutions

One System – Many Industries

Successful Customers

A N D M A N Y M O R E …

ENERGY & INFRASTRUC TURE

S I E M E N S S P R E C H E R A U T O M AT I O N A L S T O M G R I D

L E I T W I N DC A P U L A R E M S D A QSEL CG AUTOMATION

GE

What we are focusing on in Energy

Energy Automation

• Substation Automation Transmission

• Substation Automation Distribution

• Hydro Power Plants

• Control Centers Distribution

• Integration of Renewables (Wind, PV)

Substation Automation with IEC 61850

It’s about communication

• IED – IED

• IED – HMI

This is how SAS typically looks like

BAY 1

WAN

Web client

Control CenterIEC60870-5-104 master

STATION ComputerEngineeringWS

ClientWS

LAN

BCUBay Control Unit

BMUBay Monitoring Unit

Protection…

BAY 2

BCUBay Control Unit

BMUBay Monitoring Unit

Protection…

BAY n

BCUBay Control Unit

BMUBay Monitoring Unit

Protection…

SERVER STAND-BY

IEC 61850GOOSE

IEC 60870-5-101/104

This is how SAS typically looks like

BAY 1

WAN

Web client

Control CenterIEC60870-5-104 master

STATION ComputerEngineeringWS

ClientWS

LAN

BCUBay Control Unit

BMUBay Monitoring Unit

Protection…

BAY 2

BCUBay Control Unit

BMUBay Monitoring Unit

Protection…

BAY n

BCUBay Control Unit

BMUBay Monitoring Unit

Protection…

SERVER STAND-BY

IEC 61850client server

Challenge

Configuration of IEC 61850 Clients

IEC 61850 Configuration

Easy configuration of a complex topic

ICD Files

SSD File

SCD File

CID File

ICD Files

CID File

CID File

Tool

Tool

Tool

Tool

IEC 61850 Configuration

Easy configuration of a complex topic

ICD Files

SSD File

SCD File

CID File

ICD Files

CID File

CID File

Tool

Tool

Tool

Tool

SCD

ICD

CID

SCD

ICD

CID

.txt

.txt

New challenge

Load shedding with IEC 61850 GOOSE

Load shedding with IEC 61850 GOOSE

• Trend to CRAS (Centralized Remedial Action Schemes)

• Short response time (within a wavelength [20.00ms/50Hz, 16.67ms/60Hz])

• High demand for guaranteed response time

Load shedding with IEC 61850 GOOSE

• Trend to CRAS (Centralized Remedial Action Schemes)

• Short response time (within a wavelength [20.00ms/50Hz, 16.67ms/60Hz])

• High demand for guaranteed response time

Can we do that with of the shelf hardware and a standard implementation of GOOSE?

How it would look like

Detects fault and trips the breaker

1

Calculates current matrix and sends trips to other relays

2

Relays execute necessary trips

3

GOOSE Publishers

GOOSE Subscribers

GOOSE Publisher

and Subscriber

Questions

• Can we do that with a Windows platform?

• Can we run a SCADA application at the same time?

• How shall the GOOSE control blocks be configured?

How we tested it

Relay PC

DSC10 Bay Control Unit (Ducati Sistemi)

© by Ducati

Load Shedding PC

Analysis PC

IEC 61850 GOOSE

t1 t2

1

2

3

How we tested it

Relay PC

DSC10 Bay Control Unit (Ducati Sistemi)

Load Shedding PC

Analysis PC

IEC 61850 GOOSE

IEC 61850 MMSDNP3

t1 t2

3ms cycle time

Results

• Combined GOOSE messages with multiple data objects do perform significantly better

• Despite the load on the network and on the SCADA host with the load shedding logic, the system is capable of delivering a fairly consistent load shedding performance

To be read here: