View
227
Download
0
Category
Preview:
Citation preview
LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
1-1
Product Description
For more information visit: www.chfire.com BR05805038K
Product Features
Transfer Switch Features
FT40 Reduced Voltage - Part Winding
January 2005
Run Period Timer
Elapsed Time Meter
Electrically and MechanicallyInterlocked
Voltage & Frequency Sensing
Test Switch
Remote Alarm Contacts
Automatic Transfer
Last 2048 Messages
Number of Operations Counter
Microprocessor Control
EATON Cutler-Hammer LMR Transfer SwitchFire Pump Controllers are microprocessorbased. All events surrounding the operation ofthe controller are stored within the memory,thus giving the ability to diagnose andtroubleshoot problems based on an actualhistory of events. Events are time and datestamped.
A main display unit provides a read-out ofparameters such as current pressure, voltsand amps and will display error messages aswell as provide alarm indication. A statusreport is available which provides a record ofthe current state of the controller. The reportcan be printed locally via the printer / recorder.
LCD Message Retrieval
The 2 line liquid crystal display allows viewing ofall messages and event information withoutopening the front door of the controller.Messages can also be downloaded to a laptopcomputer via the communications port locatedon the top of the main microprocessor board.
The run period timer is built into the LMRmicroprocessor and can be accessed via themembrane / keypad. It is programmable from0-45 minutes and should be reset to ten (10)minutes when the controller is placed in service.
The internal microprocessor stores the mostrecent 2048 messages in it’s memory. Themessages can be printed, viewed on the LCDscreen or downloaded to a laptop. Eachmessage is time and date stamped. The LCDdisplay acts as a paperless chart recorder.
Emergency Start Operator
A mechanically operated emergency start handleactivates the motor contactor independent of anyelectrical control circuits or pressure switch input.
The LMR monitors and records the run time ofthe motor, in hours, whenever the pump isrunning. The actual run time can be viewed onthe LCD display in 1 hour increments.
The LMR controller monitors and records thenumber of times the pump has started. The actualcount can be viewed on the LCD display.
The FT40 Transfer Switch Controllers are a fullservice, part winding reduced voltagecontroller. A part winding fire pump controllerreduces the starting current by up to 40% whilemaintaining up to 50% motor starting torque.The FT40 is the most economical method ofreduced voltage starting, however, requires aspecial motor wound for part winding starting.The FT40 can be programmed for either fullyautomatic or semi-automatic operations.
The Automatic Transfer Switch Option may beadded to any FD type Fire Pump Controllerwhenever automatic transfer from normal toalternate power is required.The automatic Transfer Switch and Fire PumpController are each mounted in separateenclosures to form one unit and interwired.
A test switch is provided on the outside of thecontroller that can be used to simulate the lossof power on the normal source. As well, asilence pushbutton is provided which de-energizes the alarm bell.
Four remote alarm contacts are available forindication ofConnected to Normal PowerConnected to Alternate SourceIsolation Switch OpenNormal Power Failure
The MP1-E controller membrane is equippedwith four keypad input buttons. In addition, a fifthuser input exists via a rear located PC serialport connection, that can be used forprogramming of options and setpoints.
The MP1-E continuously monitors the normalsource for out of range setpoint values. When thesource is outside the dropout setpoints, the sourcewill become unavailable.This prompts a transfer to the alternate source.Retransfer occurs when the normal source’sfrequency and/or voltage return within pickupsetpoints.
The FT Series Transfer Switcheswill perform an automatic transferfrom Normal to Alternate sourcewhen the Voltage drops to 85% ofnormal, or there is a loss of anyphase and/or Phase Reversal.
Four LED’s indicate the status of the powersources.Source 1 Available Source 1 ConnectedSource 2 Available Source 2 Connected
The microprocessor basedMP1-E controller accuratelymonitors two powersources and provides thenecessary intelligence tooperate the transfer switchin an appropriate and timelymanner.
Volts and Amps Display
The LCD display located on the main display panel,simultaneously indicates the voltage and amps onall three phases of power coming into the controller.
NEMA 2 Enclosures
ATS - MP1-E
LED Status Indication
Keypad Programming
All LMR controllers come standard with NEMA2 enclosures unless otherwise ordered.Available options include: NEMA 3R, 4, 4X, 12.
SOURCE1 PHASE AB460V 60.0Hz
The FT Series transfer switch operatingmechanisms are mechanically interlocked toprevent the normal and alternate source fromconnecting at the same time.The switch operates upon signals receivedfrom the MP1-E microprocessor.
Technical Data and Specifications
Standards & Certification
Line Terminals (Incoming Cables)
Status & Alarm Indication
BR05805038K
Pressure
102 PSI
The LMR Electric Fire Pump Controllers meetor exceed the requirements of UnderwritersLaboratories, Underwriters LaboratoriesCanada, Factory Mutual, the CanadianStandards Association, New York City buildingcode, CE mark requirements and are built toNFPA 20 standards.
An additional output relay labeled Future #1,can be user programmed to operate for nine(9) different functions. Programming is done inthe LMR menu using the membrane / keypad.
Product Features
Additional Output Relay
Common Alarm Relay and Contacts
The LMR controller has a common alarm relaywhich de-energizes whenever there are anyalarm conditions present. This relay isenergized under normal conditions and hasLED status indication on the main relay board.
LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
1-2
FT40 Reduced Voltage - Part Winding
January 2005
For more information visit: www.chfire.com
N. Y. C.APPROVED
* Coils available: 380V-50Hz, 380V-60Hz, 415V-50Hz, 415V-60Hz.
Line Terminals on Main Isolation Switch (Incoming Cables)
Max. Hp
200 - 208
40 40 100 100 -
75 75 150 200 200
100 125 200 250 300
150 200 350 400 400
30 30 60 75 100
LINE VOLTAGE
220 - 240 * 380 - 415 440 - 480 550 - 600
Qty. & Cable Sizes Service Entrance GND.LUGQty. & Cable Sizes
(1)#14-1/0 PER (CU/AL) (1)#14-2/0 (CU/AL)
(1)#4-4/0 PER (CU/AL) (1)#14-2/0 (CU/AL)
(1)#3-350MCM (CU/AL) (1)#4-350MCM (CU/AL)
(2)3/0-250MCM (CU/AL) (2)#4-350MCM (CU/AL)
(2)250-350MCM (CU/AL) (2)#2-600MCM (CU/AL)
Alarm & Status Indication
The display panel is equipped with nine redAlarm LED’s and nine green Status LED’s whichindicate various functions and operations of thecontroller. The membrane keypad has curveddome windows which allow viewing from a wideangle.
Extra Set of Form-C Contacts forPhase Reversal and Phase Failure
The phase reversal and phase failure relayscome standard with an extra set of contactsthat can be used for remote alarm indication.
Pressure Transducer: 0 - 600 psi
Each LMR controller is equipped with astainless steel, 0-600 psi pressure switchcapable of withstanding a momentary surgepressure of 1000 psi.
NEMA Rated Contactors
NEMA rated Freedom or A200 Series EATONCutler-Hammer contactors are used in all LMRfire pump controllers. A wide variety of coilvoltages are available for domestic andinternational use.
Weekly Test Timer
The weekly test timer allows the user to set thecontroller to automatically start and stop thecontroller once per week. The number of weeksbetween tests is set via the front keypad. Theweekly test date and time can be viewed on theLCD display.
Sequential Start Timer
The sequential start timer is used to program astart delay after an automatic start request. Thisfunction is used for staging the start of pumps in amultiple pump application and also in Dieselbackup applications.
The industrial grade thermal printer is housedin a rugged steel enclosure within the controller.The on/off switch, feed and reset buttons arefront accessible. A bi-color status LED is alsovisible on the front of the printer. Greenindicates - “Printer Operational’ while yellowindicates - “Out of Paper”.
Printer / Recorder
Power TransferSwitch
����
������
���� �
���� �
������ � �����
SwitchPower Transfer
��������
��������
��� ����� �
� �� ����
���� �� ���� ��
�� ���
� �� ���
� �� ���
����
� ��
������
� �
ControllerFire Pump
���
Dimensions
For more information visit: www.chfire.com
1-3
N. Y. C.APPROVED
NOTES:1. All enclosures finished in FirePump red.2. Cable Entrance either top or bottom.3. Standard Enclosure type NEMA 2.
FT40 Part Winding
Withstand Rating
Standard Intermediate High
Line VoltageMotor Hp Approx. WeightLbs. (Kg)
5 - 40
5 - 50
5 - 75
5 - 100
5 - 100
200 - 208V
220 - 240V
* 380 - 415V
440 - 480V
550 - 600V 25,000 100,000
150,000 200,000100,000 655
(297)
* Coils available: 380V-50Hz, 380V-60Hz, 415V-50Hz, 415V-60Hz.
LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
FT40 Reduced Voltage - Part Winding
BR05805038K
January 2005
Power TransferSwitch
�� ������ �� ������� ��������
�� ���� � ����
�� ���� ����������� ��������
�������� � ������
�� ������� ���� � ������� �������
�� ���� ��� �� ����
� �� ���
� �� ���
���� ��
�� ���
��� ����� �
������ � �����
���� �
���� �
����
������ ����
� ��
������
��������
��������
� �� ����
���� ��
� �
Power TransferSwitch Controller
Fire Pump
���
Dimensions
For more information visit: www.chfire.com
N. Y. C.APPROVED
NOTES:1. All enclosures finished in FirePump red.2. Cable Entrance either top or bottom.3. Standard Enclosure type NEMA 2.
Withstand Rating
Standard Intermediate High
Approx.WeightLbs. (Kg)
A B C D E
200 - 208V
220 - 240V
* 380 - 415V
* 380 - 415V
440 - 480V
440 - 480V
550 - 600V
550 - 600V
200 - 208V
50 - 100
60 - 125
100 - 200
125 - 250
125 - 300
250 - 300
125 - 150
300 - 400
150 - 200
350 - 500
220 - 240V
1005(456)
1110(503)
53.79(1366)
47.79(1214)
80.27(2039)
74.27(1886)
56.27(1429)
50.27(1277)
58.64(1489)
48.00(1219)
70.00(1778)
64.00(1626)
25,000
25,000
ConsultFactory
35,000
100,000
35,000
100,000
ConsultFactory
ConsultFactory
LineVoltage
Motor Hp
* Coils available: 380V-50Hz, 380V-60Hz, 415V-50Hz, 415V-60Hz.
FT40 Part Winding
LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
1-4
FT40 Reduced Voltage - Part Winding
BR05805038K
January 2005
�� ������ �� ������� ��������
�� ���� ����������� ��������
�������� � ������
�� ������� ���� � ������� �������
�� ���� ��� �� ����
ControllerFire Pump
�� ���� � ����
Power Transfer
������
� ��
����
������ � �����
�� ���
���� ��
� �� ���
� �� ���
��� ����� �
����
������
���� �
���� �
� �� ����
��������
��������
���� ��
Switch
� �
�� ������ �� ������� ��������
�� ���� ����������� ��������
�������� � ������
�� ������� ���� � ������� �������
�� ���� ��� �� ����
�� ���� � ����
ControllerFire Pump
���
�� ������ �� ������� ��������
�� ���� ����������� ��������
�� ���� � ����
�������� � ������
�� ������� ���� � ������� �������
�� ���� ��� �� ����
1-5LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
FT40 Reduced Voltage - Part Winding
For more information visit: www.chfire.com BR05805038K
N. Y. C.APPROVED
NOTES:1. All enclosures finished in FirePump red.2. Cable Entrance either top or bottom.3. Standard Enclosure type NEMA 2.
Withstand Rating
Standard Intermediate High
Line VoltageMotor Hp Approx. WeightLbs. (Kg)
200 - 250
250 - 300
350 - 500
450 - 600
550 - 700
200 - 208V
220 - 240V
* 380 - 415V
440 - 480V
550 - 600V 25,000 35,000
Consult Factory Consult Factory100,000 1290
(585)
* Coils available: 380V-50Hz, 380V-60Hz, 415V-50Hz, 415V-60Hz.
Dimensions
FT40 Part Winding
January 2005
����
�����
���
����
Electrical Wiring Schematic
For more information visit: www.chfire.com
N. Y. C.APPROVED
FT40 Part Winding
LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
1-6
FT40 Reduced Voltage - Part Winding
BR05805038K
January 2005
SOURCEEMERGENCY
SOURCENORMAL
For more information visit: www.chfire.com
N. Y. C.APPROVED
Electrical Wiring Schematic
FT Automatic Power Transfer Switch
1-7LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
FT40 Reduced Voltage - Part Winding
BR05805038K
January 2005
#2UTILITY UTILITY
#1
For more information visit: www.chfire.com
N. Y. C.APPROVED
FT2U Automatic Power Transfer Switch c/w Second Utility
LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
1-8
FT40 Reduced Voltage - Part Winding
BR05805038K
January 2005
Options - Wiring Diagram
Main Terminal Block: TB1 Transfer Switch Terminal Block
Typical Controller Connection
Relay Card
NOTES:1. Terminal 49 is common to all dry contact inputs.DO NOT APPLY A VOLTAGE ON THESE TERMINALS2. Contacts shown in de-energized state (Fail Safe).
NOTES:1. To Control Circuit2. Spare for Customer Connections3. To TB14. To Shunt Trip5. Contacts Shown in De-Energized State - (Fail Safe)
For more information visit: www.chfire.com
1-9LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
FT40 Reduced Voltage - Part Winding
BR05805038K
January 2005
Catalog Number Selection
FT40 PART WINDING Controller Catalog Numbering System
For more information visit: www.chfire.com
LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
1-10
FT40 Reduced Voltage - Part Winding
BR05805038K
Catalog Number Selection Chart - FT40 (Gen Set) Catalog Number Selection Chart - FT40 (Gen Set)
Catalog Number Voltage Hp Price Catalog Number Voltage Hp Price
FT40-15A 200-208V 15 $17,780 FT40-15D 440 - 480V 15 $17,780
FT40-20A 60 HZ 20 $17,780 FT40-20D 60 HZ 20 $17,780
FT40-25A 25 $17,780 FT40-25D 25 $17,780
FT40-30A 30 $18,000 FT40-30D 30 $17,780
FT40-40A 40 $19,420 FT40-40D 40 $17,780
FT40-50A 50 $20,100 FT40-50D 50 $18,080
FT40-60A 60 $21,440 FT40-60D 60 $19,200
FT40-75A 75 $21,820 FT40-75D 75 $19,420
FT40-100A 100 $25,860 FT40-100D 100 $20,760
FT40-125A 125 $34,820 FT40-125D 125 $21,440
FT40-150A 150 $34,820 FT40-150D 150 $21,440
FT40-200A 200 Consult FT40-200D 200 $26,560
FT40-250A 250 Factory FT40-250D 250 $29,880
FT40-15B 220 - 240V 15 $17,780 FT40-300D 300 $34,820
FT40-20B 60 HZ 20 $17,780 FT40-350D 350 $34,820
FT40-25B 25 $17,780 FT40-400D 400 $37,320
FT40-30B 30 $17,780 FT40-450D 450
FT40-40B 40 $19,420 FT40-500D 500
FT40-50B 50 $19,420 FT40-600D 600
FT40-60B 60 $21,440 FT40-15E 550 - 600V 15 $17,780
FT40-75B 75 $21,440 FT40-20E 60 HZ 20 $17,780
FT40-100B 100 $25,860 FT40-25E 25 $17,780
FT40-125B 125 $29,880 FT40-30E 30 $17,780
FT40-150B 150 $34,820 FT40-40E 40 $17,780
FT40-200B 200 $37,320 FT40-50E 50 $18,080
FT40-250B 250 Consult FT40-60E 60 $19,200
FT40-300B 300 Factory FT40-75E 75 $19,200
FT40-15C 380 - 415V 15 $17,780 FT40-100E 100 $20,760
FT40-20C 50 / 60 HZ 20 $17,780 FT40-125E 125 $20,760
FT40-25C 25 $17,780 FT40-150E 150 $21,440
FT40-30C 30 $17,780 FT40-200E 200 $23,380
FT40-40C 40 $18,080 FT40-250E 250 $29,880
FT40-50C 50 $18,080 FT40-300E 300 $29,880
FT40-60C 60 $19,420 FT40-350E 350 $29,880
FT40-75C 75 $19,420 FT40-400E 400 $37,320
FT40-100C 100 $21,440 FT40-450E 450 $38,820
FT40-125C 125 $21,440 FT40-500E 500 $40,320
FT40-150C 150 $25,500 FT40-600E 600 Consult
FT40-200C 200 $26,560 FT40-700E 700 Factory
FT40-250C 250 $29,880
FT40-300C 300 $34,820
FT40-350C 350
FT40-400C 400 Consult
FT40-450C 450 Factory
FT40-500C 500
Consult
Factory
January 2005
For more information visit: www.chfire.com
Catalog Number Selection
FT40 - Adder for Second Utility Alternate Power Source - Option 2U
To determine the price of a Second Utility Transfer Sw itch:
Add together both the list price of the Standard Transfer Sw itch Controller and the above 2U price.
Standard FT Controlle r + 2U Dual Utility Price Adder = Dual Utility Trans fe r Sw itch Controlle r
FT40-100D-LMR-L1-X1 + 2U = FT40-100D-LMR-L1-X1-2U
20,760.00 + 4,010.00 = 24,770.00
1-11LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
FT40 Reduced Voltage - Part Winding
BR05805038K
Catalog Number Selection Chart - 2nd Utility Adder Catalog Number Selection Chart - 2nd Utility Adder
Catalog Number Voltage Hp Price Catalog Number Voltage Hp Price
FT40-15A 200-208V 15 $4,010 FT40-15D 440 - 480V 15 $4,010
FT40-20A 60 HZ 20 $4,010 FT40-20D 60 HZ 20 $4,010
FT40-25A 25 $4,010 FT40-25D 25 $4,010
FT40-30A 30 $4,010 FT40-30D 30 $4,010
FT40-40A 40 $4,010 FT40-40D 40 $4,010
FT40-50A 50 $4,010 FT40-50D 50 $4,010
FT40-60A 60 $4,010 FT40-60D 60 $4,010
FT40-75A 75 $4,010 FT40-75D 75 $4,010
FT40-100A 100 $4,010 FT40-100D 100 $4,010
FT40-125A 125 $5,750 FT40-125D 125 $4,010
FT40-150A 150 $5,750 FT40-150D 150 $4,010
FT40-200A 200 Consult FT40-200D 200 $4,010
FT40-250A 250 Factory FT40-250D 250 $4,010
FT40-15B 220 - 240V 15 $4,010 FT40-300D 300 $5,750
FT40-20B 60 HZ 20 $4,010 FT40-350D 350 $5,750
FT40-25B 25 $4,010 FT40-400D 400 $5,750
FT40-30B 30 $4,010 FT40-450D 450
FT40-40B 40 $4,010 FT40-500D 500
FT40-50B 50 $4,010 FT40-600D 600
FT40-60B 60 $4,010 FT40-15E 550 - 600V 15 $4,010
FT40-75B 75 $4,010 FT40-20E 60 HZ 20 $4,010
FT40-100B 100 $4,010 FT40-25E 25 $4,010
FT40-125B 125 $4,010 FT40-30E 30 $4,010
FT40-150B 150 $5,750 FT40-40E 40 $4,010
FT40-200B 200 $5,750 FT40-50E 50 $4,010
FT40-250B 250 Consult FT40-60E 60 $4,010
FT40-300B 300 Factory FT40-75E 75 $4,010
FT40-15C 380 - 415V 15 $4,010 FT40-100E 100 $4,010
FT40-20C 50 / 60 HZ 20 $4,010 FT40-125E 125 $4,010
FT40-25C 25 $4,010 FT40-150E 150 $4,010
FT40-30C 30 $4,010 FT40-200E 200 $4,010
FT40-40C 40 $4,010 FT40-250E 250 $4,010
FT40-50C 50 $4,010 FT40-300E 300 $4,010
FT40-60C 60 $4,010 FT40-350E 350 $4,010
FT40-75C 75 $4,010 FT40-400E 400 $5,750
FT40-100C 100 $4,010 FT40-450E 450 $5,750
FT40-125C 125 $4,010 FT40-500E 500 $5,750
FT40-150C 150 $4,010 FT40-600E 600 Consult
FT40-200C 200 $4,010 FT40-700E 700 Factory
FT40-250C 250 $4,010
FT40-300C 300 $5,750
FT40-350C 350
FT40-400C 400 Consult
FT40-450C 450 Factory
FT40-500C 500
Consult
Factory
January 2005
Product Selection
For more information visit: www.chfire.com
FT40 PART WINDING Controller Catalog Numbering System
LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
1-12
FT40 Reduced Voltage - Part Winding
BR05805038K
FT LMR
30 = Across the Line A - Built-in Alarm System40 = Part Winding B - Alarm Bell50 = Primary Resistor C1 - Extra Contacts "Pump Run" (one N.O. std.)60 = Autotransformer C2 - Extra Contacts "AC Power Failure" (two sets std.)70 = Wye Delta (Star-Delta) Open C3 - Extra Contacts "Phase Rev." (two sets std.)80 = Wye Delta (Star-Delta) Closed C4 - Remote Contacts (2 Form C) Low Reservoir90 = Soft Start C5 - Remote Contacts (2 Form C) High Reservoir
E1 - NEMA 3R - Raintight Enclosure
E2 - NEMA 4 - Watertight Enclosure (Ref Dwg. Page 1-3)NEMA 4 - Watertight Enclosure (Ref Dwg. Page 1-4, 1-5)
Horsepower E3 - NEMA 12 - Industrial Dust Tight Enclosure15 40 100 250 450 E5 - NEMA 4X - Stainless Steel Enclosure (Ref Dwg. Page 1-3)20 50 125 300 500 NEMA 4X - Stainless Steel Enclosure (Ref Dwg. Page 1-4, 1-5)25 60 150 350 *600 E8 - Tropicalization30 75 200 400 *700 E9 - NEMA 4X - Painted Steel (Ref. Dwg. Page 1-3)
* Consult Factory for pricing. NEMA 4X - Painted Steel (Ref. Dwg. Page 1-4, 1-5)
E10 - NEMA 4X - 316 Stainless Steel Enclosure (Ref. Dwg. Page 1-3)NEMA 4X - 316 Stainless Steel Enclosure (Ref. Dwg Page 1-4, 1-5)
Voltage EX - Export CratingA = 200 - 208V 60 HZ F - Floor Stand (Standard c/w floor mounted enclosures)B = 220 - 240V 60 HZ F2 - Floor Stand - 2 Inch HeightC = 380 - 415V 50/60 HZ H - High Withstand Rating (refer to tables)D = 440 - 480V 60 HZ I - Intermediate Withstand Rating (refer to tables)E = 550 - 600V 60 HZ P7 - Low Suction Pressure Switch c/w Pilot Light
P8 - Low Suction Shutdown (Requires P7)
P10 - Pressure Transducer - Sea Water Rated
P13 - Externally Mounted Pressure Transducer
R1 - Space Heater (120 / 220V)
R2 - Space Heater c/w Thermostat
R3 - Space Heater c/w Humidistat
R4 - Low Pump Room Temperature Switch and Pilot LightL1 = English X1 - Printer/Pressure RecorderL2 = French X2 - 4 - Inch Chart Recorder (10 - 300 psi fresh water)L5 = Spanish 2U - Second Utility
Language
Microprocessor Control
OptionsStarting Type
LMR Series
January 2005
Product Selection
Options
For more information visit: www.chfire.com
1-13LMR Electric Fire Pump Controllers with Transfer SwitchFeatures
FT40 Reduced Voltage - Part Winding
BR05805038K
Catalog Number Option SelectionDesignation Description Price
A Built-in Alarm System $350
B Alarm Bell $110
C1 Extra Contacts "Pump Run" (one N.O. std.) $90
C2 Extra Contacts "AC Pow er Failure" (tw o sets std.) $90
C3 Extra Contacts "Phase Rev." (tw o sets std.) $90
C4 Remote Contacts (2 Form C) Low Reservoir $90
C5 Remote Contacts (2 Form C) High Reservoir $90
E1 NEMA 3R - Raintight Enclosure $760
E2 NEMA 4 - Watertight Enclosure (Ref Dw g. Page 1-3) $2,400
NEMA 4 - Watertight Enclosure (Ref Dw g. Page 1-4, 1-5) $4,400
E3 NEMA 12 - Industrial Dust Tight Enclosure $50
E5 NEMA 4X - Stainless Steel Enclosure (Ref Dw g. Page 1-3) $4,000
NEMA 4X - Stainless Steel Enclosure (Ref Dw g. Page 1-4, 1-5) $6,000
E8 Tropicalization $550
E9 NEMA 4X - Painted Steel (Ref. Dw g. Page 1-3) $3,200
NEMA 4X - Painted Steel (Ref. Dw g. Page 1-4, 1-5) $5,200
E10 NEMA 4X - 316 Stainless Steel Enclosure (Ref. Dw g. Page 1-3) $7,200
NEMA 4X - 316 Stainless Steel Enclosure (Ref. Dw g. Page 1-4, 1-5) $11,000
EX Export Crating $525
F Floor Stand (Standard c/w f loor mounted enclosures) Std.
F2 Floor Stand - 2 Inch Height $25
H High Withstand Rating (refer to tables) $3,230
I Intermediate Withstand Rating (refer to tables) $1,520
L1 Language - English N / C
L2 Language - French N / C
L5 Language - Spanish $200
P7 Low Suction Pressure Sw itch c/w Pilot Light $570
P8 Low Suction Shutdow n (Requires P7) Std.
P10 Pressure Transducer - Sea Water Rated $300
P13 Externally Mounted Pressure Transducer $250
R1 Space Heater (120 / 220V) $250
R2 Space Heater c/w Thermostat $320
R3 Space Heater c/w Humidistat $320
R4 Low Pump Room Temperature Sw itch and Pilot Light $290
X1 Printer/Pressure Recorder $1,075
X2 4 Inch Chart Recorder ( 10 - 300 psi fresh w ater) $700
2U Second Utility See Page 1-11 for details
January 2005
EATONCutler-Hammer403 East Lake Blvd., Airdrie, Alberta, T4A 2G1Canadatel: 403-948-7955fax: 403-948-6967www.chfire.com
© 2005 Eaton CorporationAll Rights ReservedPrinted in CanadaPublication No.: BR05805038KJanuary 2005
FIRE PUMP CONTROLLERS
Fire Pump Controller Family
FD20
Limited Service Controller
FD30
Across-the-Line
FD40
Part Winding
FD50
Primary Resistor
FD60
Autotransformer
FD70
WYE DELTAOpen Transition
(Star-Delta)
FD80
WYE DELTAClosed Transition
(Star-Delta)
FD90
Soft Start
FT SERIES
Transfer Switches
FDM
FD100 / 110
Diesel EngineControllers
FDF
FDM
Medium VoltageControllers
FDF
Foam PumpControllers
FDC
CompactControllers
FDR
ResidentialControllers
FDJP / JY
Jockey PumpControllers
FDAP-M
Remote AlarmPanels
For more information on Eaton Cutler-Hammer Fire Pump Controllers, email us at chcfirepump@eaton.com or call us at 1-877-860-7955.
January 2005
Recommended