chiller system by Mr.Seng Sunhor

Preview:

Citation preview

MINISTER OF EDUCATION YOUTH AND SPORT

1

INSTITUTE OF TECHNOLOGY OF CAMBODIA

INDUSTRIAL AND MECHANICAL ENGINEERING

THESIS

Title :Water Cooled Chiller System Selection

Student : Mr. SENG Sunhor Major : Industrial and Mechanical EngineeringAdviser : Mr. UN AmataAcademic year: 2015 – 2016

Outline

2

I. Introduction of Comin Khmere

II. Water Cooled Chiller System

IV. Conclusion

III. Calculation and Selection

I. Introduction

1. Comin Khmer Co. Ltd.,

3

The first MEP Company

Mechanical Electrical Plumbing

Figure2.1. Comin Khmere

Address: No 8b, Down Town Road, Phnom Penh,

4

II. Water Cooled Chiller System

1. Introduction of water cooled chiller system

2. Equipment of Water Cooled Chiller System

5

1. Introduction of water cooled chiller system

A kind of Air-conditioning system It was installed by combined many

components• Chiller• Pump: Condenser water pump &

: Chilled water pump • Cooling Tower

• Expansion Tank

6

2. Equipment of Water Cooled Chiller System

AHU/PHU FCU

Used for indoor unit

Figure 2.2. Fain coil unitFigure 2.1. Air handing unit

7

• Condenser

• Compressor

• Evaporator

Components of Chiller

2. Equipment of Water Cooled Chiller System

Figure 2.3. Fain coil unit

8

2. Equipment of Water Cooled Chiller System

Cooling Tower Pump

Figure 2.4.Pump Figure 2.5.Cooling Tower

9

III. Calculation and Selection

1. Building Load Calculation

2. Cooling Tower

4. Make-Up Tank

3. Pump (CHWP & CDWP)

2. Chiller

10

1. Building Load Calculation

ACLEDA DATA CENTER BUIDING

It has many kind of rooms

• There are six level; GF, 1F to 4F and Terrace Floor.

• Data center room• Office• UPS room• Meeting room

11

Hourly Analysis Program (HAP)

1. Building Load Calculation

Figure 3.1. Hourly Analysis Program

12

1. Building Load Calculation

FCU Selection from the Catalogs

• Total load in building = 2299kW

Calculation by HAP

• Total Load = 2357 kW Chiller selection

No Description Cooling Chiller Qty Duty StandbyLoad(kW) kW Total

1 Total load 2357 843.9 4 3 1

Table 3.1. Number of chiller; duty & standby

13Figure.3.2 Chiller Catalog

Cooling Capacity

14

2. Cooling Tower

Net Heat Calculation ; ( kW) Water flow rate ; (kg/s or L/s) Inlet and out let temperature in CT

W input=QH−QL=Q c𝑑−QevaSecond law of Thermodynamic

(eq.1)

15

Cooling Coefficient of Performance (COPR)

(eq.2)

• =843.9 kW; Cooling Capacity

• : Power input (kW)

5; in water cooled chiller system

2. Cooling Tower

16

(eq.3)

Water flow rate: ; =4.179 kJ/kg.K

=174.6

(eq.1); =>

Q cd=1012.68𝑘𝑊

2. Cooling Tower

17

No Description Qcd EWT LWT

kW

1 CT-01 1012.68 37 32 174.6

2 CT-01 1012.68 37 32 174.6

3 CT-01 1012.68 37 32 174.6

4 CT-01 1012.68 37 32 174.6

Table 3.1. Cooling selection

Data for selection cooling tower

2. Cooling Tower

18

Cooling tower catalog

Fig 3.3. Cooling tower Catalog

Flow rate 197.9

2230E

2. Cooling Tower

19

2230E

Fig 3.4. Cooling tower Catalog

20

Flow rateand Pressure drop;

;

Q eva=mw c p∆T CH ;∆T CH=T CH (en )−T CH (out ); eq .4

mw=Q eva

c p(T ¿¿CH (en)−T CH (out ))=843.9

4.179×5¿

mw=40.4 l /s

3. Chiller Water Pump

21

=[2L(m)100% 400 (kPa/m)+FCU(kPa) +Chiller(kPa)] eq.5

Estimation method

]

=268.2 kPa

3. Chiller Water Pump

22

Detail Calculation Method= (drop by piping) + (drop by fitting) eq.6

Pt 1=Pa× 𝐿 eq.7

��𝑤=40.4 𝑙 /𝑠

260pa

Figure 3.5. pipe sizing

D=150mm

3. Chiller Water Pump

23

⇒P t1=260×16=4160Pa=4.16 kPa Pressure drop by fitting

• Elbow, Tee; Y-strainer, Flexible• Valves: Balancing, Butterfly, Motorize, check valve

Conservation of mass : eq.8

; eq.8;

3. Chiller Water Pump

24

Elbow;

eq.7

Fig 3.6. Equivalent length in meters of pipe for 90 Elbows

3. Chiller Water Pump

L=5.1m

25

Tee• Tee (300mm to 150mm)The % of water flowing through circled branch

L=n×l eq.9

• n: number of elbow; • l: equivalent length in meter (m)

3. Chiller Water Pump

26

100%

Flow condition

n=1.7

Fig 3.7 % of water

3. Chiller Water Pump

27

eq.10

• 154.53 l/s D=300mm=0.3m

V=4×154.53

1000×3.14×0.32 =2.187=2.2m / s

Fig 3.7. L=1.7 9.1=15.47

Fig 3. 5 Pt=120×15.47=1856.4 Pa

3. Chiller Water Pump

28

Equivalent length in meter of valves; l(m)Dimension, D=150mm

Accessory Y-strainer Balancing Motorize Flexible Butterfly CheckLength(m) 34 34 1.4 1.4 1.4 18

Table.2. Equivalent length in meter of valves

Y-strainerBalancing valve Pt=260×34=8840 Pa

Butterfly valve

Motorize valve

Check valveFlexible

3. Chiller Water Pump

29

Summarize total loss in pipe & fitting for the system

Comparison

Estimation: Detail:

Pressure drop total selection: Error

3. Chiller Water Pump

30

Chiller water pump Data selection

No Description

Flow

Rate

Pressure

drop Safety Coeff.

Total Pressure

drop

l/s kPa 20% kPa

1 CHWP-1 40.4 270 1.2 324

2 CHWP-2 40.4 270 1.2 324

3 CHWP-3 40.4 270 1.2 324

4 CHWP-4 40.4 270 1.2 324

Table 3.2. Cooling selection

3. Chiller Water Pump

31

Chilled Water Pumps ScheduleITEM DESCRIPTION SPECIFIED

1 Ref. CHP-1~4 2 Quantity (set) 4 ( 3 Duty + 1 Standby )3 System Chilled Water System4 Location GF Chiller Plant Room

5 Type End suction or Horizontal Split Casing

6 Flow Rate (L/s) 40.47 Pump Head (m) 32.48 Pump Speed (rpm) 1450 9 Pump Efficiency (%) Not Specified

10 Motor Power (kW) 30

11 Power Supply (Volt/Phase/Hz) 380/3/50

12 Motor - Type TEFC

Table 3.3. chilled water pump schedule

32

Mass flow rate: From: eq.3

Total Pressure drop: Estimation method

=[2L(m)100% 400 (kPa/m)+CT(kPa) +H(kPa)]eq.11

• H=3.8m=38kPa Height of CT; L=105m; Loss in CT=65kPa; 100%: loss by fitting; 2: Return and supply pipe

𝐏𝐓𝐨𝐭𝐚𝐥=𝟐𝟕𝟏𝐤𝐏𝐚

3. Condenser water pump

33

Detail Calculation, we calculate as Chiller water pump

Comparison

Estimation: Detail:

Pressure drop total selection: Error

3. Condenser water pump

34

No DescriptionFlowrate Pressure drop Safety Coeff P: total

l/s kPa 20% kPa

1 CHWP-1 48.5 280 1.2 336

2 CHWP-2 48.5 280 1.2 336

3 CHWP-3 48.5 280 1.2 336

4 CHWP-4 48.5 280 1.2 336

3. Chiller Water Pump

Table 3.4. Condenser water pump data selection

35

Condenser Water Pumps ScheduleITEM DESCRIPTION SPECIFIED     

1 Ref. CWP-1~4 2 Quantity (set) 4 ( 3 Duty + 1 Standby )3 System Condenser Water System4 Location GF Chiller Plant Room

5 Type End suction or Horizontal Split Casing

6 Flow Rate (L/s) 48.57 Pump Head (m) 33.68 Pump Speed (rpm) 1450 9 Pump Efficiency (%) Not Specified10 Motor Power (kW) 30

11 Power Supply (Volt/Phase/Hz) 380/3/50

12 Motor - Type TEFCTable 3.5. Condenser water pump schedule

36

4. Make-Up Tank

Evaporation loss, Drift loss and Blowdown loss

Make upwater=Eva . loss+Drift loss+Blowdownloss Estimation of make up water calculation

• Evaporation loss=0.85%; • Drift loss=0.02%; • Blowdown loss=0.22%

=> Make up water=0.85+0.02+0.22%=1.09%

Water loss in

37

; : water volume

V M=48.5× 1.09100 ×2 (h )=48.5×0.0109×2×3600

V M=3806 l=3.8𝑚3

V T=3.8𝑚3×4=15.2𝑚3

V T=15.2𝑚3

4. Make-Up Tank

CHILLER

FAN COIL UNIT

AIR HANDLING UNIT

2 WAY VALVE 2 WAY VALVE

FRESH AIR

TEMPERATURE SENSOR

RETURN AIRSUPPLY AIR

PRESSURE SENSOR

CHECK VALVETEMPERATURE SENSOR

PRIMARY CHILLED WATER PUMP(WITHOUT VSD CONTROL)

THERMOSTAT

25 %

24 °C

10 %

7 °C

23.5 °C

12 °C

COOLING TOWER

CONDENSER WATER PUMP

TEMPERATURE SENSOR

37 °C

32 °C

39

After I finished my thesis

• Calculation

• Selection

V. Conclusion

• Understand about water cooled chiller system

• Concept of designing

40

41

Recommended