TCI  Services,  Inc.  Kevin  Kupitz  Levi  Laughlin    

Tank  Inspection  Decision  Process  Simplified  

American  Petroleum  Institute  API-­‐653  

“Tank  Inspection,  Repair,  Alteration  and  Construction”  

Steel  Tank  Industry  STI  SP001  5th  Edition  

“Standard  for  the  Inspection  of  Above  Ground  Storage  Tanks”  

Federal,  State,  Local  Regulations  

Good  Engineering  Practices  Best  Practice  

Industry  Accepted  Practices  for  ASTs  

•         Vertical,  cylindrical,  Above  Ground,  Closed  and  Open  Top,  Welded  Storage  Tanks  in  various  sizes  and  capacities  for  internal  pressure  approximate  of  atmospheric    pressure.        •       Max  design  temp  of  200°F.    •       For  storage  of  petroleum,  petroleum  products  and  other  liquid  products.    •       Field  Erected    

•         Applies  to  the  inspection  of  Above  Ground  Storage  tanks.      •       These  storage  tanks  include  shop-­‐fabricated  tanks,  field  erected  tanks  and  portable  containers  as  defined  in  this  standard,  as  well  as  their  containment  systems.  

•       For  ASTs  storing  stable,  flammable  and  combustible  liquids  at  atmospheric  pressure  with  a  specific  gravity  less  than  1.0.        •       For  temperatures  between  ambient  and  200°F.    

Field  Erected  Tank  

Vertical  Tank  

Shop-­‐  Built  Tank  

Horizontal  Tank  

API-­‐650  Name  plate  

Over  30’  Diameter  

Over  50’  Tall  

More  than  50,000  gallons  

Small  Vertical  Tank  with  manway  

Rests  on  grade  

On  concrete  pad    

API  653  

API  653  

 

 

API  653  

API  653  

API  653  

API  653  

API  653  

API-­‐653  

     

STI-­‐  SP001  

STI-­‐  SP001  

STI-­‐  SP001  

STI-­‐  SP001  

 

 

 

 

 

 

STI-­‐  SP001  

Certified  API-­‐653  Inspector  

¡  Internal  Inspection      20  Years  

¡  External  Inspection      5  Years  

Owners  inspector  

¡  Periodic  –  [SPCC  Plan]    Monthly    

     

¡  Visual  §  Roof  §  Shell  §  Nozzles  §  Appurtenances,  etc.    

¡  Ultrasonic  Thickness  §  Shell  §  Roof  (If  needed)  §  Other  (If  needed)  

¡  Final  Report  

¡  Initial  Internal  §  (API  Certified  Inspector)  

 ¡  Subsequent  Internal  Inspection  Interval  §  (API  Certified  Inspector)  

Within  10  years  of  Initial  Service  Date  (Could  go  longer  with  safeguards)    20  Years    (Can  be  30  years  with  RPB  6.4.22.1  but  need  to  check  with  state  regulations  first)  

¡  Visual  §  Shell  Internal  and  External  Roof  Internal  and  External  Floor  Internal  

§  Appurtenances  §  Nozzles  Etc.      

¡  Ultrasonic  Thickness  §  Shell  §  Roof  §  Nozzles  §  Repads  §  Floor  §  Other  

¡ Magnetic  Flux  Leakage  §  Floor  

¡  Vacuum  Box  §  Floor  

¡ Magnetic  Particle  §  Floor/Shell  

 

¡  External  Inspections    STI  Certified  Inspector  ¡  Internal  Inspections    STI  Certified  Inspector  ¡  Periodic  Inspections    Owners  Inspector  

¡  Categories  (Risk  Based)  1.  Spill  Control  and  CRDM  2.  Spill  Control  and  No  CRDM  3.  No  Spill  Control  and  No  CRDM  

¡  Spill  Control  §  Remote  Impounding  §  Secondary  Containment  dike/BERM  §  Secondary  Containment  AST  §  Secondary  Containment  System    

¡  CRDM  (Continuous  Release  Detection  System)  §  RPB-­‐  Release  Prevention  Barrier  §  Secondary  Containment  AST  (Double  Walls,  Double  Button)  §  Elevated  AST  

¡  Access  to  all  sides  ¡  Double  wall  ¡  Outside  ¡  On  concrete  pad  ¡  3,000  gallon  ¡  Built  1989  ¡  RPB/Double  Wall  ¡  SC  No  ¡  No  tank  info  

¡  Outside  ¡  On  curbed  concrete  pad  

¡  5,000  Gallon  ¡  Access  to  all  sides  ¡  Double  wall  ¡  Built  1999  ¡  SC/No  ¡  RPB/Double  Wall  

¡  4,000  gallon    ¡  Built  1962  ¡  No  other  information  ¡  SC/dike  ¡  RPB/None  

¡  12,700  gallon  ¡  No  other  information  ¡  Single  Bottom  ¡  SC/Dike  ¡  RPB/None  

¡  Outside  ¡  Secondary  containment  ¡  RPB/  Concrete  Pad  and  Base  

¡  2500  gallon  ¡  Built  1997  ¡  Field  Erected?  

¡  Outside  ¡  ≤  1,100  ¡  On  legs  ¡  SC/Yes  ¡  RPB/access  to  all  sides  

¡  12,000  gallon  tank  ¡  Insulated  Tank  ¡  Outside  ¡  RPB/Access  to  all  sides?  

¡  SC/None  

Recommended