Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 1
Smile Controller Family
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 2
• There are controllers from 3 to 12 relays• applications cover heating, district heating,• all controllers have proprietary communication• controllers have 4 language menues• DIN housing
Features
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 3
• spring terminals in wall socket• backlit 3 line display• push and turn operation with softkeys• standard wall module and wall module for individual access• service interface on controller front• several applications in one „box“
Features Highlights
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 4
Information key
Heating characteristics
Operating mode key forPermanent and temp. modes
Manual mode key
Multi-functional Display
Rotary Pushbuttom
Cover clip for service jack
Daytime room temp
Nighttime room temp
DHW daytime temp
User Interface
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 5
C = Central Area, E = Eastern Europe ...p = panel mount w = wallmount1x..4x = heating, 5x = district heating, 6x = ventilation, 7x= boiler cascade, 8x = solar
1 = number of analog outputs*3, 8 = number of relaysSmile = controller family (smile digital contr.)
Type key
SDC 9 x-21 P C
* is only mentioned when there is an analog output. For example SDC 41-61 PC
District heating only:DHC 43 - 1 PC / WC (7 Relais)DHC 43 - 2 PC / WC (9 Relais)
Controller Types
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 6
C = Central Area: D, GB, F, I
Language versions
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 7
Easy system architecture:
Max 5 controllers per systemMax 3 wall modules per controller
Architecture
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 8
System architekture (max size)
MK 2
MK 1
DK
MK 2
MK 1
DK
MK 2
MK 1
DK
MK 2
MK 1
DK
MK 2
MK 1
DK
Architecture
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 9
Displaytest at power on
- 21 x 14 –segments characters- 16 symbols- timescale divided in 30 min segments. - 13 hour marks
°CKWhmin%qqqqq qqqq
°CKWhmin%
0 4 6 82 10 12 14 16 18 20 22 24
qqqqqqqqqqqqI II
the 14 segment characters can show also kyrilic and hebrew letters
Display
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 10
Push and turn knob
Operation
2
3
1
The centrally positioned push and turn knob has several functions:Turning clockwise will change to highervalues and vice versaA short push will confirm the settingA long push (appr. 3 secs) will a)start the parameter menueb)go back to the previous input level
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 11
User hierarchy
entering the installer or OEM code will enable additional parameters for adjustmentPlease press and at the same time and hold
Enter the code by turning and pushing the knob for confirmation for each number separately.
The installer code default is 1234
Parameter input
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 12
Operating keys
Day room setpoint
Night (reduced)room setpoint
Operation
This key enters the desired room setpoint for automatic operation and the operation modes „heating“ and „party“. In the standard functionthis is the setpoint for all heating circuits of the controller
This key enters the desired reduced room setpoint for automatic operation and the operation modes „absent“ and „reduced“. In the standard functionthis is the setpoint for all heating circuits of the controller
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 13
c
Operation
Operating keys
Warm water day setpoint
Operating mode key
This key enters the desired warm water setpoint for automatic operation and the operation modes „heating“ and „party“ and „summer“.
This key enters the desired operating mode. A cursor will show at the bottom of the display in combination with an explanatory text in the first line. In the standard function the operation mode is valid for the whole controller The same key serves as escape key i.o. to return to the standard display
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 14
Heating curve
Operation, heating curve
Operating keys
This key enters the desired heating curve for all circuits in the controller. Adjustment range: 0,20...3,5Default: unmixed heating circuit:=1,50
mixed heating circuit:=1,00 Returning to the basic display is either possible by pressing this key twice or waiting for 60 seconds
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 15
Operation, status info
With this info key the user can displayvarious status information about inputs andoutputs.The info is always starting with the outdoor temperature. By turning the knob clockwiseall activated information can be reached.Setpoint can be displayed by pressing the knob.
When entering a value this key can also be used
to move the cursor one position back.
System information
Operating keys
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 16
Manual Operation Operating keys, district heatingManual key
Pressing this key longer than 5 sec. will switch the controller into manual mode.Here the heat generator setpoint can be adjusted with the knob. All pumps will be running, while vales can only be operated by moving either the motor or the valve by hand.The heatgenerator setpoint is adjustable between 5..80°C. The setpoint is displayed as well as the actual temperature.
The switching differential is according to the parameter And is symmetrical to the setpoint.
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 17
Manual Operation
Operating keys, heatingManual key, emission test
In addition to the described manual function, this keycan be used to start the emission test phase for theservice man.With a short push of this button the boiler will operatewith it´s adjusted max. temperature limit for a periodeof 20 minutes.The remaining time will be displayed.
By pushing and holding the key the controller will ignore the max. limit and the temperature an reach a higher value in order to test the safety limiter.
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 18
Cold start
By pressing and holding all 4 keys at the same time a cold start is carried out. (return to default settings)This cold start will only effect the parameters of the activated operating hierarchy.The date/time setting and all switching programmes are effected also
Variable cold start
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 19
1. Check controller wiring2. Switch on power after segmenttest a similar line will appear:
26.06 V.1.00 date und version of software .
3. Please check if weekday, date, month and actual time are ok . If not please adjust in appropriate parameter menue. (controller will be delivered with running clock)
4. Please press the keys and at the same time and hold until CODE appears in the top line Enter installer code 1 2 3 4 with push and turn knob The display will switch to the standard picture after about 2 sek.
5. Hold push and turn knob until the menue switching times will appear and turn the knob clockwise until the menue hydraulic appears. Confirm by pushing, then parameter 01 will show 0000
6. Enter system hydraulic number, e.g. 0201 , or individual hydraulic parameters.
First start up
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 20
Decisions before start up:
Do I treat all heatconsumers as one?(Then: System/operation mode=1)Do I use only one time program per consumer?(Then: system/ program = P1)Do I treat heatconsumers individually?(Then: System/operation mode=2)Do I want different time programs for individual heatconsumers?(Then: System/operation mode=2 and system/program=P1-P3)
Start up
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 21
Operation mode= 1: Equal day-night setpoints and operation mode for all heating circuits
Operation mode= 2: individual day-night setpoints and operation modes for all heating circuits
Operation modes
Menue:System/Operation
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 22
Time program DK MK 1 MK 2 WW ZirkP 1 P1 individually adjustable for each consumer
Time program DK MK 1 MK 2 WW ZirkP1..3 P1 + P2 + P3 individually adjustable for each
consumer
Time programs
Menue: System/time programs
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 23
Time programs
Timeprograms, default values
Timeprogram P1 Timeprogram P1...P3
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 24
Overview Controller TypesH
oney
wel
l typ
e pr
opos
al
Num
ber
of s
tand
ard
rela
ys +
var
iabl
e ou
tput
s
2nd
stag
e or
DH
-va
lve
clos
e
1st
stag
e or
DH
-va
lve
open
unm
ixed
/ va
riab
le
outp
ut 3
mix
ing
circ
uit
1
mix
ing
circ
uit
2
DH
W lo
adin
g pu
mp
var
iabl
e ou
tput
2
SDC3-10 3-Rel. x x xSDC3-40 3-Rel. xSDC6-20 6-Rel. x x x xSDC7-21 7-Rel. x x x x xSDC8-21 6-Rel.+ 2 Variable x x x x xSDC9-21 7-Rel.+ 2 Variable x x x x x x
SDC12-31 10-Rel.+ 2 Variable x x x x x x xDHC 43-1 7-Rel x x x x xDHC 43-2 7-Rel.+ 2 Variable x x x x x x
Each Controller is available for Panel Mount (PC) or for Wall Mount (WC)
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 25
Mounting - Panel mount
Panel mountwith 4 terminalrows at the back of the controller
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 26
Mounting – Wall mount
Wall mountwith screwsor on DIN rail
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 27
10= standard room unit 20=comfort room unitSmile = controller family
Type key
SDW 20
SDW20
Room Units
SDW 10
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 28
Application Codes
0901, ...Special Applications
0801, 0802, ....Solar Applications
0701, 0702, ....Bolier Sequence
0601, 0602, ....Ventilation Applications
0501, 0502, ....District Heating Applications
0401, ....Additional Heating Circuits
0301, 0302, ....Basic Applications with 3 Heating Circuits
0201, 0202, ....Basic Applications with 2 Heating Circuits
0101, ....Basic Applikations with 1 Heating Circuit
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 29
Heating Hydraulic 0101 SDC 12-31SDC 9-21SDC 8-21SDC 7-21SDC 6-20SDC 3-10- 1 stage burner- unmixed heating circuit- DHW
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 30
Heating Hydraulic 0201 SDC 12-31SDC 9-21SDC 8-21SDC 7-21SDC 6-20- 1 stage burner- unmixed heating circuit- mixed heating circuit- DHW
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 31
Heating Hydraulic 0202 SDC 12-31SDC 9-21SDC 7-21- 2 stage burner- unmixed heating circuit- mixed heating circuit- DHW
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 32
Heating Hydraulic 0301 SDC 12-31- 1 stage burner- unmixed heating circuit- 2 mixed heating circuits- DHW
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 33
Heating Hydraulic 0302 SDC 12-31- 2 stage burner- unmixed heating circuit- 2 mixed heating circuits- DHW
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 34
Heating Hydraulic 0401 SDC 12-31SDC 9-21SDC 8-21SDC 7-21SDC 6-20SDC 3-40- 1 mixed heating circuit
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 35
District Heating Hydraulic 0501 DHC 43-2DHC 43-1- District Heating Valve- unmixed heating circuit
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 36
District Heating Hydraulic 0502 DHC 43-2DHC 43-1- District Heating Valve- unmixed heating circuit- DHW
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 37
District Heating Hydraulic 0503 DHC 43-2DHC 43-1- District Heating Valve- unmixed heating circuit- separate DHW control
/////// //
STB W F
///
VFB
//////
////
V 1
P 1
P 4
P 3//AF
//
SF
0503
.cdr
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 38
District Heating Hydraulic 0504 DHC43-2- District Heating Valve- unmixed heating circuit- layered DHW storage tank
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 39
District Heating Hydraulic 0505 DHC 43-2DHC 43-1- District Heating Valve- mixed heating circuit
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 40
District Heating Hydraulic 0506DHC 43-2DHC 43-1- District Heating Valve- unmixed heating circuit- mixed heating circuit
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 41
District Heating Hydraulic 0507 DHC 43-2DHC43-1- District Heating Valve- mixed heating circuit- DHW
Smile training
Smile_training_engl. Sept.02.ppt Honeywell Proprietary Jan. 31st, 2002 42
District Heating Hydraulic 0508 DHC43-2- District Heating Valve- unmixed heating circuit- mixed heating circuit- DHW