XPower Full DC Inverter Mini VRF with DC inverter compressor and DC fan motor delivers a highly efficient solution for small commercial buildings. Four to nine rooms require only one outdoor unit, and individual control is enabled in each room.
XPower Mini VRF Series
• DC inverter compressor• DC fan motor• Capacity up to 15,5kW• Connectable indoor units quantity up to 7• Precise oil control technology• Advanced silence technology• Intelligent defrosting technology• Simple communication wiring• Auto addressing• Easy maintenance• Eurover Certified
Indoor UnitsXpower VRF indoor unit
VentilationHeat recovery ventilator (HRV)
Control SystemsSmart control systems
39
Wide range of outdoor units
Flexible indoor units connection
The capacity range of outdoor unit is from 12kW to 15,5kW with three models and two air-discharge type.
Maximum connectable up to 7 indoor units with capacity up to 130% of total outdoor units can be connected in one refrigeration system.
Mini VRF with intelligent control gives you independent zoning control with maximum flexibility. A single outdoor unit supports up to nine indoor units, freeing up considerable space outside. Use your backyard more wisely with much more space available created by less number of outdoor units.
12,3/14/15,5 kW
Features
40
Long piping length
The Mini VRF provides a total piping length possibility of 100m, a maximum height difference between outdoor and indoor units of 30m. The height difference between indoors unit can be up to 8m. These generous allowances facilitate an extensive array of system designs.
*1: Total pipe length is equal to all the liquid pipe or all the gas pipe length.
Permitted value (m)
Actual total piping length*1
Longest pipingPiping length
Level difference
Level difference between indoor units
Level difference between indoor and outdoor units
Outdoor unit up
Outdoor unit down
Actual length
Equivalent length
12/14/16/18kW
100
60
70
20
30
20
8
Equivalent p iping length from the farthest I DU t o the first indoor branch joint
The
long
est p
ipin
g le
ngth
is 7
0m
The
first
bra
nch
join
t to
thef
arth
est I
DU
is 2
0m
The
IDU
to th
e ne
ares
t br
anch
join
t is
15m
Leve
l diff
eren
ce b
etw
een
IDU
and
OD
U is
30m
Leve
l diff
eren
ce b
etw
een
IDU
s is
8m
Features
41
Auto addressing
Easy Installation
Space saving design
Easy installation:No special area is required for outdoor units.
Easy transportation:All outdoor units can be transported by elevator, which greatly simplifies installation and reduces time and labour.
The Mini VRF indoor and outdoor units are almost as easy to install as residential air conditioning systems, making them ideal for small offices and shops.
The Mini VRF units are slimmer and more compact, resulting in significant savings in installation space. In some large residential and light commercial areas, such as villas, restaurants, usually it need more than one indoor unit, which in turn requires multiple outdoor units. Mini VRF system removes this problem, and retains buildings’ original aesthetics.
Addresses of indoor units can be set automatically by outdoor units. Wireless controller can inquire and modify every indoor units address.
Easy to transport
63 64
Addresses of indoor units can be set automatically by outdoor units.Wireless controller can inquire and modify every indoor units address.
Space saving design
Easy installation
The Mini VRF units are slimmer and more compact, resulting in significant savings in installation space. In some large residential and light commercial areas, such as villas, restaurants, usually it need more than one indoor unit, which in turn requires multiple outdoor units.Midea's Mini VRF system removes this problem, and retains buildings' original aesthetics.
The Mini VRF provides a total piping length possibility of 100m, a maximum height difference between outdoor and indoor units of 30m. The height difference between indoors unit can be up to 8m. These generous allowances facilitate an extensive array of system designs.
Easy to transport
Shield signal wire
Outdoor unit can distribute addresses to indoor unit.
KJR-29B RM05
Flexible piping design
High performance heat exchanger
High COP and EER values
The
long
est p
ipin
g le
ngth
is 7
0m
The
first
bra
nch
join
t to
thef
arth
est I
DU
is 2
0m
The
IDU
to th
e ne
ares
t br
anch
join
t is
15m
Leve
l diff
eren
ce b
etw
een
IDU
and
OD
U is
30m
Leve
l diff
eren
ce b
etw
een
IDU
s is
8m
*1: Total pipe length is equal to all the liquid pipe or all the gas pipe length.
Permitted value (m)
Actual total piping length*1
Longest pipingPiping length
Level difference
Level difference between indoor units
Level difference between indoor and outdoor units
Outdoor unit up
Outdoor unit down
Actual length
Equivalent length
8/10.5kW
100
45
50
20
30
20
8
12/14/16/18kW
100
60
70
20
30
20
8
High Efficiency
New design Original design High efficiency inner-threaded pipe, enhance heat transfer.
Reduce air resistance
Hydrophilic fins + inner-threaded pipes
The new designed window fins enlarge the heat-exchanging area , decrease the air resistance, save more power and enhance heat exchange performance.Hydrophilic film fins and inner-threaded copper pipes optimize heat exchange efficiency.The specially coated blue fins enhance durability and protect against corrosion from air, water and other corrosive agents, assures a longer coil service life.
Easier Installation and Service
Auto addressing
Equivalent piping length from the farthest IDU to the first indoor branch joint
3.9EER
8kW 10.5kW 12kW 14kW 16kW 18kW
3.92 3.783.54 3.43 3.3
COP
8kW 10.5kW 12kW 14kW 16kW 18kW
4.02 3.97 3.8 3.7 3.563.8
Easy installation: No special area is required for outdoor units. Easy transportaion: All outdoor units can be transported by elevator, which greatly simplifies installation and reduces time and labor.The Mini VRF indoor and outdoor units are almost as easy to install as residential air conditioning systems, making them ideal for small offices and shops.
42
More convenience in installation
More convenience in installation
More convenient piping connector - branch box
A four-direction space is available for connecting pipes and wiring in various installation sites.
A four-direction space is available for connecting pipes and wiring in various installation sites.
Easier and safer installation thanks to a branch box that simplifies piping work and the adoption of screw connection. Both left and right pipe flare connection from outdoor unit to branch box is reserved, which greatly simplifies field installation. Two sets of pipe size converter are packed with branch box to transfer the pipe size from Φ6,35mm to Φ9,53mm and from Φ12,7mm to Φ15,9mm.
Low noise The branch pipe is linear expansion design regulates the flow of refrigerant and reduces the noise. By locating the branch box in the ceiling or outside, noise generated by the branch box can be kept clear of living spaces, thus makes noise level to a minimum.
Brazing-free quick installationAll the piping leading to and from the branch box is connected using screw joints,which can be installed quickly and easily.
Indoor installationThe branch box can be installed in the ceiling rather than outside. Removing the side and bottom covers provides easy access for maintaining inner components such as circuit boards.
Front side Back sideRight side Bottom side
Front sideBottom side
Back side
Right side
Features
43
Noise reducing design
Full DC inverter technology
At the heart of our system is a highly intelligent inverter driven compressor. This advanced technology enables the output of the outdoor unit to be modulated by the cooling or heating demands of the zone that it controls. This advanced system ensures precise temperature regulation and highly efficient energy usage, making a significant contribution to the limiting the impact on the environment.
Optimally designed fan shape and air discharge grille increases air volume and reduces running noise.
High efficiency DC fan motor saved power up to 50%.
Full DC
Inverter M
ini VR
F
65 66
Compressor (Twin Rotary) structure
Highly Efficient DC Motor:
- Creative motor core design
- High density neodymium magnet
- Concentrated type stator
-Wider operating frequency range
Better balance and Extremely Low Vibration:
- Twin eccentric cams
- 2 balance weights
Highly Stable Moving Parts:
- Optimal material matching rollers and vanes
-Optimize compressor drive technology
- Highly robust bearings
-Compact structure
Optimally designed fan shape and air discharge grille increases air volume and reduces running noise.
Noise reducing design
Newly Designed Fan Guard Powerful Large Propeller
New fan
Air deflector
New grille
More convenience in installation
A four-direction space is available for connecting pipes and wiring in various installation sites.
Front side Back sideRight side Bottom side
Front sideBottom side
Back side
Right side
At the heart of our system is a highly intelligent inverter driven compressor. This advanced technology enables the output of the outdoor unit to be modulated by the cooling or heating demands of the zone that it controls. This advanced system ensures precise temperature regulation and highly efficient energy usage, making a significant contribution to the limiting the impact on the environment.
High efficiency DC fan motor saved power up to 50%.
More convenient piping connector - branch box
New piping connection design
The branch pipe is linear expansion design regulates the flow of refrigerant and reduces the noise. By locating the branch box in the ceiling or outside ,noise generated by the branch box can be kept clear of living spaces, thus makes noise level to a minimum.
All the piping leading to and from the branch box is connected using screw joints,which can be installed quickly and easily.
Brazing-free quick installation
Indoor installationThe branch box can be installed in the ceiling rather than outside. Removing the side and bottom covers provides easy access for maintaining inner components such as circuit boards.
Low noise
Full DC inverter technology
Mot
or s
peed
(RP
M)
System pressure
DC inverter stepless adjustment
AC inverter multistep adjustment
Advanced Technologies
Easier and safer installation thanks to a branch box that simplifies piping work and the adoption of screw connection. Both left and right pipe flare connectin from outdoor unit to branch box is reserved, which greatly simplifies field installation.T 6.35mm to 9.53mm and from 12.7mm mm.
44
Notes:Capacities are based on the following conditions:Cooling: Indoor temperature 27oC DB/19oC WB; Outdoor temperature 35oC DB/24oC WB.Heating: Indoor temperature 20oC DB/15oC WB; Outdoor temperature 7oC DB/6oC WB.Piping length: Interconnecting piping length is 5m, level difference is 0m.Sound values are measured in a semi-anechoic room, at a position 1m in front of the unit and 1m above the floor.2010: When the * is omit, the model stands for 220-240V/1ph/50Hz unit.9010: When the * is R, the model stands for 380-415V/3ph/50Hz unit.
15.5
4.52
3.43
17.0
4.77
3.56
45-130
7
57
Ф9.53
Ф19.1
DC
2
6.000
1
R410A
3.9
102
113
14.0
3.95
3.54
15.4
4.16
3.70
45-130
6
57
Ф9.53
Ф15.9
DC
2
6.000
1
R410A
3.9
95
106
12.3
3.25
3.78
13.2
3.47
3.80
45-130
6
57
Ф9.53
Ф15.9
DC
2
6.000
1
R410A
3.3
95
106
15.5
4.52
3.43
17.0
4.77
3.56
45-130
7
57
Ф9.53
Ф19.1
DC
2
6.000
1
R410A
3.9
100
111
14.0
3.95
3.54
15.4
4.16
3.70
45-130
6
57
Ф9.53
Ф15.9
DC
2
6.000
1
R410A
3.9
95
106
12,3
3.25
3.78
13.2
3.47
3.80
45-130
6
57
Ф9.53
Ф15.9
DC
2
6.000
1
R410A
3.3
95
106
Power supply
Cooling
Heating
Sound pressure level
Fan motor
Refrigerant
Net dimension (W×H×D)
Packing size (W×H×D)
Net weight
Gross weight
Capacity
Input
EER
Capacity
Input
COP
Total capacity
Max. quantity
Liquid pipe
Gas pipe
Type
Quantity
Air flow rate
Quantity
Type
Factory charging
Cooling
Heating
V/Ph/Hz
kW
kW
kW/kW
6.055.925.676.055.925.67SEER kW/kW
kW
kW
kW/kW
3.043.863.9 3.043.863.9SCOP kW/kW
%
dB(A)
mm
mm
m3/h
kg
mm
mm
kg
kg
°C
°C
Connectable indoor unit
Pipe connections
Operating temperature range
Rotarycompressor
-15~43
-15~27
900×1.327×400
1.030×1.456×435
900×1.327×400
1.030×1.456×435
220-240/1/50 380-415/3/50
Specifications
Model 38VR004H11201E 38VR005H11201E 38VR006H11201E 38VR004H11901E 38VR005H11901E 38VR006H11901E
Notes:Capacities are based on the following conditions:Cooling: Indoor temperature 27oC DB/19oC WB; Outdoor temperature 35oC DB/24oC WB.Heating: Indoor temperature 20oC DB/15oC WB; Outdoor temperature 7oC DB/6oC WB.Piping length: Interconnecting piping length is 5m, level difference is 0m.Sound values are measured in a semi-anechoic room, at a position 1m in front of the unit and 1m above the floor.2010: When the * is omit, the model stands for 220-240V/1ph/50Hz unit.9010: When the * is R, the model stands for 380-415V/3ph/50Hz unit.
15.5
4.52
3.43
17.0
4.77
3.56
45-130
7
57
Ф9.53
Ф19.1
DC
2
6.000
1
R410A
3.9
102
113
14.0
3.95
3.54
15.4
4.16
3.70
45-130
6
57
Ф9.53
Ф15.9
DC
2
6.000
1
R410A
3.9
95
106
12.3
3.25
3.78
13.2
3.47
3.80
45-130
6
57
Ф9.53
Ф15.9
DC
2
6.000
1
R410A
3.3
95
106
15.5
4.52
3.43
17.0
4.77
3.56
45-130
7
57
Ф9.53
Ф19.1
DC
2
6.000
1
R410A
3.9
100
111
14.0
3.95
3.54
15.4
4.16
3.70
45-130
6
57
Ф9.53
Ф15.9
DC
2
6.000
1
R410A
3.9
95
106
12,3
3.25
3.78
13.2
3.47
3.80
45-130
6
57
Ф9.53
Ф15.9
DC
2
6.000
1
R410A
3.3
95
106
Power supply
Cooling
Heating
Sound pressure level
Fan motor
Refrigerant
Net dimension (W×H×D)
Packing size (W×H×D)
Net weight
Gross weight
Capacity
Input
EER
Capacity
Input
COP
Total capacity
Max. quantity
Liquid pipe
Gas pipe
Type
Quantity
Air flow rate
Quantity
Type
Factory charging
Cooling
Heating
V/Ph/Hz
kW
kW
kW/kW
6.055.925.676.055.925.67SEER kW/kW
kW
kW
kW/kW
3.043.863.9 3.043.863.9SCOP kW/kW
%
dB(A)
mm
mm
m3/h
kg
mm
mm
kg
kg
°C
°C
Connectable indoor unit
Pipe connections
Operating temperature range
Rotarycompressor
-15~43
-15~27
900×1.327×400
1.030×1.456×435
900×1.327×400
1.030×1.456×435
220-240/1/50 380-415/3/50
45
38VR004/005/006H11201E
Dimensions13
27
900
600
348
320
400
360
46
• DC inverter compressor• DC fan motor• Capacity up to 45kW• Connectable indoor units quantity up to 15• Precise oil control technology• Advanced silence technology• Intelligent defrosting technology• Simple communication wiring• Auto addressing• Easy maintenance
XPower Mini VRF / Side Discharge
Indoor UnitsXpower VRF indoor unit
VentilationHeat recovery ventilator (HRV)
Control SystemsSmart control systems
XPower Full DC Inverter Mini VRF / Side Discharge it is designed to optimize performance and better match varieties of application requirement. It is focused on providing better air solutions for the small and middle-sized buildings.
47
Wide range of outdoor units
Wide operation range
The capacity range of outdoor unit is from 22.4kW to 45kW with four models side air-discharge type.
Maximum 15 indoor units with capacity up to 130% of total outdoor units can be connected in one refrigeration system.
It operates stably at extreme temperatures ranging from -15°C to 48°C.
20/22.4/26 kW 40/45 kW
Features
Outdoor Temperature
01 02 03 04 0 50-1 0-2 0
COOLING MODE
HEATING MODE*
Outdoor temperature (DB)
48°C
-15°C
-5°C Outdoor Temperature
48
Long piping length
High efficiency DC fan motor, saving power 50%
The Mini VRF provides a total piping length possibility of 100m, a maximum height difference between outdoor and indoor units of 30m. The height difference between indoors unit can be up to 8m. These generous allowances facilitate an extensive array of system designs.
According to the running load and pressure, it controls the speed of DC fan to achieve the minimum energy consumption, to reach the best effect. Used across entire range of models (from 8 to 72HP). Efficiency improved up to 45% especially at low speed.
The fluctuation range of motor rotor speed is within ±5 rpm and the motor can rapidly match the output of DC inverter compressor. The efficiency is enhanced under part load.
Carrier VRF realized the industry’s top class energy efficiency by adoption of Brushless Reluctance DC compressor control, All DC fan motor and improved heat exchanger.
High efficiency DC inverter compressor, saving power 25%
High efficiency and energy-saving
Permitted value
Piping length
Level difference
Total piping length (Actual)
Longest piping
Equivalent piping length from the farthest IDU to the first indoor branch joint
Level difference between IDU~ODU
Level difference between IDU~IDU
Actual length
Equivalent length
Outdoor unit up
Outdoor unit down
120
60
70
20
30
20
8
20-26kW 40-45kW
250
100
120
40
30
20
8Leve
l diff
eren
ce b
etw
een
IDU
~ID
U H
2
L2
Long
est a
ctua
l pip
ing
leng
th L
1
Leve
l diff
eren
ce b
etw
een
IDU
~OD
U H
1
*1: Total pipe length is equal to two times pipe length plus pipe length. *2: When the piping length from the farthest IDU to the first indoor branch joint is more than 40m, it needs to meet specific conditions according to the installation part of the technical manual to achieve 90m.
Permitted value
Piping length
Level difference
Total piping length (Actual)
Longest piping
Equivalent piping length from the farthest IDU to the first indoor branch joint
Level difference between IDU~ODU
Level difference between IDU~IDU
Actual length
Equivalent length
Outdoor unit up
Outdoor unit down
120
60
70
20
30
20
8
20-26kW 40-45kW
250
100
120
40
30
20
8Leve
l diff
eren
ce b
etw
een
IDU
~ID
U H
2
L2
Long
est a
ctua
l pip
ing
leng
th L
1
Leve
l diff
eren
ce b
etw
een
IDU
~OD
U H
1
*1: Total pipe length is equal to two times pipe length plus pipe length. *2: When the piping length from the farthest IDU to the first indoor branch joint is more than 40m, it needs to meet specific conditions according to the installation part of the technical manual to achieve 90m.
53 54
Optimized fan blade shape with new air outlet grille enhanced air flow volume which greatly improves fan performance and decreases noise.
Optimized fan shape and fan grille
DC motor
High efficiency DC fan motorAccording to the running load and system pressure, the system controls the speed of DC fan to achieve the minimum energy consumption and best performance.
Mot
or s
peed
(RP
M)
System pressure
DC inverter stepless adjustment
AC inverter multistep adjustment
Midea V4 Plus Individual Series adopt two type high efficiency DC inverter compressor. Side air-discharge type adopts high efficiency DC twin rotary compressor, top air-discharge type adopts high efficiency DC scroll compressor.
High EfficiencyHigh efficiency DC inverter compressor
High efficiency DC inverter twin rotary compressor (20-45kW)
Highly Efficient DC Motor:- Creative motor core design- High density neodymium magnet- Concentrated type stator-Wider operating frequency rangeBetter balance and Extremely Low Vibration:- Twin eccentric cams- 2 balance weightsHighly Stable Moving Parts:- Optimal material matching rollers and vanes-Optimize compressor drive technology- Highly robust bearings-Compact structure
High efficiency DC inverter scroll compressor (56-90kW)
New structure enhances mid-frequency performanceSpecially designed scroll profile for R410A
More compact, weight reduced by 50%
Advanced permanent magnet DC motor improves low-frequency band performance
Powerful magnets provide high torque and efficiency and achieve 70% reduction in volume.
New fan
Air deflector
New grille
Side air discharge type Top air discharge type
Outdoor Temperature
0 1 0 2 0 3 0 4 0 50-1 0-2 0
COOLING MODE
HEATING MODE*
Outdoor temperature (DB)
48°C
24°C-15°C
-5°C Outdoor Temperature
The V4 Plus Individual series system operates stably at extreme temperatures ranging from -15°C to 48°C.
40Pa
Wide operation range
Long piping length
High external static pressure
Max. 40Pa external static pressure can be customized for the top air-discharge outdoor unit type, flexible to build-in installation.
A standard 0-20Pa external static pressure is equipped by default for the top air-discharge outdoor unit type. 20-40Pa external static pressure can be customized.
Permitted value
Piping length
Level difference
Total piping length (Actual)
Longest piping
Equivalent piping length from the farthest IDU to the first indoor branch joint
Level difference between IDU~ODU
Level difference between IDU~IDU
Actual length
Equivalent length
Outdoor unit up
Outdoor unit down
120
60
70
20
30
20
8
20-26kW 40-45kW 56-67kW 73-90kW
1000*1
175
200
40/90*2
70
110
30
250
100
120
40
30
20
8
1000*1
165
190
40/90*2
50
90
30Leve
l diff
eren
ce b
etw
een
IDU
~ID
U 3
0m
90mLo
nges
t act
ual p
ipin
g le
ngth
175
m
Leve
l diff
eren
ce b
etw
een
IDU
~OD
U 1
10m
*1: Total pipe length is equal to two times pipe length plus pipe length. *2: When the piping length from the farthest IDU to the first indoor branch joint is more than 40m, it needs to meet specific conditions according to the installation part of the technical manual to achieve 90m.
V4 P
lus I Seies
V4 P
lus I Seies
Features
49
Intelligent defrosting technology
Optimized fan shape and fan grille
Optimize heat exchange design, heat exchange efficiency increased by 10%
Optimized fan blade shape with new air outlet grille enhanced air flow volume which greatly improves fan performance and decreases noise.
12°C sub-cooling degree makes the cooling capacity increased efficiently. Innovative designed outdoor high efficiency heat exchanger can reach up to 12°C sub-cooling degree one time, reduces the system resistance and improves reliability.
Intelligent defrosting program will judge the defrosting time according to the system real requirement, reduce the heating loss by unnecessary defrosting and make the indoor side more comfortable.
Defrosting time can be shortened to 4 min. due to the specialized defrosting valve.
53 54
Optimized fan blade shape with new air outlet grille enhanced air flow volume which greatly improves fan performance and decreases noise.
Optimized fan shape and fan grille
DC motor
High efficiency DC fan motorAccording to the running load and system pressure, the system controls the speed of DC fan to achieve the minimum energy consumption and best performance.
Mot
or s
peed
(RP
M)
System pressure
DC inverter stepless adjustment
AC inverter multistep adjustment
Midea V4 Plus Individual Series adopt two type high efficiency DC inverter compressor. Side air-discharge type adopts high efficiency DC twin rotary compressor, top air-discharge type adopts high efficiency DC scroll compressor.
High EfficiencyHigh efficiency DC inverter compressor
High efficiency DC inverter twin rotary compressor (20-45kW)
Highly Efficient DC Motor:- Creative motor core design- High density neodymium magnet- Concentrated type stator-Wider operating frequency rangeBetter balance and Extremely Low Vibration:- Twin eccentric cams- 2 balance weightsHighly Stable Moving Parts:- Optimal material matching rollers and vanes-Optimize compressor drive technology- Highly robust bearings-Compact structure
High efficiency DC inverter scroll compressor (56-90kW)
New structure enhances mid-frequency performanceSpecially designed scroll profile for R410A
More compact, weight reduced by 50%
Advanced permanent magnet DC motor improves low-frequency band performance
Powerful magnets provide high torque and efficiency and achieve 70% reduction in volume.
New fan
Air deflector
New grille
Side air discharge type Top air discharge type
Outdoor Temperature
0 1 0 2 0 3 0 4 0 50-1 0-2 0
COOLING MODE
HEATING MODE*
Outdoor temperature (DB)
48°C
24°C-15°C
-5°C Outdoor Temperature
The V4 Plus Individual series system operates stably at extreme temperatures ranging from -15°C to 48°C.
40Pa
Wide operation range
Long piping length
High external static pressure
Max. 40Pa external static pressure can be customized for the top air-discharge outdoor unit type, flexible to build-in installation.
A standard 0-20Pa external static pressure is equipped by default for the top air-discharge outdoor unit type. 20-40Pa external static pressure can be customized.
Permitted value
Piping length
Level difference
Total piping length (Actual)
Longest piping
Equivalent piping length from the farthest IDU to the first indoor branch joint
Level difference between IDU~ODU
Level difference between IDU~IDU
Actual length
Equivalent length
Outdoor unit up
Outdoor unit down
120
60
70
20
30
20
8
20-26kW 40-45kW 56-67kW 73-90kW
1000*1
175
200
40/90*2
70
110
30
250
100
120
40
30
20
8
1000*1
165
190
40/90*2
50
90
30Leve
l diff
eren
ce b
etw
een
IDU
~ID
U 3
0m
90mLo
nges
t act
ual p
ipin
g le
ngth
175
m
Leve
l diff
eren
ce b
etw
een
IDU
~OD
U 1
10m
*1: Total pipe length is equal to two times pipe length plus pipe length. *2: When the piping length from the farthest IDU to the first indoor branch joint is more than 40m, it needs to meet specific conditions according to the installation part of the technical manual to achieve 90m.
V4 P
lus I Seies
V4 P
lus I Seies
Hea
ting
capa
city
Usual defrosting
Time
t min
Intelligent defrosting
50
Easy Installation
Easy installation: No special area is required for outdoor units.
Easy transportaion: All outdoor units can be transported by elevator, which greatly simplifies installation and reduces time and labor.
The Mini VRF indoor and outdoor units are almost as easy to install as residential air conditioning systems, making them ideal for small offices and shops.
The Mini VRF units are slimmer and more compact, resulting in significant savings in installation space.
In some large residential and light commercial areas, such as villas, restaurants, usually it need more than one indoor unit, which in turn requires multiple outdoor units.
Mini VRF system removes this problem, and retains buildings’ original aesthetics.
Space saving design
Easy to transport
63 64
Addresses of indoor units can be set automatically by outdoor units.Wireless controller can inquire and modify every indoor units address.
Space saving design
Easy installation
The Mini VRF units are slimmer and more compact, resulting in significant savings in installation space. In some large residential and light commercial areas, such as villas, restaurants, usually it need more than one indoor unit, which in turn requires multiple outdoor units.Midea's Mini VRF system removes this problem, and retains buildings' original aesthetics.
The Mini VRF provides a total piping length possibility of 100m, a maximum height difference between outdoor and indoor units of 30m. The height difference between indoors unit can be up to 8m. These generous allowances facilitate an extensive array of system designs.
Easy to transport
Shield signal wire
Outdoor unit can distribute addresses to indoor unit.
KJR-29B RM05
Flexible piping design
High performance heat exchanger
High COP and EER values
The
long
est p
ipin
g le
ngth
is 7
0m
The
first
bra
nch
join
t to
thef
arth
est I
DU
is 2
0m
The
IDU
to th
e ne
ares
t br
anch
join
t is
15m
Leve
l diff
eren
ce b
etw
een
IDU
and
OD
U is
30m
Leve
l diff
eren
ce b
etw
een
IDU
s is
8m
*1: Total pipe length is equal to all the liquid pipe or all the gas pipe length.
Permitted value (m)
Actual total piping length*1
Longest pipingPiping length
Level difference
Level difference between indoor units
Level difference between indoor and outdoor units
Outdoor unit up
Outdoor unit down
Actual length
Equivalent length
8/10.5kW
100
45
50
20
30
20
8
12/14/16/18kW
100
60
70
20
30
20
8
High Efficiency
New design Original design High efficiency inner-threaded pipe, enhance heat transfer.
Reduce air resistance
Hydrophilic fins + inner-threaded pipes
The new designed window fins enlarge the heat-exchanging area , decrease the air resistance, save more power and enhance heat exchange performance.Hydrophilic film fins and inner-threaded copper pipes optimize heat exchange efficiency.The specially coated blue fins enhance durability and protect against corrosion from air, water and other corrosive agents, assures a longer coil service life.
Easier Installation and Service
Auto addressing
Equivalent piping length from the farthest IDU to the first indoor branch joint
3.9EER
8kW 10.5kW 12kW 14kW 16kW 18kW
3.92 3.783.54 3.43 3.3
COP
8kW 10.5kW 12kW 14kW 16kW 18kW
4.02 3.97 3.8 3.7 3.563.8
Easy installation: No special area is required for outdoor units. Easy transportaion: All outdoor units can be transported by elevator, which greatly simplifies installation and reduces time and labor.The Mini VRF indoor and outdoor units are almost as easy to install as residential air conditioning systems, making them ideal for small offices and shops.
63 64
Addresses of indoor units can be set automatically by outdoor units.Wireless controller can inquire and modify every indoor units address.
Space saving design
Easy installation
The Mini VRF units are slimmer and more compact, resulting in significant savings in installation space. In some large residential and light commercial areas, such as villas, restaurants, usually it need more than one indoor unit, which in turn requires multiple outdoor units.Midea's Mini VRF system removes this problem, and retains buildings' original aesthetics.
The Mini VRF provides a total piping length possibility of 100m, a maximum height difference between outdoor and indoor units of 30m. The height difference between indoors unit can be up to 8m. These generous allowances facilitate an extensive array of system designs.
Easy to transport
Shield signal wire
Outdoor unit can distribute addresses to indoor unit.
KJR-29B RM05
Flexible piping design
High performance heat exchanger
High COP and EER values
The
long
est p
ipin
g le
ngth
is 7
0m
The
first
bra
nch
join
t to
thef
arth
est I
DU
is 2
0m
The
IDU
to th
e ne
ares
t br
anch
join
t is
15m
Leve
l diff
eren
ce b
etw
een
IDU
and
OD
U is
30m
Leve
l diff
eren
ce b
etw
een
IDU
s is
8m
*1: Total pipe length is equal to all the liquid pipe or all the gas pipe length.
Permitted value (m)
Actual total piping length*1
Longest pipingPiping length
Level difference
Level difference between indoor units
Level difference between indoor and outdoor units
Outdoor unit up
Outdoor unit down
Actual length
Equivalent length
8/10.5kW
100
45
50
20
30
20
8
12/14/16/18kW
100
60
70
20
30
20
8
High Efficiency
New design Original design High efficiency inner-threaded pipe, enhance heat transfer.
Reduce air resistance
Hydrophilic fins + inner-threaded pipes
The new designed window fins enlarge the heat-exchanging area , decrease the air resistance, save more power and enhance heat exchange performance.Hydrophilic film fins and inner-threaded copper pipes optimize heat exchange efficiency.The specially coated blue fins enhance durability and protect against corrosion from air, water and other corrosive agents, assures a longer coil service life.
Easier Installation and Service
Auto addressing
Equivalent piping length from the farthest IDU to the first indoor branch joint
3.9EER
8kW 10.5kW 12kW 14kW 16kW 18kW
3.92 3.783.54 3.43 3.3
COP
8kW 10.5kW 12kW 14kW 16kW 18kW
4.02 3.97 3.8 3.7 3.563.8
Easy installation: No special area is required for outdoor units. Easy transportaion: All outdoor units can be transported by elevator, which greatly simplifies installation and reduces time and labor.The Mini VRF indoor and outdoor units are almost as easy to install as residential air conditioning systems, making them ideal for small offices and shops.
Features
51
Auto addressing
Easy piping connection
Addresses of indoor units can be set automatically by outdoor units.
Wireless controller can inquire and modify every indoor units address.
The side out discharge type offering four-directions to connect pipes and wirings for meet a variety installation request.
63 64
Addresses of indoor units can be set automatically by outdoor units.Wireless controller can inquire and modify every indoor units address.
Space saving design
Easy installation
The Mini VRF units are slimmer and more compact, resulting in significant savings in installation space. In some large residential and light commercial areas, such as villas, restaurants, usually it need more than one indoor unit, which in turn requires multiple outdoor units.Midea's Mini VRF system removes this problem, and retains buildings' original aesthetics.
The Mini VRF provides a total piping length possibility of 100m, a maximum height difference between outdoor and indoor units of 30m. The height difference between indoors unit can be up to 8m. These generous allowances facilitate an extensive array of system designs.
Easy to transport
Shield signal wire
Outdoor unit can distribute addresses to indoor unit.
KJR-29B RM05
Flexible piping design
High performance heat exchanger
High COP and EER values
The
long
est p
ipin
g le
ngth
is 7
0m
The
first
bra
nch
join
t to
thef
arth
est I
DU
is 2
0m
The
IDU
to th
e ne
ares
t br
anch
join
t is
15m
Leve
l diff
eren
ce b
etw
een
IDU
and
OD
U is
30m
Leve
l diff
eren
ce b
etw
een
IDU
s is
8m
*1: Total pipe length is equal to all the liquid pipe or all the gas pipe length.
Permitted value (m)
Actual total piping length*1
Longest pipingPiping length
Level difference
Level difference between indoor units
Level difference between indoor and outdoor units
Outdoor unit up
Outdoor unit down
Actual length
Equivalent length
8/10.5kW
100
45
50
20
30
20
8
12/14/16/18kW
100
60
70
20
30
20
8
High Efficiency
New design Original design High efficiency inner-threaded pipe, enhance heat transfer.
Reduce air resistance
Hydrophilic fins + inner-threaded pipes
The new designed window fins enlarge the heat-exchanging area , decrease the air resistance, save more power and enhance heat exchange performance.Hydrophilic film fins and inner-threaded copper pipes optimize heat exchange efficiency.The specially coated blue fins enhance durability and protect against corrosion from air, water and other corrosive agents, assures a longer coil service life.
Easier Installation and Service
Auto addressing
Equivalent piping length from the farthest IDU to the first indoor branch joint
3.9EER
8kW 10.5kW 12kW 14kW 16kW 18kW
3.92 3.783.54 3.43 3.3
COP
8kW 10.5kW 12kW 14kW 16kW 18kW
4.02 3.97 3.8 3.7 3.563.8
Easy installation: No special area is required for outdoor units. Easy transportaion: All outdoor units can be transported by elevator, which greatly simplifies installation and reduces time and labor.The Mini VRF indoor and outdoor units are almost as easy to install as residential air conditioning systems, making them ideal for small offices and shops.
Front side Back sideRight side Bottom side
Front sideBottom side
Back side
Right side
52
Specifications
Notes:Capacities are based on the following conditions:Cooling: Indoor temperature 27oC DB/19oC WB; Outdoor temperature 35oC DB/24oC WB.Heating: Indoor temperature 20oC DB/15oC WB; Outdoor temperature 7oC DB/6oC WB.Piping length: Interconnecting piping length is 7,5m, level difference is 0m.Sound values are measured in a semi-anechoic room, at a position 1m in front of the unit and 1,3m above the floor.
38VR008H11901S 38VR010H11901S 38VR014H119012 38VR016H119012Model
Power supply
Cooling
Heating
Connectable indoor unit
Sound pressure level
Pipe connections
Fan motor
Rotary compressor
Refrigerant
Net dimension (W×H×D)
Packing size (W×H×D)
Net weight
Gross weight
Capacity
Power input
EER
Capacity
Power input
COP
Total capacity
Max. quantity
Liquid pipe
Gas pipe
Type
Quantity
Air flow rate
Quantity
Type
Factory charging
Cooling
Heating
V/Ph/Hz
kW
kW
kW/kW
kW
kW
kW/kW
%
dB(A)
mm
mm
m3/h
kg
mm
mm
kg
kg
°C
°C
Operating temperature range
146,5
162,5
-15~46
-15~24
1.120×1.558×528
1.270×1.720×565
22,4
7,2
3,11
24,5
6,7
3,66
50-130
11
59
Ф9,53
Ф19,1
DC
2
10.494
1
R410A
6,2
380-415/3/50
16.
40,0
11,9
3,35
45,0
11,1
4,05
50-130
14
62
Ф12,7
Ф22,2
575
2
R410A
9
1360×1650×540
1450×1785×560
240
260
45,0
13,6
3,32
50,0
12,7
3,93
50-130
15
62
Ф12,7
Ф25,4
16.575
2
R410A
12
1460×1650×540
1550×1785×560
275
290
DC
2
26,0
8,4
3,09
28,5
7,9
3,61
SEER
SCOP
kW/kW
kW/kW
6,07
3,74
5,08
3,51
5,03
3,46
5,43
3,76
50-130
12
60
Ф9,53
Ф22,2
10.494
1
R410A
6,2
147
163
-5~48
-15~24
Notes:Capacities are based on the following conditions:Cooling: Indoor temperature 27oC DB/19oC WB; Outdoor temperature 35oC DB/24oC WB.Heating: Indoor temperature 20oC DB/15oC WB; Outdoor temperature 7oC DB/6oC WB.Piping length: Interconnecting piping length is 7,5m, level difference is 0m.Sound values are measured in a semi-anechoic room, at a position 1m in front of the unit and 1,3m above the floor.
38VR008H11901S 38VR010H11901S 38VR014H119012 38VR016H119012Model
Power supply
Cooling
Heating
Connectable indoor unit
Sound pressure level
Pipe connections
Fan motor
Rotary compressor
Refrigerant
Net dimension (W×H×D)
Packing size (W×H×D)
Net weight
Gross weight
Capacity
Power input
EER
Capacity
Power input
COP
Total capacity
Max. quantity
Liquid pipe
Gas pipe
Type
Quantity
Air flow rate
Quantity
Type
Factory charging
Cooling
Heating
V/Ph/Hz
kW
kW
kW/kW
kW
kW
kW/kW
%
dB(A)
mm
mm
m3/h
kg
mm
mm
kg
kg
°C
°C
Operating temperature range
146,5
162,5
-15~46
-15~24
1.120×1.558×528
1.270×1.720×565
22,4
7,2
3,11
24,5
6,7
3,66
50-130
11
59
Ф9,53
Ф19,1
DC
2
10.494
1
R410A
6,2
380-415/3/50
16.
40,0
11,9
3,35
45,0
11,1
4,05
50-130
14
62
Ф12,7
Ф22,2
575
2
R410A
9
1360×1650×540
1450×1785×560
240
260
45,0
13,6
3,32
50,0
12,7
3,93
50-130
15
62
Ф12,7
Ф25,4
16.575
2
R410A
12
1460×1650×540
1550×1785×560
275
290
DC
2
26,0
8,4
3,09
28,5
7,9
3,61
SEER
SCOP
kW/kW
kW/kW
6,07
3,74
5,08
3,51
5,03
3,46
5,43
3,76
50-130
12
60
Ф9,53
Ф22,2
10.494
1
R410A
6,2
147
163
-5~48
-15~24
53
38VR008/010H11901S
38VR014/016H119012
Dimensions
668 205.8
414
400
528
494
1558
1120
475
1650
C
540
500
505
450
AB
225
175
555
505
1460
136040kW
AB C
45kW
ModelSize
Recommended