Solution

Feb. 15. 2007

Samsung Electronics

1. Solution Lineup

2. Wired remote controller

3. 7-day scheduler

4. Interface module

5. Centralized control

6. Power distribution

7. DMS

8. S-Net 2 Plus

9. S-Net I

10. S-Net 3

11. S-Net mini

INDEXINDEX

3 / 84

Solution LineupSolution Lineup1.1.

System A/C Wired R/CI/MCentralizedA/C Control

GHP

ERV Domestic

BAC

FJM

Mini DVM

DVM

DVM Plus

DVM Plus II

MWR-TH01

MWR-BS00

MWR-WS00

MIM-B04A

MIM-B02

MIM-B13

MIM-B07

S-Net mini

MCM-B102

MIM-B12

MCM-A202

MCM-A100

S-Net mini

MIM-B06

MWR-BS00

MST-S1P

MIM-D00

MST-P3P

MST-P1W0

S-Net mini

4 / 84

Wired remote controllerWired remote controller2.2.

■ Features

FeaturesModel

Support COM 1 and COM 2 wiring RMC address assignment

Only support COM 2 wiring Support 2400 / 9600 bps Newly designed Sleep mode, Silent mode, Child lock Real time clock & 7-day schedule function Temperature sensor Service mode (Additional functions)

- Indoor unit option code setting function etc.

Image

MWR-TH01

MWR-WS00

5 / 84

■ Communication channel

N YInstall on COM 1 Install on COM 2

Dose the outdoorunit support thePLUS protocol?

Wired remote controllerWired remote controller2.2.

■ Connection units

COM 1 Wiring

■ Connection units

COM 2 Wiring

– Outdoor unit– Indoor units– Interface module (Key-tag, Lonworks, 485)– Wired remote controller– Power distribution unit

– Indoor units– Wired remote controller– 7-day scheduler

■ Old error display (Er XX) ■ Error code display (E XXX)

6 / 84

COM 2 wiring

COM 1 wiring12VDC for wiredRemote controller

■ Terminal block on the indoor unit

Wired remote controllerWired remote controller2.2.

7 / 84

■ COM 1 wiring of wired remote controller

Terminal Block

WhiteBlack

Red

Blue

12VDC Power Supply

Communication Line

Wired Remote Control

(MWR-TH01)

Wired remote controllerWired remote controller2.2.

Only CAC non-inverter model supports COM 1 wiring.

8 / 84

■ COM 1 wiring of wired remote controller

Wired remote controllerWired remote controller2.2.

Outdoor Unit

MWR-TH01

Main 0RMC 0 RMC 2RMC 1

Main 1 Main 2

RMC 1 RMC 2RMC 0

RMC AddressMain Address

Wired R/C Enable/DisableI/M Enable/Disable

Indoor Unit Option Setting

9 / 84

■ COM 2 wiring of wired remote controller

Terminal Block

White

Black

RedBlue

12VDC Power Supply

Communication Line(Non-polarity)

Wired Remote Control

(MWR-TH01 / WS00)

Wired remote controllerWired remote controller2.2.

10 / 84

■ Option switch setting (MWR-TH01)

SW No Off On Default

SW 1 Cooling only Cooling and heating On

SW 2 COM 2 Wiring (F3 / F4) COM 1 Wiring (F1 / F2) Off

SW 3 Celsius (C) display Fahrenheit (F) display Off

SW 4Wireless remote controller also available

Only wired remote controller can be used

Off

SW 5 Assign RMC (Group) address with wired remote controller Off

DS01

DS02DS03

Address switch

DS01 DS02

SW1 SW8SW5SW4

Wired remote controllerWired remote controller2.2.

SW 2 Off (COM 2) On (COM 1)

Address switch0 : Master Matches with Indoor

unit RMC addressOthers : Slave

11 / 84

Wired remote controllerWired remote controller2.2.

■ Assign RMC address (MWR-TH01 COM 2 wiring)

SW 5 ‘OFF’ – Set SW 5 of DS02 switch on the wired remote controller PCB to ‘OFF’.

– Press the ‘Mode’ button and ‘Fan speed’ button in front of the wired remote control simultaneously for more than 5 seconds.

– Adjust RMC address using “Up” and “Down” buttons.

Change confirm

Operation mode

– Press the “Operation” button to select the required group address. Then, the group address display flickers and changes.

– Press the button once to set the selected group address with the ‘beep’ sound.

– Wired remote controller LCD displays main address and RMC (Group) address and changes to the “Indoor unit group address setting mode”.

– Press the button again to quit the setting mode and enter the operation mode.

Enter ‘Group address setting

mode’

Change RMC

RMC change

12 / 84

■ Option switch setting (MWR-WS00)

SW No Off On Default

SW 1 Cooling and heating Cooling only Off

SW 2Wireless remote controller also available

Only wired remote controller can be used

Off

SW 3 Master Slave Off

SW 4 Celsius (C) display Fahrenheit (F) display Off

SW 5 Use indoor unit temperature sensorUse wired remote controller temperature sensor

Off

SW 6 -Use the average of indoor unit and wired remote controller temperature sensor

Off

SW 7 - - Off

SW 8 Service mode monitor Service mode setup Off

Wired remote controllerWired remote controller2.2.

– After adding / removing indoor units or indoor unit PCB change, press the “Set” button and “Cancel” button simultaneously for 5 seconds.

13 / 84

Wired remote controllerWired remote controller2.2.

■ Service mode (MWR-WS00)

Menu Description

1 Monitoring and setting the indoor unit option code

2 Monitoring and setting the indoor unit RMC address

3 Monitoring the indoor unit cycle data

4 Setting the indoor unit temperature sensor compensation

5 Setting the fan RPM compensation

6 Setting the EEV step when the indoor unit is off in heating mode

7 Setting the filter time

8 Setting the heating capacity compensation

9 Checking the indoor unit centralized control switch setting

10 Checking the indoor unit drain pump switch setting

11 Checking the indoor unit electric heater switch setting

12 Checking the indoor unit hot water heater switch setting

13 Checking the number of connected indoor units (April. 2007)

14 Checking the program version of wired remote controller (April. 2007)

– If the option switch SW8 is set to ‘OFF’, the above service modes can be only monitored. Set the option switch SW8 to ‘ON’ to set the above service modes.

14 / 84

Indoor Unit

RMC Address Anything OK

DIP Switch K1 Anything OK

MWR-TH01

Address Switch 0

DIP Switch SW2 Off

Indoor Unit

RMC Address Anything OK

DIP Switch K1 Anything OK

MWR-WS00

DIP Switch SW3 Off

■ COM 2 basic wiring

Wired remote controllerWired remote controller2.2. Check List

15 / 84

Indoor Unit

RMC Address Anything OK

DIP Switch K1 Anything OK

MWR-TH01 (Master)

Address Switch 0

DIP Switch SW2 Off

MWR-TH01 (Slave)

Address Switch Except 0

DIP Switch SW2 Off

MWR-WS00 (Master)

DIP Switch SW3 Off

MWR-WS00 (Slave)

DIP Switch SW3 On

Max 2 Wired remote controller

■ 2 Wired remote controller wiring

Wired remote controllerWired remote controller2.2. Check List

16 / 84

Indoor Unit

RMC Address Anything OK

DIP Switch K1 Anything OK

MWR-TH01

Address Switch 0

DIP Switch SW2 Off

Indoor Unit

RMC Address Anything OK

DIP Switch K1 Anything OK

MWR-WS00

DIP Switch SW3 Off

Max 16 Indoor units

■ Group control using wired remote controller

Wired remote controllerWired remote controller2.2. Check List

17 / 84

Indoor Unit

RMC Address Anything OK

DIP Switch K1 Anything OK

Indoor Unit

RMC Address Anything OK

DIP Switch K1 Anything OK

Max 16 Indoor units

MWR-TH01 (Master)

Address Switch 0

DIP Switch SW2 Off

MWR-TH01 (Slave)

Address Switch Except 0

DIP Switch SW2 Off

MWR-WS00 (Master)

DIP Switch SW3 Off

MWR-WS00 (Slave)

DIP Switch SW3 On

Max 2 Wired remote controller

■ Group control using 2 wired remote controllers

Wired remote controllerWired remote controller2.2. Check List

18 / 84

■ Features

7-day scheduler7-day scheduler3.3.

FeaturesModel

Weekly schedule for 1 or 16 groups Can interface with wired remote controller

or centralized controller Can skip schedule on specified date

Image

MWR-BS00

With MWR-TH00 / MWR-TH01 With MCM-A201

– Connects to COM 2 wiring (F3 / F4)

– Connects to R1 / R2 communication port– Does not support individual group schedules– Controls all indoor units under centralized controller

19 / 84

Indoor Unit

RMC Address Anything OK

DIP Switch K1 Anything OK

MWR-TH01 (Master)

Address Switch 0

DIP Switch SW2 Off

MWR-BS00 (Slave)

SW 2 On : Disable the On/Off button on the wired remote controller

■ Wired remote controller / 7-day scheduler

7-day scheduler7-day scheduler3.3. Check List

20 / 84

Indoor Unit

RMC Address Anything OK

DIP Switch K1 Anything OK

Max 16 Indoor units

MWR-TH01 (Master)

Address Switch 0

DIP Switch SW2 Off

MWR-BS00 (Slave)

SW 2 On : Disable the On/Off button on the wired remote controller

■ Wired remote controller / 7-day scheduler (Group control)

7-day scheduler7-day scheduler3.3. Check List

21 / 84

Indoor Unit

RMC Address Anything OK

DIP Switch K1 Anything OK

MWR-TH01 (Master)

Address Switch 0

DIP Switch SW2 Off

MWR-BS00

SW 2 On : Disable the On/Off button on the wired remote controller

MWR-TH01 (Slave)

Address Switch Except 0

DIP Switch SW2 Off

■ 2 Wired remote controller / 7-day scheduler

7-day scheduler7-day scheduler3.3. Check List

22 / 84

Max 16 Interface modules

MCM-A201MIM-B04

Address 0

DIP Switch K1 On

Outdoor Unit

■ Centralized control using 7-day scheduler

7-day scheduler7-day scheduler3.3.

In case of mini-DVM & DVM Plus II, this combination is impossible .

Max 16 Interface modules

MWR-BS00

MCM-A100

MIM-B04

Address 0

DIP Switch K1 On

Outdoor Unit

Check List

23 / 84

■ Features

Interface moduleInterface module4.4.

FeaturesModel

485 communication interface module 2400 / 9600 bps auto detection BAC, DVM, FJM, DVM Plus series

485 communication interface module 2400 / 9600 bps auto detection Support earlier version include DVM Plus II

Image

MIM-B04A

MIM-B13

MIM-B02

MIM-B07

Key-tag interface module Be used in hotel where the A/C need

to turn off if vacant

Lonworks interface module BMS connection using Lonworks protocol

24 / 84

Interface moduleInterface module4.4.

■ Key-tag interface module (MIM-B02)

– BeBe widely used in hotels where the A/C needs to turn off if vacant.– CCan be used with the 485 interface module simultaneously only on selected outdoor units. (RVMH060GDM3, RVMH100GCM3, RVMR100GCM0)– From DVM Plus II Indoor units, MIM-B14 (External control interface module) has the Key-Tag function.

If two indoor units are installed in the room

Wire according to the main address of the indoor unit.

If only one indoor unitis installed in the room

MIM-B14

25 / 84

■ Key-tag I/M Option switch setting (MIM-B02)

SW No Off On

SW 1 Normal close contact (B type) Normal open contact (A type)

SW 2 Address D4 (with 485 I/M) Address D0

SW 3 External control (On/Off control) Key-tag control (Off Control)

SW 4 Enable initial event control Disable initial event control

Interface moduleInterface module4.4.

– Only available in external control mode ( SW 3 Off )– This function is used for indoor units without breakout recovery function.

– If power reset occurs, an event signal is generated to recover operation status of indoor unit after checking the external contact status.– If the indoor units were ON before power reset, an event signal is generated to turn on the indoor units after power reset. If the indoor units OFF before power reset, they remain OFF after power reset.

Initial event control

26 / 84

Off Control

by contact status

ON

1 2 3 4

DS01

ON

1 2 3 4

DS01

Contact Status

Command

Indoor Operation

HIGH(SHORT)

LOW(OPEN)

 Working  Working  Stop   Stop

 On event by other controller

OFF Command OFF Command

Contact Status

Command

Indoor Operation

HIGH(SHORT)

LOW(OPEN)

 Working  Working  Stop   Stop

On event by other controller

OFF Command

OFF Command

■ Key-tag interface function

Interface moduleInterface module4.4.

27 / 84

On/Off Control by contact status

Contact Status

Command

Indoor Operation

HIGH(SHORT)

LOW(OPEN)

ON Command

OFF Command

ON Command

 Working

   Stop    Stop Working

 Off event by other controller

Power In

Contact Status

Command

Indoor Operation

HIGH(SHORT) LOW(OPEN)

ON Command

OFF Command

ON Command

 Working   Stop    Stop Working

Off event by other controller

Power In

ON

1 2 3 4

DS01

ON

1 2 3 4

DS01

■ Key-tag interface function

Interface moduleInterface module4.4.

28 / 84

Interface moduleInterface module4.4.

■ Key-tag interface module wiring

Outdoor Unit

Samsung Scope

Central monitoring panel

Key rack Room management system (RMS)Floor I/M

MIM-B02

DIP Switch K2 On

Indoor units

Main Address Manual

DIP Switch K2 Anything OK

Max 16 Indoor units

Check List

29 / 84

Samsung Scope

MIM-B02

DIP Switch K2 Off

Max 16 Indoor units

MIM-B04A

Address Anything OK

DIP Switch K1 On

MCM-A202

■ Key-tag interface module / Centralized controller

Central monitoring panel

Key rack Room management system (RMS)Floor I/M

Interface moduleInterface module4.4.

Indoor units

Main Address Manual

DIP Switch K2 Off

RVMH060GDM3, RVMH100GCM3, RVMR100GCM0

Check List

30 / 84

■ External control interface module

Interface moduleInterface module4.4.

MIM-B14

DB93-04159A External Control PBA

DB39-01263A Cable for timer input

DB39-01264A Cable for output

– Control indoor unit by “External contact signal”. (Switch, Timer etc.)– Display “Compressor operation and error status”.– Set DIP switch K11 to “Off” on the indoor unit’s PCS.

– Note 1. Operation is as same as last operation status. (At first , “Auto mode, Set temp. 24 , Auto airflow”)℃ 2. Impossible to connect with wall mounted Indoor units. (Vivace, Prestige, Premium)

Wire No. Description

1, 2 Error check

3, 4 Comp. operation Check

5, 6 Input signal

31 / 84

Interface moduleInterface module4.4.

DB39-01263A

CN83

Signal with power

ExternalSignal

External Signal

Operation

Relay

■ External control interface module (Direct connection)

PCB of duct type indoor unit

DIP S/W K11 : Off

Check List

32 / 84

Interface moduleInterface module4.4.

MIM-B14(DB93-04159A)

DB39-01263A

Off DelayTimer Relay

Power

PushButtonSwitch

Supplied by installer

External Signal

Operation

Timer setting

DB39-01264A

DIP S/W K11 : Off

CN83 CN81

■ External control interface module (Timer Delay)

Check List

33 / 84

■ Lonworks interface module (MIM-B07)

Interface moduleInterface module4.4.

MIM-B07 is used to manage DVM air conditioner with other devices using one of BMS open protocol Lonworks.

Function Item Description

Control

On/Off control Run or stop indoor unit

Operation mode Set operation mode (Auto / Cool / Heat / Fan mode)

Setting temperature Set target temperature (Cool : 18~30 C, Heat : 16~30 C)

Fan speed Set fan speed (Auto / Low / Mid / High)

Monitoring

Running status Monitor indoor unit running status (Run / Stop)

Operation mode Monitor operation mode (Auto / Cool / Heat / Fan mode)

Room temperature Monitor current room temperature

Error status Monitor error status (Error code)

34 / 84

■ Lonworks interface module (MIM-B07)

Interface moduleInterface module4.4.

• Lonworks Interface Module

• Model Code : MIM-B07

• CPU : Neuron 3150 Smart Transceiver

• Communication : RS485 to FTT-10A

FTT-10A 78Kbps

Free topology

• Service Pin : Auto-binding

• Power Input : DC 12V

• Size : 50mm x 80mm

• Parallel connection (4 units)

• Lonworks Interface Module

• Model Code : MIM-B07

• CPU : Neuron 3150 Smart Transceiver

• Communication : RS485 to FTT-10A

FTT-10A 78Kbps

Free topology

• Service Pin : Auto-binding

• Power Input : DC 12V

• Size : 50mm x 80mm

• Parallel connection (4 units)

Neuron Chip Transceiver

35 / 84

■ SNVT (Standard Network Variable Type) Configuration

Interface moduleInterface module4.4.

DVMIndoor[12]

nviFanSpeed

nviIndoorMode

nviSetTemp

nvoIndoorStatus

nvoRoomTemp

No NV Name Index NV Type Description

1 nviIndoorMode[12] 2~13 SNVT_hvac_mode On/Off & operation mode

2 nviSetTemp[12] 14~25 SNVT_temp_f Setting temperature

3 nviFanSpeed[12] 26~37 SNVT_Switch Fan speed

4 nvoIndoorStatus[12] 38~49 SNVT_hvac_Status On/Off, Mode, Error Monitoring

5 nvoRoomTemp[12] 50~61 SNVT_temp_f Current room temperature

36 / 84

■ SNVT (Standard Network Variable Type) Configuration

Interface moduleInterface module4.4.

SNVT_hvac_mode Operation

HVAC_OFF Stop

HVAC_AUTO Auto mode

HVAC_COOL Cooling mode

HVAC_HEAT Heating mode

HVAC_FAN_ONLY Fan mode

Value Operation

0 (Default) Auto

1 Low

2 Mid

3 High

nviIndoorMode nviFanSpeed

Field Type Description

mode Hvac_t Control mode

heat_output_primary Signed long Indoor unit address

fan_output Signed long Error code

in_alarm Unsigned short Error status (True / False)

nviIndoorStatus

37 / 84

– Function

1) “A” : Service Pin – Use Binding with other Lonworks I/M.

2) “B” : RS485 Comm. connector with DVM Outdoor and indoors.

3) “C” : Power connector (12VDC) from Outdoor units.

4) “D” : Terminal block for FTT-10A (Twisted Pair).

Display Status Action

Off Normal

Flickering Un-Configured Need re-commission

On Application Less Need program download

– Test using LED

1) D3(Service Pin LED) : Turn on when pushing service pin

2) D4 (Command Status LED) : Command receive on Network (0.2s)

3) D5 (RS485 Tx) : Flicking when data send on RS485 comm. Line (0.06s)

4) D6 (RS485 Rx) : Flicking when data receive on RS485 comm. Line (0.06s)

■ MIM-B07 Installation test

Interface moduleInterface module4.4.

A

C

D

B

D3

D4

D5D6

E

38 / 84

Outdoor Unit

Samsung Scope

MMI

Indoor units

Main Address Manual

DIP Switch K2 Off

Max 12 Indoor units

Lonworks Twisted PairLonworks

BMS SYSTEMBMS SYSTEM

Lon to TPC/IPRouter

Ethernet

Workstation Client 1 Client 2

PowerPower

EquipmentEquipment

EntranceEntrance

LightLight

MIM-B07

Address 0

■ Lonworks interface module wiring

Interface moduleInterface module4.4. Check List

39 / 84

Outdoor Unit

Samsung Scope

Indoor units

Main Address Manual

RMC Address Anything OK

DIP Switch K2 Off

Max 48 Indoor unitsMax 4 Lonworks interface modules

MIM-B07

Address 0

MIM-B07

Address 1

MIM-B07

Address 2

MIM-B07

Address 3

MMI

Lonworks Twisted PairLonworks

■ Lonworks I/M wiring (More than 12 indoor units)

Interface moduleInterface module4.4.

Power source : Install maximum 2 I/M from each outdoor module

Check List

40 / 84

■ Features

FeaturesModel

Use with 7-day scheduler BAC, DVM, FJM, DVM Plus series

High speed communication version Use with 7-day scheduler Support earlier version include DVM Plus II

Image

MCM-A201

Centralized controlCentralized control5.5.

MCM-A202

Used with centralized controller Group control up to 16 indoor groups Error display function

MCM-A100

41 / 84

■ Installing the centralized controller (MCM-A202)

Centralized controlCentralized control5.5.

NL

R1R2C1C2

220V AC Power input

485 Interface Module

Function ControllerSNET II+

FRONT VIEW

– LED On equivalent to interface module

address at tracking.– Green LED of PCB backside is flickering

when communication with interface

module. Red LED is flickering when

communication with DMS.– If “11” and “15” button press at the same

time for 5 seconds, centralized controller

is reset.

42 / 84

■ Option switch setting (MCM-A202)

SW No Off On

SW 3Group tracking

mode

Room tracking

mode

SW 4Communication

Speed 9600 bps

Communication

Speed 2400 bps

Centralized controlCentralized control5.5.

Control level SW 1 SW 2

0 Off Off

1 On Off

2 Off On

3 On On

Upper controller is set to “Room mode” & SW 3 is set to “Off”

Upper controller is set to “Group mode” & SW 3 is set to “On”

Upper controller is set to “2400 bps” & SW 4 is set to “Off”

Upper controller is set to “9600 bps” & SW 4 is set to “On”

Setting error display : Rotated flickering

43 / 84

■ Centralized control level

FeaturesLevel

No priority level. Wired and wireless remote controller can be used.

Wired and wireless remote controller are disabled when

the indoor unit is stopped by centralized controller.

0

Centralized controlCentralized control5.5.

1

The “All ON” button determines stand-by state. When the

“All ON” button is pressed, ON-state LED turns on without

turning on all the indoor units and the remote controllers

are allowed to use.

3

Remote controllers are disabled at all time2

44 / 84

■ Cooling / heating selection switch

Centralized controlCentralized control5.5.

– If set to “cool”, the indoor units will turn on to the cooling mode. However, this does not mean that heating mode is disabled.

– If set to “heat”, the indoor units will turn on to the heating mode.

MCM-C200

To prevent cooling/heating mode confusion error on the heatpump outdoor unit, MCM-C200 also can be used.

45 / 84

■ Installing the function controller (MCM-A100)

Centralized controlCentralized control5.5.

DC 12V Communication Line From Centralized Controller

C1 C2V2 V1

Front Rear

DC 12V

46 / 84

Indoor Unit

Main Address 0 (Manual)

RMC Address 0

DIP Switch K2 Off

Indoor Unit

Main Address 1 (Manual)

RMC Address 1

DIP Switch K2 Off

Indoor Unit

Main Address F (Manual)

RMC Address F

DIP Switch K2 Off

Max 16 Indoor units

Outdoor Unit

MIM-B04A

Address Anything OK

DIP Switch K1 On

※ Include DVM Plus less than 16 indoor units

■ Wiring (mini-DVM, DVM, DVM HR : Individual)

Centralized controlCentralized control5.5.

MCM-A202

SW 3 Off

Check List

47 / 84

From 17 to max 32 Indoor units

Outdoor Unit

MIM-B04A

Address Anything OK

DIP Switch K1 On

MIM-B04A

Address Anything OK

DIP Switch K1 Off

Indoor Unit

Main Address 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

RMC Address 0 1 2 3 4 5 6 7 8 9 A B C D E F

DIP S/W K2 Off

DIP S/W K10 On

Indoor Unit

Main Address 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31

RMC Address 0 1 2 3 4 5 6 7 8 9 A B C D E F

DIP S/W K2 Off

DIP S/W K10 Off

■ Wiring (DVM Plus : Individual)

Centralized controlCentralized control5.5.

MCM-A202

SW 3 Off

Check List

48 / 84

Indoor Unit

Main (Ten) 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1

Main (One) 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5

RMC (1) 0

RMC (2) 0 1 2 3 4 5 6 7 8 9 A B C D E F

DIP Switch K2 Off

Less than 16 Indoor units

Outdoor Unit

MIM-B13

Address Ch 1 Anything OK

Address Ch 2 Anything OK

Address Ch 3 Anything OKChannel 1

■ Wiring (DVM Plus II : Individual)

Centralized controlCentralized control5.5.

MCM-A202

SW 3 Off

Check List

49 / 84

Outdoor UnitMIM-B13

Address Ch 1 Anything OK

Address Ch 2 Anything OK

Address Ch 3 Anything OK

From 17 to max 32 Indoor units

Indoor Unit

Main (Ten) 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1

Main (One) 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5

RMC (1) 0

RMC (2) 0 1 2 3 4 5 6 7 8 9 A B C D E F

DIP S/W K2 Off

Indoor Unit

Main (Ten) 1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3

Main (One) 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1

RMC (1) 1

RMC (2) 0 1 2 3 4 5 6 7 8 9 A B C D E F

DIP S/W K2 Off

Channel 1

Channel 2

■ Wiring (DVM Plus II : Individual)

Centralized controlCentralized control5.5.

MCM-A202

SW 3 Off

Check List

50 / 84

Outdoor Unit MIM-B13

Address Ch 1 Anything OK

Address Ch 2 Anything OK

Address Ch 3 Anything OK

Indoor Unit

Main (Ten) 0 - 1 - 1 1 - 2 - 3 3 - 4 - 4

Main (One) 0 - 0 - 5 6 - 0 - 1 2 - 0 - 7

RMC (1) 0 1 2

RMC (2) 0 - A - F 0 - 4 - F 0 - 8 - F

DIP S/W K2 Off

From 33 to max 48 Indoor units

Channel 1

Channel 2

Channel 3

■ Wiring (DVM Plus II : Individual)

Centralized controlCentralized control5.5.

MCM-A202

SW 3 Off

Check List

51 / 84

Indoor Unit

Main Address 0 (Manual)

RMC Address 0

DIP Switch K2 Off

Indoor Unit

Main Address 1 (Manual)

RMC Address 0

DIP Switch K2 Off

Indoor Unit

Main Address F (Manual)

RMC Address F

DIP Switch K2 Off

Max 16 Indoor units and 16 Groups

Outdoor Unit

MIM-B04A

Address Anything OK

DIP S/W K1 On

■ Wiring (mini-DVM, DVM, DVM HR : Group)

Centralized controlCentralized control5.5.

MCM-A202

SW 3 Off

Check List

52 / 84

Outdoor Unit

MIM-B04A

Address 0

DIP Switch K1 On

Indoor Unit

Main Address 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

RMC Address 0 0 1 1 2 2 3 3 4 4 5 5 6 6 7 7

DIP S/W K2 Off

DIP S/W K10 On

Indoor Unit

Main Address 16 1718

19

20

2122

23

24

25

2627

28

29 30 31

RMC Address 8 8 9 9 A A B B C C D D E E F F

DIP S/W K2 Off

DIP S/W K10 On

From 17 to max 32 Indoor units and less than 16 Groups

■ Wiring (DVM Plus : Group)

MIM-B04A

Address 1

DIP Switch K1 Off

Centralized controlCentralized control5.5.

MCM-A202

SW 3 Off

Check List

53 / 84

Outdoor Unit

MIM-B13

Address Ch 1 Anything OK

Address Ch 2 Anything OK

Address Ch 3 Anything OK

Indoor Unit

Main (Ten) 0 - 1 - 1 1 - 2 - 3 3 - 4 - 4

Main (One) 0 - 0 - 5 6 - 0 - 1 2 - 0 - 7

RMC (1) 0 1 2

RMC (2) 0 - A - F 0 - 4 - F 0 - 8 - F

DIP S/W K2 Off

Channel 1

Channel 2

Channel 3

Max 48 Groups

■ Wiring (DVM Plus II : Group)

Centralized controlCentralized control5.5.

MCM-A202

SW 3 Off

Check List

54 / 84

Max 32 Groups (without DVM Plus II)

Outdoor UnitMIM-B04A

Address 0

DIP Switch K1 On

Indoor Units

DIP Switch K2 OffMax 16 Interface modules

Indoor Units

DIP Switch K2 Off

DIP Switch K10 On

Outdoor Unit

MIM-B04A

Address 0

DIP Switch K1 Off

Indoor Units

DIP Switch K2 Off

DIP Switch K10 Off

Max 16 Interface modules

■ Wiring (Combination : Group)

MIM-B04A

Address 1

DIP Switch K1 On

Centralized controlCentralized control5.5.

MCM-A202

SW 3 Off

Check List

55 / 84

Outdoor Unit MIM-B13

Address Ch 1 1

Address Ch 2 Anything OK

Address Ch 3 Anything OK

Channel 1

Channel 2

Max 48 Groups (with DVM Plus II)

Outdoor Unit

MIM-B04A

Address 0

DIP Switch K1 On

Indoor Units

DIP Switch K2 Off

Max 16 Interface modules

Max 16 Interface modules

Indoor Units

RMC (1) 0 1 2

DIP Switch K2 Off

Max 16 Interface modulesChannel 3

■ Wiring (Combination : Group)

Centralized controlCentralized control5.5.

MCM-A202

SW 3 Off

Check List

56 / 84

Outdoor UnitMIM-B13

Address Ch 1

1

Address Ch 2

Anything OK

Address Ch 3

Anything OK

Channel 1

Channel 2

Max 16 Interface modules

Max 16 Interface modules

Channel 3

MIM-B04A

Address Anything OK

DIP S/W K1 On

Indoor Units

DIP S/W K2 Off Off

DIP S/W K10 On Off

Outdoor Unit

MIM-B04A

Address 0

DIP S/W K1 OffMax 16 Interface modules

Max 16 Interface modules

Indoor Units

RMC (1) 0 1 2

DIP Switch K2 Off

■ Wiring (Combination : Group) with DVM Plus & DVM Plus II

Centralized controlCentralized control5.5.

MCM-A202

SW 3 Off

Check List

57 / 84

Outdoor Unit

MIM-B13

Address Ch 1 0

Address Ch 2 Anything OK

Address Ch 3 Anything OK

Channel 1

Max 16 Interface modules

MCM-A100

MIM-B04A

Address 1

DIP S/W K1 On

Outdoor Unit

■ Wiring (Function controller / Centralized controller)

Centralized controlCentralized control5.5.

MCM-A202

Address Same wit F.C

SW 3 Off

SW 4 On

Check List

58 / 84

■ Features

FeaturesModel

PDU (Power distribution unit) Can connect maximum 48 indoor units Alarm of measuring failure Total / Individual power consumption display

Image

Power distributionPower distribution6.6.

MCM-B102

PDIM (Power distribution interface module) Can connect maximum 32 PDU

MIM-B06

When one outdoor unit is used several households for common use like studio apartment / arcade etc, display and management of accumulated power consumption of each household air conditioner.

Total demand capacity of indoor unitsTotal power consumption x

Demand capacity of Room ARoom A’s electric power consumption

=

59 / 84

■ PDU Specification

Power distributionPower distribution6.6.

Model code MCM-B102

Power supply 1 Phase 220VAC, 50/60Hz

Power meter makerRS485 type

Omni System

Korea Micronics

LS Industrial Systems

Hansuk Tech

Pulse type Anything

Power meter communication type RS485 or Pulse type

Remote measuring company

Omni System

Korea Micronics

LS Industrial Systems

Total power consumption display Power Consumption of one Outdoor unit

Power consumption of each indoor unit Maximum 48 Indoor units

Search Auto / Manual Search Function

Operation temperature -40 C ~ 80 C

Dimension 131 Width x 196 Height x 56.5 Depth

60 / 84

Outdoor Unit

Indoor units

Main Address Manual

RMC Address Anything OK

Max 48 Indoor units

MCM-B102

Address Anything OK

Power meter

■ Wiring (PDU)

Power distributionPower distribution6.6. Check List

61 / 84

Outdoor Unit

Indoor units

Main Address Manual

RMC Address Anything OKMCM-B102

Address 0

Indoor units

Main Address Manual

RMC Address Anything OKMCM-B102

Address 1 Samsung Scope

Max 32 PDU

Max 16 PDIM

Remote measuring

MIM-B06

Address 0

MIM-B06

Address 1

■ Wiring (PDU / PDIM)

Power distributionPower distribution6.6. Check List

In case of DVM Plus & DVM Plus II, remote measuring is impossible .

62 / 84

DMSDMS7.7.

FeaturesModel

DMS (Data management server) Lower level : System A/C data storage server Upper level : Gateway for multi connection

Image

MIM-D00

SIM for power distribution on DMS level Can connect maximum 8 power metersMIM-B12

■ Features

– Embedded web server, Operation without PC– 16 Centralized controller and 256 indoor unit group/individually control – Error and operation status reports to the upper level controller– Edit and save yearly / weekly schedules– Power distribution function (Save 62 days worth of power distribution data)– Support multi user and compatible with multiple controllers (S-Net i, S-Net 3)– Connectable 8 SIM (MIM-B12) and 64 power meters– Current time back up for 24 hours when the power is cut off

63 / 84

DMSDMS7.7.

■ Menu architecture

Menu architecture

Control & Monitor Features Monitoring System environment

Control & Monitoring Control Periodical power use Tracking

Error history Power distribution Run time ratio Rename

Peak power control Power use per IU User management

Daily run time

Peak control status

■ DMS connectable devices

No Product Model Note

1 Indoor / Outdoor BAC, DVM, DVM Plus, DVM Plus II

2 Interface module MIM-B04A / MIM-B13 Don’t use MIM-B04

3 Centralized controller MCM-A202 Don’t use MCM-A200 / 201

4 SIM MIM-B12 Power distribution

64 / 84

DMSDMS7.7.

■ DI (Digital input) / DO (Digital output)

② ① ④ ③ ⑤ ⑥

1 DI – 1 External contact signal control

2 DI - 2 External contact signal control

3 DO – 1

Outputs 12V if at least one indoor unit is running.

(External circuit may be built for display using the

12V output) Equivalent to the ‘A/C Running’ LED

on the DMS external display.

4 DO - 2

Outputs 12V if there is an error on the indoor or

outdoor unit or if communication error occurs.

(External circuit may be built for display using the

12V output) Equivalent to the ‘Error’ LED on the

DMS external display.

5 LAN LAN connection port

6 COM Communication port to centralized controller / SIM

65 / 84

DMSDMS7.7.

■ DI (Digital input) External contact control

PatternDIP Switch

Control details1 2

Pattern 1 Off Off No response to the external contact signal control. (Factory setting)

Pattern 2 On Off – Used for emergency cases such fire.– When there is an input ON signal on DI-1, turns off all the indoor

units, and disables the use of all the remote controllers.– During an emergency stop, the DMS will ignore any request from

the higher level controllers.– The schedules and the peak power control will not operate as well.– The indoor units are restored to the previous operation status,

when the input signal changes to OFF. (The DI-2 is not used)

Fire Sensor

66 / 84

DMSDMS7.7.

■ DI (Digital input) External contact control

PatternDIP Switch

Control details1 2

Pattern 3 Off On – Changes the on/off status of all the indoor units depending on the

ON/OFF status of the DI-1 input.– Enables/disables the remote controllers depending on the

ON/OFF status of the DI-2 input. (ON: enable/ OFF: disable)– The schedules and the peak power control will run regardless of

pattern 3.

Pattern 4 On On – Turns on all the indoor units when there is a pulse input on DI-0.– Turns off all the indoor units when there is a pulse input on DI-1.– Turns off all the indoor units when there is a pulse input on DI-1,

DI-2. (The pulse width is valid only for 0.5~1.0 sec.)– The schedules and the peak power control will run regardless of

pattern 4.

67 / 84

DMSDMS7.7.

■ DI (Digital input) External contact control

No Pattern Control details

1 Power (Red) Power display.

2 CPU Alive (Yellow)Flickers every second in normal operation.

3 Linked (Green) Internet cable connection status display.

4 Active (Green) Flickers during data transmit & receive.

5 RS485 Tx (Green)Flickers during data transmission from theDMS to the centralized controller.

6 RS485 Rx (Green)Flickers during data transmission from thecentralized controller to the DMS.

7 DI-1 Status (Green)Lights on when using the DI-1 externalcontact signal control.

8 DI-2 Status (Green)Lights on when using the DI-2 externalcontact signal control.

9 A/C Running (Green)Lights on if at least one indoor unit connected to the DMS is running.

10 Error (Green)Lights on if there is an error on at leastone indoor or outdoor unit.

68 / 84

MIM-D00

MIM-B13

Address Ch 1 2

Address Ch 2 Anything OK

Address Ch 3 Anything OK

Channel 1

Outdoor Unit

MIM-B04A

Address 0

DIP Switch K1 OnMax 16 Interface modules

MIM-B04A

Address 1

DIP Switch K1 On

Outdoor Unit

Outdoor Unit

Max 256 indoor unitsMax 16 Centralized controllers

Web browser

DMSDMS7.7.

■ Wiring

MCM-A202

Address 0

SW 4 Off

MCM-A202

Address 1

SW 4 Off

Check List

69 / 84

■ Wiring with SIM

MIM-D00

MIM-B13

Address Ch 1 2

Address Ch 2 Anything OK

Address Ch 3 Anything OK

Channel 1

Outdoor Unit

MIM-B04A

Address 0

DIP Switch K1 OnMax 16 Interface modules

MIM-B04A

Address 1

DIP Switch K1 On

Outdoor Unit

Outdoor Unit

Max 256 indoor unitsMax 16 Centralized controllersMax 8 SIM

Web browser

Max 8 Power metersMIM-B12

Address 0

DMSDMS7.7.

MCM-A202

Address 0

SW 4 Off

Check List

70 / 84

S-Net 2 PlusS-Net 2 Plus8.8.

FeaturesModel

System A/C control PC software using RS-232C communication. Individual / Group / Zone control. Weekly / Daily / Timely scheduling. Maximum 256 groups, 4096 indoor units control. Enable / disable individual use of remote controllers. Peak power control (Korea domestic only)

MST-S1P

■ Features

PC–Converter Comm. Status Display LED

Converter–485 Comm. State Display LED

Power LED

RS232 Cable Connection Connector

RS485 Communication Connector

Converter Power Input Connector

MIM-C00

485 / 232Converter

Centralized controllers CANNOT be used in individual control.

71 / 84

MIM-B13

Address Ch 1 2

Address Ch 2 Anything OK

Address Ch 3 Anything OK

Channel 1

Outdoor Unit

MIM-B04A

Address 0

DIP Switch K1 On

Max 16 Interface modules

MIM-B04A

Address 1

DIP Switch K1 On

Outdoor Unit

MCM-C202

Address 0

MCM-C202

Address 1

MIM-C00

Max 4096 indoor unitsMax 256 indoor groupsMax 16 Centralized controllers

MST-S1P

S-Net 2 PlusS-Net 2 Plus8.8.

■ Wiring

Check List

Less than 32 indoor units with DVM Plus 2

72 / 84

S-Net iS-Net i9.9.

FeaturesModel

DMS based system A/C control. Color LCD touch panel web pad. (Windows CE) Connect maximum 4 DMS, Control 256 indoor units.MST-P1W0

■ Features

Centralized controllers CANNOT be used in room tracking mode.

Image

– Individual / Group / Multi / Whole control.– Schedule management.– Group management. (Logical, not physical group by switch setting)– Monitoring of connection structure, error log, detailed cycle information.– Power management (Peak power control )– Upper / Lower temperature limit, remote control, peak circulation, priority

of indoor unit setup function.

73 / 84

■ Menu architecture

Menu architecture

Control Schedule Group management Monitoring

Individual control

(Group control)

Schedule list

(Add / Edit / Delete)

(Apply / Stop)

(Make / Edit / Delete) Connection status

Error log

Multi control Detailed information

(Only room tracking)Whole control

System environment System setting

Tracking Date / Time

DMS IP setup Brightness control

Change password Volume control

Time synchronization IP setup

Stylus adjustment

S-Net iS-Net i9.9.

74 / 84

MIM-B13

Address Ch 1 2

Address Ch 2 Anything OK

Address Ch 3 Anything OK

Channel 1

Outdoor Unit

MIM-B04A

Address 0

DIP Switch K1 On

Max 16 Interface modules

MIM-B04A

Address 1

DIP Switch K1 On

Outdoor Unit

S-Net iS-Net i9.9.

■ Wiring

Max 256 indoor unitsMax 16 Centralized controllers

MIM-D00

MST-P1W0

Max 4 DMS

MCM-A202

Address 0

SW 4 Off

MCM-A202

Address 1

SW 4 Off

Check List

75 / 84

FeaturesModel

DMS based system A/C control PC software through LAN. Version comparison and auto update. Various statistical analysis using database management and reporting. Data backup and recover with DMS. Support remote access. (Multi PCs can connect to a single DMS) Connect maximum 16 DMS and 4096 indoor units control.

MST-P3P

■ Features

S-Net 3S-Net 310.10.

– User classification (General, Manager, Installer)– Individual / Group / Multi / Whole control, setup and monitoring.– Schedule management.– Group management. (Management structure, Installation structure)– Power management (Power distribution, Peak power control )– Statistical analysis and reporting (Device list, Event log, Operation ratio,

Power consumption, Demand control etc)

76 / 84

■ Menu architecture

Menu architecture

Control & Monitoring Schedule management Power demand control Usage analysis

Indoor Make schedule Demand list Time & power usage

Outdoor Schedule list Demand history Power report

DMS Daily schedule Indoor classification Power management

Management structure Setup exception day Setup target demand Setup power section

Installation structure

System management Toolbar

Environment Log out

Setup DMS Full screen

Event log Edit structure

Device list renewal Device list

Backup & recover Whole indoor stop

S-Net 3S-Net 310.10.

77 / 84

S-Net 3S-Net 310.10.

MIM-D00

MIM-B13

Address Ch 1 2

Address Ch 2 Anything OK

Address Ch 3 Anything OK

Channel 1

Outdoor Unit

MIM-B04A

Address 0

DIP Switch K1 On

Max 16 Interface modules

MIM-B04A

Address 1

DIP Switch K1 On

Outdoor Unit

■ Wiring

Max 256 indoor unitsMax 16 Centralized controllers

Max 16 DMS

S-Net 3

MCM-A202

Address 0

SW 4 Off

MCM-A202

Address 1

SW 4 Off

Check List

78 / 84

S-Net 3S-Net 310.10.

MIM-B13

Address Ch 1 2

Address Ch 2 Anything OK

Address Ch 3 Anything OK

Channel 1

Outdoor Unit

MIM-B04A

Address 0

DIP Switch K1 On

Max 16 Interface modules

MIM-B04A

Address 1

DIP Switch K1 On

Outdoor Unit

Max 256 indoor unitsMax 16 Centralized controllersMax 8 SIM

MIM-D00

Max 8 Power metersMIM-B12

Address 0

Max 16 DMS

■ Wiring with SIM

S-Net 3

MCM-A202

Address 0

SW 4 Off

Check List

79 / 84

FeaturesModel

Free connection control device. (With DMS, interface module, centralized controller) 7 inch wide touch screen LCD. Connect USB keyboard. Maximum 256 indoor units individual / group control.

S-Net mini

■ Features

S-Net miniS-Net mini11.11.

Image

Control targetInterface module / Centralized controller

(Basic Function)DMS

Function

– Tracking– Individual / Zone control– Schedule / Zone management– Status monitoring– Installation structure– Access control (Touch lock)

– Basic function– Error log– Peak power management– Demand control– Power distribution

Function (TBD)

80 / 84

S-Net mini

Outdoor UnitMIM-B13

Address Ch 1 0

Address Ch 2 Anything OK

Address Ch 3 Anything OK

Channel 1

Max 16 Interface modules

MIM-B04A

Address 1

DIP Switch K1 On

Outdoor Unit

■ Wiring (Connection with interface module)

S-Net miniS-Net mini11.11.

81 / 84

MIM-B13

Address Ch 1 2

Address Ch 2 Anything OK

Address Ch 3 Anything OK

Channel 1

Outdoor Unit

MIM-B04A

Address 0

DIP Switch K1 On

Max 16 Interface modules

MIM-B04A

Address 1

DIP Switch K1 On

Outdoor Unit

Max 256 indoor unitsMax 16 Centralized controllers

S-Net mini

■ Wiring (Connection with centralized controller)

S-Net miniS-Net mini11.11.

MCM-A202

Address 0

SW 4 Off

MCM-A202

Address 1

SW 4 Off

82 / 84

MIM-B13

Address Ch 1 2

Address Ch 2 Anything OK

Address Ch 3 Anything OK

Channel 1

Outdoor Unit

MIM-B04A

Address 0

DIP Switch K1 On

Max 16 Interface modules

MIM-B04A

Address 1

DIP Switch K1 On

Outdoor Unit

■ Wiring (Connection with DMS)

Max 256 indoor unitsMax 16 Centralized controllers

MIM-D00

Max 4 DMS

S-Net mini

S-Net miniS-Net mini11.11.

MCM-A202

Address 0

SW 4 Off

MCM-A202

Address 1

SW 4 Off

83 / 84

Channel 1

MIM-B04A

Address 0

DIP Switch K1 OnMax 16 Interface modules

MIM-B04A

Address 1

DIP Switch K1 On

Outdoor Unit

MCM-C00

S-Net 1

MIM-B04A

Address 2

DIP Switch K1 On

S-Net 1 series (Freeware)S-Net 1 series (Freeware)12.12.

■ S-Net 1 Wiring

Outdoor Unit

Outdoor Unit

Check List

84 / 84

Anything OKAddress Ch 2

MIM-B13

Anything OKAddress Ch 3

2Address Ch 1

Channel 1

Outdoor Unit

MIM-B04A

OnDIP Switch K1

0Address

Max 16 Interface modules

MIM-B04A

OnDIP Switch K1

1Address

Outdoor Unit

Outdoor Unit

0Address

MCM-C202

MCM-C00

S-Net 1 Plus

S-Net 1 series (Freeware)S-Net 1 series (Freeware)12.12.

■ S-Net 1 Plus Wiring

Check List