3 Closed-Loop Control Closed-loop control systems are more effective than open- loop systems With the addition of a feedback loop they become self-regulating Components of a closed- loop system include: – The primary element - sensor – The controlled variable – The measured variable – The control signal – The final correcting element
Citation preview
Process Control Methods
1
Open-Loop Control
2
• Process control operations are performed automatically byeither open-loop or closed-loop systems
• Processes controlled only by set-point commands without feedback are open-loop
• Open-loop systems are used in applications where simple processes are performed
• Open-loop systems are relatively inexpensive
3
Closed-Loop Control• Closed-loop control systems
are more effective than open- loop systems
• With the addition of a feedback loop they become self-regulating
• Components of a closed-loop system include:– The primary element -
sensor– The controlled
variable– The measured
variable– The control signal– The final correcting
element
4
Process Behavior• The objective of process control is to cause a
controlled variable to remain at a constant value at or near some desired set-point
• The controlled variable changes because of:– A disturbance appears– Load demands vary– Set points are adjusted
Process Behavior Example
• Flow through the pipe is theprocess
• Fluid flow rate is the controlled variable
• Valve position is the set point• Demand for the fluid
downstream is the load
• Variance in upstream pressureis the disturbance 5
6
Single-Variable Control Loop• Several process variables are controlled at once in a typical
production machine• Usually, only one individual feedback loop is required to control
each variable• Single-variable control loops consist of the following elements:
– Measuring device– Transducer/transmitter– Controller– Final Control Element
7
Response Time of the Instrument
• All instruments have a time lag - the time from when a variable is measured till the corrective action is taken
• Factors affecting lag:– Response time of sensor– Time lag of transducer– Distance the signal must
travel– Time required for thecontroller to process– Distance control signal must
travel– Time lag of the final
correcting element
8
Time Lag• The controlled variable itself may contribute to
lagproblems because of inertia in the variable
• Lag due to inertia of the variable is referred to aspure lag
• Another factor that affects time lag is dead time - this is the elapsed time from when the deviation occurs and corrective action takes place
Illustration of Pure Lag
9
10
Selecting a Controller• The controller mode selection is based upon the
requirements of the process and one of the following control modes will be used:– On/Off– Proportional– Integral– Derivative
On-Off Control
• Used for slow acting operations where lag is unavoidable
• Final correcting element is either fully-on or fully-off
• The primary drawback of on-off control is the rapid switching of the final control element
• On-off differential or hysteresis isprogrammed into the controller
• Deadband refers to the differing levels at which a controller switches on and off
11
12
Continuous Control• On/Off control is acceptable for process where the variable
isset between two limits
• For processes where the variable needs to be kept at particular setpoint level, proportional control is used
• Proportional action can be accomplished in two ways:– Time Proportioning Method– Amplitude Proportional Method
Time Proportioning• Is a method whereby the
output of the controller is continually switched on and off
• On versus off times are varied dependent upon process requirements
13
14
Amplitude Proportional• Most common technique to produce a
proportional signal• The control signal is proportional in amplitude to
the error signal• The signal may be amplified and the
amplification may be referred to as proportional gain and proportional band
Proportional Gain Comparison
Level control at a gain of 1
15
Proportional Gain Comparison
(Gain set at 2)
16
Proportional Band
• Proportional band is defined as the percentage change in the controlled variable that causes the final correcting element to go through 100 percent of its range
PB =Controlled Variable % ChangeFinal Correcting Element %
Change
17
Integral Control
• Because of the introduction of offset in a control process, proportional control alone is often used in conjunction with Integral control
• Offset is the difference between set point and the measured value after corrective action has taken place
18
Reset Action• Integral control is also
referred to as reset control as the set point is continuously reset as long as an error is present
• Integral adjustments that affect the output are labeled 3 ways:– Gain - expressed as a whole
number– Reset - Expressed in
repeats per minute– Integral Time - Expressed in
minutes per reset
19
Derivative Mode
• For rapid load changes, the derivative mode is typically used to prevent oscillation in a process system
• The derivative mode responds to the rate of change of the error signal rather than its amplitude
• Derivative mode is never used by itself, but in combination with other modes
• Derivative action cannot remove offset
20
Control Mode Summary
21
22
Tuning the Controller• Fine-tuning is the process to optimize the controller
operationby adjusting the following settings:– Gain setting (proportional mode)– Reset rate (integral mode)– Rate (derivative mode)
• Three steps are taken when tuning a systems– Study the control loop– Obtain clearance for tuning procedures– Confirm the correction operation of the system components
23
Trial-and-Error Tuning• Does not use mathematical methods, instead a chart
recorder is used and several bump tests are made in the proportional and integral modes
• Trial-and-error tuning is very time consuming and requires considerable experience on the part of the technician or operator
24
Ziegler-Nichols Tuning Methods
• Two formal procedures for tuningcontrol loops:–Continuous cycling method–Reaction curve method
25
Continuous Cycling Method• The continuous cycling method analyzes the process by
forcing the controlled variable to oscillate in even, continuous cycles
• The time duration of one cycle is called an ultimate period. The proportional setting that causes the cycling is called the ultimate proportional value
• These two values are then used in mathematical formulas tocalculate the controller settings
26
Continuous Cycle Calculations• Proportional only controller• Proportional Gain
– Kc = Gu x 0.5• KC = proportional gain,• Gu= ultimate gain
• Proportional Band– PB = Pbu x 2
• PB = proportional band• Pbu = ultimate proportional band
Continuous Cycling Formulas
27
28
Ziegler-Nichols Reaction Curve Tuning Method• This method avoids the forced oscillations that are found in
the continuous cycle tuning method• Cycling should be avoided if the process is hazardous
or critical• This method uses step changes and the rate at which
theprocess reacts is recorded
• The graph produces three different values used in mathematical calculations to determine the proper controller settings
Reaction Curve Tuning Formulas
29
Direct Synthesis Method• The direct synthesis method uses the
same procedures to analyze the process times as the Ziegler-Nichols reaction curve method
• One advantage of this method is that it directly matches (synthesizes) synthesizes the process
• The first step in this method is perform a bump test and recording the dynamic settling time
• Depending upon the complexity of the process, one of several dynamic response signals may develop as shown on the right
30
Direct Synthesis Tuning Calculations
31
32
Advanced Control Techniques• Some complex manufacturing operations require
more precise control than available with PID controllers
• Four Techniques frequently used are:– Cascade control– Feed forward control– Ratio control– Adaptive control
Cascade Control• Cascade control
systems use a second feedback loop with a separate sensor and controller
• Cascade control is effective in overcoming lag in some systems
33
Feedforward Control• Feedforward control
measures a variable that enters a process and takes corrective action if it is affected by a disturbance, reducing or eliminating deviation from the set point
34
Ratio Control• Used in mixing systems
where an uncontrolled flow of material (wild flow) is monitored and used to control the second material which is controlled according to the desired ratio between the two components
35
36
Adaptive Control
• To accommodate a nonlinear process, a microelectronic controller uses software that has adaptive control capabilities to compensate for nonlinear transducers and sensors
END
37
• This workforce solution was funded by a grant awarded by the U.S. Department of Labor’s Employment and Training Administration. The solution was created by the grantee and does not necessarily reflect the official position of the U.S. Department of Labor. The Department of Labor makes not guarantees, warranties, or assurances of any kind, express or implied, with respect to such information, including any information on linked sites and including, but not limited to, accuracy of the information or tis completeness, timeliness, usefulness, adequacy, continued availability, or ownership.