SPRECON®-E-T3COmPaCT mOdulE fOR auTOmaTiON aNd REmOTE CONTROl
TEChNiCal BROChuRE
ENgliSh
www.sprecher-automation.com
2
SPRECON-E SCada aNd auTOmaTiONSCADA systems are indispensable for the central control and monitoring of distributed installations in the power in-dustry. Depending on the field of application, the RTUs have to satisfy various requirements, regarding I/O quantities, I/O types, environmental conditions, communication protocols, and logic functions.SPRECON-E SCADA and Automation Systems are desig-ned in such a way that the optimum solution, technically and economically, is available for the project, while still maintai-ning an integrated system.The SPRECON-E SCADA and Automation system consists of the following devices from the SPRECON-E product fa-mily:
• Multifunctional automation unit SPRECON-E-C• Compact modules SPRECON-E-T3• Protection devices SPRECON-E-P• SPRECON V460 Control Room Computer System
All are integral parts of a uniform and system concept (data structures, communication, logic functions, engineering and service tools). However, they differ regarding their size and various operation parameters.
SPRECON-E-T3SPRECON-E-T3 modules have been developed specifically for operation in small and medium-sized load quantities. They can be used within a SCADA system as RTU, optionally with automation functions.The standard communication protocols, IEC 60870- 5-104 (Ethernet) and IEC 60870-5-101 are implemented. Interfa-cing of various IEDs is possible using the Modbus protocol.Thanks to its modularity SPRECON-E-T3 provides the requi-red flexibility and scalability.
fiEldS Of aPPliCaTiONThe SPRECON-E-T3 is used for:
• Electrical power supply• Substations and distribution stations• Caloric Power Plants• Hydroelectric Power Plants• Traction Power Supply• Industrial Grids• Wind Power Plants• Smart Grid
• Municipal utilities• Water Supply• Sewage• Gas Supply• District Heating• Traffic Control Systems• Tunnel Control Systems
CONfiguRaTiON aNd ENgiNEERiNgEach SPRECON-E-T3 unit consists of an intelligent basic module and the appropriate I/O modules communicating via the internal system bus. Optionally a SPRECON-E control panel (CP, CCP) can be connected. The RTUs can be indi-vidually adapted to the application by combining various I/O modules.All functions are engineered using the SPRECON-E Designer, allowing separate system configuration and unit configuration. The SPRECON-E Designer can be used offline, online and from remote. The device configuration can be read-out from the device online.A flexible licensing model allows to adapt the engineering and service tools to the customer requirements.
SPRECON-E-T3 fEaTuRES• Configuration can be saved on an external storage de-
vice via an integrated interface, and transferred to a re-placement device.
• Pluggable screw-type terminals for I/Os• PLC functions (optional) based on IEC 61131-3 using
the SPRECON-PLC Designer• Control, alarm panel (optional)
gENERal OvERviEw
3
maiN fuNCTiONS• Configurable communication interfaces• Plug-and-play USB Memory• Control and monitoring of primary equipment, e.g. CBs,
valves etc.• Interlocking of switch gear• Flexible command sequence according IEC• Single and double commands with 1-, 1½-, 2-pole com-
mand output• Local / Remote• LED signalling on the I/O modules• Analog threshold monitoring• Mean value calculation• Maximum/minimum value calculation• Configurable transmission modes for measured values• Pulse counter inputs• Counters for operating hours, switching operations• PLC logic acc. IEC 61131 (optional)• Event logging• Alarm logging• Time Synchronisation via DCF-77, GPS, NTP or from
SCADA centre• Self-monitoring• Remote maintenance and configuration
The software features described above are typically configu-red using the SPRECON-E Engineering Center.
REmOvaBlE mEmORyThe SPRECON-E-T3 is equipped with a removable memory interface as standard. It is used to save all the relevant data such as configuration and firmware version. On each restart, the data of the internal flash memory are compared to tho-se on the memory. If changed, the data from the memory is transferred.This functionality means that it is very easy to replace modu-les without additional tools like Laptop etc. onsite. Moreover, a configuration prepared previously can be transferred on the memory and easily taken to site.
TyPiCal aPPliCaTiONS aNd CONfiguRaTiONS
SPRECON-E-T3 Configuration Example
4
COmmuNiCaTiON• RS232, RS422/485, 10/100 MBit Ethernet• Permanent or dial-up connection (via external modem)• Wireless communication via GSM/GPRS radio modem• Interfacing of IEDs (metering and measuring instru-
ments, protective relays, voltage regulators, controllers for Petersen coils, etc.)
• Extensive protocol library; further protocols can be im-plemented on request (see Technical Data)
SECuRiTyThe progress of information and communication structures demands adequate measures against unauthorized data manipulation and cyber attacs. To meet the high security re-quirements, SPRECON-E-T3 supports encrypted VPN com-munication (e.g. IPsec).
CONfiguRaTiONAll available functions can be individually configured, where-by overall project definitions and specific device configurati-on is done separately.A complete SCADA system can be configured using only one database. Logic functions permit the implementation of special solutions for substation automation.All engineering and programming can be done locally or from remote via the user-friendly software tool SPRECON-E Designer.
PlC fuNCTiONaliTyThe SPRECON-PLC Designer supports standardized pro-gramming in accordance with IEC61131-3:
• FBD: Function Block Diagramm• ST: Structured Text• SFC: Sequential Function Chart
COmmaNd OuTPuTSCommands are issued after the relevant checks as follows:
• The switching device is ready for operation.• The operating equipment is not already in the required
position.• Whether another command is already active in the stati-
on or command group (1 out of n check).• Whether the command has been initiated at an autho-
rised level (control authority).• Whether the new status is permitted by the topological
interlocking condition.After a command output, the operating time of each device is monitored and, when exceeded, an alarm is generated.
PREPROCESSiNg Of BiNaRy daTaBinary data preprocessing provides various functions for processing of binary inputs. These functions can be enabled and adjusted independently for each input.
CONTaCT dEBOuNCiNgThis feature is used for debouncing signals from mechanical contacts. The debouncing period can be adjusted individually.
ChaTTER BlOCkiNgThe chatter blocking function detects faulty inputs that show unstable status. In case of permanent status changes the in-put is blocked in order to suppress overflow on data streams.
SigNal filTERiNg aNd dElaySignal filtering is used to suppress spikes at the binary inputs.The signal change is only registered if the status is present for a certain period of time. Moreover, the binary signal can be delayed, allowing correction of mechanically signal de-lays.
5
SigNal gENERaTiONAfter pre-processing the digital input data, spontaneous tele-grams are generated in case of status change. The switching device position is transmitted as double-indication. Interme-diate position and malfunction can be displayed in addition to the defined ON/OFF positions.
COuNTER valuESEnergy can be counted from the measured current and vol-tage values for SCADA purposes (not for billing). Additionally, the integrated function of an operating hour counter and a switching operations counter are available.If an external meter with pulse output is connected, the pul-ses are counted at the digital inputs, and processed inter-nally. All counter values are stored in a non-volatile memory, and can be set and reset individually.Following functions are available for counter value proces-sing:
• Accumulation of absolute- and relative values• Specification of a counter constant (also per remote)• Adjustable storage criteria (cyclica, via command, de-
pending on changes, etc.)• Transmission and reset is controllable
mEaSuREd valuE aCquiSiTiONThe analog value acquisition provides a wide range of func-tions, pre-processing and transmission of measurands, which in turn permit sophisticated monitoring and easy commissi-oning in the project phase. Standardized DC signals from external measurement transducers are processed, using an optional live zero monitoring for the detection of cable faults.
aNalOg valuE PROCESSiNg
mEaSuREd valuE aCquiSiTiONThe analog value acquisition provides a wide range of func-tions, pre-processing and transmission of measurands, which in turn permit sophisticated monitoring and easy com-missioning in the project phase.Standardized DC signals from external measurement trans-ducers are processed, using an optional live zero monitoring for the detection of cable faults.
SCalE magNifiCaTiON (zOOm-iN fuNCTiON)It may be necessary to considerably enlarge a small range of the input value when using measuring transducers, for ex-ample, in case of a frequency measurement of 45 to 55 Hz or the like. Additionally, this function allows a measured-value adaption by use of a non-linear curve.
limiT mONiTORiNgAll measured and counter values can be monitored for thresholds. The threshold value as well as a time delay can be modified online. An alarm is generated if such limit is ex-ceeded.
mEaN valuE CalCulaTiONBased on the actual measured values over a certain period of time, arithmetic mean values can be calculated such as the 15-minute mean value.
TRaNSmiSSiON Of aNalOg valuESDue to the fact that bandwidth is mostly limited for the com-munication to the Control Centre, a compromise must be found between reducing the data volume and providing the most recent data to the operator.Thus, different concepts for initiation of measured value transmissions can be applied, which can also be combined:
• Cyclic transmission• Spontaneous transmission - by exceeding a certain
threshold• Spontaneous transmission – with adaptive threshold cri-
terion
The transmission mode can be configured individually for each measured value.
6
iNfORmaTiON BlOCkiNgDuring testing in the substation, transfer of information to the Control Centre can be blocked on individual signal level as well as for groups of signals or for the whole station.
dERivEd SigNalS, gROuPEd SigNalS, CalCulaTEd aNalOg aNd COuNTER valuESFurther data objects and even commands may be derived from a
• Data object• Signal• Measured value• Counter value.
This is an essential feature for maximum flexibility.Deriving of signals by Boolean terms, calculation of analog values and counter values is supported, reducing the data quantity being transferred to the Control Centre to the mini-mum.
lOgiC fuNCTiONSSuch logic functions defined by Boolean terms allow easy implementation of automatic functions. Through combination of data objects in logic equations, user-specific signals can be defined and further actions can be derived there from.
auTOmaTiON fuNCTiONSIn addition to the logic functions, any required sequences can be programmed by this facility. Thus, sequential control, change-over automatisms or closed-loop control can be per-formed.
EvENT aRChivEEvent recording allows to continually archive and store ope-rational events in a non-volatile memory. In doing so, all re-levant events are stored in chronological order together with time stamps.
TimE maNagEmENTTime synchronization can be achieved via the synchroniza-tion signal of an external clock receiver like DCF77- or GPS, via NTP servers or higher level control systems.Moreover, direct synchronisation from the Control Centre over the SCADA protocol is possible. All signals, measu-rands and counter values are stamped with date and time.
CONTiNuOuS SElf-mONiTORiNgComprehensive test routines monitor both hardware and software continuously, helping to detect irregularities imme-diately and to take the appropriate measures. This ensures a very high degree of safety and system reliability.
SPRECON-E CONTROl PaNEl (OPTiONal)To allow convenient local control, the SPRECON-E control panel can be connected via the control panel interface mo-dule (CI-3900, included in MC-33xx):
• CP: Control panel with monochrome display• CCP: Control panel with colour display• AP: Alarm panel with 100 LEDs acting as alarm annun-
ciator
7
mC-3211• Management of up to 8 SPRECON-E-T3 I/O modules• IEC 61131-3 programming• USB Interface• 10 ms cycle time• 1 x Ethernet LAN• Time synchronisation via serial interface (GPS, DCF-77)• 1 x serial RS232 communication interface (isolated), 1 x
serial service interface (RJ45, isolated)• 2 binary outputs on the module• LED status displays• Online test• SPRECON-E-C compatible
mC-3221 Same as above plus additional
• 1 x serial RS232 communication interface (isolated), 1 x serial RS485 communication interface (isolated)
mC-33xx1• Management of up to 8 SPRECON-E-T3 I/O modules• IEC 61131-3 programming• 512 KB non-volatile memory for user program• Slot for Micro SD-Card• 10 ms cycle time• 2 x Ethernet LAN• Time synchronisation via serial interface (GPS, DCF-77)• 1 x serial service interface (RJ45, isolated)• Connector for a control panel and alarm panels (max. 2
total)• up to 2 x serial RS232 communication interface (isolated) • up to 1 x serial RS485 communication interface (isolated)• 2 binary outputs on the module• 1 optional Quad-Band GSM/GPRS radio modem
(MC-3340)• LED status displays• Online test• SPRECON-E-C compatible
availaBlE SPRECON-E-T3 mOdulESiNTElligENT BaSiC mOdulES
MC-3211 / 3221
MC-3310 / 3320 / 3340
1 availbable from Q2/2014, variant characteristics see page 14
8
mC-34xx1• Power supply of up to 2 SPRECON-E-T3 modules• IEC 61131-3 programming• 512 KB non-volatile memory for user program• Slot for Micro SD-Card• 10 ms cycle time• 2 x Ethernet LAN• Time synchronisation via serial interface (GPS, DCF-77)• 1 x serial service interface (RJ45, isolated)• up to 1 x serial RS232 communication interface (isolated) • up to 2 x serial RS485 communication interface (isolated)• 2 binary outputs on the module• 1 optional Quad-Band GSM/GPRS radio modem
(MC-3430 / 3440 / 3450)• LED status displays• Online test• SPRECON-E-C compatible
iNTElligENT BaSiC mOdulES
MC-3410 / 3430 / 3440 / 3450 / 3460
1 availbable from Q2/2014, variant characteristics see page 14
9
PS-3003 / 3005• For power supply via system bus• Power Supply modules
• PS-3003: 24 to 60 V DC• PS-3005: 110 to 220 V DC / 110 to 230 V AC
PS-3004 / 3006, SamE aS aBOvE, BuT• For signalling voltage (no power supply via system bus)• With signal relay• Output voltage Vout = 24 VDC
Ci-31001• Quad-Band GSM/GPRS radio modem• GPRS-Class 10• Sending and receiving of data, SMS• Integrated real time clock• Universal interface (RS232)1 to the basic module• For use with MC-32xx
ax-31002• Transducer inputs 3VT/4CT• 1A / 5A• (Direct) Measurement 230 V AC/400 V AC• Tansducer inputs 110V• 50/60 Hz• Up to 2 modules at an MC-3xxx interface• Power supply via system bus
ax-31102, SamE aS aBOvE, BuT• Power supply for detached operation• Up to 15 modules at an MC-3xxx interface
1 connection cable necessary, see order sheet on page 342 availbable from Q2/2014
POwER SuPPly mOdulES
PS-3003/3005
gSm/gPRS RadiO mOdEm
CI-3100
C/v mEaSuRiNg mOdulES
AX-3100/3110
10
lOCal hmi iNTERfaCE
CI-3900
digiTal iNPuT mOdulES
DI-3111…5 / DI-3121…5
digiTal iNPuT / OuTPuT mOdulES
DX-3011…5
Ci-3900• Universal interface (RS232/RS485)1 to the basic module• LED status display• Power supply for CP/AP via connection cable• Connector for a control panel and alarm panels (max. 2
total)
di-3111…5• 8 digital inputs, single size• 2 galvanically isolated groups• Four voltage ranges available
• DI-3111: 24 V DC• DI-3113: 48 to 60 V DC• DI-3114: 110 V DC• DI-3115: 220 V DC
• LED status displays
di-3121…5, SamE aS di-3111…5 hOwEvER• 16 digital inputs, double size• 4 galvanically isolated groups
dx-3011…5• 8 digital inputs• Four voltage ranges available
• DX-3011: 24 V DC• DX-3013: 48 to 60 V DC• DX-3014: 110 V DC• DX-3015: 220 V DC
• 4 electrically isolated command outputs (relays)• Voltage range 24 to 220 V AC/DC• LED status displays
.....
1 connection cable necessary, see order sheet on page 34
11
dO-3005• 4 galvanically isolated command outputs1 (relays), single
size• 2 galvanically isolated groups• Heavy duty output relays• Voltage range 24 to 220 V AC/DC• LED status displays
dO-30152, SamE aS dO-3005 hOwEvER• 8 electrically isolated command outputs1 (relays), com-
pact design• 4 electrically isolated groups
dO-3115• 8 galvanically isolated signal outputs (relays), single size• 2 galvanically isolated groups• Voltage range 24 to 220 V AC/DC• LED status displays
dO-31252, SamE aS dO-3115 hOwEvER• 16 galvanically isolated signal outputs1 (relays), double
size• 4 galvanically isolated groups
dO-32122• 8 signal outputs1 (transistor)• 2 galvanically isolated groups• Voltage range 24 to 48 V DC• LED status displays
dO-32222• 16 signal outputs1 (transistor)• 4 galvanically isolated groups• Voltage range 24 to 48 V DC• LED status displays
1 for details, see Technical Data2 not available today
digiTal OuTPuT mOdulES
DO-3005 / DO-3015
digiTal OuTPuT mOdulES
DO-3115 / DO-3125
digiTal OuTPuT mOdulES
DO-3212 / DO-3222
12
ai-3100• 4 analog inputs1, single size• 2 galvanically isolated groups• Current loop inputs (0…±20 mA) and/or voltage inputs
(0…±10 V)
ai-31102• 4x2 analog inputs1, double size• 2 galvanically isolated groups• Current loop inputs (0…±20 mA) and/or voltage inputs
(0…±10 V)
AI-3200• 4 PT100 inputs, single size• -100 bis +300 °C• 2- or 4-wire measuring• Line resistance compensation at 2-wire measuring• Accuracy: ±0,2% of the measured resinstor
aO-3000• 4 analog outputs, single size• 4 galvanically isolated groups• Current loop outputs (0…±20 mA)
1 for details, see Technical Data2 not available today
aNalOg iNPuT mOdulES
AI-3100, AI-3110
aNalOg iNPuT mOdulE (PT100)
AI-3200
ERRORREADY
T3
SENSOR 1-4
AO-3000
aNalOg OuTPuT mOdulE
AO-3000
13
gENERal dEviCE daTaaSSEmBly TS-35 DIN rail (DIN EN 50022)dimENSiONS Single size modules (L x W x H)
Double size modules (L x W x H)Triple size modules (L x W x H)Fourfold size modules (L x W x H)Fivefold size modules (L x W x H)
99 x 22.5 x 114.5 mm99 x 45 x 114.5 mm
99 x 67.5 x 114.5 mm99 x 90 x 114.5 mm
99 x 112.5 x 114.5 mm
dEgREE Of ENClOSuRE IEC 60529 IP20TERmiNalS COMBICON Typ MSTBO 2,5/4-6 ST
POwER SuPPly (PS-300x)NOmiNal vOlTagE 24 to 60 V DC (-20 %, +30 %)
110 to 220 V DC / 110 to 230 V AC (±20 %)
OuTPuT POwER 30 WBRigdiNg TimE aT SuPPly failuRE ≥10 msiNRuSh CuRRENT acc. to IEC 870-4, HD546.4, 1992 Class S1
CuRRENT CONSumPTiON (miN. / max.) POwER CONSumPTiON (max.)iNTElligENT BaSiC mOdulES MC-3211
MC-3221MC-3310MC-3320MC-3340MC-3410MC-3430MC-3440MC-3450MC-3460
150 mA / 200 mA150 mA / 200 mA90 mA / 120 mA90 mA / 120 mA
105 mA / 180 mA120 mA / 160 mA140 mA / 220 mA140 mA / 220 mA120 mA / 160 mA140 mA / 220 mA
4.8 W4.8 W2.88 W2.88 W4.32 W3.48 W5.28 W5.28 W3.48 W5.28 W
gSm/gPRS RadiO mOdEm CI-3100 15 mA / 65 mA 1.56 Whmi uSER iNTERfaCE CI-3900 15 mA / 20 mA 0.48 W CONTROl PaNEl CP
CCP75 mA / 175 mA50 mA / 170 mA
4.2 W4.1W
alaRm PaNEl AP 20 mA / 190 mA 4.56 WdigiTal OuTPuT mOdulES DO-3005
DO-311515 mA / 100 mA15 mA / 100 mA
2.4 W2.4 W
digiTal iNPuT mOdulES DI-311xDI-312x
10 mA / 20mA10 mA / 20mA
0.48 W0.48 W
digiTal iNPuT / OuTPuT mOdulES DX-3011DX-3013DX-3014DX-3015
15 mA / 100 mA15 mA / 100 mA15 mA / 100 mA15 mA / 100 mA
2.4 W2.4 W2.4 W2.4 W
aNalOg iNPuT mOdulE AI-3100AI-3200
10 mA / 20 mA23 mA / 25 mA
0.48 W0.6 W
aNalOg OuTPuT mOdulE AO-3000 70 mA / 130 mA 3.12 WCTvT mOdulES AX-3100
AX-311025 mA40 mA
0.6 W0.96 W
TEChNiCal daTa (1 Of 3)
14
iNTElligENT BaSiC mOdulE „maiN CONTROl“CONTROl
Clock frequencyMain memoryNon-volatile data memoryNon-volatile parameter memoryPower supply
MC-32xx MC-33xx MC-34xx200 MHz32 MB
---16 MB
via PS-3004/3006
454 MHz128 MB512 KB128 MB
via system bus (PS-3003/3005)
200 MHz32 MB512 KB16 MB
24 V DC (stab.), ±10 %
COmmuNiCaTiONDesign
Connection
Service interface System communication interfaces CP/CCP/AP GPRSserialRJ45
RS232Male, DSUB 9-pole
RS485Female, DSUB 9-pole
Ethernet/LANRJ45
---RJ45
---SMA
MC-3211MC-3221
1 x1 x
1 x2 x
---1 x
1 x1 x
------
------
MC-3310MC-3320MC-3340
1 x1 x1 x
1 x2 x2 x
---1 x1 x
2 x2 x2 x
1 x1 x1 x
------1 x
MC-3410MC-3430MC-3440MC-3450MC-3460
1 x1 x1 x1 x1 x
------1 x------
1 x1 x2 x2 x2 x
2 x2 x2 x2 x2 x
---------------
---1 x1 x---1 x
Note: For details, see „Communication interfaces“
SwiTChiNg OuTPuTS 2 digital alarm outputsNote: For details, see „Digital outputs“
COmmuNiCaTiON iNTERfaCESSERviCE iNTERfaCE for local connection of a service PC RS232 Connection
Baud rateElectric isolationDistance
Connector design RJ45300 to 115200 baud
1 kV rms15 m max. (at 19200 Baud)
SySTEm COmmuNiCaTiON iNTERfaCES For any type of process communication RS232 Connector
Baud rateProtocol typesElectric isolationDistance
Male connector DSUB 9-pole300 to 115200 Baud
synchronous and asynchronous1 kV rms
15 m max. (at 19200 Baud) RS485 Connector
Baud rateProtocol typesElectric isolationDistance
Female connector DSUB 9-pole300 to 115200 Baud
synchronous and asynchronous1 kV rms
max. 1000 m at 38400 Baud Ethernet LAN Connector
Transmission rateRJ45
100 Mbit/s (10/100MBase-T)
COmmuNiCaTiON PROTOCOlS Telecontrol protocols IEC 60870-5-101/ -104 Station bus protocols IEC 60870-5-101/ -104 IED protocols IEC 60870-5-101/ -103/ -104
ModbusSAT 1703
Electric metering protocol IEC 62056 (IEC 1107)
TimE SyNChRONiSaTiON NTP Ethernet External connector DCF-77 or GPS clock via serial communication interface Via telecontrol protocol Recommended synchronization interval 1 min
gSm/gPRS RadiO mOdEm (Ci-3100)Supported standards GSM / GPRSGSM frequencies 850, 900, 1800, 1900 MHzGPRS terminal device class BInterface to basic module Connection
Baud rateConnector design RJ45
300 to 115200 BaudConnection antenna SMA male
TEChNiCal daTa (2 Of 3)
15
iO mOdulESBiNaRy iNPuTS Auxiliary voltages (Vaux)
Admissible toleranceMaximum counting frequency
24 V DC48 to 60 V DC
110 V DC220 V DC
-20 to + 15 %20 Hz
BiNaRy OuTPuTS TechnologyMaximum switching voltageMaximum contact currentMaking/breaking capacity
Minimum switching current
Pickup time
continous
Electromechanical relay250 V AC/DC
1 A30 W / 24 V DC
250 VA / 250 V AC10 mA at 12 V100 mA at 5 V
typ. < 7 ms
COmmaNd OuTPuTS TechnologyMaximum switching voltageMaximum contact current Making/breaking cap.
Pickup time
On
Off
Electromechanical relays440 V AC / 300 V DC
8 A (at 250 V AC / 1 35 V DC)1000 VA at cos φ = 0.11000 W at L/R < 40 ms920 VA at cos φ = 0.440 W at L/R < 40 ms
typ. < 7 ms
aNalOg iNPuTS Nominal value XNomResolutionAccuracy (incl. over/range)LinearityOver-rangeUpdate interval of inputs1
Input impedance, currentInput impedance, voltage
adjustable from 0 to ±20 mA or 0 to ±10 V12 Bit±0.2 %±2 LSB
1.25 · XNomapprox. 4 ms min.
122.5 Ω11.3 kΩ
PT100 iNPuTS Measuring rangeAccuracyResolutionMeasuring currentMaximum line resistance
-100 to +300 °C±0.2% of the measured resistor
11 mΩ1 to 2 mA
For feed- and return line together max. 40Ω
TRaNSduCER iNPuTS2 Nominal frequency fnom 50 / 60 HzOperating range 45...65 Hz
CuRRENT TRaNSduCER Nominal current Inom 1 / 5 AOver-range current 2*InomPower consumption current
16
TESTSiNSulaTiON TESTS
Characteristics Product standard Test standard Class Value
imPulSE vOlTagE IEC 60870-2-1IEC 61010-1
IEC 60664-1 VW3 5 kV peak1.2/50μs
high vOlTagE IEC 60870-2-1IEC 61010-1
IEC 60664-1 VW3 2.5 kV eff. AC2.83 kV DC
EmC TESTSCharacteristic Product standard Test standard Class Value
CONduCTEd iNTERfERENCE IEC 60870-2-1 EN 55011/55022 A 0.15 to 30 MHzRadiO iNTERfERENCE fiEld STRENgTh EN 55011/55022 A 30 to 1000 MHzSuRgE1 IEC 60870-2-1 IEC 61000-4-5 2/3 / 2/3 Line – Earth: 2 kV
Line – Line: 1 kV
immuNiTy TO CONduCTEd, high-fREquENCy vOlTagES IEC 61000-4-6 - / 3 150kHz to 80MHz1kHz AM 80%
faST TRaNSiENT (BuRST) IEC 60870-2-1 IEC 61000-4-4 3, X(>3) 2 kV at 5 kHz.ElECTROSTaTiC diSChaRgE IEC 60870-2-1 IEC 61000-4-2 3 / 3 6/8 kVPOwER fREquENCy magNETiC fiEld
IEC 60870-2-1IEC 61000-4-8 3 / 4
16 2/3 + 50 Hz 30 A/m (continous)
300 A/m (short time)
damPEd OSCillaTORy magNETiC fiEld IEC 60870-2-1 IEC 61000-4-10 4 / 5 100 A/m (0,1 MHz)100 A/m (1 MHz)
RadiaTEd, RadiO-fREquENCy ElECTROmagNETiC fiEld IEC 60870-2-1 IEC 61000-4-3 4 / 3 10 V/m; 80 bis 3000 MHz
1 depending on input parametrization
ENviRONmENTal TESTSCharacteristic Product standard Test standard Class Value
ClimaTiC TESTS dRy hEaT IEC 60870-2-2 IEC 60068-2-2 >B2 +55 °C/16 h dRy COld IEC 60870-2-2 IEC 60068-2-1 -25 °C/16 h mOiST hEaT IEC 60870-2-2 IEC 60068-2-30 relative humidity 93 % at +55 °C / 6 x 24 hviBRaTiON aNd ShOCk viBRaTiON TEST IEC 60870-2-2 IEC 60068-2-6 Bm, x 2 to 500 Hz ShOCk TEST (fuNCTiON / STORagE) IEC 60870-2-2 IEC 60068-2-27 Bm 100 m/s² SEiSmiC wiThSTaNd CaPaBiliTy (PROCEduRE a) IEC 60870-2-2 IEC 60068-3-3 S3 3 to 35 HzdEgREE Of ENClOSuRE IEC 60529 IP 20 IP 20
TOlERaTEd amBiENT CONdiTiONSRECOmmENdEd OPERaTiON TEmPERaTuRE RaNgE -5° to +55 °CSTORagE TEmPERaTuRE RaNgE -25° to +55 °CTRaNSPORT TEmPERaTuRE RaNgE -25° to +70 °ClimiTS -25° to +70 °C (on request)RElaTivE humidiTy iN aNNual avERagE
17
SizES aNd dimENSiONS
114,
5 m
m
1 X4 4
1 X6 4
1 X5 4
22,5
mm
1 X3 4
1 X2 4
1 X1 4
AI-
3200
ERRO
RRE
ADY
T3
SENS
OR 1-
4
45 m
m
PS
-300
3
T3
T3
U in
24 –
60VD
C
24VD
C OK
PWR
67,5
mm
MC
-331
0
ACT/
LKLA
NX6
T3
T3
T3
TXRX
ERRO
RST
ATUS
BO 01
BO 02
COM2
X3
TXRXPA
NEL
X2AC
T/LK
LAN
X7
TXRX COM1
X5
MC
-334
0
ACT/L
KLA
NX6
T3
ERRO
RST
ATUS
ACT/L
KLA
NX7
T3
BO 01
BO 02
TXRXCO
M4X9
TXRXCO
M3X1
2
T3
TXRXCO
M2X3
TXRXPA
NEL
X2
TXRXCO
M1X5
ONLI
NESI
M
NET
T3
SIMINSIDE
90 m
m11
2,5
mm
MC
-344
0
T3
T3
TXRXCO
M1X5
ACT/
LKLA
NX6
ERRO
RST
ATUS
ACT/
LKLA
NX7
T3
T3
BO 01
BO 02
TXRXCO
M3X1
2
ONLI
NESI
M
NET
T3
SIMINSIDE
109 mm
TXRXCO
M4X9
TXRXCO
M2X3
SPRECON-E-T3 single to fivefold size module
18
aSSEmBly aNd addRESS SETTiNg
1 An electrical link to the earthing contact must be ensured (caution when using DIN rails made of anodized aluminium!)
All SPRECON-E-T3 modules can be snapped-on side by side on the standard TS-35 DIN rails (DIN EN 50022):• Before assembly, the pluggable bus connectors supplied with the equipment must be mounted on the DIN rail, as shown
in the figure below.• For this purpose two bus connectors must be lined up for double-width modules (45 mm).• Subsequently, the modules can be snapped on the DIN rail1.• The intelligent basic module is snapped-onto the bus connector left to the I/O modules.• The other modules are snapped-onto the other bus connectors in line, after setting the address.
SPRECON-E-T3 Assembly and address setting
Address settingThe address setting must be done before assembly and with the terminal X1 removed, as is also shown in the figure. The addresses must be set from the left to the right, starting from 1. The basic module must always be mounted left to the I/O mo-dules; no address is set on it.
19
PS-300x CONNECTiON mOdEl dESigNaTiON dESCRiPTiONPS-3003 aNd PS-3005
X6.1 .2 .3 .4
Terminal V+ / LV+ / LV- / NV- / N
Power supply +Power supply +Power supply -Power supply -
x1 ONly ON PS-3004 aNd PS-3006X1.1 .2 .3 .4
Terminal AUX V+AUX V-N/ON/O
Output voltage +Output voltage -N/O contactN/O contact
mC-3211 CONNECTiON mOdEl dESigNaTiON dESCRiPTiON
Galv
anic
iso
lation
Galv
anic
iso
lation Galvanic isolation
Galva
nic
isolat
ion
1 2 3 4X4
RS232
TTL
RS232
TTL
ETH
TTL
1 2 3 4X10
ControlFlash-RAM SD-RAM NV-RAM CPU T-Bus
T3
COM1
/RS2
32
LAN
10/10
0CO
M2/
RS23
2
SERV
ICE
BO 01
_N/C
BO 01
_N/O
BO 02
_N/O
IN/O
UT C
OM
MC-3211
TXRX
ERRORSTATUS
COL/FDACT/LK
LANX6
TXRX
COM1X5
COM2X3
T3
BO 01BO 02
X3
X5X6
USBMass storage
USBDIN railearth
+
Powe
r su
pply
+ --
X3 DSUB9 m COM2 RS232X4.1 .2 .3 .4
Terminal +Power supply–Power supply+Power supply–Power supply
Supply „+“Supply „-“Supply „+“Supply „-“
X5 RJ45 COM1 RS232 ServiceX6 RJ45 LAN Base-T (10/100)
X10.1 .2 .3 .4
Terminal B01_N/CB01_N/OB02_N/OIN/OUT COM
Change-over contact (NC)Change-over contact (NO)NO contactCommon contact
mC-3221 CONNECTiON mOdEl dESigNaTiON dESCRiPTiON
Galva
nic
isolat
ion
Galva
nic
isolat
ion
Galv
anic
iso
lation
Galv
anic
iso
lation
Galv
anic
iso
lation Galvanic isolation
1 2 3 4X4
COM1
/RS2
32
LAN
10/10
0CO
M2/
RS23
2
COM4
/RS
485
X3
RS232
TTL
RS232
TTL
ETH
TTL
SERV
ICE
1 2 3 4X10
RS485
TTL
X9
COM3
/RS2
32
X12
TTL
RS232
ControlFlash-RAM SD-RAM NV-RAM CPU T-Bus
MC-3221
TXRX
ERRORSTATUS
COL/FDACT/LK
LANX6
TXRX
COM1X5
COM2X3
T3
TXRX
COM3X12
TXRX
COM4X9
T3
BO 01BO 02
BO 01
_N/C
BO 01
_N/O
BO 02
_N/O
IN/O
UT C
OM
X5X6
USB
USBMass storage
DIN railearth
+
Power supply
+ --
X3 DSUB9 m COM2 RS232X4.1 .2 .3 .4
Terminal +Power supply–Power supply+Power supply–Power supply
Supply „+“Supply „-“Supply „+“Supply „-“
X5 RJ45 COM1 RS232 ServiceX6 RJ45 LAN Base-T (10/100)X9 DSUB9 f COM4 RS485
X10.1 .2 .3 .4
Terminal B01_N/CB01_N/OB02_N/OIN/OUT COM
Change-over contact (NC)Change-over contact (NO)NO contactCommon contact
X12 DSUB9 m COM3 RS232
mOdulE fuNCTiONS & CONNECTiON (1 Of 15)
20
mC-3310
COM1
/RS2
32
LAN
10/10
0
COM2
/RS
232
X3
RS232
TTL
RS232
TTL
SERV
ICE
1 2 3 4X10
BO 01
_N/C
BO 01
_N/O
BO 02
_N/O
IN/O
UT C
OM
X5X6
Micro SDMass storage
ControlFlashSD-RAMCPU T-BusLA
N 10
/100
X7
RS422
TTL
PANEL
24 V
DC
X2
NV-RAM
T-B
us
Power supplyPS-3003/3005
RTC
MAC+
PHY
T3
BO 01BO 02
TXRX
COM1X5
TXRX
COM2X3
T3
TXRX
PANELX2
MAC+
PHY
T3
ERRORSTATUS
ACT/LK LANX6
ACT/LK LANX7
MC-3310
For use withCP/CCP/AP
only!
CONNECTiON mOdEl dESigNaTiON dESCRiPTiONX2 RJ45 PANEL RS422 proprietaryX3 DSUB9 m COM2 RS232X5 RJ45 COM1 RS232 ServiceX6 RJ45 LAN Base-T (10/100)X7 RJ45 LAN Base-T (10/100)
X10.1 .2 .3 .4
Terminal B01_N/CB01_N/OB02_N/OIN/OUT COM
Change-over contact (NC)Change-over contact (NO)NO contactCommon contact
mOdulE fuNCTiONS & CONNECTiON (2 Of 15)
21
mC-3320
COM1
/RS2
32
LAN
10/10
0
COM2
/RS
232
COM4
/RS
485
X3
RS232
TTL
RS232
TTL
SERV
ICE
1 2 3 4X10
RS485
TTL
X9
COM3
/RS2
32
TTL
RS232
BO 01
_N/C
BO 01
_N/O
BO 02
_N/O
IN/O
UT C
OM
X5X6
Micro SDMass storage
ControlFlashSD-RAMCPU T-BusLA
N 10
/100
X7
RS422
TTL
PANEL
24 V
DC
X2
NV-RAM
T-B
us
Power supplyPS-3003/3005
RTC
MAC+
PHY
TXRX
COM3X12
TXRX
COM4X9
T3
BO 01BO 02
TXRX
COM1X5
TXRX
COM2X3
T3
TXRX
PANELX2
MAC+
PHY
T3
ERRORSTATUS
ACT/LK LANX6
ACT/LK LANX7
MC-3320
X12
For use withCP/CCP/AP
only!
CONNECTiON mOdEl dESigNaTiON dESCRiPTiONX2 RJ45 PANEL RS422 proprietaryX3 DSUB9 m COM2 RS232X5 RJ45 COM1 RS232 ServiceX6 RJ45 LAN Base-T (10/100)X7 RJ45 LAN Base-T (10/100)X9 DSUB9 f COM4 RS485
X10.1 .2 .3 .4
Terminal B01_N/CB01_N/OB02_N/OIN/OUT COM
Change-over contact (NC)Change-over contact (NO)NO contactCommon contact
X12 DSUB9 m COM3 RS232
mOdulE fuNCTiONS & CONNECTiON (3 Of 15)
22
mC-3340
COM1
/RS2
32
LAN
10/10
0
COM2
/RS
232
COM4
/RS
485
X3
RS232
TTL
RS232
TTL
SERV
ICE
1 2 3 4X10
RS485
TTL
X9
COM3
/RS2
32
TTL
RS232
BO 01
_N/C
BO 01
_N/O
BO 02
_N/O
IN/O
UT C
OM
X5X6
Micro SDMass storage
X13
GSM
ControlFlashSD-RAMCPU T-Bus
LAN
10/10
0
X7
For use withCP/CCP/AP
only!
RS422
TTL
PANEL24
V D
C
X2
NV-RAM
T-B
us
Power supplyPS-3003/3005
RTC
MAC+
PHY
T3T3
NET
SIMONLINE
SIM
INSI
DE
TXRX
COM3X12
TXRX
COM4X9
T3
BO 01BO 02
TXRX
COM1X5
TXRX
COM2X3
T3
TXRX
PANELX2
MAC+
PHY
T3
ERRORSTATUS
ACT/LK LANX6
ACT/LK LANX7
MC-3340
X12
CONNECTiON mOdEl dESigNaTiON dESCRiPTiONX2 RJ45 PANEL RS422 proprietaryX3 DSUB9 m COM2 RS232X5 RJ45 COM1 RS232 ServiceX6 RJ45 LAN Base-T (10/100)X7 RJ45 LAN Base-T (10/100)X9 DSUB9 f COM4 RS485
X10.1 .2 .3 .4
Terminal B01_N/CB01_N/OB02_N/OIN/OUT COM
Change-over contact (NC)Change-over contact (NO)NO contactCommon contact
X12 DSUB9 m COM3 RS232X13 SMA Antenna GSM-Antenna
mOdulE fuNCTiONS & CONNECTiON (4 Of 15)
23
mC-3410
1 2 3 4X4
COM1
/RS2
32
LAN
10/10
0RS232
TTL
SERV
ICE
1 2 3 4X10
COM3
/RS4
85
TTL
RS485
BO 01
_N/C
BO 01
_N/O
BO 02
_N/O
IN/O
UT C
OM
X5X6
Micro SDMass storage
+ -Po
wer
supp
lyControl
FlashSD-RAMCPU T-Bus
LAN
10/10
0
X7 X12
NV-RAM RTC
+ -
DC
DC
MAC+
PHY
TXRX
COM3X12
T3
BO 01BO 02
TXRX
COM1X5
T3T3
ERRORSTATUS
ACT/LK LANX6
ACT/LK LANX7
MC-3410
T3
MAC+
PHY
CONNECTiON mOdEl dESigNaTiON dESCRiPTiONX4.1 .2 .3 .4
Terminal +Power supply+Power supply–Power supply–Power supply
Supply „+“for further wiringSupply „-“for further wiring
X5 RJ45 COM1 RS232 ServiceX6 RJ45 LAN Base-T (10/100)X7 RJ45 LAN Base-T (10/100)
X10.1 .2 .3 .4
Terminal B01_N/CB01_N/OB02_N/OIN/OUT COM
Change-over contact (NC)Change-over contact (NO)NO contactCommon contact
X12 DSUB9 f COM3 RS485
mOdulE fuNCTiONS & CONNECTiON (5 Of 15)
24
mC-3430
1 2 3 4X4
COM1
/RS2
32
LAN
10/10
0
RS232
TTL
SERV
ICE
1 2 3 4X10
COM3
/RS4
85
TTL
RS485
BO 01
_N/C
BO 01
_N/O
BO 02
_N/O
IN/O
UT C
OM
X5X6
Micro SDMass storage
+ -Po
wer
supp
ly
X13
GSM
ControlFlashSD-RAMCPU T-Bus
LAN
10/10
0X7 X12
NV-RAM RTC
+ -
DC
DC
MAC+
PHY
T3T3
NET
SIMONLINE
SIM
INSI
DE
TXRX
COM3X12
T3
BO 01BO 02
TXRX
COM1X5
T3T3
ERRORSTATUS
ACT/LK LANX6
ACT/LK LANX7
MC-3430
T3
MAC+
PHY
CONNECTiON mOdEl dESigNaTiON dESCRiPTiONX4.1 .2 .3 .4
Terminal +Power supply+Power supply–Power supply–Power supply
Supply „+“for further wiringSupply „-“for further wiring
X5 RJ45 COM1 RS232 ServiceX6 RJ45 LAN Base-T (10/100)X7 RJ45 LAN Base-T (10/100)
X10.1 .2 .3 .4
Terminal B01_N/CB01_N/OB02_N/OIN/OUT COM
Change-over contact (NC)Change-over contact (NO)NO contactCommon contact
X12 DSUB9 f COM3 RS485X13 SMA Antenna GSM-Antenna
mOdulE fuNCTiONS & CONNECTiON (6 Of 15)
25
mC-3440
1 2 3 4X4
COM1
/RS2
32
LAN
10/10
0
COM2
/RS
232
COM4
/RS
485
X3
RS232
TTL
RS232
TTL
SERV
ICE
1 2 3 4X10
RS485
TTL
X9
COM3
/RS4
85
TTL
RS485
BO 01
_N/C
BO 01
_N/O
BO 02
_N/O
IN/O
UT C
OM
X5X6
Micro SDMass storage
+ -Po
wer
supp
ly
X13
GSM
ControlFlashSD-RAMCPU T-Bus
LAN
10/10
0
X7 X12
NV-RAM RTC
+ -
DC
DC
MAC+
PHY
T3T3
NET
SIMONLINE
SIM
INSI
DE
TXRX
COM3X12
TXRX
COM4X9
T3
BO 01BO 02
TXRX
COM1X5
TXRX
COM2X3
T3T3
ERRORSTATUS
ACT/LK LANX6
ACT/LK LANX7
MC-3440
T3
MAC+
PHY
CONNECTiON mOdEl dESigNaTiON dESCRiPTiONX3 DSUB9 m COM2 RS232
X4.1 .2 .3 .4
Terminal +Power supply+Power supply–Power supply–Power supply
Supply „+“for further wiringSupply „-“for further wiring
X5 RJ45 COM1 RS232 ServiceX6 RJ45 LAN Base-T (10/100)X7 RJ45 LAN Base-T (10/100)X9 DSUB9 f COM4 RS485
X10.1 .2 .3 .4
Terminal B01_N/CB01_N/OB02_N/OIN/OUT COM
Change-over contact (NC)Change-over contact (NO)NO contactCommon contact
X12 DSUB9 f COM3 RS485X13 SMA Antenna GSM-Antenna
mOdulE fuNCTiONS & CONNECTiON (7 Of 15)
26
mC-3450
1 2 3 4X4CO
M1/R
S232
LAN
10/10
0
COM4
/RS
485
RS232
TTL
SERV
ICE
1 2 3 4X10
RS485
TTL
X9
COM3
/RS4
85
TTL
RS485
BO 01
_N/C
BO 01
_N/O
BO 02
_N/O
IN/O
UT C
OM
X5X6
Micro SDMass storage
+ -Po
wer
supp
ly
ControlFlashSD-RAMCPU T-Bus
LAN
10/10
0
X7 X12
NV-RAM RTC
+ -
DC
DC
MAC+
PHY
TXRX
COM3X12
TXRX
COM4X9
T3
BO 01BO 02
TXRX
COM1X5
T3T3
ERRORSTATUS
ACT/LK LANX6
ACT/LK LANX7
MC-3450
T3
MAC+
PHY
CONNECTiON mOdEl dESigNaTiON dESCRiPTiONX4.1 .2 .3 .4
Terminal +Power supply+Power supply–Power supply–Power supply
Supply „+“for further wiringSupply „-“for further wiring
X5 RJ45 COM1 RS232 ServiceX6 RJ45 LAN Base-T (10/100)X7 RJ45 LAN Base-T (10/100)X9 DSUB9 f COM4 RS485
X10.1 .2 .3 .4
Terminal B01_N/CB01_N/OB02_N/OIN/OUT COM
Change-over contact (NC)Change-over contact (NO)NO contactCommon contact
X12 DSUB9 f COM3 RS485
mOdulE fuNCTiONS & CONNECTiON (8 Of 15)
27
mC-3460
1 2 3 4X4
COM1
/RS2
32
LAN
10/10
0
COM4
/RS
485
RS232
TTL
SERV
ICE
1 2 3 4X10
RS485
TTL
X9
COM3
/RS4
85
TTL
RS485
BO 01
_N/C
BO 01
_N/O
BO 02
_N/O
IN/O
UT C
OM
X5X6
Micro SDMass storage
+ -Po
wer
supp
ly
X13
GSM
ControlFlashSD-RAMCPU T-Bus
LAN
10/10
0
X7 X12
NV-RAM RTC
+ -
DC
DC
MAC+
PHY
T3T3
NET
SIMONLINE
SIM
INSI
DE
TXRX
COM3X12
TXRX
COM4X9
T3
BO 01BO 02
TXRX
COM1X5
T3T3
ERRORSTATUS
ACT/LK LANX6
ACT/LK LANX7
MC-3460
T3
MAC+
PHY
CONNECTiON mOdEl dESigNaTiON dESCRiPTiONX4.1 .2 .3 .4
Terminal +Power supply+Power supply–Power supply–Power supply
Supply „+“for further wiringSupply „-“for further wiring
X5 RJ45 COM1 RS232 ServiceX6 RJ45 LAN Base-T (10/100)X7 RJ45 LAN Base-T (10/100)X9 DSUB9 f COM4 RS485
X10.1 .2 .3 .4
Terminal B01_N/CB01_N/OB02_N/OIN/OUT COM
Change-over contact (NC)Change-over contact (NO)NO contactCommon contact
X12 DSUB9 f COM3 RS485X13 SMA Antenna GSM-Antenna
mOdulE fuNCTiONS & CONNECTiON (9 Of 15)
28
dx-301x CONNECTiON mOdEl dESigNaTiON dESCRiPTiON SigNal NO.
Galvanic isolation
Galvanic-isolation
1 2 3 4X41 2 3 4X5
1 2 3 4X6
T-BusControl 0 1 2
3
456
78
9
4 3 2 1X14 3 2 1X2
4 3 2 1X3DX-3011
BI 03BI 02BI 01
ERRORREADY
T3
BI 04BI 05BI 06BI 07BI 08BO 01BO 02BO 03BO 04
AUX
V2+
AUX
V2-
BI 06
BI 01
BI 03
BI 02
BI 05
BI 08
BI 04
BI 07
AUX
V2+
AUX
V2-
BO 03
BO 04
AUX
V1-
AUX
V1+
BO 01
BO 02
AUX
V1-
AUX
V1+
AUX
V1-
AUX
V1+
AUX
V1-
AUX
V1+
4 3 2 1X1
X1.1 .2 .3 .4
Terminal AUX V1+AUX V1–AUX V1+AUX V1–
Command volt. 1+Command volt. 1–Command volt. 1+Command volt. 1–
X2.1 .2 .3 .4
Terminal BO 01BO 02AUX V1+AUX V1–
Command outp.1Command outp.2Command volt. 1+Command volt. 1–
0x010x02
X3.1 .2 .3 .4
Terminal BO 03BO 04AUX V1+AUX V1–
Command outp.3Command outp.4Command volt. 1+Command volt. 1–
0x030x04
X4.1 .2 .3 .4
Terminal AUX V2+AUX V2–AUX V2+AUX V2–
Inp.Volt. 2+Inp.Volt. 2–Inp.Volt. 2+Inp.Volt. 2–
X5.1 .2 .3 .4
Terminal BI 01BI 02BI 03BI 04
Digital input 1Digital input 2Digital input 3Digital input 4
0x110x120x130x14
X6.1 .2 .3 .4
Terminal BI 05BI 06BI 07BI 08
Digital input 5Digital input 6Digital input 7Digital input 8
0x150x160x170x18
di-3111…5 CONNECTiON mOdEl dESigNaTiON dESCRiPTiON SigNal NO.
Galvanic-isolation
Galvanic-isolation
1 2 3 4X41 2 3 4X5
1 2 3 4X6
4 3 2 1X14 3 2 1X2
4 3 2 1X3
T-Bus
AddressControl 0 1 2
3
456
78
9
DI-311x
BI 08BI 07BI 06BI 05BI 04BI 03BI 02BI 01
ERRORREADY
T3
BI 01
AUX
V1-
AUX
V1+
AUX
V1-
AUX
V1+
BI 02
AUX
V1+
AUX
V1+
BI 03
BI 04
AUX
V1+
AUX
V1+
BI 05
BI 06
AUX
V2+
AUX
V2+
BI 07
BI 08
AUX
V2+
AUX
V2+
AUX
V2-
AUX
V2-
AUX
V2+
AUX
V2+
X1.1 .2 .3 .4
Terminal AUX V1+AUX V1–AUX V1+AUX V1–
Inp.Volt. 1+Inp.Volt. 1–Inp.Volt. 1+Inp.Volt. 1–
X2.1 .2 .3 .4
Terminal BI 01AUX V1+BI 02AUX V1+
Digital input 1Inp.Volt. 1+Digital input 2Inp.Volt. 1+
0x01
0x02
X3.1 .2 .3 .4
Terminal BI 03AUX V1+BI 04AUX V1+
Digital input 3Inp.Volt. 1+Digital input 4Inp.Volt. 1+
0x03
0x04
X4.1 .2 .3 .4
Terminal AUX V2+AUX V2–AUX V2+AUX V2–
Inp.Volt. 2+Inp.Volt. 2–Inp.Volt. 2+Inp.Volt. 2–
X5.1 .2 .3 .4
Terminal BI 05AUX V2+BI 06AUX V2+
Digital input 5Inp.Volt. 2+Digital input 6Inp.Volt. 2+
0x05
0x06
X6.1 .2 .3 .4
Terminal BI 07AUX V2+BI 08AUX V2+
Digital input 7Inp.Volt. 2+Digital input 8Inp.Volt. 2+
0x07
0x08
mOdulE fuNCTiONS & CONNECTiON (10 Of 15)
29
di-3121…5
Galvanic-isolation
Galvanic-isolation
1 2 3 4X41 2 3 4X5
1 2 3 4X6
Galvanic-isolation
Galvanic-isolation
1 2 3 4X101 2 3 4X11
1 2 3 4X12
4 3 2 1X74 3 2 1X8
4 3 2 1X9
T-Bus
AddressControl 0 1 2
3
456
78
9
4 3 2 1X14 3 2 1X2
4 3 2 1X3DI-312x
BI 08BI 07BI 06BI 05BI 04BI 03BI 02BI 01
ERRORREADY
BI 16BI 15BI 14BI 13BI 12BI 11BI 10BI 09
T3 T3
BI 01
AUX
V1-
AUX
V1+
AUX
V1-
AUX
V1+
BI 02
AUX
V1+
AUX
V1+
BI 03
BI 04
AUX
V1+
AUX
V1+
BI 09
AUX
V3-
AUX
V3+
AUX
V3-
AUX
V3+
BI 10
AUX
V3+
AUX
V3+
BI 11
BI 12
AUX
V3+
AUX
V3+
BI 05
BI 06
AUX
V2+
AUX
V2+
BI 07
BI 08
AUX
V2+
AUX
V2+
AUX
V2-
AUX
V2-
AUX
V2+
AUX
V2+
BI 13
BI 14
AUX
V4+
AUX
V4+
BI 15
BI 16
AUX
V4+
AUX
V4+
AUX
V4-
AUX
V4-
AUX
V4+
AUX
V4+
CONN. mOdEl dES. dESCRiPTiON SigNal NO. CONN. Bauf mOdEl dESCRiPTiON SigNal NO.X1.1 .2 .3 .4
Terminal AUX V1+AUX V1–AUX V1+AUX V1–
Inp.Volt. 1+Inp.Volt. 1–Inp.Volt. 1+Inp.Volt. 1–
X7.1 .2 .3 .4
Terminal AUX V3+AUX V3–AUX V3+AUX V3–
Inp.Volt. 3+Inp.Volt. 3–Inp.Volt. 3+Inp.Volt. 3–
X2.1 .2 .3 .4
Terminal BI 01AUX V1+BI 02AUX V1+
Digital input 1Inp.Volt. 1+Digital input 2Inp.Volt. 1+
0x01
0x02
X8.1 .2 .3 .4
Terminal BI 09AUX V3+BI 10AUX V3+
Digital input 09Inp.Volt. 3+Digital input 10Inp.Volt. 3+
0x09
0x0A
X3.1 .2 .3 .4
Terminal BI 03AUX V1+BI 04AUX V1+
Digital input 3Inp.Volt. 1+Digital input 4Inp.Volt. 1+
0x03
0x04
X9.1 .2 .3 .4
Terminal BI 11AUX V3+BI 12AUX V3+
Digital input 11Inp.Volt. 3+Digital input 12Inp.Volt. 3+
0x0B
0x0C
X4.1 .2 .3 .4
Terminal AUX V2+AUX V2–AUX V2+AUX V2–
Inp.Volt. 2+Inp.Volt. 2–Inp.Volt. 2+Inp.Volt. 2–
X10.1 .2 .3 .4
Terminal AUX V4+AUX V4–AUX V4+AUX V4–
Inp.Volt. 4+Inp.Volt. 4–Inp.Volt. 4+Inp.Volt. 4–
X5.1 .2 .3 .4
Terminal BI 05AUX V2+BI 06AUX V2+
Digital input 5Inp.Volt. 2+Digital input 6Inp.Volt. 2+
0x05
0x06
X11.1 .2 .3 .4
Terminal BI 13AUX V4+BI 14AUX V4+
Digital input 13Inp.Volt. 4+Digital input 14Inp.Volt. 4+
0x0D
0x0E
X6.1 .2 .3 .4
Terminal BI 07AUX V2+BI 08AUX V2+
Digital input 7Inp.Volt. 2+Digital input 8Inp.Volt. 2+
0x07
0x08
X12.1 .2 .3 .4
Terminal BI 15AUX V4+BI 16AUX V4+
Digital input 15Inp.Volt. 4+Digital input 16Inp.Volt. 4+
0x0F
0x10
mOdulE fuNCTiONS & CONNECTiON (11 Of 15)
30
dO-3005 CONNECTiON mOdEl dESigNaTiON dESCRiPTiON SigNal NO.
Galvanic isolation
Galvanic isolation
1 2 3 4X41 2 3 4X5
1 2 3 4X6
T-Bus
AddressControl 0 1 2
3
456
78
9
4 3 2 1X14 3 2 1X2
4 3 2 1X3DO-3005
ERRORREADY
T3
BO 01BO 02BO 03BO 04
BO 01
COM
01
AUX
V1-
BO 02
AUX
V1+
COM
02
AUX
V1-
AUX
V1+
AUX
V1-
AUX
V1+
AUX
V1-
AUX
V1+
BO 03
AUX
V2-
COM
03
BO 04
AUX
V2+
COM
04
AUX
V2-
AUX
V2-
AUX
V2+
AUX
V2+
AUX
V2+
AUX
V2-
X1.1 .2 .3 .4
Terminal AUX V1+AUX V1–AUX V1+AUX V1–
Command volt. 1+Command volt. 1–Command volt. 1+Command volt. 1–
X2.1 .2 .3 .4
Terminal BO 01COM 01AUX V1+AUX V1–
Command outp.1Command outp.1Command volt. 1+Command volt. 1–
0x01
X3.1 .2 .3 .4
Terminal BO 02COM 02AUX V1+AUX V1–
Command outp.2Command outp.2Command volt. 1+Command volt. 1–
0x02
X4.1 .2 .3 .4
Terminal AUX V2+AUX V2–AUX V2+AUX V2–
Command volt. 2+Command volt. 2–Command volt. 2+Command volt. 2–
X5.1 .2 .3 .4
Terminal BO 03COM 03AUX V2+AUX V2–
Command outp.3Command outp.3Command volt. 2+Command volt. 2–
0x03
X6.1 .2 .3 .4
Terminal BO 04COM 04AUX V2+AUX V2–
Command outp.4Command outp.4Command volt. 2+Command volt. 2–
0x04
dO-3115 CONNECTiON mOdEl dESigNaTiON dESCRiPTiON SigNal NO.
Galvanic isolation
Galvanic isolation
1 2 3 4X41 2 3 4X5
1 2 3 4X6
T-Bus
AddressControl 0 1 2
3
456
78
9
4 3 2 1X14 3 2 1X2
4 3 2 1X3DO-3115
ERRORREADY
T3
BO 01BO 02BO 03BO 04BO 05BO 06BO 07BO 08
BO 01
AUX
V1-
AUX
V1+
AUX
V1-
AUX
V1+
BO 02
AUX
V1-
BO 03
AUX
V1-
BO 04
AUX
V1-
AUX
V1-
BO 05
AUX
V2-
AUX
V2-
BO 07
AUX
V2-
AUX
V2-
AUX
V2+
AUX
V2+
BO 06
AUX
V2-
AUX
V2-
BO 08
X1.1 .2 .3 .4
Terminal AUX V1+AUX V1–AUX V1+AUX V1–
Command volt. 1+Command volt. 1–Command volt. 1+Command volt. 1–
X2.1 .2 .3 .4
Terminal BO 01AUX V1–BO 02AUX V1–
Command outp.1Command volt. 1–Command outp.2Command volt. 1–
0x01
0x02
X3.1 .2 .3 .4
Terminal BO 03AUX V1–BO 04AUX V1–
Command outp.3Command volt. 1–Command outp.4Command volt. 1–
0x03
0x04
X4.1 .2 .3 .4
Terminal AUX V2+AUX V2–AUX V2+AUX V2–
Command volt. 2+Command volt. 2–Command volt. 2+Command volt. 2–
X5.1 .2 .3 .4
Terminal BO 05AUX V2–BO 06AUX V2–
Command outp.5Command volt. 2–Command outp.6Command volt. 2–
0x05
0x06
X6.1 .2 .3 .4
Terminal BO 07AUX V2–BO 08AUX V2–
Command outp.7Command volt. 2–Command outp.8Command volt. 2–
0x07
0x08
mOdulE fuNCTiONS & CONNECTiON (12 Of 15)
31
mOdulE fuNCTiONS & CONNECTiON (13 Of 15)Ci-3100 CONNECTiON mOdEl dESigNaTiON dESCRiPTiON
T-Bus
CI-3100
TXRX
READY
MCX3
T3
RS232
TTL
RS232 MC
POWER
X3
NET
SIMONLINE
X6
GSM
SIM
INSI
DE
X3 RJ45 MC RS232
X6 SMA Antenna GSM-Antenna
Ci-3900 CONNECTiON mOdEl dESigNaTiON dESCRiPTiON
T-Bus
CI-3900
TXRX
READY
PANEL
TXRX
PANELX6
MCX3
T3
RS232
TTL
RS485
TTL
RS232/RS485 MC
RS422
TTL
=1
PANEL
24 V
DC
POWER
For use with SPRECON-E-CP/CCP/AP only!
X6
X3
X3 RJ45 MC RS232 / RS485
X6 RJ45 PANEL RS422 proprietary
ai-3200 CONNECTiON mOdEl dESigNaTiON dESCRiPTiON SigNal NO.
T3
rww
T-Bus
AddressControl 0 1 2
3
456
78
9
rrww r
AI-3200
ERRORREADY
r wr w r wr w
SENSOR 1-4
AUX
V2-
AUX
V2+
AUX
V2+
AUX
V2-
AUX
V1-
AUX
V1+
AUX
V1-
AUX
V1+
PT100PT100
PT100PT100
4 3 2 1X14 3 2 1X2
1 2 3 4X41 2 3 4X5
4 3 2 1X3
1 2 3 4X6
X1.1 .2 .3 .4
Terminal AUX V1+AUX V1-AUX V1+AUX V1-
Voltage 1+Voltage 1-Voltage 1+Voltage 1-
X2.1 .2 .3 .4
Terminal rrww
4 wire r2/4 wire r2/4 wire w4 wire w
0x01
X3.1 .2 .3 .4
Terminal rrww
4 wire r2/4 wire r2/4 wire w4 wire w
0x02
X4.1 .2 .3 .4
Terminal AUX V2+AUX V2-AUX V2+AUX V2-
Voltage 2+Voltage 2-Voltage 2+Voltage 2-
X5.1 .2 .3 .4
Terminal rrww
4 wire r2/4 wire r2/4 wire w4 wire w
0x03
X6.1 .2 .3 .4
Terminal rrww
4 wire r2/4 wire r2/4 wire w4 wire w
0x04
32
mOdulE fuNCTiONS & CONNECTiON (14 Of 15)ai-3100 CONNECTiON mOdEl dESigNaTiON dESCRiPTiON SigNal NO.
T3
Galvanic isolation
Galvanic isolation
1 2 3 4X41 2 3 4X5
1 2 3 4X6
V1 I+
AUX
V1-
AUX
V1+
AUX
V1-
AUX
V1+
V1 U
-
V1 I-
T-Bus
AddressControl 0 1 2
3
456
78
9
V1 U
+
U
#
MUX
V2 I+
V2 U
-
V2 I-
V2 U
+
=
U
#
MUX
4 3 2 1X14 3 2 1X2
4 3 2 1X3AI-3100
ERRORREADY
V4 I+
AUX
V2-
AUX
V2+
AUX
V2+
V4 I-
V4 U
+
V4 U
-
AUX
V2-
V3 I+
V3 I-
V3 U
+
V3 U
-
X1.1 .2 .3 .4
Terminal AUX V1+AUX V1-AUX V1+AUX V1-
Voltage 1+Voltage 1-Voltage 1+Voltage 1-
X2.1 .2 .3 .4
Terminal V1 I+V1 U+V1 U–V1 I–
Current input 1+Voltage input 1+Voltage input 1–Current input 1–
0x01
X3.1 .2 .3 .4
Terminal V2 I+V2 U+V2 U–V2 I–
Current input 2+Voltage input 2+Voltage input 2–Current input 2–
0x02
X4.1 .2 .3 .4
Terminal AUX V2+AUX V2-AUX V2+AUX V2-
Voltage 2+Voltage 2-Voltage 2+Voltage 2-
X5.1 .2 .3 .4
Terminal V3 I+V3 U+V3 U–V3 I–
Current input 3+Voltage input 3+Voltage input 3–Current input 3–
0x03
X6.1 .2 .3 .4
Terminal V4 I+V4 U+V4 U–V4 I–
Current input 4+Voltage input 4+Voltage input 4–Current input 4–
0x04
aO-3000 CONNECTiON mOdEl dESigNaTiON dESCRiPTiON SigNal NO.
1 2 3 4X41 2 3 4
I1+
AUX
V1-
AUX
V1+
AUX
V1-
AUX
V1+
I1-
T-Bus
AddressControl 0 1 2
3
456
78
9
I2+I2- 4 3 2 1X1
I4+
AUX
V2-
AUX
V2+
AUX
V2+I4-
AUX
V2-I
3+ I3-
4 3 2 1X24 3 2 1X3
X51 2 3 4X6
Galva
nic is
olatio
nGa
lvanic
isola
tion
U
#
U#
Galva
nic is
olatio
n
U#
-+ +- -+ +-
-++-
n.c.
n.c.
n.c.
n.c.
n.c.
n.c.
Galva
nic is
olatio
n
n.c.
n.c.
U
#
-++-
T3T3
AO-3000
ERRORREADY
AO 02AO 01
AO 04AO 03
X1.1 .2 .3 .4
Terminal AUX V1+AUX V1-AUX V1+AUX V1-
Voltage 1+Voltage 1-Voltage 1+Voltage 1-
X2.1 .2 .3 .4
Terminal I1+
I1–
Current output 1+not connectednot connectedCurrent output 1–
0x01
X3.1 .2 .3 .4
Terminal I2+
I2–
Current output 2+not connectednot connectedCurrent output 2–
0x02
X4.1 .2 .3 .4
Terminal AUX V2+AUX V2-AUX V2+AUX V2-
Voltage 2+Voltage 2-Voltage 2+Voltage 2-
X5.1 .2 .3 .4
Terminal I3+
I3–
Current output 3+not connectednot connectedCurrent output 3–
0x03
X6.1 .2 .3 .4
Terminal I4+
I4–
Current output 4+not connectednot connectedCurrent output 4–
0x04
33
mOdulE fuNCTiONS & CONNECTiON (15 Of 15)ax-3100 CONNECTiON mOdEl dESigNaTiON dESCRiPTiON
Galvanic isolation
1 2 3 4X41 2 3 4X5
1 2 3 4X6
X10
X9X8
X7
N ~
L3 ~
L2 ~
L1 ~
Controller
L3 Nn.c.
n.c. L1 L2n.c
.
n.c.
~
A BRE
S
GND
MODBUS
AX-3100
ERRORSTATUS
T3
1A 5A230V110V
COM - Address
0 1 2
34
56
789A
BC
D
E F
T-Bu
s
Power supplyPS-3003/3005
terminator strap
X4.1 .2 .3 .4
Terminal ABRESGND
MODBUS Channel AMODBUS Channel BRESISTOR (Terminator)MODBUS GND
X5.1 .2 .3 .4
Terminal V L1
V L2
Voltage input L1not connectednot connectedVoltage input L2
X6.1 .2 .3 .4
Terminal V L3
V N
Voltage input L3not connectednot connectedVoltage input N
X7 Tranducer I L1 Current input L1X8 Tranducer I L2 Current input L2X9 Tranducer I L3 Current input L3X10 Tranducer I N Current input N
ax-3110 CONNECTiON mOdEl dESigNaTiON dESCRiPTiON
Galvanic isolation
Galv.isolation
4 3 2 1X1
1 2 3 4X41 2 3 4X5
1 2 3 4X6
AX-3110
T3 T3
1A 5A230V110V
COM - Address
0 1 2
34
56
789A
BC
D
EF
+-Po
wer
supp
ly+-
X10
X9X8
X7
N ~
L3 ~
L2 ~
L1 ~
Controller
L3 Nn.c.
n.c. L
1 L2n.c.
n.c.
~
DC
DC
A BRE
S
GND
MODBUS
ERRORSTATUS
terminator strap
X1.1 .2 .3 .4
Terminal AUX V1+AUX V1+AUX V1-AUX V1-
Voltage 1+Voltage 1+Voltage 1-Voltage 1-
X4.1 .2 .3 .4
Terminal ABRESGND
MODBUS Channel AMODBUS Channel BRESISTOR (Terminator)MODBUS GND
X5.1 .2 .3 .4
Terminal V L1
V N
Voltage input L1not connectednot connectedVoltage input L2
X6.1 .2 .3 .4
Terminal V L2
V L3
Voltage input L3not connectednot connectedVoltage input N
X7 Tranducer I L1 Current input L1X8 Tranducer I L2 Current input L2X9 Tranducer I L3 Current input L3X10 Tranducer I N Current input N
34
ORdERiNg fORm (1 Of 2)IntellIgent basIc module
dESigNaTiON hOuSiNg widTh laN gSm (C)CP/aP RS232 RS485 ORdERiNg SElECTiONMC-3211 45 mm 1 x --- --- 1 x --- 94.3.527.00-01MC-3221 45 mm 1 x --- --- 2 x 1 x 94.3.527.00-02MC-33101 67.5 mm 2 x --- 1 x 1 x --- 94.3.528.00-01MC-33201 67.5 mm 2 x --- 1 x 2 x 1 x 94.3.528.00-02MC-33401 90 mm 2 x 1 x 1 x 2 x 1 x 94.3.528.00-04MC-34101 90 mm 2 x --- --- --- 1 x 94.3.532.00-01MC-34301 112.5 mm 2 x 1 x --- --- 1 x 94.3.532.00-03MC-34401 112.5 mm 2 x 1 x --- 1 x 2 x 94.3.532.00-04MC-34501 90 mm 2 x --- --- --- 2 x 94.3.532.00-05MC-34601 112.5 mm 2 x 1 x --- --- 2 x 94.3.532.00-06
Power suPPly moduledESigNaTiON hOuSiNg widTh SuPPly vOlTagE N/O CONTaCT ORdERiNg SElECTiON
PS-3003 45 mm 24 - 60 V DC no 94.3.530.00-20PS-3004 45 mm 24 - 60 V DC yes 94.3.530.00-21PS-3005 45 mm 110 - 220 V DC / 110 - 230 V AC no 94.3.530.00-10PS-3006 45 mm 110 - 220 V DC / 110 - 230 V AC yes 94.3.530.00-11
HmI user InterfacedESigNaTiON hOuSiNg widTh PaNEl (CP/CCP) RS232 RS485 ORdERiNg SElECTiON
CI-3900 22.5 mm 1 x 1 x 1 x 94.3.522.00-01Connection cable RS232 94.3.540.01Connection cable RS485 94.3.540.02
gsm/gPrs radIo modemdESigNaTiON hOuSiNg widTh aNTENNa RS232 ORdERiNg SElECTiON
CI-3100 22.5 mm 1 x 1 x 94.3.529.00-01Connection cable RS232 94.3.540.04
dIgItal InPut modulesdESigNaTiON hOuSiNg widTh NumBER Of iNPuTS NOmiNal vOlTagE (v
aux) ORdERiNg SElECTiON
DI-3111
22.5 mm 2 x 42
24 V DC 94.3.525.00-01DI-3113 48 to 60 V DC 94.3.525.00-03DI-3114 110 V DC 94.3.525.00-04DI-3115 220 V DC 94.3.525.00-05DI-3121
45 mm 4 x 42
24 V DC 94.3.526.00-01DI-3123 48 to 60 V DC 94.3.526.00-03DI-3124 110 V DC 94.3.526.00-04DI-3125 220 V DC 94.3.526.00-05
1 available from Q2/20142 not available today
35
ORdERiNg fORm (1 Of 2)dIgItal outPut modules
dESigNaTiON hOuSiNg widTh NumBER Of OuTPuTS NOmiNal vOlTagE (vaux
) ORdERiNg SElECTiONDO-3005 22.5 mm 2 x 21 Relay (command outputs)
24 to 220 V AC/DC
94.3.510.00-01DO-30152 45 mm 4 x 21 Relay (command outputs) 94.3.511.00-01DO-3115 22.5 mm 2 x 41 (signal outputs) 94.3.508.00-01DO-31252 45 mm 4 x 41 (signal outputs) 94.3.509.00-01DO-32122 22.5 mm 8 transistor outputs 24 to 48 V DC
94.3.505.00-01DO-32222 45 mm 16 transistor outputs 94.3.506.00-01
dIgItal InPut / outPut modulesdESigNaTiON hOuSiNg widTh NumBER Of iNPuTS / OuTPuTS NOmiNal vOlTagE (v
aux) ORdERiNg SElECTiON
DX-3011
22.5 mm8 inputs
4 relays (command outputs)
24 V DC 94.3.515.00-01DX-3013 48 to 60 V DC 94.3.515.00-03DX-3014 110 V DC 94.3.515.00-04DX-3015 220 V DC 94.3.515.00-05
analog InPut modulesdESigNaTiON hOuSiNg widTh NumBER Of iNPuTS iNPuT vaRiaBlE i
N, u
NORdERiNg SElECTiON
AI-3100 22.5 mm 2 x 21 ±0…20 mA, ±0…10 V94.3.512.00-01
AI-31102 45 mm 4 x 21 94.3.513.00-01AI-32003 22.5 mm 2 x 21 PT100 Temperature 94.3.514.00-01
analog outPut modulesdESigNaTiON hOuSiNg widTh NumBER Of OuTPuTS OuTPuT vaRiaBlE ORdERiNg SElECTiON
AO-3000 45 mm 1 x 41 ±0…20 mA 94.3.516.00-01
c/V measurIng modules3
dESigNaTiON hOuSiNg widTh NumBER Of iNPuTS SuPPly vOlTagE ORdERiNg SElECTiONAX-3100 45 mm
4 x V, 4 x Ivia system bus 94.3.531.00-10
AX-3110 67.5 mm via internal power unit 94.3.531.00-11
Alternatively, these modules can also be ordered with the SPRECON-E CONFIGURATOR. It is part of the SPRECON-E ENGINEERING CENTER, but can also be separate downloaded at the Sprecher Automation website.
1 Number of electrically isolated groups x number of inputs/outputs per group.2 not available today3 available from Q2/2014
SPRECON-E-T3Compact Module for Automation and Remote Control
Technical Brochure
94.3.910.25en G 18. März 2014, 4:05 nachm.
English
© Sprecher Automation 2014Sprecher Automation, the Sprecher Automation logo and any alternative version thereof are trademarks and service marks of Sprecher
Automation. Other names mentioned, either registered or not, are the property of their respective companies.
Any liability regarding the correctness and completeness of any information and/or specifications in the brochure is excluded. All rights are reserved to alter specifications, make modifications, or terminate models without prior notice. The specifications of a model may vary from
country to country.
www.sprecher-automation.com
Sprecher Automation GmbH
Franckstraße 51, 4018 LinzAustriaT: +43 732 6908-0F: +43 732 6908-278
Ignaz-Köck-Straße 10, 1210 WienAustria T: +43 732 6908-601F: +43 732 6908-5601
info@sprecher-automation.comwww.sprecher-automation.at
Sprecher Automation Deutschland GmbH
Möllendorffstraße 47, 10367 BerlinGermanyT: +49 30 6449241-70F: +49 30 6449241-99
Fraunhoferstraße 8, 82152 MartinsriedGermany T: +49 89 4520599-0F: +49 89 4520599-99
Wilhelmstraße 1, 59439 HolzwickedeGermanyT: +49 2301 18466-00F: +49 2301 18466-29
Stotternheimer Straße 9A, 99086 ErfurtGermany T: +49 361 430405-71F: +49 361 430405-99
info-de@sprecher-automation.comwww.sprecher-automation.de
Sprecher Automation Polska Sp z o.o.
ul. Łączna 4, 58-100 ŚwidnicaPolandT: +48 74 85135-31F: +48 74 85135-32
ul. Wólczańska 128/134, 90-527 ŁódźPoland T: +48 42 25688-22F: +48 42 25688-23
info-pl@sprecher-automation.comwww.sprecher-automation.pl
Sprecher Automation spol. s r.o.
Kopčianska 14, 851-01 BratislavaSlovakiaT: +421 2 682055-00F: +421 2 682055-10
info-sk@sprecher-automation.comwww.sprecher-automation.sk