View
280
Download
3
Category
Preview:
Citation preview
Power Transmission and Distribution
Medium voltage – cleverly switched Gas-insulated switchgear: Compact, maintenance-free and climate-independent
�
There is one thing you just have to rely on: Smooth and safe operation of your system. Around the clock. Here, switch-gear assemblies as points of intersection play a decisive role – and switchgear con-cepts from Siemens offer the best solu-tion with no doubt.
As a pioneer for gas-insulated switchgear we bring along �5 years of know-how, so that you can take full advantage of this technology – with a compact, main-tenance-free and climate-independent design. For lower ratings we also offer air-insulated switchgear type SIMOSEC with SF6 switch-disconnectors. The only decisive factor are your requirements.
With Siemens you are always on the safe side. Whether for secondary or for primary distribution switchgear – all our switchgear is already type-tested today for indoor installation according to IEC 6��71-�00 (in main aspects also according to ANSI C37.�0). In this way you profit from our leading position as regards fulfillment of this new standard. Regardless of the fact that Siemens switchgear has been a synonym for maxi-mum personal and operational safety.
We take care that you can “switch cleverly”. Combining innovation and experience. With comprehensive know-how, world-wide service – and profound understand-ing of your markets. Go and see for yourself!
For perfect operation of your system:
�
High demands – in practical imple-mentation: The 3D CAD procedure
�D CAD design tools provide for the precise implementation of quality and reliability for our switchgear in develop-ment and production. The technical data of your switchgear is transferred directly from the purchase order to the produc-tion department via the design depart-ment with mathematical precision. Using innovative technologies we can offer a maximum of quality and flexibility in production – with short delivery times.
Everything tailor-made:The laser cutting system
The use of CNC-controlled laser cutting systems guarantees the manufacture of precise, exact parts with a surface free of scratches – at a high cutting speed. Maximum material utilization is ensured by the programs generated by the NC nesting processor.
For surge-proof operation:Cast-resin part manufacture
Insulating parts made of cast resin guarantee the dielectric strength of high-voltage phases to earth. The complete production process of such parts – which are essential for switch-gear – is integrated in our production. The quality of these components is 100% routine-tested by means of X-ray, tightness, high-voltage and partial discharge tests.
Systematic quality – by innovative procedures, technologies and production processes
With six product families for the primaryand secondary distribution level, theSwitchgear Factory Frankfurt/Main has a top position on the world market for gas-insulated switchgear.
The reason is a distinct understanding of quality, reaching far beyond the certifica-tion according to DIN EN ISO 9001 and 14001. Thousands of switchgear assem-blies running reliably all over the world are an impressive proof for this.
Decades of experience in development,manufacture, quality and environmental management as well as in service sup-port the leading position of the factory – as a worldwide center of competence and leading production for medium-volt-age switchgear from Siemens.
� 4
Strict eyes: Type and routine tests as an integral part of quality assurance
Very modern testing laboratories ensurethe high quality of our products. Here, type and routine tests for the different switchgear types as well as continuous process-accompanying quality assurance according to ISO 9001 and 14001 are performed. Our accredited testing labo-ratories in Frankfurt/Main and Berlin are among the largest in the world.
Being associated with PEHLA, they have the status of independent test insti-tutes. Furthermore, our type tests are internationally accepted. For example, we take over the testing and certifica-tion of packaged substations from other manufacturers who do not have a test-ing laboratory of their own.
With standards to success:Assembly
Standards play an important part at the Switchgear Factory Frankfurt/Main. The sequence of a process is document-ed in a reproducible way – to guarantee that the quality level the customer ex-pects is reached in a fast, safe and re-producible way. For example, assembly: It is divided into clearly defined opera-tions and organized following the one-piece-flow principle.
Necessary tools are always ready to hand, parts and materials are supplied to the workplace – all this saves en-ergy, time and supports precision. Ac-cording to the push-pull principle, the subsequent process always controls the preceding process: For example, by the information that an operation has been completed or that material is required.
More precise, faster, tighter:The laser welding equipment
The application of laser welding tech-nology leads to maximum precision, fast throughput times and gas tight-ness. The electrical bushings of the stainless-steel vessels are welded in without seals – as well as the metal bellows for transmission of the operat-ing energies from outside the vessel to the switching devices located inside.
Everything tight, everything all right: Integral leakage detection system
“Sealed for life” is the target for each and every switchgear vessel. For this purpose, the vessel is evacuated to-gether with the test chamber and then filled separately with helium, which has a smaller molecular structure than SF6. If no escaping helium is detected, gas tightness is guaranteed for life. The helium gas is absorbed again, the switchgear vessel is refilled with SF6, and the filling socket is welded tight.
5
Quality inmedium-voltage switchgearYour requirements – and the suitable so-lution from Siemens. For every distribu-tion level, every rating, every application and every switchgear type. According to the different criteria, you can easily find out on which page of this brochure the medium-voltage switchgear you need is described. Just leave this page unfolded.
Selection matrix
Secondarydistribution level
Gas insulation
Air insulation
Cubicle-type & metal-clad
Metal-clad
Metal- enclosed
Single
SIMOSEC
8DH10
8DJ
NXPLUS C
Primarydistribution level
Gas insulation
Air insulation
Cubicle-type & metal-clad
Metal-clad Single
SIMOSEC
8DH10
NXPLUS C
Single
NXPLUS
8DB10
NXPLUS C
NXPLUS
8DA10
Single
Double
Switchgear type
Busbar system
Enclosure/Partitions
InsulationDistributionlevel
Contents
17.5 �5 630 630 �4 �0 630 630
17.5 �5 1�50 630 �4 �0 1�50 630
15 31.5 �500 �500 �4 �5 �500 �000
17.5 �5 1�50 1�50 �4 �0 1�50 1�50
Page 6 – 7
Page 8
Page 9
Page 12
17.5 �5 1�50 630 �4 �0 1�50 630
15 31.5 �500 �500 �4 �5 �500 �000
17.5 �5 1�50 1�50 �4 �0 1�50 1�50
Page 8
Page 9
Page 12
36 31.5 �500 �500
40.5 40 4000 �500
�4 �5 �000 1�50
40.5 31.5 �500 �500
40.5 40 4000 �500 Page 10
Page 11
Page 9
Page 10
Page 11
Ibusbar
[A]
Ur
[kV]
IK
[kA]
Ifeeder
[A]
Electrical data (max.)
Generation leveland high-voltage system
Low voltage
Primary distribution level
Secondary distribution level
6
8DJ10 switchgear for secondary distribution systems up to 24 kV
Ring-main feeder Transformer feeder
Scheme 10 Scheme 71 Scheme 6�
8DJ10 switchgear
Technical features Up to 17.5 kV, �5 kA, 1 s
Up to �4 kV, �0 kA, 3 s
Busbar up to 630 A
Feeders up to 630 A
Metal-enclosed
Gas-insulated
Block-type construction
Ring-main feeders, transformer feeders
Factory-assembled, type-testedswitchgear according to IEC 6��71-�00
Classification according to IEC 62271-200
Partition class PM
Loss of service continuity category
Switchgear with HV HRC fuses:
LSC �A
Accessibility to compartments
Busbar compartment: non-accessible
Switching-device compartment:
non-accessible
Cable compartment: interlock-controlled
Internal arcclassification (option)
Wall-standing arrangement:
IAC A FL �1 kA, 1 s
Dimensions
Switchgear height 1360 mm and 1650 mm
Switchgear depth 775 mm
Switchgear width 710 mm, 1060 mm, 1410 mm
Your advantages:Independent of environment and climateCompact Maintenance-free Safe for operatorsReliable and safe operationEcologicalCost-efficient
Product range
7
8DJ20 switchgearfor secondary distribution systems up to 24 kV
Ring-main feeder Transformer feeder
Your advantages:Independent of environment and climateCompact Maintenance-freeSafe for operatorsReliable and safe operationEcologicalCost-efficient
Product range (in extracts)
Scheme 01 Scheme �1 Scheme 10 Scheme 71 Scheme 10 LST Scheme �1 LST
Ring-main feeder Circuit-breaker feeder
Switchgear with HV HRC fuses Switchgear with circuit-breaker feeder
8DJ20 switchgear
Technical features Up to 17.5 kV, �5 kA, 1 s
Up to �4 kV, �0 kA, 3 s
Busbar up to 630 A
Feeders up to 630 A
Metal-enclosed
Gas-insulated
Block-type construction
Ring-main feeders, transformer feeders,circuit-breaker feeders
Factory-assembled, type-testedswitchgear according to IEC 6��71-�00
Classification according to IEC 62271-200
Partition class PM
Loss of service continuity category
Switchgear without HV HRC fuses:
LSC �B
Switchgear with HV HRC fuses:
LSC �A
Accessibility to compartments
Busbar compartment: non-accessible
Switching-device compartment:
non-accessible
Low-voltage compartment:
tool-based
Cable compartment: interlock-controlled
Internal arc classification (option)
Wall-standing arrangement:
IAC A FL �1 kA, 1 s
Dimensions
Switchgear height 1�00 mm, 1400 mm or 1760 mm
Switchgear depth 775 mm
Switchgear width 510 mm, 710 mm, 1060 mm, 1410 mm, 1760 mm
8
8DH10 switchgear for secondaryand primary distribution systems up to 24 kV
8DH10 switchgear
Technical features Up to 17.5 kV, �5 kA, 1 s
Up to �4 kV, �0 kA, 3 s
Busbar up to 1�50 A
Feeders up to 630 A
Metal-enclosed
Single busbar
Gas-insulated
Modular and extendable as individual panel or as panel block
Factory-assembled, type-testedswitchgear according to IEC 6��71-�00
Classification according to IEC 62271-200
Partition class PM
Loss of service continuity category
Panels without HV HRC fuses: LSC �B
Panels with HV HRC fuses: LSC �A
Accessibility to compartments
Busbar compartment: tool-based
Switching-device compartment:
non-accessible
Low-voltage compartment: tool-based
Cable compartment• with HV HRC fuses:• without HV HRC fuses:• panel type K:
interlock-controlledinterlock-controlledtool-based
Internal arcclassification (option)
Wall-standing arrangement: IAC A FL �1 kA, 1 s
Free-standing arrangement: IAC A FLR �1 kA, 1 s
Dimensions
Switchgear height 1400 mm, �000 mm with low-voltage compartment
Switchgear depth 775 mm
Panel widths 350 mm and 500 mm, metering panels 600 mm or 850 mm
Product range (in extracts)
Your advantages:Independent of environment and climateCompact Maintenance-freeSafe for operatorsReliable and safe operationEcologicalCost-efficient
Ring-main paneltype RK
Transformer paneltype TR
Circuit-breaker paneltype LS1
Bus sectionalizer type LT1
Circuit-breaker panel type LST1
Billing metering paneltype ME1
9
NXPLUS C switchgear for secondaryand primary distribution systems up to 24 kV
NXPLUS C switchgear
Technical features Up to 15 kV, 31.5 kA, 3 s
Up to �4 kV, �5 kA, 3 s
Busbar up to �500 A
Feeders up to �500 A
Metal-enclosed
Single and double busbar
Gas-insulated
Hermetically sealed
Factory-assembled, type-testedswitchgear according to IEC 6��71-�00
Classification according to IEC 62271-200
Partition class PM
Loss of service continuity category
Panels without HV HRC fuses:
LSC �B
Panels with HV HRC fuses:
LSC �A
Accessibility to compartments
Busbar compartment: tool-based
Switching-device compartment:
non-accessible
Low-voltage compartment:
tool-based
Cable compartment• with HV HRC fuses:• without HV HRC fuses:
interlock-controlled tool-based
Internal arc classification
7.� kV up to 15 kV: IAC A FLR 31.5 kA, 1 s
17.5 kV up to �4 kV: IAC A FLR �5 kA, 1 s
Dimensions
Switchgear height ��50 mm
Switchgear depth 1�50 mm
Panel widths 600 mm, 1�00 mm at �000 A and �500 AProduct range (in extracts)
Circuit-breaker panel Disconnector panel Bus sectionalizer Switch-disconnector panel
Contactor panel Metering panel
Your advantages:Independent of environment and climateCompactMaintenance-freeSafe for operatorsReliable and safe operationEcologicalCost-efficient
10
8DA/B10 switchgearfor primary distribution systems up to 40.5 kV
8DA/B10 switchgear
Technical features Up to 40.5 kV, 40 kA, 3 s
Busbar up to 4000 A
Feeders up to �500 A
Metal-enclosed
Single and double busbar
Gas-insulated
Sealed
Factory-assembled, type-testedswitchgear according to IEC 6��71-�00
Classification according to IEC 62271-200
Partition class PM
Loss of service continuity category LSC �B
Accessibility to compartments
Busbar compartment: tool-based
Switching-device compartment:
tool-based
Low-voltage compartment:
tool-based
Cable compartment: tool-based
Internal arc classification
IAC A FL 40 kA, 1 s
Dimensions
Switchgear height �350 mm (standard), �700 mm (option)
Switchgear depth SBB 3-pole: 1675 mm, SBB �-pole: 1�65 mm, SBB 1-pole: 915 mm DBB 3-pole: �710 mm
Panel width 600 mm
Product range (in extracts)
Circuit-breaker panel
SBB
8DA10 3-pole
Disconnector panel
SBB
8DA11 1-pole
Bus sectionalizer
SBB
Circuit-breaker panel
DBB
8DA12 2-pole
Bus coupler
DBB
Bus sectionalizer
DBB
8DB10 3-pole
Your advantages:Independent of environment and climateCompact Low-maintenanceSafe for operatorsReliable and safe operationEcologicalCost-efficient
11
NXPLUS switchgearfor primary distribution systems up to 40.5 kV
NXPLUS switchgear
Technical features Up to 40.5 kV, 31.5 kA, 3 s
Busbar up to �500 A
Feeders up to �500 A
Metal-enclosed
Single and double busbar
Gas-insulated
Hermetically sealed
Factory-assembled, type-testedswitchgear according to IEC 6��71-�00
Classification according to IEC 62271-200
Partition class PM
Loss of service continuity category
LSC �B
Accessibility to compartments
Busbar compartment: tool-based
Switching-device compartment:
non-accessible
Low-voltage compartment:
tool-based
Cable compartment: tool-based
Internal arc classification
IAC A FLR 31.5 kA, 1 s
Dimensions
Switchgear height SBB �450 mm, DBB �600 mm
Switchgear depth SBB 1600 mm, DBB 1840 mm
Panel width 600 mm
Product range (in extracts)
Bus coupler
DBB
Bus sectionalizer
DBB
Circuit-breaker panel
IC DBB
Bus sectionalizer
SBB
Circuit-breaker panel
IC SBB
Circuit-breaker panel
OC SBB
Your advantages:Independent of environment and climateCompactMaintenance-freeSafe for operatorsReliable and safe operationEcologicalCost-efficient
1�
SIMOSEC switchgear
Technical features Up to 17.5 kV, �5 kA, 1 s
Up to �4 kV, �0 kA, 3 s
Busbar and feeders up to 1�50 A
Metal-enclosed
Single busbar
Air-insulated
Hermetically sealed switchgear vessel
Factory-assembled, type-tested switchgear according to IEC 6��71-�00
Classification according to IEC 62271-200
Partition class PM
Loss of service continuity category
Panels without HV HRC fuses, as well as panel types without removable circuit-breaker type 3AH6: LSC �B
Panels with HV HRC fuses, as well as panel types with 3AH6: LSC �A
Accessibility to compartments
Busbar compartment: tool-based
Switching-device compartment:
non-accessible
Switching-device compartment with 3AH6:
accessible, interlock-controlled
Low-voltage compartment: tool-based
Cable compartment• without HV HRC fuses:• with HV HRC fuses:
tool-basedinterlock-controlled,tool-based
Internal arc classification (option)
Wall-standing arrangement: IAC A FL �0 kA, 1 s
Free-standing arrangement: IAC A FLR �0 kA, 1 s
Dimensions
Switchgear height 1750 mm (standard), �100 mm (option)
Switchgear depth 1�30 mm
Panel widths 375 mm, 500 mm, 750 mm
Ring-main panel RK
Metering panel ME1
Circuit-breaker panel LS1 with 3AH5
Transformer panelTR
Circuit-breaker panel LS11 with 3AH6
Your advantages:CompactSafe for operatorsReliable and safe operationEcologicalCost-efficient
This switchgear is also available as SIMOSEC ANSI, and it is type-tested and UL-listed according to the standard ANSI/IEEE C37.
Product range (in extracts)
SIMOSEC switchgear for secondaryand primary distribution systems up to 24 kV
13
25 years of gas-insulated medium- voltage switchgear from Siemens
In 198� Siemens introduced a world nov-elty to the market: The first gas-insulated switchgear for medium voltage. Right from the beginning, this innovation has written a success story.
For us, this is a commitment for con- tinuous development: As a leader in technology we have been permanently redefining performance and economic efficiency for a quarter century – a process you, as the customer, benefit from. Even tomorrow and the day after tomorrow.
Innovationby tradition
Milestones from a quarter century 1977Siemens brings the first vacuum circuit-breaker to market, setting new standards regarding the reachable number of op-erating cycles, necessary maintenance, small dimensions, reliability and environ-mental independence.
1982The first gas-insulated switchgear for the primary distribution level is available with the type designation 8DA10 and 8DB10. And for the secondary distribution level, Siemens offers the type 8DJ10 as the first hermetically welded, maintenance-free gas-insulated switchgear worldwide. This is the first switchgear that is extremely compact and climate-independent.
1985With 7SA50�, Siemens was the first worldwide provider to introduce a micro-processor-based multifunction protection relay to the market, thus initiating the age of numerical protection and control systems.
1993As the first switchgear of its kind, 8DH10 switchgear for the secondary distribution level combines hermetically welded tech-nology and maintenance-free design with simple extensibility. In the same year, the first maintenance-free, hermetically welded switchgear appears on the prima-ry distribution level: NXPLUS C. Gas work for installation and extension is therefore a thing of the past.
2000Siemens offers sealed systems for the complete medium-voltage range – up to 40.5 kV, 40 kA, 4500 A.
2006Every gas-insulated switchgear from Siemens complies with the new switch-gear standards IEC 6��71-100 and -�00.
First gas-insulated switchgear forsecondary distribution levels8DJ10 – Stadtwerke Lambrecht (Pfalz) GmbH, Germany
First gas-insulated switchgear forprimary distribution levels8DA10 – BELG (today, E.ON Bayern AG),Station Kulmbach Mitte, Germany
14
Subject to change without prior noticeOrder no. E50001-U��9-A310-X-7600Printed in GermanyDispo 30403GB 0700�1 10��81 WS 0�076.
The information in this document contains general descriptions of the technical features, which may not always be available.An obligation to provide the respective performance feature shall exist only if expressly agreed in the terms of contract.
Siemens AGPower Transmission and DistributionMedium Voltage DivisionMozartstr. 31 c9105� ErlangenGermany
www.siemens.com/energy
For questions on power transmission anddistribution, please contact our CustomerSupport Center, �4 hours a day.
Tel.: +49 180 / 5�4 70 00Fax: +49 180 / 5�4 �4 71(Subject to charge: e.g. 1� ct/min)
E-mail: support.energy@siemens.comwww.siemens.com/energy-support
Recommended